VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

Similar documents
VIESMANN. Installation and service instructions VITODENS 200-W. for contractors

VIESMANN. Installation instructions VITODENS 200-W. for contractors

VIESMANN. Service instructions VITODENS 200-W. for contractors

VIESMANN. Installation and service instructions VITODENS 111-W. for contractors

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation and service instructions VITOTROL 300A. for contractors. Vitotrol 300A. Remote control, part no

VIESMANN. Installation and service instructions VITOTROL 200 RF. for contractors. Vitotrol 200 RF. Wireless remote control for one heating circuit

VIESMANN. Service instructions VITOLADENS 300-T. for contractors. Vitoladens 300-T Type VW3B Inox-Radial heat exchanger for oil fired condensing Unit

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Installation instructions VITOCROSSAL 200. for contractors. Vitocrossal 200 Type CM2 Gas fired condensing boiler with MatriX radiant burner

VIESMANN. Installation and service instructions VITODENS 343-F. for contractors

VIESMANN. Service instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation and service instructions VITODENS 050-W. for contractors

VIESMANN. Service instructions VITOCELL 300-B VITOCELL 300-V. for contractors

VIESMANN. Installation and service instructions VITOTRONIC 200. for contractors

VIESMANN. Installation instructions. Mixer extension kit. for contractors. Mixer extension kit. For one heating circuit with mixer

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

Service Instructions for use by heating contractor

VIESMANN. Installation instructions VITORONDENS 200-T. for contractors. Vitorondens 200-T Type BR2A, 20.2 to 53.7 kw Oil Unit condensing boiler

VIESMANN. Installation and service instructions VITOCELL 340-M/360-M. for contractors. Vitocell 340-M/360-M Type SVKA Type SVSA

VIESMANN. Service instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CR3 and CR37, 787 and 978 kw Gas condensing boiler

VIESMANN. Operating instructions VITODENS 111-W. for the system user

VIESMANN. Operating instructions VITODENS 100-W. for the system user

VIESMANN. Operating instructions VITODENS VITOPEND. for the system user. Heating system with Vitotronic 100 control unit for constant temperature mode

VIESMANN. Installation instructions. Extension AM1. Safety instructions. for contractors. Part no

VIESMANN. Operating instructions VITODENS 050-W. for the system user. With constant temperature or weather-compensated control unit

Installation and Service Instructions for use by heating contractor. VITOTRONIC r 200 VITOTRONIC r 300-K IMPORTANT

VIESMANN. Installation instructions VITOMAX 200-HW. for contractors

VIESMANN. Installation and service instructions VITOTRONIC 200 VITOTRONIC 300. for contractors

VIESMANN. Installation instructions VITOCELL 300-B. for contractors. Vitocell 300-B Type EVBA-A. Dual mode DHW cylinder, 300 and 500 l

for use by heating contractor Vitotronic 300 Type GW2B IMPORTANT Read and save these instructions for future reference.

Installation and Service Instructions SM1 SOLAR CONTROL MODULE IMPORTANT. Read and save these instructions for future reference.

VIESMANN. Installation instructions VITOCROSSAL 300. for contractors. Vitocrossal 300 Type CM3 Gas condensing boiler with MatriX radiant burner

VIESMANN. Installation instructions. Extension EA1. Safety instructions. for contractors. Part no

VIESMANN. Installation and service instructions. Solar-Divicon SR. Safety instructions. Application. for contractors. Part no and

for contractors Vitoplex 200 Type SX2A For applicability, see the last page Please keep safe.

for contractors Vitosolic 100 Type SD1 For applicability, see the last page Please keep safe.

VIESMANN. Installation instructions VITOCELL 300-V/W. for contractors. Vitocell 300-V/W Type EVIA-A

VIESMANN. Service instructions. MatriX radiant burner. for contractors

VIESMANN. Installation and service instructions VITODENS 100. for heating engineers

VIESMANN. Operating instructions VITODENS 100. for system users. Heating system with control unit for constant temperature operation

Installation instructions PYROMAT ECO. for contractors PYROMAT ECO GB 8/2012 Dispose after installation.

VIESMANN. Operating instructions VITODENS VITOLADENS VITOPEND. for the system user

VIESMANN. Operating instructions VITOTRONIC 200. for the system user

VIESMANN. Installation and service instructions VITOCAL 200-S. for contractors

The competent brand for energy saving systems NEW. Gas-combi boiler CGG-1K-24/28

VIESMANN. Operating instructions DIGITAL TIME SWITCH. for the system user. Digital time switch for the Vitodens 100-W, type WB1B

ProCon Streamline Gas Condensing Boiler. Installation and Operating Manual.

Installation and Service Instructions. VITOTRONIC r 100 IMPORTANT. Read and save these instructions for future reference.

VIESMANN. Installation and service instructions VITOCAL 300-G. for contractors

WOLF GAS CONDENSING BOILERS COMFORTLINE

O. Gas boiler. Gaz 6000 W WBN H-E-N/L-S2400. Operating instructions for the end customer (2017/09) en

Operating Instructions for use by heating contractor. VITOTRONIC r 100 VITOTRONIC r 300-K IMPORTANT

VIESMANN VITOCROSSAL 300 Gas condensing boiler 187 to 635 kw

VIESMANN. Operating and service instructions VITOMAX 200-HW. for contractors

Installation, operating and servicing instructions

WHE 2.24 / WHE 2.24 FF

Gas Instantaneous Water Heater

Operating instructions Oil condensing boiler

VIESMANN VITOROND 100. Datasheet Part numbers and prices: see pricelist VITOROND 100. Cast iron low temperature oil and gas fired boiler.

