AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers

Similar documents
Performance Rating of Commercial and Industrial Unitary Air-Conditioning Condensing Units

Standard for 2006 Performance Rating Of Positive Displacement Ammonia Compressors and Compressor Units

AHRI Standard 870 (I-P) Standard for Performance Rating of Direct Geoexchange Heat Pumps

AHRI Standard 751 (SI) 2016 Standard for Performance Rating of Thermostatic Refrigerant Expansion Valves

Performance Rating of Refrigerant Pressure Regulating Valves

Performance Rating of Heat Pump Pool Heaters

ANSI/AHRI Standard 911 (SI) 2014 Standard for Performance Rating of Indoor Pool Dehumidifiers

Performance Rating of Automatic Commercial Ice-makers

2013 Guideline for Specifying the Thermal Performance of Cool Storage Equipment. AHRI Guideline T (I-P)

Performance Rating of Heat Pump Pool Heaters

Flow Capacity Rating of Suction Line Filters and Suction Line Filter Driers

Sound Performance Rating of Outdoor Unitary Equipment

ANSI/AHRI Standard 620 (I-P) 2014 Standard for Performance Rating of Self-contained Humidifiers for Residential Applications

Performance Rating of Computer and Data Processing Room Air Conditioners

Sound Performance Rating of Non-ducted Indoor Airconditioning

Performance Rating of Active Chilled Beams

Performance Rating of Unit Ventilators

Specifications for Fluorocarbon Refrigerants

Specifications for Fluorocarbon Refrigerants

2016 Annual Conference

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

AIR CONDITIONERS MINIMUM ENERGY PERFORMANCE, LABELLING AND TESTING REQUIREMENTS FOR LOW CAPACITY WINDOW TYPE AND SINGLE-SPLIT

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

Application Engineering

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

Performance Rating of Commercial and Industrial Humidifiers

Pressure Enthalpy Charts

Low Global Warming Refrigerants For Commercial Refrigeration Systems

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

A Treatise on Liquid Subcooling

Acoustical Test Methods and Sound Power Rating Procedures for Transport Refrigeration Equipment

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

Refrigerant Glide and Effect on Performances Declaration

ANSI/AHRI Standard Standard for Performance Rating of Indoor Pool Dehumidifiers

REFRIGERATION CYCLE Principles of Mechanical Refrigeration Level 2: Cycle Analysis

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

Carwin COMPRESSOR SELECTION PROGRAM

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Technical Bulletin (TB-0037)

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

January 16 th, 2014 New York City

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

Sustainable Techniques in Refrigerated Space

RSES Technical Institute Training Manual 1 70 hours, 70 NATE CEHs, 7.2 CEUs

B. A. T. Basic Appliance Training

WATER-SOURCE HEAT PUMPS CERTIFICATION PROGRAM For 50 Hz Products

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

AIR CONDITIONING. Carrier Corporation 2002 Cat. No

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Specifications for Refrigerants

System Modeling of Gas Engine Driven Heat Pump

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

AHRI Guideline W (I-P) 2014 Guideline for Selecting, Sizing, & Specifying Packaged Air-to-Air Energy Recovery Ventilation Equipment

FORM ACCL-PC1 ACCL WITNESS TEST PROCEDURE AND CHECKLIST

UPDATED: DECEMBER 28, 2018 U.S. DEPARTMENT OF ENERGY (DOE) WALK IN COOLER & FREEZER ENERGY EFFICIENCY RULEMAKING SUMMARY & FREQUENTLY ASKED QUESTIONS

Multiple split-system air-conditioners and air-to-air heat pumps Testing and rating for performance

AHRI Guideline N Guideline for Assignment of Refrigerant Container Colors. ARI Standard 1200

ANSI/AHRI Standard 1351 (SI) 2014 Standard for Mechanical Performance Rating of Central Station Air-handling Unit Casings

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

Section 1: Theory of Heat Unit 3: Refrigeration and Refrigerants

Low GWP Refrigerants for Air Conditioning Applications

The Essentials Of Working With R-410A

ISO 7183 INTERNATIONAL STANDARD. Compressed-air dryers Specifications and testing. Sécheurs à air comprimé Spécifications et essais

AHRI Certification Program Scopes - COOLING

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

Performance of an Improved Household Refrigerator/Freezer

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

U.S. DEPARTMENT OF ENERGY (DOE) WALK-IN COOLER & FREEZER ENERGY EFFICIENCY RULEMAKING SUMMARY & FREQUENTLY ASKED QUESTIONS. Rulemaking History

R07. Answer any FIVE Questions All Questions carry equal marks *****

The Saturation process

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

REFRIGERATION AND AIR CONDITIONING

BASIC HEAT PUMP THEORY By: Lloyd A. Mullen By: Lloyd G. Williams Service Department, York Division, Borg-Warner Corporation

Specifications for Refrigerants

1997 STANDARD for APPLICATION OF SOUND RATING LEVELS OF OUTDOOR UNITARY EQUIPMENT. Standard NORTH FAIRFAX DRIVE! ARLINGTON, VIRGINIA 22203

R4H4. Product Specifications

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

2015 Standard for Performance Rating of Refrigerant Recovery Equipment and Recovery/Recycling Equipment

Steady and Cyclic Performance Testing of Packaged R-410A Units

0.4 In the preparation of this standard, assistance has been derived from the following standards:

Refrigeration Technology in Building Services Engineering

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Energy Use in Refrigeration Systems

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

LONG LINE SET APPLICATION R-410A

Transcription:

AHRI Standard 1250P (I-P) 2009 Standard for Performance Rating of Walk-In Coolers and Freezers -

