Test Report: ICL/H18/9039 Rev 1

Similar documents
Test Report: ICL/CR15/11/087

Test Report No: ICL/H17/7967

ASTM F25 SEMINAR Fire Testing for SOLAS and Navy Vessels New Test Procedures and Materials Approval Process

Test report. NanoPhos coating system EPR and EEN. Name of client: NanoPhos SA. Date: Pages: 5 Encl.: 1 Ref: BP / KTO

BS EN ISO : 2010

BS EN ISO : 2010

Test Report Reg.no 12.

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

IMO Resolution MSC 61(67): Annex 1: Part 2

BS EN ISO : 2010

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

EU DECLARATION OF CONFORMITY (Doc) issued in accordance with the MARINE EQUIPMENT DIRECTIVE (MED) and EU/US MRA

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

NF X : Parts 1, 2, 3, 4 & 5

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

EN : A Report To: Poliuretanos S.A. Document Reference: (Issue 2), (Issue 2) & (Issue 4) Date: 13 th February 2015

Review Fire Test Report

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

BS EN : 2001 & IEC :2000

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

BCTC CARPET TECHNICAL CENTRE

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

C-01 FIRE DECKS AND BULKHEADS

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

BS 476: Part 6: 1989+A1:2009

BS 476: Part 6: 1989+A1:2009

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:

Reaction to fire testing of Vescom vinyl wall covering with a Fibre Structure, a total weight of 550 g/m 2 according to EN 13823:2002

Contact person Date Reference Page Richard Johansson P (2) Fire Research

Benefiting Government, Industry and the Public Through Innovative Science and Technology. Barry L. Badders, Jr. P.E.

Vescom bv Sint-Jozefstraat AV Deurne Nederland

New European Fire Testing Classification for Construction Products

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

Analysis Report

Reaction to fire classification report No C-rev.1

IMO COMPREHENSIVE REVIEW OF THE FIRE TEST PROCEDURES CODE

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

TFI Report Reaction to fire test

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Analysis Report

Reaction to fire classification report No C

First Revision No. 6-NFPA [ Section No. 2.2 ]

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

Fire Test Reports for Interpon D Powder Coatings

New European Cable Testing and Classification

Classification of Fire Performance of Wall and Ceiling Lining Materials

WARRES No Page 1 of 27. Fire Resistance Test Generally In Accordance With BS 476: Part 22: 1987, Clause 5, on an Insulated Fabric Barrier

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Test on extruded rigid PVC profile for concrete formwork at 50 kw/m² irradiance in

ISO INTERNATIONAL STANDARD. Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source

Y. ORMIERES. Fire risk analysis method for nuclear installations

ISO INTERNATIONAL STANDARD

RESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO

Global Requirements for the Fire Protection of Ships. Dr Janet Murrell Warrington Certification Ltd

In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa

Heat and Smoke Release of a Ceiling-Installed Speaker

PREDICTING LARGE-SCALE FIRE PERFORMANCE FROM SMALL- SCALE FIRE TEST DATA

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

CERTIFICATE OF APPROVAL No ME 5085

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

Classification of reaction to fire performance in accordance with EN : A1: 2009 on Superfoil SFNC. Prepared for:

Public Comment No. 1-NFPA [ Section No ]

Additional reaction to fire classification report No H

NBS Smoke Density Chamber

Are Your Kitchen Hood Filters Compliant?

BS 6387: 1994 Specification for performance requirements for cables required to maintain circuit integrity under fire conditions.

Analysis Report

MGN 453 (M) Maritime and Coastguard Agency Logo MARINE GUIDANCE NOTE

CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation

DualGuard Fluoropolymer Barrier FRP Duct. Composites USA. Fluoropolymer Barrier FRP Duct. A Critical Process Systems Group Company LISTED

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

Report VNLF Test Report

Fire propagation over combustible exterior facades exposed to intensified flame in Japan

Annex to the Accreditation Certificate D-PL according to DIN EN ISO/IEC 17025:2005

SBI. Single Burning Item - EN THE BENCHMARK IN FIRE TESTING

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

ISO INTERNATIONAL STANDARD. Reaction to fire tests for floorings Part 1: Determination of the burning behaviour using a radiant heat source

Centrum stavebního inženýrství a.s.