Solar-Divicon and solar pump assembly. Please follow these safety instructions closely to prevent accidents and material losses.

12.0 Servicing. Electrode Position Fig Annual Servicing Inspection (Cont) 4 ±0.5

Installation and maintenance instructions

and Installation Instructions The installation instructions for the Unit pressure jet oil burner is included in the pressure jet oil burner pack.

Installation instructions. Pump Group. For wall hung gas-fired condensing boiler GB162-50/65/80/ TD UK/IE (2014/09)

Service Instructions for use by heating contractor VITOCROSSAL 300 IMPORTANT. Read and save these instructions for future reference.

for contractors Vitosolic 200 Type SD4 For applicability, see the last page Please keep safe.

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

Service manual. Riva Plus HE. M296.28SR/C System boiler. Wall hung, fanflue, roomsealed, high efficiency gas boiler

Service Instructions for use by heating contractor. VITODENS r 222-F IMPORTANT. Read and save these instructions for future reference.

Mikrofill Ethos Condensing combination boiler. Maintenance Instructions 24cc

VIESMANN VITOCROSSAL 300 Gas condensing boiler 787 to 1400 kw

Installation and maintenance instructions

Service Instructions. VITODENS r 200-W IMPORTANT. Read and save these instructions for future reference. for use by heating contractors

Installation and maintenance instructions for contractors

Vitodens 100W WB1B - Service and Maintenance

Service Instructions for use by heating contractor. VITODENS r 200-W IMPORTANT. Read and save these instructions for future reference.

INSTALLATION AND MANINTENANCE INSTRUCTIONS

ir-range 8G /03.15 Changes reserved.

VIESMANN. Installation and service instructions VITOCAL 300-A. for contractors

1 VICTRIX ZEUS Superior kw I features

IDE 20 / IDE 30 / IDE 50 IDE 60 / IDE 80

Service booklet for the Engineer for Gas Condensing Boilers

VIESMANN. Installation and service instructions. EHE immersion heater. for contractors. EHE immersion heater

Technical documentation. ComfortLine gas condensing boilers CGB-2(K) CGW-2 CGS-2 CSZ-2 NEW

VIESMANN. Datasheet VITOMAX 200-WS. Hot water boiler for permissible flow temperatures up to 110 C 1.75 to MW

TopGas Cascade Condensing Gas Boilers Technical Information and Assembly Manual Output range 60 to 720 kw /17 Subject to modification

Oxiperm C 164 Fully automatic chlorine dioxide processing plant C, -6000C, -7500C, C. Service manual. Oxiperm 164C 4-10 kg Service en

VIESMANN VITOCELL 300-V Vertical DHW cylinder 130 to 500 l capacity

Operating instructions

VIESMANN. VITOMAX 200-WS Rated heating output 1.75 to MW. Datasheet. VITOMAX 200-WS Type M250

Residential Gas Condensing Boiler Greenstar ZBR16/21/28/35/42-3A... ZWB28/35/42-3A...

Service Instructions for use by heating contractor. VITODENS r 200-W IMPORTANT. Read and save these instructions for future reference.

VIESMANN VITOLADENS 300-C Oil condensing boiler 12.9 to 28.9 kw

Aqua Balance. AquaBalance TM CONTROL MODULE QUICK START GUIDE LEGEND

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A

Wall hung combination boilers. This is a CAT II2H3+ appliance USER, INSTALLATION AND SERVICING INSTRUCTIONS SUPPORTED BY

Sirius FS. Working towards a cleaner future

Installation and maintenance instructions

Transcription:

Installation and service instructions for contracrs VIESMANN Videns 200-W Type B2HA, 80 and 100 kw Wall mounted gas condensing boiler Natural gas and LPG version For applicability, see the last page VITODENS 200-W 5/2012 Please keep safe.

Safety instructions Safety instructions Please follow these safety instructions closely prevent accidents and material losses. Safety instructions explained Danger This symbol warns against the risk of injury.! Please note This symbol warns against the risk of material losses and environmental pollution. Note Details identified by the word "Note" contain additional information. Target group These instructions are exclusively designed for qualified personnel. Work on gas equipment must only be carried out by a qualified gas fitter. Work on electrical equipment must only be carried out by a qualified electrician. The system must be commissioned by the system installer or a qualified person authorised by the installer. Regulations Observe the following when working on this system all legal instructions regarding the prevention of accidents, all legal instructions regarding environmental protection, the Code of Practice of relevant trade associations, all current safety regulations as defined by DIN, EN, DVGW, TRGI, TRF, VDE and all locally applicable standards, Gas Safety (Installation & Use) Regulations the appropriate Building Regulation either the Building regulations, the Building Regulation (Scotland), Building Regulations (Northern Ireland), the Water Fittings Regulation or Water Bylaws in Scotland, the current I.E.E. Wiring Regulations. If you smell gas Danger Escaping gas can lead explosions which may result in serious injury. Never smoke. Prevent naked flames and sparks. Never switch lights or electrical appliances ON or OFF. Close the gas shut-off valve. Open windows and doors. Remove all people from the danger zone. Notify your gas or electricity supplier from outside the building. Shut off the electricity supply the building from a safe place (outside the building). 2