ERRATA SHEET FOR AHRI STANDARD 1250 (I-P)-2009, PERFORMANCE RATING OF WALK-IN COOLERS AND FREEZERS December 2015 The corrections listed in this errata sheet apply to AHRI Standard 1250 (I-P)-2009. Page Erratum 25 Equation 67. The temperature term t IIH in the denominator of Equation 67 must be changed to t VH. This was a typo that must be corrected. The correction only applies to the second instance of t IIH in the denominator. Current equation: b= EER SS k=1 (t IH )-EER SS k=2 (tiih )-d [EER SS k=1 (tih )-EER SS k=i (tvh )] t IH- t IIH -d [t IH- t IIH ] 67 New equation: b= EER SS k=1 (t IH )-EER SS k=2 (tiih )-d [EER SS k=1 (tih )-EER SS k=i (tvh )] t IH- t IIH -d [t IH- t VH ] 67 Page t VH : t IIH : The outdoor temperature at which the unit, when operating at the intermediate capacity that is tested under the designated condition, provides a refrigeration capacity that is equal to the total walk-in system heat load during high load period, The outdoor temperature at which the total walk-in system heat load equals system net capacity when the compressor operates at high or maximum capacity (k=2) during the high load period, Erratum 27 Equation 83. The temperature term t IIH in the denominator of Equation 83 must be changed to t VL. This was a typo that must be corrected. The correction only applies to the second instance of t IIH in the denominator. Current equation: b= EER SS k=1 (t IH )-EER SS k=2 (tiih )-d [EER SS k=1 (tih )-EER SS k=i (tvl )] t IH- t IIH -d [t IH- t IIH ] 83 New equation: b= EER SS k=1 (t IH )-EER SS k=2 (tiih )-d [EER SS k=1 (tih )-EER SS k=i (tvl )] t IH- t IIH -d [t IH- t VL ] 83 t VL : t IIL : The outdoor temperature at which the unit, when operating at the intermediate capacity that is tested under the designated condition, provides a refrigeration capacity that is equal to the total walk-in system heat load during low load period, The outdoor temperature at which the total walk-in system heat load equals system net capacity when the compressor operates at high or maximum capacity (k=2) during the low load period,

IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. AHRI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. AHRI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard is a new standard. For SI ratings, Refer to AHRI Standard 1251 (SI) 2009. Price $10.00 (Members) $20.00 (Non-Members) Printed in U. S.A. Copyright 2009, by -Conditioning, Heating, and Institute Registered United States Patent and Trademark Office

TABLE OF CONTENTS PAGE Section 1 Purpose... 1 Section 2 Scope... 1 Section 3 Definitions... 1 Section 4 Test Requirements... 3 Section 5 Rating Requirements... 5 Section 6 Calculation for Walk-in Box Load... 17 Section 7 Calculation for Annual Walk-in Energy Factor... 18 Section 8 Symbols and Subscripts... 35 Section 9 Minimum Data Requirements for Published Ratings... 37 Section 10 Marking and Nameplate Data... 37 Section 11. Conformance Conditions... 37 TABLES Table 1 Instrumentation Accuracy... 3 Table 2 Test Operating and Test Condition Tolerances for Steady-State Test... 4 Table 3 Fixed Matched Refrigerator System, Condensing Unit Located Indoor... 5 Table 4 Fixed Matched Refrigerator System, Condensing Unit Located Outdoor... 6 Table 5 Two Matched Refrigerator System, Condensing Unit Located Outdoor... 6 Table 6 Variable Matched Refrigerator System, Condensing Unit Located Outdoor... 7 Table 7 Fixed Matched Freezer System, Condensing Unit Located Indoor... 9 Table 8 Fixed Matched Freezer System, Condensing Unit Located Outdoor... 9 Table 9 Two Matched Freezer System, Condensing Unit Located Outdoor... 10 Table 10 Variable Matched Freezer System, Condensing Unit Located Outdoor... 11 Table 11 Fixed Refrigerator Condensing Unit, Condensing Unit Located Indoor... 14 Table 12 Fixed Refrigerator Condensing Unit, Condensing Unit Located Outdoor... 14 Table 13 Fixed Freezer Condensing Unit, Condensing Unit Located Indoor... 15 Table 14 Fixed Freezer Condensing Unit, Condensing Unit Located Outdoor... 15 i

TABLES (continued) PAGE Table 15 Refrigerator Unit Cooler... 16 Table 16 Freezer Unit Cooler... 16 Table 17 EER for Remote Commercial Refrigerated Display Merchandisers and Storage Cabinets... 31 FIGURES Figure 7-1 Schematic of the operation for units with single capacity compressor... 19 Figure 7-2 Schematic of the various modes of operation for units with two capacity compressors... 21 Figure 7-3 Schematic of the various modes of operation for units with variable capacity compressors... 24 Figure 7-4 Diagram of the linear fit based rating procedure... 29 APPENDICES Appendix A. References Normative... 38 Appendix B. References Informative... 39 Appendix C. Methods of Testing Walk-in Cooler and Freezer Systems Normative... 39 Appendix D. Weather Data in Region IV Normative... 51 TABLES FOR APPENDICES Table C1 Test Readings... 42 Table C2 Data To be Recorded... 43 Table D1 Bin temperatures and corresponding Bin hours for AWEF Calculation... 51 FIGURES FOR APPENDICES Figure C1 Method 1: DX-Dual Instrumentation... 45 Figure C2 Method 2: DX- Calibrated Box... 46 ii

PERFORMANCE RATING OF WALK-IN COOLERS AND FREEZERS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish, for walk-in coolers and freezers: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data and conformance conditions. 1.1.1 Intent. This standard is intended for the guidance of the industry, including manufacturers, designers, installers, contractors and users. 1.1.2 Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to mechanical refrigeration equipment consisting of an integrated single package refrigeration unit, or separate unit cooler and condensing unit sections, where the condensing section can be located either outdoor or indoor. Controls may be integral, or can be provided by a separate party as long as performance is tested and certified with the listed mechanical equipment accordingly. 2.2 Exclusions. This standard does not apply to: a. Enclosures used for telecommunications switch gear or other equipment requiring cooling b. Enclosures designed for medical, scientific or research purposes c. Performance testing and efficiency characterization of large parallel rack refrigeration systems (condensing unit) Section 3. Definitions All terms in this document follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation -Conditioning and, unless otherwise defined in this section. 3.1 Annual Walk-in Energy Factor (AWEF). A ratio of the total heat, not including the heat generated by the operation of refrigeration systems, removed, in Btu, from a walk-in box during one year period of usage for refrigeration to the total energy input of refrigeration systems, in watt-hours, during the same period. 3.2 Energy Efficiency Ratio, (EER). A ratio of the in Btu/h to the power input values in watts at any given set of Rating Conditions expressed in Btu/W h. 3.3 Forced-Circulation Free-Delivery Unit Coolers (Unit Coolers). A factory-made assembly, including means for forced air circulation and elements by which heat is transferred from air to refrigerant without any element external to the cooler imposing air resistance. These may also be referred to as Coolers, Cooling Units, Units or Evaporators. 3.4 Glide. The absolute value of the difference between the starting and ending temperatures of a phase-change process (condensation or evaporation) for a zeotropic refrigerant exclusive of any liquid subcooling or vapor superheating. 3.5 Gross. The heat absorbed by the refrigerant, Btu/h. This is the sum of the Net and the heat equivalent of the energy required to operate the Unit Cooler. This includes both sensible and latent cooling. 3.6 High Box Load (BLH ). Walk-in box load during a high load period. 3.7 High Load Period. A period of the day corresponding to frequent door openings, product loading events, and other design load factors, 1