Fire Test Methods ASTM NFPA UL ISO IEC

Fire Tests of Non-Metallic Materials for Walls and Ceilings in Rolling Stock

The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

FIRE TESTING SERVICES FIRE TESTING SER

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

Full-scale test of fire detection in a facade using heat detection cable and flame detector

Transcription:

Interscience Fire Laboratory Building 63 Haslar Marine Technology Park Haslar Road, Gosport Hampshire PO12 2AG United Kingdom Tel. : +44 (0) 20 8692 5050 Fax.: +44 (0) 20 8692 5155 Email: firetesting@intersciencecomms.co.uk Test Report: ICL/H18/9039 Rev 1 International Maritime Organisation, Fire Test Procedure Code: 2010 Part 5 APPENDIX 1 FIRE TEST PROCEDURES FOR SURFACE FLAMMABILITY OF BULKHEAD, CEILING, DECK FINISH MATERIALS AND PRIMARY DECK COVERINGS Sponsored By Vescom BV St. Jozefatraat 20 5753AV Deurne The Netherlands Registered Office: Building 63, Haslar Marine Technology Park, Haslar Road, Gosport PO12 2AG, UK Email: firetesting@intersciencecomms.co.uk; Web: intersciencecomms.co.uk Company Registration 1896939 VAT No. GB 407 519 5 54 Page 1 of 6

Test Report: ICL/H18/9039 Rev 1 International Maritime Organisation, Fire Test Procedure Code: 2010 Part 5 APPENDIX 1 FIRE TEST PROCEDURES FOR SURFACE FLAMMABILITY OF BULKHEAD, CEILING, DECK FINISH MATERIALS AND PRIMARY DECK COVERINGS Sponsored By Vescom BV St. Jozefatraat 20 5753AV Deurne The Netherlands 1 Introduction International Maritime Organisation, Fire Test Procedure Code Part 5 Appendix 1: FIRE TEST PROCEDURES FOR SURFACE FLAMMABILITY OF BULKHEAD, CEILING, DECK FINISH MATERIALS AND PRIMARY DECK COVERINGS The principle of the test method is for evaluating flammability characteristics of specimens held in the vertical orientation. By exposure to a radiant heat source and a pilot flame, means are provided to observe the times to ignition, spread and extinguishment of flames along the length. Additionally, the measurement of the stack gas thermocouples are taken as the burning progresses. The test method provides a means for the comparative assessment of products, however, it does not model a real fire situation and the results cannot therefore be used to describe the fire hazard of materials under actual fire conditions. 2 Description of Test Specimens The description of the specimens given below has been prepared from information provided by the sponsor of the test. All values quoted are nominal, unless tolerances are given. The product was a 0.37mm thick Vescom vinyl wall covering with digital printing (Batch Number 165618-001) having a nominal mass of 350g/m 2 and consisting of : Face: Flame retardant Vinyl film nominally 0.2mm thick. (Weight approximately 310g/m 2 ) Backing: Non woven Cutron (Weight 40g/m 2 ). The wall covering was bonded to one face of a 12mm thick Calcium silicate board (Density 780g/m 3 ) using Starch and PVAc adhesive referenced Vescom 2000 applied at 170g/m 2. The sponsor of the test did not supply further details relating to the composition of the product tested. Page 2 of 6