Safety instructions Safety instructions (cont.) If you smell flue gas Danger Flue gas can lead life-threatening poisoning. Shut down the heating system. Ventilate the boiler room. Close all doors leading the living space. Working on the system When using gas as fuel, also close the main gas shut-off valve and safeguard against unauthorised reopening. Isolate the system from the power supply and check that it is no longer 'live', e.g. by removing a separate fuse or by means of a main isolar. Safeguard the system against unauthorised reconnection. Ancillary components, spare and wearing parts Please note! Spare and wearing parts which have not been tested gether with the heating system can compromise its function. Installing non-authorised components and non-approved modifications/conversion can compromise safety and may invalidate our warranty. For replacements, use only original spare parts from Viessmann or those which are approved by Viessmann.! Please note Electronic modules can be damaged by electro-static discharges. Touch earthed objects, such as heating or water pipes, discharge static loads. Repair work! Please note Repairing components which fulfil a safety function can compromise the safe operation of your heating system. Replace faulty components only with original Viessmann spare parts. 3

Index Index Installation instructions Preparing for installation Product information... 6 Preparing for installation... 7 Installation sequence Fitting the boiler and making connections... 9 Heating water side connection... 11 Flue gas connection... 11 Condensate connection... 12 Gas connection... 12 Opening the control unit casing... 13 Electrical connections... 15 Closing the control unit casing and inserting the programming unit... 25 Service instructions Commissioning, inspection, maintenance Steps - commissioning, inspection and maintenance... 27 Further details regarding the individual steps... 29 Code 1 Calling up coding level 1... 64 General/group "1"... 65 Boiler/group "2"... 68 DHW/group "3"... 68 Solar/group "4"... 69 Heating circuit 1, heating circuit 2, heating circuit 3/group "5"... 71 Code 2 Calling up coding level 2... 78 General/group "1"... 79 Boiler/group "2"... 88 DHW/group "3"... 90 Solar/group "4"... 92 Heating circuit 1, heating circuit 2, heating circuit 3/group "5"... 96 Diagnosis and service scans Calling up the service level... 105 Diagnosis... 106 Checking outputs (relay test)... 112 4

Index Index (cont.) Troubleshooting Fault display... 115 Fault codes... 117 Repair... 133 Function description Constant temperature control unit... 141 Weather-compensated control unit... 142 Internal extensions (accessories)... 143 External extensions (accessories)... 146 Control functions... 150 Assigning heating circuits the remote control... 158 Electronic combustion control unit... 158 Designs Connection and wiring diagram internal connections... 160 Connection and wiring diagram external connections... 162 Parts lists Ordering parts... 164 Overview of the assemblies... 165 Casing assembly... 166 Heat cell assembly... 167 Burner assembly... 170 Hydraulic assembly... 171 Control unit assembly... 174 Miscellaneous assembly... 175 Commissioning/service reports... 177 Specification... 178 Certificates Declaration of conformity... 179 Manufacturer's certificate according the 1st BImSchV [Germany]... 179 Keyword index... 180 5

Preparing for installation Product information Videns 200-W, B2HA Preset for operation with natural gas E and LL. For conversion LPG P (without conversion kit), see the service instructions. Conversion for other countries The Videns 200-W should generally only be delivered those countries specified on the type plate. For deliveries alternative countries, an approved contracr must arrange individual approval on his own initiative and in accordance with the law of the country in question. Multi boiler system In connection with the installation of a multi boiler system observe the installation instructions of the multi boiler system accessories. 6

Preparing for installation Preparing for installation Dimensions and connections! Please note To prevent equipment damage, 480 install all pipework free of load and rque stresses. 236 40 752 850 200 M 1975 1690 1300 N O 875 L Installation K P B C E G A D 160 160 F H 100 530 A Cylinder flow G1½ B Safety valve C Expansion vessel connection G1 D Boiler flow 7 42 mm E Gas connection R 1 F Boiler return 7 42 mm 7

Preparing for installation Preparing for installation (cont.) G Connection set (accessories, shown without the thermal insulation supplied) H Cylinder return G1½ K Cable entry area at the back L Without connection set (accessories) M With connection set (accessories) N Recommended dimension (single boiler system) O Recommended dimension (multi boiler system) P Condensate drain Preparing for the boiler installation Note This boiler (IP rating: IP X4 D) is approved for installation in wet rooms inside safety zone 1 according DIN VDE 0100 [Germany], if hosed water can be prevented. Observe DIN VDE 0100 [or local regulations]. 1. Prepare the water connections. Thoroughly flush the heating system. 2. Prepare gas connection TRGI [or local regulations]. 3. Prepare the electrical connections. Power cable: NYM-J 3 x 1.5 mm 2, max. fuse 16 A, 230 V~ Accessory cables: NYM with the required number of conducrs for the external connections Allow all cables in area "K" protrude 1200 mm from the wall 8

Installation sequence Fitting the boiler and making connections Fitting the wall mounting bracket Note The enclosed screws and rawl plugs are only suitable for concrete. For other construction materials, use fixing materials that are suitable for 100 kg loads. A 1. 480 Ø 10 1975 Installation 2. D B C A Reference point: boiler p edge B Installation template (included with the boiler) C Top edge finished floor D Recommendation 9

Installation sequence Fitting the boiler and making connections (cont.) Hook the boiler in the wall mounting bracket and level it 3. 4. 2. 5. 2x 1. 2x 10