3.8 Load Factor. A ratio of the total walk-in system heat load to the steady-state net refrigeration capacity. 3.9 Low Box Load (BLL ). Walk-in box load during a low load period. 3.10 Low Load Period. Any period of the day other than a high load period. 3.11 Net. The refrigeration capacity available for space and product cooling, Btu/h. It is equal to the Gross less the heat equivalent of energy required to operate the Unit Cooler (e.g: evaporator fans, defrost) 3.12 Positive Displacement Condensing Unit. A specific combination of refrigeration system components for a given refrigerant, consisting of one or more electric motor driven positive displacement compressors, condensers, and accessories as provided by the manufacturer. 3.13 Published Rating. A statement of the assigned values of those performance characteristics, under stated rating conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. The term Published Rating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufacturer, at stated Rating Conditions. 2 3.13.1 Application Rating. A rating based on tests performed at application Rating Conditions, (other than Standard Rating Conditions). 3.13.2 Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.14 Rated Fan Power. 3.14.1 For single phase motors, total fan motor input power, W. 3.14.2 For polyphase motors, individual fan motor output power, W. 3.15 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur. 3.15.1 Standard Ratings Conditions. Rating conditions used as the basis of comparison for performance characteristics. 3.16. The capacity associated with the increase in total enthalpy between the liquid refrigerant entering the expansion valve and superheated return gas multiplied by the mass flow rate of the refrigerant. 3.17 "Shall" or "Should". "Shall or should shall be interpreted as follows: 3.17.1 Shall. Where "shall" or "shall not" is used for a provision specified, that provision is mandatory if compliance with the standard is claimed. 3.17.2 Should. "Should," is used to indicate provisions which are not mandatory, but which are desirable as good practice. 3.18 Refrigerant Saturation Temperature. Refrigerant temperature at the Unit Cooler inlet or outlet determined either by measuring the temperature at the outlet of the two-phase refrigerant flow, for a Liquid Overfeed Unit Cooler, or by measuring refrigerant pressure and determining the corresponding temperature from reference thermodynamic tables or equations for the refrigerant, ºF. For zeotropic refrigerants, the corresponding temperature to a measured pressure is the refrigerant Dew Point. 3.19 Steady-State Conditions. An operating state of a system, including its surroundings, in which the extent of change with time is within the required limits (refer to Table 2). 3.20 Temperature Difference (TD). The difference between the dry-bulb temperature of the air entering the Unit Cooler and the Refrigerant Saturation Temperature at the unit cooler outlet, ºF.

3.21 Test Measurement. The reading of a specific test instrument at a specific point in time. The Test Measurement may be averaged with other measurements of the same parameter at the same time to determine a Test Reading or averaged over the duration of the test to determine the value for the Test Run. Refer to Table C1 for test reading minimum time rate, number of test readings and minimum test duration. 3.22 Test Reading. The recording of one full set of the Test Measurements required to assess the performance of the test unit. 3.23 Total Walk-in System Heat Load. Total heat load to the walk-in system including walk-in box load and the heat load to the box contributed by the operation of the refrigeration system. 3.24 Volatile Refrigerant. A refrigerant which changes from liquid to vapor in the process of absorbing heat. 3.25 Walk-in Box Load. Heat load to the walk-in box resulting from conduction, infiltration and internal heat gains from equipment that is not related to the refrigeration system, such as lights and anti-sweat heaters, etc. 3.26 Walk-in System High Load. Total Walk-in System Heat Load during a High Load Period. 3.27 Walk-in System Low Load. Total Walk-in System Heat Load during a Low Load Period. Section 4. Test Requirements 4.1 Instruments. All measuring instruments shall be selected to meet or exceed the accuracy criteria listed in Table 1 for each type of measurement. All temperature measurement shall be made in accordance with Table 2, Test Tolerance. Precision instruments and automated electronic data acquisition equipment shall be used to measure and record temperature, pressure and refrigerant flow rate test parameters. All measuring instruments and instrument systems (e.g. data acquisition coupled to temperature, pressure, or flow sensors) shall be calibrated by comparison to primary or secondary standards with calibrations traceable to National Institute of Standards and Technology (NIST) measurements, other recognized national laboratories, or derived from accepted values of natural physical constants. All test instruments shall be calibrated annually, whenever damaged, or when the accuracy is called into question. Table 1. Instrumentation Accuracy Measurement Medium Minimum Accuracy dry-bulb wet-bulb ± 0.2 F Temperature Refrigerant liquid Refrigerant vapor ± 0.5 F Dew Point Others ± 0.5 F ± 1.0 F Relative humidity 1 ± 3 % points rh Pressure corresponding to ± 0.2 F of saturation Refrigerant Pressure temperature ±0.05 inches of mercury Flow Refrigerant 1 % of reading Liquids 1 % of reading Motor kilowatts/amperes/voltage Electrical Auxiliary kilowatt input 1 % of reading (e.g. heater) Speed Motor / fan shaft 1 % of reading Weight Oil / refrigerant solution 0.5 % of reading 3

Table 1. Instrumentation Accuracy Measurement Medium Minimum Accuracy Specific Gravity Brine 1 % of reading Time Hours / minutes / seconds 0.5 % of time interval Note: (1) Relative humidity and air dew point measurements are intended to confirm the dry coil condition. Table 2. Test Operating and Test Condition Tolerances for Steady-State Test Indoor dry-bulb, F temperature... Leaving temperature... Indoor wet-bulb, F temperature... Leaving temperature... Outdoor dry-bulb, F temperature... Leaving temperature... Outdoor wet-bulb, F temperature... Leaving temperature... Electrical voltage, % of reading.... Test Operating Tolerance (1) 3.6 3.6 3.6 3.6 3.6 3.6 3.6 3.6 2.0 Test Condition Tolerance (2) 1.0 0.5 0.5 0.3 Notes: (1) Test Operating Tolerance is the maximum permissible range of any measurement. When expressed as a percentage, the maximum allowable variation is the specified percentage of the average value, (2) Test Condition Tolerance is the maximum permissible variation of the average value of the measurement from the specified test condition. 4

