LMS-188-4P-BMS 4 POINT DIGITAL MONITOR/ALARM WITH PROTOCOL CONVERTER OPERATING INSTRUCTIONS

Similar documents
LMS-188-4P 4 POINT DIGITAL MONITOR/ALARM OPERATING INSTRUCTIONS

AU-3000 SINGLE PROBE DIGITAL TEMPERATURE ALARM WITH REMOTE ALARM DELAY OPTION OPERATING INSTRUCTIONS WARNING:

Beacon 800 Gas Monitor Operator s Manual

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

CA5000 Liquid CO 2 Freezer Backup System

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Beacon 410A Gas Monitor Operator s Manual

Contents 1 Set Up 2 Gateway information 3 Operation of the App 4 Troubleshooting Description of sensors. 1 Set Up. 1.1 Connect the Gateway

Beacon 110 Gas Monitor Operator s Manual

Pioneer-R16 Gas Monitor Operator s Manual

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

F PC and AO OUTPUT BOARDS INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

LEAKMONITOR MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND USER OPERATION MANUAL

Added password for IP setup page : Password must be in IP format!

THX-DL Data Logger USER & INSTALLATION MANUAL V

User Manual. Dryer Controller M720

DMWD 1 to 4 Zone Water Detection Alarm with Distance to Leak Measurement Installation and Operation Manual

Carbon Monoxide Transmitter

Dryer Controller M720

OnTrac Boiler Management System

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

EasyTronic III MANUAL SERVICE

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

RF SCOUT PLUS INSTRUCTION MANUAL. Dielectric, LLC 22 Tower Rd. Raymond, ME Phone: January 2015, Rev B 1

SCAN200E USER S MANUAL

Duct and Rough Service Carbon Monoxide Sensor

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION MEGATRON MODEL 10NB-LF 4 HOT & COLD INLETS 4 MIXED OUTLET 2 RETURN PIPING

Beacon 200 Gas Monitor Operator s Manual

Submittal S-NV-150-LF-M November, 2018 MEGATRON MODEL NV-150-LF DIGITAL TEMPERATURE CONTROL STATION

Refrigeration Controller Operator s Manual (HRC) PO Box 6183 Kennewick, WA

Table of Contents SECTION PAGE

Oxygen Monitor Operating Manual

ECO-MIX COMPLETE WATER TEMPERATURE CONTROL STATION

EVO192 v3.0 Fire and Burglary What s New

Submittal S-NV-200-LF-M DIGITAL TEMPERATURE CONTROL STATION. Valve assembly is ASSE 1017 Certified. Valve assembly is cupc Certified

MC4000 Series Advanced Solid State Dual Unit Lead/Lag Controller with Ethernet Remote Communication Option

INSTALLATION INSTRUCTIONS

The Kryos LN2 Liquid Level Control & Cryogenic Temperature Control

Remote Storage Safety 3 Alarm Installation Guide

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

CO2 Monitor Operating Instructions

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

Sample Draw Aspirator Adapter Operator s Manual

Universal Monitoring System. Model IMEC8A. User Manual Version 1.10 Software version 2.3.1

Model A1700 Series Annunciator

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

1.7. Insulation fault evaluators EDS460/490 EDS461/491

INSTRUCTION MANUAL Portable Refrigerator Units MODEL 15-LITER Including the Standard Battery Backup System (BBS)

FOR TM-16 EMERGENCY WARNING SYSTEM

600 Range Dialer Installation Manual. Version 1.0

Product Manual SZ1145

Two-Channel Gas Controller

RMS/RPX Reader. User Manual

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

Laboratory Airflow Monitors & Controls TYPE C STANDARD & NIGHT SETBACK LED & DIGITAL - VAV SYSTEMS

Installation Manual. ATS Remote Annunciator Catalog 5350 DANGER WARNING D

FLOW CONTROLLER TYPE S/601

Analox 1000 Series. User Manual. Analox Sensor Technology Ltd. 15 Ellerbeck Court, Stokesley Business Park North Yorkshire, TS9 5PT, UK