Fitting the boiler and making connections (cont.) Installation sequence Note on step 4 Place the supplied circular level on the boiler and align boiler vertically using the adjusting screws. Heating water side connection B C A E D A Cylinder flow B Expansion vessel connection C Boiler flow D Cylinder return E Boiler return Flue gas connection Note The labels "System certificate" and "Skoberne GmbH flue system" enclosed with the technical documentation may only be used in conjunction with the Viessmann flue system made by Skoberne. Connect the balanced flue. Flue system installation instructions Installation 11

Installation sequence Condensate connection 1. Plug condensate hose on hose adapr A. Ensure the hose adapr is connected tightly. A 2. Connect the condensate hose with a constant fall and a pipe vent the public sewage system or a neutralising system. Gas connection Notes regarding operation with LPG We recommend the installation of an external safety solenoid valve when installing the boiler in rooms below ground level. 1. Seal gas shut-off valve A in the gas supply pipe. A 12

Installation sequence Gas connection (cont.) 2. Carry out a tightness test. Note Only use suitable and approved leak detection agents (EN 14291) and devices for the tightness test. Leak detection agents with unsuitable constituents (e.g. nitrites, sulphides) can cause material damage. Remove residues of the leak detection agent after testing. Please note! Excessive test pressure may damage the boiler and the gas valve. Max. test pressure 150 mbar. Where higher pressure is required for tightness tests, disconnect the boiler and the gas valves from the gas supply pipe (undo the fitting). 3. Vent the gas line. Conversion other gas types: Service instructions Installation Opening the control unit casing! Please note Electronic assemblies can be damaged by electrostatic discharge. Before beginning work, uch earthed objects, such as heating or water pipes, discharge static loads. 13

Installation sequence Opening the control unit casing (cont.) 3. 2. 2x 1. 5. 4. 4x 14

Installation sequence Electrical connections X19 5 X4 145 X14 2 1 145 2 5 4 32 1 X3 A 1 M 1~ 21 N L N 100 35 21 B C L 1 D 20 96 N L1 L N 40 L Installation 230 V~ 230 V~ 20 96 40 A Radio clock receiver B Heating circuit pump or boiler circuit pump C Vitrol 100 UTDB (only for constant temperature control units) When making this connection, remove jumper between "1" and "L" D Vitrol 100 UTA (only for constant temperature control units) or Vitrol 100 UTDB-RF wireless receiver. When making this connection, remove jumper between "1" and "L" 15

Installation sequence Electrical connections (cont.) Connections at plug 230 V~ sö Boiler circuit pump or heating circuit pump Variable speed with 0-10 V connection sa Circulation pump, optional connection: DHW circulation pump External heating circuit pump Circulation pump for cylinder heating fö Power supply lh Power supply for accessories External demand/blocking Vitrol 100 UTA Vitrol 100 UTDB Vitrol 100 UTDB-RF Connections at LV plug! Outside temperature sensor? Flow temperature sensor for low loss header (accessories) % Cylinder temperature sensor (part of the DHW cylinder connection set) avg KM BUS subscriber (accessories) Vitrol 200A or 300A remote control Vicom 100 GSM Extension kit for one heating circuit with mixer Solar control module, type SM1 Visolic Extension AM1 Extension EA1 Wireless base station Information on connecting accessories When connecting accessories observe the separate installation instructions provided with them. Circulation pump at plug sö A M 1~ Rated current 2(1) A~ Rated voltage 230 V~ L? N sö x4 B A Circulation pump B Plug in 0-10 V connection at X4 16

Installation sequence Electrical connections (cont.) Circulation pump at plug sa M 1~ A Rated current 2(1) A~ Rated voltage 230 V~ L? N sa A Circulation pump Set function of connected component in coding address "39" Function Code DHW circulation pump 39:0 Heating circuit pump for 39:1 heating circuit without mixer A1 Circulation pump for cylinder 39:2 heating (delivered condition) Installation External demand via switching contact Connection options: Extension EA1 (accessory, see separate installation instructions). Plug lh. Connection! Please note 'Live' contacts lead short circuits or phase failure. The external connection must be floating. 17

Installation sequence Electrical connections (cont.) Plug lh Extension EA1 A [{A DE [{S DE [{D DE B 1 L? N lh A A Floating contact When making this connection, remove jumper between 1 and L. A Floating contact B Extension EA1 Burner operation is load-dependent if the contact is closed. The boiler water is heated the value set in coding address "9b" in group "General"/"1". The boiler water temperature is limited by this set value and the electronic maximum limit (coding address "06" in group "Boiler"/"2"). Codes Plug lh Extension EA1 "4b:1" in group "General"/"1" Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) in group "General"/"1" 2. Select effect of the function on the relevant heating circuit pump in coding address "d7" in group "Heating circuit"/"5". Select effect of the function on the circulation pump for cylinder heating in coding address "5F" in group "DHW"/"3". External demand via 0 10 V input Connection at 0 10 V input extension EA1. Ensure DC separation between the earth conducr and the negative pole of the on-site voltage source. 18

Installation sequence Electrical connections (cont.) [{{] abj 0-10V f-]a fö 0 1 V no default set boiler water temperature 1 V Set value 10 C 10 V Set value 100 C 1 2 SÖ P L?N N? L = 0-10 V + 230 V~ Installation External blocking via switching contact Connection options: Plug lh. Extension EA1 (accessory, see separate installation instructions).! Please note 'Live' contacts lead short circuits or phase failure. The external connection must be floating. 19