4.2 Method of test/test procedure. The test procedure for walk-in cooler and freezer systems that have matched unit coolers and condensing units, and the procedures of testing condensing units and unit coolers individually for mix-matched systems are described in Appendix C of this standard. 4.3 Test conditions. Walk-in systems, condensing units and unit coolers shall be tested under the standard rating conditions defined in Section 5. Section 5. Rating Requirements 5.1 Standard Ratings. Standard Ratings shall be established at the Standard Rating Conditions in the following listed tables and shall include its associated power input and Energy Efficiency Ratio (EER). When tested with a specified motor, the associated compressor speed (external drive compressors only) shall also be included as part of the rating. The power required to operate all included accessories such as condenser fans, water pumps, controls, and similar accessories shall be accounted for in the power input and Energy Efficiency Ratio. When external accessories such as water pumps, remote fans, and similar accessories are required for the operation of the unit but not included with the unit, the manufacturer shall clearly state that the rated power input and Energy Efficiency Ratio do not account for additional power required by these external accessories. If a water-cooled condenser is used, the cooling water flow rate and pressure drop shall be specified as part of the rating. Table 3. Fixed Matched Refrigerator System, Condensing Unit Located Indoor Test Description Off Cycle Fan Power Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor 35 <50 - - Compressor Off 35 <50 90 75 Compressor On Test Objective Measure fan input wattage during compressor off cycle of Unit Cooler, input power, and EER at Rating Condition 5

Table 4. Fixed Matched Refrigerator System, Condensing Unit Located Outdoor Test Description Off Cycle Fan Power A B C Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-bulb, Wet-Bulb, F Compressor 35 <50 - - Compressor Off 35 <50 95 75 Compressor On 35 <50 59 54 Compressor On 35 <50 35 34 Compressor On Test Objective Measure fan input wattage during compressor off cycle of Unit Cooler, input power, and EER at Rating Condition of Unit Cooler and system input power at moderate condition of Unit Cooler and system input power at cold condition Table 5. Two Matched Refrigerator System, Condensing Unit Located Outdoor 6 Test Description Off Cycle Fan Power A Low Speed A High Speed B Low Speed Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor 35 <50 - - Compressor Off 35 <50 95 75 Mininum 35 <50 95 75 Maximum 35 <50 59 54 Mininum Test Objective Measure fan input wattage during compressor off cycle of Unit Cooler and input power at Rating Condition and minimum compressor capacity of Unit Cooler, input power, and EER at Rating Condition and maximum compressor capacity of Unit Cooler and system

Table 5. Two Matched Refrigerator System, Condensing Unit Located Outdoor Test Description B High Speed C Low Speed C High Speed Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor 35 <50 59 54 Maximum 35 <50 35 34 Minimum 35 <50 35 34 Maximum Test Objective input power at moderate condition and minimum compressor capacity of Unit Cooler and system input power at moderate condition and maximum compressor capacity of Unit Cooler and system input power at cold condition and minimum compressor capacity of Unit Cooler and system input power at cold condition and maximum compressor capacity Table 6. Variable Matched Refrigerator System, Condensing Unit Located Outdoor Test Description Off Cycle Fan Power A Low Speed A Variable Speed Unit Cooler Dry-Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor Test Objective 35 <50 - - Compressor Off Measure fan input wattage during compressor off cycle 35 <50 95 75 Mininum of Unit Cooler and system input power at Rating Condition and minimum compressor capacity 35 <50 95 75 Intermediate * of Unit Cooler and system input power at Rating Condition and intermediate compressor capacity 7

Table 6. Variable Matched Refrigerator System, Condensing Unit Located Outdoor Test Description A High Speed B Low Speed B Variable Speed B High Speed C Low Speed C Variable Speed Unit Cooler Dry-Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor 35 <50 95 75 Maximum Test Objective of Unit Cooler, system input power, and EER at Rating Condition and maximum compressor capacity 35 <50 59 54 Mininum of Unit Cooler and system input power at moderate condition and minimum compressor capacity 35 <50 59 54 Intermediate * 35 <50 59 54 Maximum of Unit Cooler and system input power at moderate condition and intermediate compressor capacity of Unit Cooler and system input power at moderate condition and maximum compressor capacity 35 <50 35 34 Minimum of Unit Cooler and system input power at cold condition and minimum compressor capacity 35 <50 35 34 Intermediate * of Unit Cooler and system input power at cold condition and intermediate compressor capacity 8

Test Description C High Speed Table 6. Variable Matched Refrigerator System, Condensing Unit Located Outdoor Unit Cooler Dry-Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor Test Objective 35 <50 35 34 Maximum of Unit Cooler and system input power at cold condition and maximum compressor capacity *For the intermediate capacity test, the compressor capacity shall be set to 40% of its maximum capacity if possible. Otherwise, it shall be set to the capacity that is the closest to the 40% of its maximum capacity. Table 7. Fixed Matched Freezer System, Condensing Unit Located Indoor Test Description Off Cycle Fan Power Defrost Frost Load Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor -10 <50 - - Compressor Off -10 <50 90 75 Compressor On -10 various 90 75 System Dependent Test Objective Measure fan input wattage during compressor off cycle of Unit Cooler, system input power, and EER at Rating Condition Test according to Appendix C Section C11. Table 8. Fixed Matched Freezer System, Condensing Unit Located Outdoor Test Description Off Cycle Fan Power A Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor -10 <50 - - Compressor Off -10 <50 95 75 Compressor On Test Objective Measure fan input wattage during compressor off cycle of Unit Cooler, system input power, and EER at Rating Condition 9

Table 8. Fixed Matched Freezer System, Condensing Unit Located Outdoor Test Description B C Defrost Frost Load Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor -10 <50 59 54 Compressor On -10 <50 35 34 Compressor On -10 various 95 75 System Dependent Test Objective of Unit Cooler and system input power at moderate condition of Unit Cooler and system input power at cold condition Test according to Appendix C Section C11. Table 9. Two Matched Freezer System, Condensing Unit Located Outdoor Test Description Off Cycle Fan Power A Low Speed A High Speed B Low Speed Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor -10 <50 - - Compressor Off -10 <50 95 75 Mininum -10 <50 95 75 Maximum -10 <50 59 54 Mininum Test Objective Measure fan input wattage during compressor off cycle of Unit Cooler and input power at Rating Condition and minimum compressor capacity of Unit Cooler, input power, and EER at Rating Condition and maximum compressor capacity of Unit Cooler and system input power at moderate condition and minimum compressor capacity 10