GLOBAL. InstallatIon & operation manual

Setup Instructions. This manual is only valid for A36D/TPSD Chargers. equipped with a 341S control card with P341S0012 or P341S0013 software

SCR100 User Manual. Version:1.1 Date:Dec 2009

1.7. Insulation fault evaluators EDS460/490 EDS461/491

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information) Rev

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

Toxic and Explosive Smart Gas Monitor PN / Installation and User Manual

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

UNC100 Integra Manual

MODEL B2 INSTALLATION MANUAL

M2 Rig Monitor Operator s Manual

Product Manual SZ1144

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

Alarm Tone Generator Model AG17

Dry Contact Probe DCP (#30008)

K00364 Electronic Bin Thermostat

Tinytag Plus LAN Data Logger with Temperature & Relative Humidity Probe (-25 to +85 C/0 to 100% RH) Standalone. Tinytag Connect

HOME AUTOMATION, INC. Lumina and Lumina Pro Lighting and Automation System. Quick-Start Installation Guide

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

THX-DL Data Logger USER & INSTALLATION MANUAL V Refrigeration

NU2 Smart Power Supply (SPS) Manual

HMS 1100 Installation Manual

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

W1/B, O, W2/E, Y1, Y2, G. Gas or electric. Wireless, 915MHz, proprietary protocol. Up to 100 feet 24VAC, 2.4VA. Molded plastic

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Central Temperature Monitoring/Control System (I IOT Cloud solution)

Analog Room Pressure Monitor RPC Series

D3000. Installation & Setup Guide

Fire Command Keypad. XR5 User s Guide

RADIANT HEATING AND COOLING SYSTEMS CLIMATE CŎNTROL ZONING SYSTEM INSTALLATION GUIDE. Climate Cŏntrol Zoning System Installation Guide

QA16 Addressable System

PTE0705 Electric Fence Monitor

ENGINE MONITOR VOTT MODEL: YEAR WARRANTY

EOS INTERFACE GUIDE AND POINTS LIST For EOS BTCII Firmware Version J1239D-570 and newer

Insulation fault evaluator EDS460-DG

Transcription:

G LMS 188 4P BMS August, 2018 LMS-188-4P-BMS 4 POINT DIGITAL MONITOR/ALARM WITH PROTOCOL CONVERTER OPERATING INSTRUCTIONS! WARNING: This product can expose you to chemicals including lead, which is known to the State of California to cause cancer. For more information, go to www.p65warnings.ca.gov 1360 Elmwood Avenue Cranston, RI 02910 Tel (401) 461-1200 Fax (401) 941-5310 Toll-free (800) 222-1208 www.leonardvalve.com

Table of Contents Front Panel... 2 Sensor Probe... 2 Probe Installation... 3 Power up... 3 Power down Sequence... 3 Runtime Display... 3 Alarm Conditions... 4 Temperature Alarms... 4 Low / High Alarm Limits... 4 Min/Max Actual Readings... 4 Installation Instructions... 5 Setting the IP Address... 5 LMS BMS/ProtoNode Connectivity/Wiring Diagrams... 6 LMS Overview... 8 RDU Option Installation Instructions....9 Solenoid Valve Control AC Powered Solenoid Control Option (SCO).......11 DC Powered Solenoid Control....12 Appendix A ProtoNode Startup Guide. 33 Pages LMS BMS Operating Manual Page 1

Front Panel The Multi-Probe Alarm System front panel consists of the following: Graphic LCD Channel Status LEDs (STATUS) Alarm LED (ALARM) Audible alarm indicator (buzzer) Buttons o Test & Reset (TEST/RESET) o Step button (STEP) o Alarm Limits & decrement button ( ) (DOWN) o Min/Max & increment button ( ) (UP) o Mute & Menu increment button (MUTE/MENU) Sensor Probe The probes supplied with the Multi-Probe Alarm System are highly accurate temperature sensors. The sensor may be put in water or other mild aqueous solutions from -148 F to 212 F. NOTE: Avoid submerging the probe in solvents or harsh chemicals. Use protective thermowells when monitoring such materials. NOTE: The warranty does NOT cover damage to probes or electronics that is caused by exceeding temperature limitations, or damage to probes caused by using them in solvents or other unsuitable environments. LMS BMS Operating Manual Page 2