Installation sequence Electrical connections (cont.) Plug lh Extension EA1 A [{A DE [{S DE B [{D DE 1 L? N lh A A Floating contact When making this connection, remove jumper between 1 and L. A Floating contact B Extension EA1 The burner is switched off if this contact is closed. The heating circuit pump and circulation pump for cylinder heating are switched according the set code (see the following table "Codes"). Please note! When blocked, there is no frost protection for the heating system. Codes Plug lh Extension EA1 "4b:2" in group "General"/"1" Set "3A" (DE1), "3b" (DE2) or "3C" (DE3) in group "General"/"1" 3 or 4. Select effect of the function on the heating circuit pump in coding address "d6" in group "Heating circuit"/"5". Select effect of the function on the circulation pump for cylinder heating in coding address "5E" in group "DHW"/"3". Outside temperature sensor! Fitting outside temperature sensor RF (wireless accessory): 20 Wireless base station

Installation sequence Electrical connections (cont.) Fitting location for outside temperature sensor North or north-westerly wall, 2 2.5 m above ground level; in multi srey buildings, in the p half of the second floor Not above windows, doors or vents Not immediately below balconies or gutters Never render over Outside temperature sensor connection 2-core lead, length up 35 m with a cross-section of 1.5 mm 2 Power supply for accessories at plug lh (230 V~) Where the boiler is installed in a wet area, the power supply connection for accessories must not be carried out at the control unit. The power supply connection for accessories can be made directly at the control unit, if the boiler is installed outside wet areas. This connection is switched directly with the ON/OFF switch of the control unit. If the tal system current exceeds 6 A, connect one or more extensions via an ON/OFF switch directly the mains supply (see next chapter). Installation 21

Installation sequence Electrical connections (cont.) Connection of accessories Power supply of all accessories via the boiler control unit A B C D 145 40 96 145 145 40 A 40 145 145 40 A 40 145 145 40 A 40 E Some accessories with direct power supply A B C D 145 40 96 145 145 40 A 40 145 145 40 A 40 145 145 40 A 40 E A Boiler control unit B Extension kit for heating circuit with mixer M2 C Extension kit for heating circuit with mixer M3 D Extension AM1, EA1 and/or solar control module, type SM1 E ON/OFF switch If the current flowing the connected working parts (e.g. circulation pumps) is higher than the safety level of the accessory, the output concerned should only be used control an on-site relay. Accessories Extension kit for heating circuit with mixer Extension AM1 Extension EA1 Solar control module, type SM1 Internal fuse protection 2 A 4 A 2 A 2 A 22

Installation sequence Electrical connections (cont.) Power supply fö Danger Incorrect core allocation can result in serious injury and damage the appliance. Take care not interchange wires "L1" and "N". Install an isolar in the power cable which simultaneously separates all non-earthed conducrs from the mains with contact separation of at least 3 mm. Furthermore, we recommend installing an AC/DC-sensitive RCD (RCD class B ) for DC (fault) currents that can occur with energy efficient equipment. Max. fuse rating 16 A. Installation 23

Installation sequence Electrical connections (cont.) Routing the connecting cables! Please note If connecting cables uch hot components they will be damaged. When routing and securing connecting cables on site, ensure that the maximum permissible temperatures for these cables are not exceeded. 5 A LV connections B 230 V connections C Internal extension D Main PCB E Communication module F Cable grommet for power cable % Plugs for connecting the cylinder temperature sensor the cable harness 24

Installation sequence Electrical connections (cont.) Remove the existing cable grommet when using larger cross-sections (up 7 14 mm). Secure the cable with the cable grommet plugged in the lower casing F (black). Closing the control unit casing and inserting the programming unit 1. Installation 2. 3. 2x 6. 4. 4. 25

Installation sequence Closing the control unit casing and inserting (cont.) Insert programming unit (packed separately) in the control unit support. Note The programming unit can also be inserted in a wall mounting base (accessories) near the boiler. Wall mounting base installation instructions 26

Commissioning, inspection, maintenance Steps - commissioning, inspection and maintenance For further information regarding the individual steps, see the page indicated Commissioning steps Inspection steps Maintenance steps Page 1. Opening the boiler... 29 2. Filling the heating system... 30 3. Venting the boiler by flushing... 31 4. Selecting the language (if required) - only for weathercompensated control units... 32 5. Setting the time and date (if required) - only for weather-compensated control units... 32 6. Venting the heating system... 33 7. Filling the siphon with water... 33 8. Checking all connections on the heating water side and DHW side for leaks 9. Checking the power supply 10. Designating heating circuits - only for weathercompensated control units... 34 11. Checking the gas type... 34 12. Gas type conversion (only for operation with LPG)... 35 13. Function sequence and possible faults... 35 14. Checking the static and supply pressure... 37 15. Max. heating output setting... 39 16. Checking the balanced flue system for tightness (annular gap check)... 40 Service 17. Removing the burner and checking the burner gasket 41 18. Checking the burner gauze assembly and replacing if required... 42 19. Checking the flue gas non-return device... 43 20. Checking and adjusting the ignition and ionisation electrodes... 44 27

Commissioning, inspection, maintenance Steps - commissioning, inspection and (cont.) Commissioning steps Inspection steps Maintenance steps Page 21. Cleaning the combustion chamber/heat exchanger and installing the burner... 45 22. Checking the condensate drain and cleaning the siphon... 46 23. Checking the neutralising system (if installed) 24. Checking the diaphragm expansion vessel and system pressure... 46 25. Checking the function of safety valves 26. Checking firm seating of electrical connections 27. Checking gas equipment for tightness at operating pressure... 47 28. Checking combustion quality... 47 29. Checking the flue system for unrestricted flow and tightness 30. Matching the control unit the heating system... 49 31. Checking the external LPG safety valve (if installed) 32. Adjusting the heating curves (only for weathercompensated control units)... 56 33. Connecting the control unit the LON... 59 34. Scanning and resetting the "Service" display... 60 35. Fitting the front panel... 62 36. Instructing the system user... 63 28