Table 9. Two Matched Freezer System, Condensing Unit Located Outdoor Test Description B High Speed C Low Speed C High Speed Defrost Frost Load Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor -10 <50 59 54 Maximum -10 <50 35 34 Minimum -10 <50 35 34 Maximum -10 various 95 75 System Dependent Test Objective of Unit Cooler and system input power at moderate condition and maximum compressor capacity of Unit Cooler and system input power at cold condition and minimum compressor capacity of Unit Cooler and system input power at cold condition and maximum compressor capacity Test according to Appendix C Section C11. Table 10. Variable Matched Freezer System, Condensing Unit Located Outdoor Test Description Off Cycle Fan Power Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor Test Objective -10 <50 - - Compressor Off Measure fan input wattage during compressor off cycle 11

Table 10. Variable Matched Freezer System, Condensing Unit Located Outdoor Test Description A Low Speed A Variable Speed A High Speed B Low Speed B Variable Speed Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor -10 <50 95 75 Mininum -10 <50 95 75 Intermediate * -10 <50 95 75 Maximum -10 <50 59 54 Mininum -10 <50 59 54 Intermediate * Test Objective of Unit Cooler and input power at Rating Condition and minimum compressor capacity of Unit Cooler and input power at Rating Condition and intermediate compressor capacity of Unit Cooler, input power, and EER at Rating Condition and maximum compressor capacity of Unit Cooler and system input power at moderate condition and minimum compressor capacity of Unit Cooler and system input power at moderate condition and intermediate compressor capacity 12

Test Description B High Speed C Low Speed C Variable Speed C High Speed Defrost Frost Load Unit Cooler Dry- Bulb, Table 10. Variable Matched Freezer System, Condensing Unit Located Outdoor Unit Cooler Relative Humidity, % Dry-Bulb, Wet-Bulb, Compressor -10 <50 59 54 Maximum -10 <50 35 34 Minimum -10 <50 35 34 Intermediate * -10 <50 35 34 Maximum -10 various 95 75 System Dependent *For the intermediate capacity test, the compressor capacity shall be set to 50% of its maximum capacity if possible. Otherwise, it shall be set to the capacity that is the closest to the 50% of its maximum capacity Test Objective of Unit Cooler and system input power at moderate condition and maximum compressor capacity of Unit Cooler and system input power at cold condition and minimum compressor capacity of Unit Cooler and system input power at cold condition and intermediate compressor capacity of Unit Cooler and system input power at cold condition and maximum compressor capacity Test according to Appendix C Section C11. 13

Table 11. Fixed Refrigerator Condensing Unit, Condensing Unit Located Indoor* Test Description at Suction A at Suction B Suction Dewpoint, Return Gas, Dry-Bulb, Wet-Bulb, Compressor 23 41** 90 75 Compressor On 18 41** 90 75 Compressor On *Subcooling to be set according to equipment specification and reported as part of standard rating ** Measured at the condensing unit inlet location. Test Objective Determine gross refrigeration capacity and input power of condensing unit at Rating Condition Determine gross refrigeration capacity and input power of condensing unit at Rating Condition Test Description A Suction A A Suction B B Suction A B Suction B C Suction A C Suction B Table 12. Fixed Refrigerator Condensing Unit, Condensing Unit Located Outdoor* Suction Dewpoint, Return Gas, Dry-Bulb, Wet- Bulb, Compressor Test Objective 23 41** 95 75 Compressor On Determine gross refrigeration capacity and input power of condensing unit at Rating Condition 18 41** 95 75 Compressor On Determine gross refrigeration capacity and input power of condensing unit at Rating Condition 23 41** 59 54 Compressor On Determine gross refrigeration capacity and input power of condensing unit at moderate condition 18 41** 59 54 Compressor On Determine gross refrigeration capacity and input power of condensing unit at moderate condition 23 41** 35 34 Compressor On Determine gross refrigeration capacity and input power of condensing unit at cold condition 18 41** 35 34 Compressor On Determine gross refrigeration capacity and input power of condensing unit at cold condition *Subcooling to be set according to equipment specification and reported as part of standard rating ** Measured at the condensing unit inlet location. 14

Test Description at Suction A at Suction B Table 13. Fixed Freezer Condensing Unit, Condensing Unit Located Indoor* Suction Dewpoint, Return Gas, Dry-Bulb, Wet-Bulb, Compressor -22 5** 90 75 Compressor On -28 5** 90 75 Compressor On *Subcooling to be set according to equipment specification and reported as part of standard rating ** Measured at the condensing unit inlet location. Test Objective Determine gross refrigeration capacity and input power of condensing unit at Rating Condition Determine gross refrigeration capacity and input power of condensing unit at Rating Condition Table 14. Fixed Freezer Condensing Unit, Condensing Unit Located Outdoor* Test Description A Suction A A Suction B B Suction A B Suction B C Suction A C Suction B Suction Dewpoint, Suction Gas, Dry-Bulb, Wet-Bulb, Compressor -22 5** 95 75 Compressor On -28 5** 95 75 Compressor On -22 5** 59 54 Compressor On -28 5** 59 54 Compressor On -22 5** 35 34 Compressor On -28 5** 35 34 Compressor On *Subcooling to be set according to equipment specification and reported as part of standard rating ** Measured at the condensing unit inlet location. Test Objective Determine gross refrigeration capacity and input power of condensing unit at Rating Condition Determine gross refrigeration capacity and input power of condensing unit at Rating Condition Determine gross refrigeration capacity and input power of condensing unit at moderate condition Determine gross refrigeration capacity and input power of condensing unit at moderate condition Determine gross refrigeration capacity and input power of condensing unit at cold condition Determine gross refrigeration capacity and input power of condensing unit at cold condition 15

Test Description Off Cycle Fan Power Suction A Suction B Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Table 15. Refrigerator Unit Cooler Saturation Temp, Liquid Inlet Subcooling, Compressor 35 <50 - - Compressor Off 35 <50 25 9 Compressor On 35 <50 20 9 Compressor On Note: Superheat to be set according to equipment specification and reported as part of standard rating Test Objective Measure fan input power during compressor off cycle of Unit Cooler of Unit Cooler Test Description Off Cycle Fan Power Suction A Suction B Unit Cooler Dry- Bulb, Unit Cooler Relative Humidity, % Table 16. Freezer Unit Cooler Saturation Temp, Liquid Inlet Subcooling, Compressor -10 <50 - - Compressor Off -10 <50-20 9 Compressor On -10 <50-26 9 Compressor On Defrost -10 various - Compressor Off Test Objective Measure fan input wattage during compressor off cycle of Unit Cooler of Unit Cooler Test according to Appendix C Section C11. Note: Superheat to be set according to equipment specification and reported as part of standard rating 5.2 Application Ratings. Application Ratings shall consist of a Rating plus the associated power input and Energy Efficiency Ratio (EER). When tested with a specified motor, the associated compressor speed (external drive compressors only), shall also be included as part of the rating. The power required to operate all included accessories such as condenser fans, water pumps, controls, and similar accessories shall be accounted for in the power input and Energy Efficiency Ratio. 16

