State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Similar documents
FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Chilled beams. TRACE 700 incorporates two chilled beam strategies: passive and active.

Summary Comparison of Simulation Program Features

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

HVAC Mandatory Provisions Part II, Page 1

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

2. CURRICULUM. Sl. No.

HVAC 101. The Basics of Heating, Ventilation and Air Conditioning

APPLICATION GUIDE BEAMS

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Single Zone System. One duct system Used mostly in small buildings Forced air system All spaces controlled by a single thermostat Single air return

CHAPTER 4. HVAC DELIVERY SYSTEMS

1. When using the COMcheck software, the compliance report submitted by the permit holder shall indicate that the applicable code is.

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.80

Chilled beam technology overview John Woollett 1, Jonas Åkesson 2 Swegon AB 1,2

b.) Technical Information:

DADANCO Technical Paper

SPACE CONDITIONING IN COMMERCIAL BUILDINGS Overview

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

An HVAC Audit of the Canberra Institute of Technology

Efficient energy recovery in AHU. DOHA, Qatar Timo Schreck Enventus AB, Sweden

Improving Performance with a Building Tune-Up. Janice Peterson, P.E. LEED AP Market Manager, Building Operations BetterBricks

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Dehumidifying with Dedicated Outdoor Air

7. MECHANICAL SYSTEM DESIGN

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Modular Active. Chilled. Beams

COMcheck Software Version Mechanical Compliance Certificate

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

MECHANICAL SERVICES 101. Ian White

2009 IECC Commercial Mechanical Requirements

HVAC 101. H V A C S y s t e m s

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

Senior Thesis Centre Community Hospital East Wing Addition - Proposal Keith Beidel Mechanical Option 12/05/02 1

To Keep Docs Cool, Dry and Happy

White Paper Dehumidification in Humid Climates - A Theoretical Case Study

Temperature. In the HVAC area, we talk about two kinds of temperatures.

ENGINEERING. Edition No. 13 October 2002

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

MT. AIRY MIDDLE SCHOOL CARROLL COUNTY PUBLIC SCHOOLS

COMcheck Software Version Mechanical Compliance Certificate

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

V4 15JUNE2016 (COPYRIGHT: DEPARTMENT OF INDUSTRY)

Heat Recovery Dehumidification (HRD) system. Designed for municipal swimming pools

Chilled Beam and Radiant Cooling Basics. Salt Lake City, UT ASHRAE Chapter December 2013 Nick Searle

Section 4 of 6 DOAS Core Technologies

The new ASHRAE-REHVA Active and Passive Beam Application Design Guide

2011 Manitoba Energy Code for Buildings (MECB) PART 5, Heating, Ventilating and Air-conditioning Systems

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

Mechanical Compliance Certificate

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

High Efficiency Heating and Cooling Systems for Community Colleges Kirk Mescher, PE, LEED AP Principal ICCCFO

HVAC Controls Upgrades: Requirement Details ( )

Passive building in Hot and Humid Climates

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1. Contextual Reminder

Madeira City Schools Madeira, Ohio. HVAC Assessment. December 2011 (Revised February 2012)

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Variable refrigerant flow (VRF) systems

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

Selected Laboratory Energy Efficiency Measures

Do All DOAS Configurations Provide the Same Benefits?

Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto

Variable Refrigeration Flow Systems Overview 10/11/2016

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

National Institutes of Health Building 37 Modernization Bethesda, Maryland MECHANICAL DEPTH EXISTING MECHANICAL SYSTEM

K.F. Fong *, C.K. Lee, T.T. Chow

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.