Further details regarding the individual steps Opening the boiler Commissioning, inspection, maintenance 4. 3. 2. 1. 2x Service 29

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Filling the heating system Fill water! Please note Unsuitable fill water increases the level of deposits and corrosion and may lead boiler damage. Flush the heating system thoroughly before filling. Only use fill water of potable quality. An antifreeze additive suitable for heating systems can be added the fill water. The antifreeze manufacturer must verify its suitability. Fill and p-up water with a water hardness in excess of the following values must be softened, e.g. with a small softening system for heating water. Total permissible hardness of the fill and p-up water Total heating Specific system volume output kw < 20 l/kw 20 l/kw < 50 l/kw 50 3.0 mol/m 3 2.0 mol/m 3 (16.8 dh) (11.2 dh) > 50 200 2.0 mol/m 3 1.5 mol/m 3 (11.2 dh) (8.4 dh) > 200 600 1.5 mol/m 3 0.02 mol/m 3 (8.4 dh) (0.11 dh) > 600 < 0.02 mol/m 3 < 0.02 mol/m 3 (0.11 dh) (0.11 dh) 50 l/kw < 0.02 mol/m 3 (0.11 dh) < 0.02 mol/m 3 (0.11 dh) < 0.02 mol/m 3 (0.11 dh) < 0.02 mol/m 3 (0.11 dh) 30

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 1. Check the pre-charge pressure of the diaphragm expansion vessel. 2. Close the gas shut-off valve. A 3. Fill the heating system at boiler drain & fill valve A (minimum system pressure > 1.0 bar). 4. Close boiler drain & fill valve A. Venting the boiler by flushing E D F 1. Close shut-off valves A and B. 2. Connect the drain hose drain valve C. Connect the fill hose boiler drain & fill valve F (if no longer connected). 3. Close shut-off valve D. 4. Open valve F. C 5. Vent the first indirect coil through shut-off valve E at mains pressure until no sound of escaping air can be heard. Service B A 6. Close shut-off valve E and open shut-off valve D. 31

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 7. Vent the second indirect coil through shut-off valve D at mains pressure until no sound of escaping air can be heard. 8. Close valves C and F. 9. Open shut-off valve E. Note Shut-off valves D and E must be open for the boiler start operation. Selecting the language (if required) - only for weather-compensated control units At the commissioning stage, the display is in German (facry setting). Extended menu: 1. å 2. "Settings" 3. "Language" Sprache Deutsch Cesky Dansk English Wählen mit Ø DE CZ DK GB ç 4. Set the required language with /. Setting the time and date (if required) - only for weather-compensated control units During commissioning, or after prolonged time out of use, the time and date need be reset. Extended menu: 1. å 2. "Settings" 3. "Time / Date" 4. Set current time and date. Note When time and date have been set, the control unit aumatically checks the function of the flue gas temperature sensor. The display shows: "Flue gas temp sensor test" and "Active". For further details regarding the flue gas temperature sensor test, see page 137. 32

Venting the heating system Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 1. Close the gas shut-off valve and switch the control unit ON. 3. Check the system pressure. 2. Activate venting program (see next steps). Note For function and sequence of the venting program, see page 152. Activating the venting function Weather-compensated control unit Constant temperature control unit Service menu Service menu 1. Press OK and å simultaneously for 1. Press OK and å simultaneously for approx. 4 s. approx. 4 s. 2. "Service functions" 2. Select "5" with Ú and confirm with 3. "Venting" OK. Venting function is enabled. "ON" flashes. 4. Ending venting function: 3. Activate the venting function with OK. Press OK or ä. "EL on" is shown constantly. 4. Ending venting function: Press ä. Filling the siphon with water 1. Pull off cap A downwards. B C 2. Undo union nut B and pull off siphon C downwards. 3. Fill siphon C with water and refit it. Service A Note Never twist the supply hose during assembly. Route the drain hose without any bends and with a constant fall. 4. Push on cap A from below. 33

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Designating heating circuits - only for weather-compensated control units In the delivered condition, the heating circuits are designated "Heating circuit 1", "Heating circuit 2" and "Heating circuit 3" (if installed). If the system user prefers, the heating circuits can be designated differently suit the specific system. To enter names for heating circuits: Operating instructions Checking the gas type The boiler is equipped with an electronic combustion controller that adjusts the burner for optimum combustion in accordance with the prevailing gas quality. Consequently, for operation with natural gas there is no adjustment required across the entire Wobbe index range. The boiler can be operated in the Wobbe index range 9.5 15.2 kwh/m 3, (34.2 54.7 MJ/m 3 ) Convert the burner for operation with LPG (see "Gas type conversion" on page 35) 1. Determine the gas type and Wobbe index by asking your local gas supply utility or LPG supplier. 2. Convert the burner for operation with LPG (see page 35). 3. Record the gas type in the report on page 177. 34