NOTE: If the displayed temperature shows a consistent high (> 212 F) or low (< -148 F) value, most likely, the probe has failed. Probe Installation RTD sensors supplied with the LMS 188 4P should be installed using the supplied fittings, which are 1/2 MNPT x 1/8 compression. After installing the fitting into a tee, insert the RTD into the fitting and adjust the depth of the probe so as the tip of the probe is approximately at the center of the piping. Tighten the nut finger tight, then with a small wrench turn the nut 1/4 to 1/2 turn past finger tight. Warning do not overtighten. Power up Shows LMS-188-4P-BMS startup screen. NO BATTERY Power Down + Install Battery The unit will run without a backup battery but will show NoBatt! on the display to indicate lack of backup battery. When a battery is properly installed battery status is shown on the display up arrow charging solid block full charge flashing block or block with blank lines battery problem Power down Sequence To shut off the battery to allow complete power down: Tap the TEST/RESET button to enter relay test, then unplug unit. Alternately you may Press-and-Hold the TEST/RESET button to trigger a hardware reset, and while the screen is blank unplug the unit and then Release the button. Runtime Display The runtime display shows the current readings of 4 probes. T1 Hot, T2 Cold, T3 Mixed and T4 Return. 1: 147'F 2: 55'F 3: 120'F 4: 110'F LMS BMS Operating Manual Page 3

Alarm Conditions Temperature Alarms If the readings are within the alarm limits, the STATUS LED will blink green. When the temperature reading meets or exceeds the temperature limits the STATUS LED will blink red. After the probe s alarm delay time is exceeded the unit will blink the ALARM LED and beep the buzzer. The user can MUTE the buzzer by tapping the MUTE/MENU button. The unit will reduce the audible signal from a loud beep, to a quieter and less frequent chirp. It will remain muted until MUTE time expires or a different probe goes into alarm. Once the Alarm state has been signaled the unit will wait the Relay Delay time before tripping the Relay. Limit Parameters 1 Low, 1 High, 2 Low, 2 High, 3 Low, 3 High, 4 Low, 4 High Time Parameters 1AlarmDelay, 2AlarmDelay, 3AlarmDelay, 4AlarmDelay, RelayDelay, Mute Low / High Alarm Limits For a quick view the Low and High Alarm Limits tap the DOWN ARROW. AlarmLow 110 F 1 2 3 4 AlarmHigh 160 F AlarmLow 34 F AlarmHigh 130 F AlarmLow 100 F AlarmHigh 130 F AlarmLow 100 F AlarmHigh 130 F Min/Max Actual Readings To view the Min/Max readings since power up or user commanded reset, tap the UP ARROW. ActualMin 144 F 1 ActualMax 152 F ActualMin 52 F 2 ActualMax 59 F ActualMin 118 F 3 ActualMax 124 F ActualMin 107 F 4 ActualMax 118 F To manually reset the Min/Max readings, while the Min/Max readings are shown on the display, tap the TEST/RESET button. You will be asked to repeat TEST/RESET to confirm. LMS BMS Operating Manual Page 4