AHRI STANDARD 1250P (I-P)-2009 When external accessories such as water pumps, remote fans, and similar accessories are required for the operation of the unit but are not included with the unit, the manufacturer shall clearly state that the rated power input and Energy Efficiency Ratio do not account for additional power required by these external accessories. Application Ratings shall be reported at rated voltage, phase, and frequency. 5.3 Tolerances. To comply with this standard, measured test results shall not be less than 95% of Published Ratings for capacity and energy efficiency. Power input shall be no more than 105% of the rated values. 5.4 Electric Conditions. Standard Rating tests shall be performed at the nameplate rated voltage(s) and frequency. For aircooled equipment which is rated with 208-230 V dual nameplate voltages, Standard Rating tests shall be performed at 230 V. For all other dual nameplate voltage equipment covered by this standard, the Standard Rating tests shall be performed at both voltages or at the lower of the two voltages if only a single Standard Rating is to be published. Section 6. Calculation for Walk-in Box Load 6.1 General Description. The walk-in box load is comprised of a high load period (BLH ) of the day corresponding to frequent door openings, product loading events, and other design load factors, and a low load period of the day (BLL) corresponding to the minimum load resulting from conduction, internal heat gains from equipment that is not related to the refrigeration system, and infiltration when the door is closed. Both the BLH and BLL are defined as a linear relationship with outdoor ambient temperature. This relationship accounts for the influence of outdoor ambient on the conduction and infiltration loads for a typical walk-in box. At the refrigeration system design point of 95 for outdoor condensing unit/coil or 90 for indoor condensing unit, the ratio of BLH to steady state refrigeration system capacity is 0.70 for refrigerators and 0.80 for freezers; the ratio of BLL to steady state refrigeration system capacity is 0.10 for refrigerators and 0.40 for freezers. The high load period for BLH is 8 hours per day, and the low load period for BLL is 16 hours per day. 6.2 Refrigerator Load Equations 6.2.1 Indoor Condensing Unit. The walk-in box and the condensing unit are both located within a conditioned space. The walk-in box load during a high load period is calculated by BLH =0.7 q ss (90) 1 In which, the box load equals to 70% of the refrigeration system steady state net capacity at the design point of 90. The Net is to be measured directly from the test by following the procedure defined in the Section 4 of this standard. The box load during a low load period equals to 10% of the refrigeration system steady state net capacity at the design point of 90, and can be calculated by BLL =0.1 q ss (90) 2 6.2.2 Outdoor Condensing Unit. The walk-in box load at different bin temperatures (t j ) during high and low load periods are calculated by BLH (t j )=0.65 q ss (95)+0.05 q ss (95) (t j-35) 60 BLL (t j )=0.03 q ss (95)+0.07 q ss (95) (t j-35) 60 3 4 6.3 Freezer Load Equations 6.3.1 Indoor Condensing Unit. The walk-in box and the condensing unit are both located within a conditioned space. The walk-in box load during a high load period is calculated as. 17

AHRI STANDARD 1250P (I-P)-2009 BLH =0.8 q ss (90) 5 In which, the box load equals to 80% of the refrigeration system steady state net capacity at the design point of 90. The net refrigeration capacity is to be measured directly from the test by following the procedure defined in the Section 4 of this standard. The box load during a low load period equals to 40% of the refrigeration system steady state net capacity at the design point of 90, and can be calculated by, BLL =0.4 q ss (90) 6 6.3.2 Outdoor Condensing Unit. The walk-in box load during high and low load periods are calculated by: BLH (t j )=0.55 q ss (95)+0.25 q ss (95) (t j+10) 105 BLL (t j )=0.15 q ss (95)+0.25 q ss (95) (t j+10) 105 7 8 Section 7. Calculation for Annual Walk-in Energy Factor 7.1 General Description. The calculation procedure described in this section is based on the data performance obtained from the tests under the standard rating conditions defined in Section 5 for single-capacity, two-capacity and variable capacity systems. The calculation method depends on outlining system capacity and power profiles over different temperature bins using laboratory test results. The annual walk-in energy factor, AWEF, is calculated by weighting system performance at individual bins with bin hours (number of hours for a given temperature occurs over the year), that is defined in Appendix D. 7.2 The total walk-in system heat load include the walk-in box load (BLH and BLL), defined in Section 6, and the heat load contributed by the operation of the refrigeration system (i.e. evaporator fan power and defrost). The total walk-in system heat load is also comprised of a high load period (WLH) and a low load period (WLL), corresponding to the walk-in box loads BLH and BLL. The refrigeration system operates 1/3 of operating hours under high load period, and 2/3 of operating time during low load period as defined in Section 6.1. 7.3 Load factor is defined as the ratio of the total walk-in system heat load to the system net refrigeration capacity. The load factors during high and low load periods at each bin temperature can be calculated by LFH(t j )= WLH (t j ) q ss (t j) LFL(t j )= WLL (t j ) q ss (t j) 9 10 7.4 Walk-in Unit with Single Compressor. 7.4.1 The operation of units with single capacity compressors is illustrated in Figure 7-1. The total walk-in system heat loads at each bin temperature during high and low load periods for the walk-in unit with single capacity compressor are calculated by the following equations. The terms of defrost power contributing to the box load, Q DF, and to the system power consumption, DḞ, in these equations shall only be applied to the walk-in freezer systems, and shall be set to zero during the calculation for the walk-in refrigerator systems. WLH (t j )=BLH (t j )+3.412 EḞ comp,off (1-LFH(t j )) +Q DF 11 WLL (t j ) =BLL (t j )+3.412 EḞ comp,off (1-LFL(t j )) +Q DF 12 18 Where