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Gas type conversion (only for operation with LPG) A 2 1 1. Set adjusting screw A on both gas trains "2". 2. Switch ON/OFF switch "8" ON. 3. Select the gas type in coding address "82": Call up code 2 Call up "General" (weather-compensated control units) or Group "1" (constant temperature control units) In coding address "11", select value "9" In coding address "82", select value "1" (LPG operation) In code "11", select value "9" End service functions. 4. Open the gas shut-off valve. 5. Affix label "G 31" (included with the technical documentation) in a clearly visible position, near the gas train on the cover panel. Function sequence and possible faults Control unit issues a heat demand Display Measures no Increase set value and ensure heat is drawn off Service yes Fan starts no After approx. 51 s fault F9 Check the fan, fan connecting cables, power at the fan and fan control 35

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) yes Ignition no Fault EE Check the ignition module (control voltage 230 V across plugs "X2.1" and "X2.2") yes Gas train opens no Fault EE Check the gas train (control voltage 230 V); check the gas supply pressure yes Ionisation current builds Symbol A no Fault EE Check the ionisation electrode adjustment and the gas line for airlocks yes Burner in operation no Sps below the set boiler water temperature and restarts immediately Check the flue gas system for tightness (flue gas recirculation), check the gas flow pressure 36

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) yes Aumatic calibration of the combustion controller no Fault E3 Ensure adequate heat transfer. Press reset butn R. Fault Eb Check gap between ionisation electrode and burner gauze assembly. Check allocation of gas type (coding address 82, gas train setting). Check flue system; remedy flue gas recirculation if required. Press reset butn R. For further details regarding faults, see page 115. Checking the static and supply pressure Danger CO build-up as a result of incorrect burner adjustment can have serious health implications. Carry out a CO test before and after work on gas appliances. Operation with LPG Flush the LPG tank twice during commissioning or replacement. Vent the tank and gas supply line thoroughly after flushing. Service 37

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 1. Close the gas shut-off valve. A 2. Undo screw A inside test nipple "PE" on one of the two gas trains, but do not remove it, and connect the pressure gauge. 3. Open the gas shut-off valve. 4. Check the static pressure and record the actual value in the report on page 177. Set value: max. 57.5 mbar. 5. Start the boiler. Note During commissioning, the boiler can enter a fault state because of airlocks in the gas line. After approx. 5 s, press R reset the burner. 6. Check the supply (flow) pressure. Set values: Natural gas 20 mbar LPG 50 mbar Note Use a suitable measuring device with a resolution of at least 0.1 mbar measure the supply pressure. 7. Record the actual value in the report. Take the action shown in the following table. 8. Shut down the boiler, close the gas shut-off valve, remove the pressure gauge and close test nipple A with the screw. 38

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Supply (flow) pressure for natural gas Supply (flow) pressure for LPG 9. Danger Gas escaping from the test nipple leads a risk of explosion. Check for gas tightness. Open the gas shut-off valve, start the boiler and check for tightness at test nipple A. Action Below 15 mbar Below 42.5 mbar Do not start the boiler. Notify your gas supply utility or LPG supplier 15 25 mbar 42.5 57.5 mbar Start the boiler Above 25 mbar Above 57.5 mbar Install a separate gas pressure governor upstream of the system and regulate the pre-charge pressure 20 mbar for natural gas or 50 mbar for LPG. Notify your gas supply utility or LPG supplier Max. heating output setting The maximum output for heating operation can be limited. The limit is set via the modulation range. The max. adjustable output is limited upwards by the boiler coding card. Weather-compensated control unit: 1. Press OK and å simultaneously for approx. 4 s. 2. "Service functions" 3. "Max. output" 4. "Change?" Select "Yes". A value appears on the display (e.g. "85"). In the delivered condition, this value represents 100 % of rated heating output. 5. Set the required value. Constant temperature control unit: 1. Press OK and å simultaneously for approx. 4 s. Service 39

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 2. Select "3" with Ú and confirm with OK. A value flashes on the display (e.g. "85") and "A" appears. In the delivered condition, this value represents 100 % of rated heating output. 3. Select required value and confirm with OK. Checking the balanced flue system for tightness (annular gap check) A A Combustion air aperture For balanced flue systems tested gether with the wall mounted gas fired boiler, the requirement for a tightness test during commissioning by the flue gas inspecr is not applicable. We recommend that your heating engineer carries out a simple leak/tightness test during the commissioning of your system. For this, it would be sufficient check the CO 2 or O 2 concentration in the combustion air at the annular gap of the balanced flue pipe. The flue pipe is deemed be gas-tight if the CO 2 concentration in the combustion air is no higher than 0.2 % or the O 2 concentration is at least 20.6 %. If actual CO 2 values are higher or O 2 values are lower, then pressure test the flue pipe with a static pressure of 200 Pa. 40

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Removing the burner and checking the burner gasket L K G F D H E C B A 1. Switch OFF the power supply and the ON/OFF switch at the control unit. 2. Close the gas shut-off valve and safeguard against reopening. 3. Unlock control unit A and pivot forwards. 4. Remove cover panel B. 5. Pull cables from fan mor C, gas train D, ignition unit E, earthing point F and ionisation electrode G. 6. Undo gas supply pipe fittings H. 7. Undo six screws K and remove the burner. Please note! To prevent damage, never uch the mesh of the burner gauze assembly. 8. Check burner gasket L for damage. Replace gasket if required. 41 Service