Installation Instructions Setting the IP Address To begin, do not plug in the Ethernet cable at this time. First enter parameters in the LMS. To configure the LMS to send temperature data to the ProtoNode please configure a static IP for the LMS and the ProtoNode and set the subnet mask and gateway. At Runtime tap MENU, you will see Edit Limits. Then tap MENU AND RESET simultaneously to access the *SETUP* group of parameters. Use STEP to advance to the IP parameters. If you need to step back, use the TEST/RESET button to step back. Special Group *SETUP* LMS IP1, LMS IP2, LMS IP3, LMS IP4, LMS IP 1.2.3.4 ProtoNode1, ProtoNode2, ProtoNode3, ProtoNode4, ProtoNode IP 1.2.3.4 Netmask1, Netmask2, Netmask3, Netmask4, Netmask 1.2.3.4 Gateway1, Gateway2, Gateway3, Gateway4, Gateway 1.2.3.4 1 Offset, 2 Offset, 3 Offset, 4 Offset, # channels, 1 Define, 2 Define, 3 Define, 4 Define, 0:tenthC 1:wholeC 2:tenthF 3:wholeF 4:wholeRH Relay Def, 0:single unit relay 1:individual channel relays DoorAlarm -1:AlarmOnContactClosed 0:NoAlarm 1:AlarmOnContactOpen To modify parameter values use DOWN and UP Enter the the IP Address for the LMS s Ethernet port in the LMS IP parameters. Enter the the IP Address for the ProtoNode s Ethernet port in the ProtoNode parameters. If necessary, change the Subnet Mask setting in the Netmask parameters. If necessary, change the IP Gateway setting in the Gateway parameters. NOTE: If the LMS is connected to a router, the IP Gateway of the ProtoNode should be set to the IP Address of that router. Once you have set all parameters, use MENU to step back to the runtime screen Hold the TEST/RESET button until the screen goes blank. This will reset the unit and restart with the assigned IP Now plug the Ethernet cable from the LMS to: IF THE BUILDING MANAGEMENT SYSTEM USES ETHERNET the network hub or router. OR IF THE BUILDING MANAGEMENT SYSTEM DOES NOT USE ETHERNET the ProtoNode. LMS BMS Operating Manual Page 5

LMS BMS/ProtoNode Connectivity/Wiring Diagrams If Building Management System uses Ethernet/IP Protocol Both the LMS-188-4P-BMS and the ProtoNode need to connect to separate 10/100 Ethernet jacks using standard CAT-5 Ethernet Patch Cables (supplied by others). They need to be connected to a switch or router on the same Ethernet Subnet as the BMS. See Figure 1. FIGURE 1 If Building Management System DOES NOT USE Ethernet/IP Protocol In this case, the LMS-188-4P-BMS Ethernet port can be directly connected to the ProtoNode s Ethernet port via standard CAT-5 Ethernet Patch Cables (supplied by others), and then the ProtoNode will be connected to the BMS via the output RS-485 connector on the ProtoNode box. In this case, serial communications with the BMS will be accomplished by using twisted pair wires on the RS-485 connection. See Figure 2. FIGURE 2 LMS BMS Operating Manual Page 6

LMS BMS Operating Manual Page 7

LMS Overview Buttons: TEST/RESET, STEP, Runtime Display 1: 147'F 2: 55'F 3: 120'F 4: 110'F DOWN, UP, MUTE/MENU Edit Parameters At Runtime tap MENU Repeat MENU, MENU,.. To Edit Limits, Edit Times, Return to Runtime Edit Limits or while in Edit tap MENU AND RESET simultaneously to access *SETUP* group 1 Low 110 To step through parameters in group use STEP To STEP BACK tap TEST To modify parameter values use DOWN, UP To step out of edit and back to runtime screen use MENU Group 1 Limits 1 Low, 1 High, 2 Low, 2 High, 3 Low, 3 High, 4 Low, 4 High Group 2 Times 1AlarmDelay, 2AlarmDelay, 3AlarmDelay, 4AlarmDelay, RelayDelay, Mute Special Group *SETUP* LMS IP1, LMS IP2, LMS IP3, LMS IP4, LMS IP 1.2.3.4 ProtoNode1, ProtoNode2, ProtoNode3, ProtoNode4, ProtoNode IP 1.2.3.4 Netmask1, Netmask2, Netmask3, Netmask4, Netmask 1.2.3.4 Gateway1, Gateway2, Gateway3, Gateway4, Gateway 1.2.3.4 1 Offset, 2 Offset, 3 Offset, 4 Offset, # channels, 1 Define, 2 Define, 3 Define, 4 Define, 0:tenthC 1:wholeC 2:tenthF 3:wholeF 4:wholeRH Relay Def, 0:single unit relay 1:individual channel relays DoorAlarm -1:AlarmOnContactClosed 0:NoAlarm 1:AlarmOnContactOpen Low/High Alarm Setpoint Display At Runtime tap DOWN 1 2 3 4 AlarmLow 110 F AlarmHigh 160 F AlarmLow 34 F AlarmHigh 130 F AlarmLow 100 F AlarmHigh 130 F AlarmLow 100 F AlarmHigh 130 F 8

