Room controllers with manual forced ventilation function

Similar documents
Room controller. RC is a room controller from the Regio Mini series intended to control heating and cooling in a single zone.

Pre-programmed room controller with communication

Pre-programmed room controller with communication and hidden setpoint

Pre-programmed room controller with communication

The RCF range. Controllers and thermostats for fan-coil units

Control equipment. Contact, Overview, Index. Guideline heating and cooling. Plexus. Professor / Professor Plus. Premum / Premax.

Room Temperature Controllers

Room Temperature Controller

The RCF range. Controllers and thermostats for fan-coil units

Room Temperature Controller

Corrigo E. Second generation which contains all applications and languages

Master devices. Type X-AIR-ZMAS. Zone master module for up to 25 zone modules, with integral webserver and interfaces to higher-level systems

Room Temperature Controller

Room Temperature Controller with LCD

Optigo OP10 Manual. Copyright AB Regin, Sweden, 2007 R E A D Y - S T E A D Y - G O

Corrigo E - User Manual Ventilation

Room thermostats with LCD for wall mounting

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Room thermostat with 24-hour time switch and large LCD

Preliminary Release. Room Temperature

Semi flush-mount room thermostat

Wall-mounted room thermostat with LCD

Installation Guide. Ceiling PIR Detector (311) Features and Connections

C-series Controllers for air handling systems

PRELIMINARY EDITION

Corrigo E - manual Ventilation application

Flush-mounted room thermostat

Room thermostat with Auto Timer, Option External Input

RVL479. Heating Controller. for use with a partner unit

Room thermostat with Auto Timer, Option External Input

Copyright AB Regin, Sweden, Corrigo E manual Ventilation application

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

Wireless room thermostat with LCD

Control solutions Biofloor

GreenCon On/Off Room Thermostat

GreenCon On/Off Room Thermostat

Use. For 2-pipe fan coils

PGDX Rectangular duct coolers with DX coil

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems

Ionisation single-tube smoke detector for duct mounting

Flush-mounted room thermostats

C User manual

Sensors and switches. Temperature, Pressure, Humidity, Air flow, CO 2., CO and NO 2

The fan is switched to the selected speed via control output Q1, Q2 or Q3.

Semi flush-mount room thermostats

for relative humidity and temperature with calibration certificates

REA22 Room Temperature Controller

No. Icon Name Function

Installation and Operation. Tracer ZN521 Zone Controller CNT-SVX07C-EN

RVL480. Heating Controller

RVL470. Heating Controller. Use. Functions. Series B

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

Satchwell. DC1100 Energy Controller SELF CONFIGURING OPTIMISER/COMPENSATOR WITH BOILER SEQUENCE AND HWS CONTROL FEATURES

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

Labkotec Ice Detector

CDR-AL Room CO 2 Traffic Light Alarm Units and Sensors

CUMULUS CUMULUS. Key figures. Construction. Function Integrated chilled beams

RDJ10. Room temperature controller with 24-hour time switch and large LCD. For heating systems

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

Room temperature controller with large LCD. Non-programmable, for heating or cooling systems

Room thermostat with Auto Timer, independent DHW

Self-learning Room Temperature Controller

EXcon zone control. Control for up to 4 individual zones _ fm. EXHAUSTO A/S Odensevej 76 DK-5550 Langeskov

District heating controller

Room thermostat with Auto Timer, Option External Input

TEC2620 Series Non-Programmable Fan Coil Network Thermostat Controller and Remote I/O Relay Packs

RVL481. Heating Controller. including d.h.w. heating

Multi-Gas-Controller MGC2

GB Art. Nr

SEQUENCE OF OPERATION GUIDELINE. AIR TERMINAL UNITS SINGLE DUCT VARIABLE AIR VOLUME with HOT WATER REHEAT or ELECTRIC HEAT

TER Active Room Temperature Sensor (Controller),

QPM21 Series Duct CO 2 and Air Quality Sensors

TEC3000 Series Wireless, Stand-Alone, and Field-Selectable BACnet MS/TP or N2 Networked Thermostat Controllers Catalog Page

T60xDFH-4 and T60xDFH-4+PIR Series Thermostat Controllers with Dehumidification and Occupancy Sensing Capability

Honeywell ENERGY SAVINGS KIT

Gas cylinder scale Model GCS-1

WE TAKE BUILDING AUTOMATION PERSONALLY MANUAL CORRIGO

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

VT8300 Series Installation Guide 24 Vac Low Voltage

Application guide RDG160 Remote control

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

Room Sensors. Building Technologies HVAC Products ... Symaro. for relative humidity (high accuracy) and temperature

Duct Air Quality Sensors

T125-E. Electric Fan Coil Thermostat. Product Bulletin. Operation. Appearance. Installation, Service and Maintenance

District heating controller

Self-learning Room Temperature Controller

Rooftop Unit, Heat Pump and Indoor Air Quality Application Guide. SE8600 Series Room Controllers

RDH10. Room temperature controller with large LCD. Non-programmable, for heating or cooling systems

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

Electronic timeswitch

Saving energy with Synco

Capacity controller EKC 331T REFRIGERATION AND AIR CONDITIONING. Manual

02/11/2015

Self-learning Room Temperature Controller

OEM Alpha Thermostat direct Analog

RDJ10. Room temperature controller with 24-hour time switch and large LCD. For heating systems

Duct Sensors. Siemens Building Technologies HVAC Products. Symaro. for relative humitidy (high accuracy) and temperature

Room thermostats with LCD RDD100..