Walk-in System Load, System - AHRI STANDARD 1250P (I-P)-2009 LFH(t j )= WLH (t j ) q ss (t j) LFL(t j )= WLL (t j ) q ss (t j) = BLH (t j )+3.412 EḞ comp,off +Q DF 13 q ss (t j)+3.412 EḞ comp,off = BLL (t j )+3.412 EḞ comp,off +Q DF 14 q ss (t j)+3.412 EḞ comp,off The annual walk-in energy factor, AWEF, is determined by n n AWEF= j=1 BL(t j ) j=1 E(t j ) 15 The term BL(t j ) and E(t j ), summed over temperature bins, are evaluated at each temperature bin, and calculated by: BL(t j )=[0.33 BLH (t j )+0.67 BLL (t j )] n j 16 E(t j )= { 0.33 [E ss(t j ) LFH(t j )+EḞ comp,off (1-LFH(t j ))] +0.67 } n j 17 [E ss(t j ) LFL(t j )+EḞ comp,off (1-LFL(t j ))] +DḞ In the calculation above, the refrigeration system operates 1/3 of operating hours under high load period, and 2/3 of operating time during low load period as defined in Section 7.2. Walk-in System High Load, WL H(t j ) Walk-in System Low Load, WL L(t j ) q ss(t j ) Ambient Temperature Figure 7-1: Schematic of the operation for units with single capacity compressor 7.4.2 The system steady state net refrigeration capacity and power consumption at a specific temperature bin shall use the measured values directly from the steady state tests if the bin temperature coincides with the designated rating conditions. When a bin temperature does not coincide with the designated rating condition, use the follow equations to calculate the net capacity and the power consumption. 19

If t j 59 If t j >59 q ss (t j)=q ss (35)+ (q ss (59)-q ss (35)) (t 59-35 j -35) 18 E ss(t j )=E ss(35)+ (E ss (59)-E 59-35 ss (35)) (t j -35) 19 q ss (t j)=q ss (59)+ (q ss (95)-q ss (59)) (t 95-59 j -59) 20 E ss(t j )=E ss(59)+ (E ss (95)-E 95-59 ss (59)) 7.5 Walk-in Unit with Two- Compressor (t j -59) 21 7.5.1 Two-capacity compressor means a walk-in unit that has one of the following: (1) A two-speed compressor, (2) Two compressors where only one compressor ever operates at a time, (3) Two compressors where one compressor (Compressor #1) operates at low loads and both compressors (Compressors #1 and #2) operate at high loads but Compressor #2 never operates alone, or (4) A compressor that is capable of cylinder or scroll unloading. For such systems, low capacity means: (1) Operating at low compressor speed, (2) Operating the lower capacity compressor, (3) Operating Compressor #1, or (4) Operating with the compressor unloaded (e.g., operating one piston of a two-piston reciprocating compressor, using a fixed fractional volume of the full scroll, etc.). For such systems, high capacity means: (1) Operating at high compressor speed, (2) Operating the higher capacity compressor, (3) Operating Compressors #1 and #2, or (4) Operating with the compressor loaded (e.g., operating both pistons of a two-piston reciprocating compressor, using the full volume of the scroll). The unit shall be tested at the designated test conditions for both high and low capacities to evaluate the steady state capacities and power consumptions. 7.5.2 For two-capacity compressor units, the annual walk-in energy factor, AWEF, is calculated by n n AWEF= j=1 BL(t j ) j=1 E(t j ) 22 The term BL(t j ) and E(t j ), summed over temperature bins, are evaluated at each temperature bin according to four possible cases shown in Figure 7-2 and described as follows. These four cases can be identified in terms of three outdoor temperatures, t IH, t IL and t IIH, which are also shown in Figure 7-2. The outdoor temperature t IH is the temperature at which the total walk-in system heat load equals system net capacity when the compressor operates at low capacity (k=1) during the high load period. The outdoor temperature t IL is the temperature at which the total walk-in system heat load equals system net capacity when the compressor operates at low capacity (k=1) during the low load period. The outdoor temperature t IIH is the temperature at which the total walk-in system heat load equals system net capacity when the compressor operates at high capacity (k=2) during the high load period. 20

Walk-in System Load, System - AHRI STANDARD 1250P (I-P)-2009 The system steady state net refrigeration capacity and power consumption at a specific temperature bin shall use the measured values directly from the steady state tests if the bin temperature coincides with the designated rating conditions, otherwise use the following equations to calculate the net capacities and the power consumptions for low capacity operation. For high capacity operation, use the same equations, but replace the superscript k=1 by k=2. If t j 59 If t j >59 q k=1 ss (t j )=q k=1 (35)+ (q ss k=1 (59)-q ss k=1 (35)) (t ss 59-35 j -35) 23 (E k=1 k=1 E ss (tj )=E ss (35)+ k=1 k=1 ss (59)-E ss (35)) 59-35 (t j -35) 24 q k=1 ss (t j )=q k=1 (59)+ (q k=1 ss (95)-q k=1 ss (59)) ss (t 95-59 j -59) 25 (E k=1 k=1 E ss (tj ) =E ss (59)+ k=1 k=1 ss (95)-E ss (59)) 95-59 (t j -59) 26 Case I: Low capacity cycling at Low q ss k=1 (t j ) Case II: Low capacity cycling for low load, and two capacities alternating for high load Case III: Two capacities alternating Case IV: High capacity running continuously for high load and two capacities alternating for low load Walk-in System High Load, WL H(t j ) Walk-in System Low Load, WL L(t j ) at High q ss k=2 (t j ), tih til tiih Ambient Temperature Figure 7-2: Schematic of the various modes of operation for units with two capacity compressors 7.5.2.1 Case I. Low capacity cycling during both low and high load periods (t j < t IH ). Units operate only at low compressor capacity, and cycle on and off to meet the total walk-in system heat load during both low and high load periods. In this case, units operate identically to single capacity units. The calculation of terms BL(t j ) and E(t j ) shall follow the single capacity compressor procedure described in Section 7.4. 21