Min/Max Temperatures Display At Runtime tap UP ActualMin 144 F 1 ActualMax 152 F ActualMin 52 F 2 ActualMax 59 F ActualMin 118 F 3 ActualMax 124 F ActualMin 107 F 4 ActualMax 118 F Relay Test At Runtime tap TEST Relay Test Relay 15 To Step, tap STEP To Hold, hold STEP * seconds counting down Min/Max Reset *while viewing Min or Max tap RESET Min & Max Reset RESET to confirm STEP to cancel 9

ALARM DELAY MODULE (RDU Option) INSTALLATION INSTRUCTIONS I Description: The Alarm Delay Module is designed to accept dry contact inputs, either Normally Open (N.O.) or Normally Closed (N.C.), and to delay the transmission of the contact change information to another device. II Application: The primary application is in alarm systems where it is desirable to insert a fixed time interval between the detection of an alarm condition and the transmission of the alarm information to monitoring systems, telephone dialers, external services, etc. Such delay is particularly important in areas where short power interruptions are frequent, or where transitory alarm conditions are likely to occur. The user can select a time period of delay that results in the minimum number of "false" (self-correcting) alarm transmissions while still providing the degree of safety required. III Installation: 1. Remove the plastic case cover by removing the 2 Phillips screws from the back. Apply light pressure on the face plate, the cover and face plate will come off together. 2. Locate the ALARM INPUT switch on the circuit board. Move the switch to the condition of the contacts in the alarm sending device when in the NON-ALARM condition. The unit is shipped with the switch in the N.O. (Normally Open) position, this will be correct for the majority of installations, however, if your alarm device opens its contacts when it alarms, simply slide the switch to the N.C. position. 3. Locate the row of pins on the short edge of the board labeled "minutes". A shorting clip will be at the 8 minute position. In this position the alarm delay module will require 8 minutes of CONTINUOUS incoming alarm indication before sending the alarm status on to the next system. Move the jumper to the set of pins marked either 0.5, 1, 2, 4, 8, 16, or 32 minutes, as your needs require. The pair of pins marked "T" are for test purposes and should not be used. 4. Install the signal wires from your alarm. Route the wires through the drilled hole at the bottom of the case and to the terminals marked 1 & 2. 5. Install the output wires to your output device, route the wires through the drilled hole at the bottom of the case and to the terminals marked 4 & 5 if it requires contact closure for operation or to terminals 3 & 4 if it requires contact opening for operation. 6. Install a 9 volt rechargeable battery in the holder provided if you desire the battery back up function AND you have the 120 Volt adapter. If you do not have the 120 Volt adapter you may use any 9Volt battery, we recommend Alkaline. 7. Check the system for proper operation and reassemble. 8. Using the peel-and-stick Velcro provided, mount the RDU where the LED indicators can be easily seen. 10