Copyright AB Regin, Sweden, Corrigo manual Ventilation application

Transcription:

revision 12 2016 RC-O Room controllers with manual forced ventilation function RC-O is a room controller from the Regio Mini series intended to control heating and cooling in a single zone. RC-O is a room controller in the Regio series. The controller does not have a communication port. Regio Regio is an extensive range of controllers for control of heating and cooling. The controllers are divided into three different series; Mini, Midi and Maxi. The Midi range consists of pre-programmed controllers with communication. Maxi consists of freely programmable controllers with communication. The Mini controller range, of which RC-O is a part, consists of pre-programmed, stand-alone controllers. Applications The Regio controllers are suitable for use in buildings requiring optimum comfort and reduced energy consumption, such as offices, schools, shopping centres, airports, hotels and hospitals. See application example on page 3. Short facts about RC-O Easy installation Built-in function for forced ventilation On/Off or 0...10 V control Input for occupancy detector, window contact, condensation detector and change-over function Easy to install The modular design, featuring a separate bottom plate for wiring, makes the entire Regio range of controllers easy to install and commission. The bottom plate can be put into place before the electronics are installed. Mounting takes place directly on the wall or on an electrical connection box. Sensor The controller has a built-in room temperature sensor. An external sensor for room temperature or change-over can also be connected (PT1000). Actuators RC-O can control 0...10 V DC valve actuators and/or 24 V AC thermal actuators.

Control mode RC-O has the control mode Heating and Cooling in sequence. A change-over function can also be activated, see below. Operating modes There are four different operating modes: Unoccupied, Stand-by, Occupied and Bypass. Occupied is the preset operating mode. It can be set to Stand-by via a DIP switch. The operating modes can be activated via an occupancy detector or the occupancy button. Unoccupied: The room in which the controller is placed is not used for a extended time period, such as during holidays or long weekends. Both heating and cooling are kept within a temperature interval with configurable min/ max temperatures (FS min = 15 C, max = 30 C). Stand-by: The room is in an energy saving mode and is not used at the moment. This can, for instance, be during nights, weekends and evenings. The controller stands by to change operating mode to Occupied if presence is detected. Both heating and cooling are disconnected within a temperature interval surrounding the current setpoint (FS heating setpoint = -3 C, cooling setpoint = +3 C). Occupied: The room is in use and a comfort mode is activated. The controller maintains the temperature around a heating setpoint (22 C) and a cooling setpoint (24 C). Bypass: The temperature in the room is controlled in the same way as in the Occupied operating mode. The output for forced ventilation is also active. This operating mode is useful for instance in conference rooms, where many people are present at the same time for a certain period of time. When Bypass has been activated by pressing the occupancy button, the controller will automatically return to its preset operating mode (Occupied or Stand-by) after 2 hours have elapsed. If an occupancy detector is used, the controller will automatically return to its preset operating mode if no occupancy is detected for 10 minutes. Occupancy detector By connecting an occupancy detector, RC-O can switch between the Bypass operating mode and its preset operating mode (Occupied or Stand-by). This way, the temperature is controlled from requirement, making it possible to save energy while maintaining the temperature at a comfortable level. The occupancy button Pressing the occupancy button for less than 5 seconds when the controller is in its preset operating mode will cause it to change to operating mode Bypass. Pressing the button for less than 5 seconds when the controller is in Bypass mode will change its operating mode to the preset operating mode If the occupancy button is pressed for more than 5 seconds will change the controller s operating mode to Unoccupied regardless of its current operating mode. A short press when in Shutdown mode will return the controller to Bypass. Forced ventilation Regio has a built-in function for forced ventilation. A closing of the digital occupancy detector input will set the controller to Bypass mode and activate the output for forced ventilation (DO1). This can for instance be used to open a damper. This function is terminated when the settable forcing interval (10 min.) has run out. The function can also be activated at the press of a button. Change-over function RC-O has an input for change-over that automatically resets output UO1 to operate with heating or cooling function. A PT1000 type sensor can be connected and mounted so that it monitors the supply temperature of the heating coil. The output function is set to Heating when the fluid temperature exceeds 22 C and to Cooling when the temperature falls below 18 C. To ensure satisfactory functioning using a sensor, the system must have continuous primary circuit circulation. When the change-over function is not used, the input must be left disconnected. Setpoint adjustment When in mode Occupied, the controller operates using a heating setpoint (FS = 22 C) or a cooling setpoint (FS = 24 C) that can be changed locally using DIP switches. Setpoint can be adjusted up and down (FS = ±3 C) using the knob on the front of the controller. Switching between heating and cooling setpoints takes place automatically in the controller depending on heating or cooling requirements. Built-in safety functions RC-O has an input for a condensation detector to detect moisture accumulation. If detected, the cooling circuit will be stopped. The controller also has frost protection which is active when a window is open and the controller is in mode Off. This prevents frost damages by ensuring that the room temperature does not drop below 8 C. 2