AHRI STANDARD 1250P (I-P)-2009 7.5.2.2 Case II. Low capacity cycling during low load period and two capacities alternating during high load period (t IH < t j < t IL ). During a low load period, units operate at low compressor capacity, and cycle on and off to meet the total walk-in system load. During a high load period, units alternate between high (k=2) and low (k=1) compressor capacities to satisfy the total walk-in system heat load at temperature t j. In such a case, the compressor operates continuously during high load period. The terms of defrost power contributing to the box load, Q DF, and to the system power consumption, DḞ, in these equations shall only be applied to the walkin freezer systems, and shall be set to zero during the calculation for the walk-in refrigerator systems. WLH (t j )=BLH (t j )+Q DF 27 WLL (t j )=BLL (t j )+3.412 EḞ comp,off (1-LFL k=1 (t j )) +Q DF 28 LFH k=1 (t j )= q k=2 ss (tj )-WLH (t j ) k=2 k=1 q ss (tj )-q ss (tj ) 29 LFH k=2 (t j )=1-LFH k=1 (t j ) 30 LFL k=1 (t j )= WLL (t j ) = BLL (t j )+3.412 EḞ comp,off +Q DF k=1 k=1 31 q ss (tj ) q ss (tj )+3.412 EḞ comp,off BL(t j )=[0.33 BLH (t j )+0.67 BLL (t j )] n j 32 0.33 (E ssk=2 (tj ) LFH k=2 (t j )+E ssk=1 LFH k=1 (t j )) +0.67 E(t j )= { } n j 33 [E ssk=1 (tj ) LFL k=1 (t j )+EḞ comp,off (1-LFL k=1 (t j ))] +DḞ 7.5.2.3 Case III. Two capacities alternating during both low and high load periods (t IL <t j <t IIH ). Units alternate between high (k=2) and low (k=1) compressor capacities to satisfy the total walk-in system load at temperature t j. In such a case, the compressor operates continuously. The terms of defrost power contributing to the box load, Q DF, and to the system power consumption, DḞ, in these equations shall only be applied to the walk-in freezer systems, and shall be set to zero during the calculation for the walk-in refrigerator systems. WLH (t j )=BLH (t j )+Q DF 34 WLL (t j )=BLL (t j )+Q DF 35 LFH k=1 (t j )= q ss k=2 (t j )-WLH (t j ) k=2 k=1 q ss (tj )-q ss (tj ) 36 LFH k=2 (t j )=1-LFH k=1 (t j ) 37 LFL k=1 (t j )= q k=2 ss (tj )-WLL (t j ) k=2 k=1 q ss (tj )-q ss (tj ) 38 LFL k=2 (t j )=1-LFL k=1 (t j ) 39 BL(t j )=[0.33 BLH (t j )+0.67 BLL (t j )] n j 40 22

E(t j )=[0.33 (E ssk=2 (tj ) LFH k=2 (t j )+E ssk=1 (tj ) LFH k=1 (t j )) +0.67 (E ssk=2 (tj ) LFL k=2 (t j )+E ssk=1 (tj ) LFL k=1 (t j )) +DḞ] n j 41 7.5.2.4 Case IV. High capacity running continuously during high load period and two capacities alternating during low load period (t IIH <t j ). During a low load period, units alternate between high (k=2) and low (k=1) compressor capacities to satisfy the total walk-in system load at temperature t j. During a high load period, units operate at high (k=2) compressor capacity continuously. The terms of defrost power contributing to the box load, Q DF, and to the system power consumption, DḞ, in these equations shall only be applied to the walk-in freezer systems, and shall be set to zero during the calculation for the walk-in refrigerator systems. WLH (t j )=BLH (t j )+Q DF 42 WLL (t j )=BLL (t j )+Q DF 43 LFH k=2 (t j )=1 44 LFL k=1 (t j )= q k=2 ss (tj )-WLL (t j ) k=2 k=1 q ss (tj )-q ss (tj ) 45 LFL k=2 (t j )=1-LFL k=1 (t j ) 46 BL(t j )=[0.33 BLH (t j )+0.67 BLL (t j )] n j 47 0.33 E ssk=2 (tj ) LFH k=2 (t j )+0.67 E(t j )= [ (E ssk=2 (tj ) LFL k=2 k=1 (t j )+E ss (tj ) LFL k=1 (t j )) +DḞ ] n j 48 7.6 Walk-in Unit with Variable Compressor 7.6.1 The annual walk-in energy factor, AWEF, for the walk-in units with variable capacity compressors is determined by: n n AWEF= j=1 BL(t j ) j=1 E(t j ) 49 The term BL(t j ) and E(t j ), summed over temperature bins, are evaluated at each temperature bin according to four possible cases shown in Figure 7-3 and described as follows. These four cases can be identified in terms of three outdoor temperatures, t IH, t IL and t IIH, which are also shown in Figure 7-3. The outdoor temperature t IH is the temperature at which the total walk-in system heat load equals system net capacity when the compressor operates at its minimum capacity (k=1) during the high load period. The outdoor temperature t IL is the temperature at which the total walk-in system heat load equals system net capacity when the compressor operates at its minimum capacity (k=1) during the low load period. The outdoor temperature t IIH is the temperature at which the total walk-in system heat load equals system net capacity when the compressor operates at its maximum capacity (k=2) during the high load period. The system steady state net refrigeration capacity and power consumption at a specific temperature bin shall use the measured values directly from the steady state tests if the bin temperature coincides with the designated rating conditions, otherwise use the following equations to calculate the net capacities and the power consumptions for minimum capacity operation. For intermediate and maximum capacities operation, use the same equations, but replace the superscript k=1 by k=i and k=2, respectively. 23

- AHRI STANDARD 1250P (I-P)-2009 If t j 59 If t j >59 q k=1 ss (t j )=q k=1 (35)+ (q ss k=1 (59)-q ss k=1 (35)) (t ss 59-35 j -35) 50 (E k=1 k=1 E ss (tj )=E ss (35)+ k=1 k=1 ss (59)-E ss (35)) 59-35 (t j -35) 51 q k=1 ss (t j )=q k=1 (59)+ (q ss k=1 (95)-q ss k=1 (59)) (t ss 95-59 j -59) 52 (E k=1 k=1 E ss (tj )=E ss (59)+ k=1 k=1 ss (95)-E ss (59)) 95-59 (t j -59) 53 Case I: Min. capacity cycling at Min. q ss k=1 (t j ) Case II: Min. capacity cycling for low load, variable capacity for high load at Int. Case III: Variable capacity for both low and high loads Case IV: Max. capacity running continuously for high load and variable capacity for low load Walk-in System High Load, WL H(t j ) Walk-in System Low Load, WL L(t j ) at Max. q ss k=2 (t j ) t IH t IL t VH t VL t IIH t HL Ambient Temperature Figure 7-3: Schematic of the various modes of operation for units with variable capacity compressors 7.6.1.1 Case I. Minimum capacity cycling during both low and high load periods ( t j < t IH ). Units operate at the minimum capacity, and cycle on and off to meet the total walk-in system load during both low and high load periods. The terms of defrost power contributing to the box load, Q DF, and to the system power consumption, DḞ, in these equations shall only be applied to the walk-in freezer systems, and shall be set to zero during the calculation for the walk-in refrigerator systems. 24