Appendices. Included in this section are

Trane CDQ Desiccant Dehumidification

COMcheck Software Version Review Mechanical Compliance Certificate

CEE 243. Week 2 HVAC systems at Y2E2

Sequence of Operations (excerpt)

RT-OA TM Rooftop Outdoor-Air (DOAS)

Radiant Cooling Nonresidential HVAC Stakeholder Meeting #2

2016 Title 24 HVAC Topics. June 4, 2013

Two essential attributes of mechanical systems intended to

August 15, 2013 Page 1 of 19

1080 Marina Village Parkway, Suite 501 Alameda, CA (510) Fax (510) HVAC DESIGN INTENT

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

In Search of the Magic Box: A Review of Crossover Conditioning/Ventilation/Dehumidification Devices on the US Market

Presented By: John Dolan, P.E.

Chilled Ceilings / Beams Working Principles & Applications

Controlling Indoor Humidity in High Performance Homes. Danny Gough, Energy Solutions, LP

design brief This design brief provides an introduction into the design and application of DV. It addresses the following issues:

AHU Air Handling Unit Fundamentals. j.ilangumaran

AHRI 920 & ASHRAE 90.1

HVAC DISTRIBUTION and DELIVERY SYSTEMS

Transcription:

Frenger Radiant chilled beam performance at

3D Model Creation

Daylight Analysis

Comparison of the performance of various HVAC systems at 1 Shelly St, Sydney VAV fancoil Active chilled beam Passive chilled beam (95% convective / 5% radiant absorption) Passive Radiant chilled beam (65% convective / 35% radiant absorption) Traditional VAV Modern VAV (temperature and CO2 control with static reset )

Systems Setup Cooling Circuit Cooling circuit (common to all air side systems) Chiller has a COP of 4 (typical chiller performance based on flow of 6 C and return temp of 12 C). Addition of Dry Air Cooler for free cooling when available. DAC efficiency = 67%, SFP of fans = 0.4W/l/s

Systems Setup Heating Circuit Heating circuit (common to all air side systems) Boiler has an efficiency of 90% and a flow set point of 65 C. DHWS also fed from this circuit.

Systems Setup DX Circuit State of the art building simulation software... DX circuit - common to all air side systems Nominal heating energy input ratio 0.261 (COP = 3.83) Nominal cooling energy input ratio 0.307 (COP = 3.26) (Performance taken from typical Mitsubishi VRF heat recovery unit)

Systems Setup VAV Fancoil State of the art building simulation software... VAV fancoil air side A high efficiency chiller supplies chilled water at 6 C to the fan coils with a nominal return temperature of 12 C. An air source heat pump supplies heating and cooling to the DX coils in the AHU The AHU is based on a total SFP of 1.8 W/l/s and includes heat recovery at 75% efficiency and provides air to the fan coil units at 14 C. The fresh air flow rate is 2.2 l/s/m 2 for perimeter zones and 1.1 l/s/m 2 for core zones. The fan coil units include EC motors and VAV control and have an SFP of 0.25 W/l/s. The fan coil units have a minimum flow turndown to 60% of the maximum flow rate.

Systems Setup Active Chilled Beam Active chilled beam air side A dedicated high efficiency chiller supplies 14 C water to the chilled beams; the chiller incorporates a "Free Cooling" circuit so that when the outdoor conditions permit the chiller can turn off. During other times the free cooling runs in conjunction with the chiller to further reduce energy usage. The pump speed is varied to ensure the chilled water return is 3K higher than the supply. A DX cooling coil provides the conditioned air at 16 C but also provides sufficient dehumidification of the supply air, to ensure latent gains within the space are controlled and maintains the dew point at 1.0 C lower than the chilled water flow temperature onto the beams. A DX heating coil provides the conditioned air at 13 C and supplies reheat during dehumidification. The AHU is based on a total SFP of 1.8 W/l/s and includes heat recovery at 75% efficiency. The fresh air flow rate is 2.2 l/s/m 2 for perimeter zones and 1.1 l/s/m 2 for core zones.