IV Operation When the unit is monitoring there are no LEDs lit, pressing RESET will light the green LED to indicate OK. A flashing yellow light indicates that an alarm condition is being timed. A flashing red light means that an alarm condition has persisted for the set time and has been transmitted to the monitoring device, this LED will continue to flash even if the alarm condition has corrected itself. Pressing RESET will cause the red LED to stop flashing and reset the output contacts to their normal non-alarm state, if the alarm condition persists the yellow LED will again flash to indicate timing and, after timing out, will light the red LED and change the output contacts. NOTE It is important that the battery condition be checked regularly by pressing RESET. A dead battery may prevent proper operation of the Alarm Delay Module. This is the hookup from a relay (contact) output of an LMS-188-4P-BMS, or other device, to the RDU. Use the slide switch on the main board to choose N.O. or N.C. input. On the output side, the RDU offers Normally Open (4, 5) or Normally Closed (3, 4) contacts, and may be connected to a dialer, beeper, strobe light, etc. 11

SOLENOID CONTROL OPTION PROVIDED BY LEONARD VALVE Description: The Solenoid Control Option (SCO) is designed to accept dry contact inputs, either Normally Open (N.O.) or Normally Closed (N.C.), in order to switch an AC powered solenoid opened or closed. Solenoid valve and associated power supply are to be provided by others. Application: The primary application is in systems where it is desirable to control an AC powered solenoid in the event that the alarm on the LMS-188-4P-BMS is active. When in non-alarm condition the relay is in a N.O. state and the solenoid will allow water to flow through it freely. Once the alarm is active, the relay on the LMS-188-4P-BMS will switch to N.C. and the solenoid will shut down. Solenoid valve and associated power supply are to be provided by others. Installation: Included with every SCO is a 12 VDC/600 ma power source with a 10 lead that requires a dedicated 110 VAC outlet to plug into. See wiring diagram below for reference. Do Not Energize SCO, LMS-188-4P-BMS, or solenoid valve until wiring is complete. Solenoid valve and associated power supply are to be provided by others. 1. Connections from the power source to the SCO (+ side to terminal 7), terminal to solid state relay (terminals 3+ to 8), and power source to solid state relay (- side to terminal 4-) have been made at the factory. 2. Properly ground the SCO by using the screw provided inside of the enclosure and connect to suitable earth ground 3. Connect terminal 5 (12VDC) to the COMMON C terminal (9) of the LMS-188-4P- BMS relay switch. 4. Connect either terminal 9 or 11 from the LMS-188-4P-BMS relay switch to terminal 6 on the terminal strip. Use terminal 9 with N.C. solenoids; use terminal 11 with N.O. solenoids. 5. Connect the positive side of the solenoid power supply to terminal 1 on the solid state relay. 6. Connect terminal 2 on the sold state relay to the positive side of the solenoid valve. Complete the circuit by connecting the neutral side of solenoid to the neutral side of power supply. LMS BMS Operating Manual Page 12

DC POWERED SOLENOID CONTROL HARDWARE SUPPLIED BY OTHERS Description: This solution is for systems that utilize a DC powered solenoid valve and want to make use of the SPDT relay switch included with LMS-188-4P-BMS. Solenoid valve and associated power supply are to be provided by others. Application: The primary application is in systems where it is desirable to control a DC powered solenoid in the event that the alarm on the LMS-188-4P-BMS is active. When in non-alarm condition the relay is in a N.O. state and the solenoid will allow water to flow through it freely. Once the alarm is active, the relay on the LMS-188-4P-BMS will switch to N.C. and the solenoid will shut down. Solenoid valve and associated power supply are to be provided by others. Installation: Solenoid power supply is to be supplied by others and is not available from Leonard Valve. The relay contacts are rated up to 30 V/1A. See wiring diagram below for reference. Do Not Energize LMS-188-4P-BMS or solenoid valve until wiring is complete. Solenoid valve and associated power supply are to be provided by others. 1. Connect positive side of power supply to the COMMON terminal (2). 2. Connect either terminal 1 or 3 from LMS-188-4P-BMS relay switch to positive side of DC solenoid. Use terminal 1 with N.C. solenoids; use terminal 3 with N.O. solenoids. 3. Connect neutral side of power supply directly to neutral side of DC solenoid. LMS BMS Operating Manual Page 13

LMS BMS Operating Manual Page 14