Indication The controller has a LED shaped as a thermometer on its front. A red light indicates heating control is active and a blue light indicates active cooling control. If the LED is switched off, it means neither heating or cooling control is active. Actuator exercise All actuators are exercised, regardless of type or model. The controller performs this exercise at an interval of 23 hours. An opening signal is sent to the actuator for as long time as its configured run time. A closing signal is then sent for an equal amount of time, after which the exercise is completed. Application example Condensation detector Occupancy detector Window contact Temperature sensor 3

Technical data Supply voltage Power consumption Ambient temperature Storage temperature Ambient humidity Protection class Built-in temperature sensor Material, casing Weight Colour Inputs External room sensor Change-over Presence detector IR24-P. Condensation detector alt. window contact Outputs Forced ventilation Valve actuators alt. thermal actuators Valve actuators Termal actuator Output 18...30 V AC, 50...60 Hz 2.5 VA 0...50 C -20...+70 C Max 90% RH IP20 NTC type, range 0...50 C, accuracy ±0.5 C at 15...30 C Polycarbonate, PC 110 g Cover: Polar white RAL9010 Bottom plate: Light gray EMC emissions & immunity standards: This product conforms to the requirements of the EMC Directive 2014/30/EU through product standards EN 61000-6-1 and EN 61000-6-3. RoHS: This product conforms to the Directive 2011/65/EU of the European Parliament and of the Council through EN 50581:2012. PT1000 sensor, 0 50 C. Suitable sensors are Regin s TG-R5/PT1000, TG-UH/PT1000 and TG-A1/PT1000. PT1000 sensor, 0 100 C. Suitable sensor is Regin s TG-A1/PT1000. Closing, potential-free contact. Suitable occupancy detector is Regin s Regin s condensation detector KG-A/1 resp. potential-free contact 24 V AC actuator, max 0.5 A 2 outputs 0 10 V DC, max. 5 ma 24 V AC, max. 2.0 A Heating or cooling Actuator exercise 23 hours interval Terminal blocks Lift type for max cable cross-section 2.1 mm 2 Basic heating setpoint, set via DIP switches The ON-position is marked on the DIP switch. The cooling setpoint is 2 C higher. Basic setpoint, heating ( C) SW1 SW2 20 OFF OFF 22 (FS) OFF ON 24 ON OFF 26 ON ON Other DIP switches ON OFF Comment SW3 Stand-by Occupied (FS) Preset operating mode SW4 SW5 SW6 DI, window switch. Closed contact indicates closed window. Digital output for 24 V AC thermal actuator. Digital output for 24 V AC thermal actuator. CI, Regin s condensation detector, KG-A/1 (FS). Analogue output for 0...10 V DC valve actuator (FS). Analogue output for 0...10 V DC valve actuator (FS). Function terminal 33, DI2/CI. Function terminal 23, UO1. Function terminal 24, UO2. SW7 External, PT1000-sensor Internal NTC-sensor (FS) Temperature sensor 4

Wiring Terminal Designation Function 10 G Supply voltage 24 V AC 11 G0 Supply voltage 0 V 12 DO1 Output for forced ventilation 13-14 No function 20 GDO 24 V AC out common for DO 21 G0 0 V common for UO (when using 0...10 V actuators) 22 No function 23 UO1 Output for 0...10 V valve actuator alt. thermal actuator. Heating or Cooling via change-over. 24 UO2 Output for 0...10 V valve actuator alt. thermal actuator, cooling. 30 AI1 Input for an external sensor 31 UI1 Input for change-over sensor 32 DI1 Input for occupancy detector 33 DI2/CI Input for Regin's condensation detector KG-A/1 alt. window contact 40 +C 24 V DC out common for DI 41 AGnd Analogue ground, reference for AI and UI (with analogue and digital function) 42-43 No function Dimensions 60 68 95 31 mm Product documentation Document Instruction Regio RC-O Product sheet TG-R4/PT1000, TG-R5/PT... Product sheet TG-UH/PT... Product sheet TG-A1/PT... Product sheet IR24-P Instruction IR24-P Product sheet KG-A/1 Type Instruction for RC-O Information about room sensors, outdoor sensors and strap-on sensors suitable for RC-O Information about occupancy detectors suitable for RC-O Instruction for IR24-P Information about condensation sensors for the Regio controllers The product documentation is available for download from Regin's website, www.regincontrols.com. Head Office Sweden Phone: +46 31 720 02 00 Web: www.regincontrols.com Mail: info@regin.se