3 Conditioning of Specimens The specimens were received on 6 th March 2018 The specimens were conditioned to constant mass at 23 ± 2 C and 50 ± 5% RH, before testing. 4 Date of Test The tests were performed on 28 th March 2018 5 Test Procedure The test was performed in accordance with the procedure called up in International Maritime Organisation, Fire Test Procedure Code Part 5 Appendix 1: FIRE TEST PROCEDURES FOR SURFACE FLAMMABILITY OF BULKHEAD, CEILING, DECK FINISH MATERIALS AND PRIMARY DECK COVERINGS. This report should be read in conjunction with these Standards. 6 Test Results The test results relate only to the behaviour of the specimens of the product under the particular conditions of test; they are not intended to the sole criterion for assessing the potential smoke and toxic emission hazard of the product in use. The test results relate only to the specimens of the product in the form in which they were tested. Small differences in the composition or thickness of the product may significantly affect the performance during the test and will therefore invalidate the test results. It is the responsibility of the supplier of the product to ensure that the product, which is supplied, is identical with the specimens, which were tested. Uncertainty measurement has not been taken into account when presenting the test results. The results of tests are summarised below in Table 1:- Average of 3 Parameter specimens Critical flux at extinguishment, CFE (kw/m 2 ) 43.73 Heat for sustained burning, Qsb (MJ/m 2 ) 2.94 Total heat release, Qt (MJ) 0.01 Peak heat release, qp (kw) 0.14 Flaming droplets 0 Full results are given in Appendix 1 Table 2 and Table 3. Page 3 of 6

7 Requirements Table 1 : Surface flammability criteria Bulkhead, wall and Floor coverings Primary deck ceiling linings coverings CFE (kw/m 2 ) 20.0 7.0 7.0 Qsb (MJ/m 2 ) 1.5 0.25 0.25 Qt (MJ) 0.7 2.0 2.0 Qp (kw) 4.0 10.0 10.0 Burning droplets Where: 8 Conclusion Not produced No more than 10 burning drops CFE = Critical flux at extinguishment Qsb = Heat for sustained burning Qt = Total heat release Qp = Peak heat release rate Not produced When tested in accordance with the procedure called up in International Maritime Organisation, Fire Test Procedure Code Part 5 Appendix 1 the product meets the requirements for Bulkhead, wall and ceiling linings. Prepared by Approved by C. B. Chong S. Kumar Fire Scientist Technical Manager Date of Issue: 5 th April 2018 Date of issue Revision 1: 10 th April 2018. Page 4 of 6

Appendix 1 Table 2 Parameter Run 1 Run 2 Run 3 Average Length of test (s) 600 600 600 600 Heat for ignition (MJ/m 2 ) 3.01 2.40 3.33 2.91 Critical flux at extinguishment, CFE (kw/m 2 ) 46.25 45.36 39.58 43.73 Heat for sustained burning, Qsb (MJ/m 2 ) 3.01 2.40 3.40 2.94 Total heat release, Qt (MJ) 0.011 0.008 0.014 0.011 Peak heat release, qp (kw) 0.11 0.17 0.14 0.14 Individual rake data from each specimen run Table 3 Run 1 Run 2 Run 3 Average Time (min, s) to s s s s ignition: 3 2 3 3 station 50mm: 7 6 7 7 station 100mm: 26 31 35 31 station 150mm: 65 52 72 63 station 200mm: 83 83 station 250mm: station 300mm: station 350mm: station 400mm: station 450mm: station 500mm: station 550mm: station 600mm: station 650mm: station 700mm: station 750mm: Flaming out time: 168 112 98 126 Flaming droplets: 0 0 0 0 Final travel (mm) 150 160 225 178 Length of the test (Sec) 600 600 600 600 Page 5 of 6

IMO FTPC Part 5 - HRR comparison 2 1.8 1.6 1.4 HRR (kw) 1.2 1 0.8 Run 1 Run 2 Run 3 0.6 0.4 0.2 0 0 200 400 600 800 Time (s) Chart 1. HRR vs time curves for the 3 specimens tested Page 6 of 6