Systems Setup Passive Chilled Beam Passive chilled beam air side system (common to both radiant and / convective) Two passive chilled beam systems were modelled; one with a 5% radiant proportion and one with a 35% radiant proportion. The room thermostat setpoint for cooling was increased by 1 C for the 35% radiant case, to compensate for the lower resultant temperatures. A dedicated high efficiency chiller supplies 15 C water to the chilled beams; the chiller incorporates a "Free Cooling" circuit so that when the outdoor conditions permit the chiller can turn off. During other times the free cooling runs in conjunction with the chiller to further reduce energy usage. The pump speed is varied to ensure the chilled water return is 3K higher than the supply. A DX cooling coil provides the conditioned air at 16 C but also provides sufficient dehumidification of the supply air, to ensure latent gains within the space are controlled and maintains the dew point at 1.0 C lower than the chilled water flow temperature onto the beams. A DX heating coil provides the conditioned air at 16 C and supplies reheat during dehumidification. The AHU is based on a total SFP of 1.8 W/l/s and includes heat recovery at 75% efficiency. The fresh air flow rate is 2.2 l/s/m 2 for perimeter zones and 1.1 l/s/m 2 for core zones.

Systems Setup Traditional VAV Traditional VAV air side A high efficiency chiller supplies chilled water at 6 C to the cooling coil with a nominal return temperature of 12 C. The VAV system is based on a total SFP of 1.8 W/l/s and includes heat recovery at 75% efficiency and provide air to the zones to meet the heating and cooling demands. The fresh air flow rate is 2.2 l/s/m 2 for perimeter zones and 1.1 l/s/m 2 for core zones. The zone dampers are set up to control air flow based on zone temperature requirements. The supply fan is controlled to maintain a constant static pressure.

Systems Setup Modern VAV State of the art building simulation software... Modern VAV air side A high efficiency chiller supplies chilled water at 6 C to the cooling coils with a nominal return temperature of 12 C. The VAV system is based on a total SFP of 1.8 W/l/s and includes heat recovery at 75% efficiency and provide air to the zones based on heating and cooling demand. The fresh air flow rate is 2.2 l/s/m 2 for perimeter zones and 1.1 l/s/m 2 for core zones. The zone dampers are set up to control air flow based on zone temperature requirements and CO 2 levels. The supply and return fans are controlled to give static pressure reset as described in Ashrae 90.1.

Systems Setup Frenger Radiant Chilled Beam (A) Passive chilled (65% convective / 35% radiant absorption) beam air side Evaporative cooling of exhaust air before heat recovery.

Systems Setup Frenger Radiant Chilled Beam (B) Passive chilled (65% convective / 35% radiant absorption) beam air side Evaporative cooling and sensible heat recovery on fresh air.

Results of the various different air conditioning systems modelled for 1 Shelly St building, Sydney. Heating (kwh) Cooling (kwh) Auxiliary (kwh) Total (kwh) VAV fancoil 84,504.39 541,862.09 252,238.47 878,604.95 Active beam 84,468.56 529,660.69 203,059.41 817,188.66 Passive Beam (95% Convective / 5% Radiant absorption) 87,021.97 509,811.69 206,553.40 803,387.06 Frenger Radiant Passive Beam (65% Convective / 35% Radiant absorption) 86,836.56 454,034.25 203,257.08 744,127.89 Traditional VAV 365,106.69 663,804.59 389,736.06 1,418,647.34 Modern VAV 86,167.17 609,406.33 276,391.29 971,964.79 From the above results the Frenger Radiant passive beam system consumes the least energy for the building modelled. Heating (kwh) Cooling (kwh) Auxiliary (kwh) Total (kwh) Frenger Radiant Passive Beam (65% Convective / 35% Radiant absorption) 86,836.56 454,034.25 203,257.08 744,127.89 By applying evaporative cooling on the exhaust air further energy savings can be achieved, however when applied to the fresh air system additional energy would be consumed. Heating (kwh) Cooling (kwh) Auxiliary (kwh) Total (kwh) Evaporative cooling on exhaust air 88,454.71 411,994.34 209,178.74 709,178.93 Evaporative cooling on fresh air 88,319.67 383,777.83 282,394.64 754,491.95