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Checking the burner gauze assembly and replacing if required F E D4x C B3x A 1. Remove electrodes A. 2. Undo three retaining clips B on thermal insulation ring C and then remove thermal insulation ring C. 3. Undo four Torx screws D and remove burner gauze assembly E. 4. Remove old burner gauze assembly gasket F. 5. Insert a new burner gauze assembly with a new gasket and secure with four Torx screws. Note Torque: 4.5 Nm. 42

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 6. Refit thermal insulation ring C and electrodes A. Checking the flue gas non-return device B A 1. Undo three screws and remove fan A. 2. Remove flue gas non-return device B. 3. Check the damper and gasket for dirt and damage. Replace if required. 4. Refit flue gas non-return device B. 5. Refit fan A and secure with three screws. Torque: 3.0 Nm. Service 43

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Checking and adjusting the ignition and ionisation electrodes 14 ±1 6 +2 0 5 +3 0 4 +0,5 0 A A B A Ignition electrodes 1. Check the electrodes for wear and contamination. 2. Clean the electrodes with a small brush (not with a wire brush) or sandpaper. Please note! Wire mesh Do not damage. B Ionisation electrode 3. Check the electrode gaps. If the gaps are not as specified or the electrodes are damaged, replace the electrodes gether with new gaskets and adjust them as required. Tighten the electrode fixing screws with a rque of 2 Nm. 44

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Cleaning the combustion chamber/heat exchanger and installing the burner A 1.! Please note Scratches on parts that are in contact with flue gas can lead corrosion. Never use brushes clean the heat exchanger. Use a vacuum cleaner remove residues from heat exchanger A in the combustion chamber. 3. Thoroughly flush heat exchanger A with water. 4. Install the burner and tighten screws diagonally with a rque of 8.5 Nm. 5. Fit the gas supply pipe with a new gasket. Tighten fittings with a rque of 15 Nm. Service 2. If necessary, spray slightly acidic, chloride-free cleaning agents based on phosphoric acid on heat exchanger A and let the solution soak in for at least 20 min. 45

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 6. Check the gas connections for tightness. 7. Connect the cables/leads the corresponding components. Danger Escaping gas leads a risk of explosion. Check all fittings for gas tightness. Checking the condensate drain and cleaning the siphon 1. Pull off cap A downwards. B C A 2. Undo union nut B and pull siphon C downwards. 3. Clean siphon C and check that the condensate can drain freely. 4. Fill siphon C with water and reassemble. Note Never twist the supply hose during assembly. Route the drain hose without any bends and with a constant fall. 5. Push on cap A from below. Checking the diaphragm expansion vessel and system pressure Note Carry out this test on a cold system. 1. Drain the system or close the cap valve on the diaphragm expansion vessel and reduce the pressure until the pressure gauge indicates "0". 2. If the pre-charge pressure of the diaphragm expansion vessel is lower than the static system pressure, p up with nitrogen until the pre-charge pressure is 0.1 0.2 bar higher. 46

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 3. Top up with water until the charge pressure of the cooled system is 0.1 0.2 bar higher than the pre-charge pressure of the diaphragm expansion vessel. Permiss. operating pressure: 4 bar. Checking gas equipment for tightness at operating pressure Danger Escaping gas leads a risk of explosion. Check gas equipment for tightness. Note Only use suitable and approved leak detection agents (EN 14291) and devices for the tightness test. Leak detection agents with unsuitable constituents (e.g. nitrites, sulphides) can cause material damage. Remove residues of the leak detection agent after testing. Checking combustion quality The electronic combustion controller aumatically ensures optimum combustion quality. During commissioning/ maintenance, only the combustion values need be checked. For this, measure the CO content plus the CO 2 or O 2 content. For a description of the electronic combustion controller functions, see page 158. Note Operate the appliance with uncontaminated combustion air prevent operating faults and damage. CO content For all gas types, the CO content must be < 1000 ppm. CO 2 or O 2 content The CO 2 content must be within the following limits (upper and lower heating output): 7.5 9.6 % for natural gas E and LL 9.0 11.3 % for LPG P For all gas types, the O 2 content must be between 3.8 and 7.3 % If the actual CO 2 or O 2 values lie outside their respective ranges, check the balanced flue system for tightness, see page 40. Note During commissioning, the combustion controller carries out an aumatic calibration. Only test the emissions approx. 30 s after the burner has started. Service 47

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) A 4. Check the CO 2 content. Should the actual value deviate from the aforementioned ranges by more than 1 %, implement steps from page 47. 5. Enter actual values in the report. 6. Select the upper heating output (see page 48). 1. Connect a flue gas analyser at flue gas port A on the boiler flue connection. 2. Open the gas shut-off valve, start the boiler and create a heat demand. 7. Check the CO 2 content. Should the actual value deviate from the aforementioned ranges by more than 1 %, implement steps from page 47. 8. After testing, press OK. 9. Enter actual values in the report. 3. Set the lower heating output (see page 48). Select higher/lower heating output Weather-compensated control unit Constant temperature control unit Service menu 1. Press OK and å simultaneously for approx. 4 s. Service menu 1. Press OK and å simultaneously for approx. 4 s. 2. "Actuar test" 2. Select " " with Ú and confirm with 3. Select the lower heating output: OK. Select "Base load OFF". Then "Base load ON" appears and the burner operates at its lower heating output. 4. Select the upper heating output: Select "Full load OFF". Then "Full load ON" appears and the burner operates at its upper heating output. 5. Ending output selection: Press ä. The display shows "I" and "ON" flashes. 3. Select the lower heating output: Press OK, "ON" will be displayed constantly. 4. Select the upper heating output: Press ä. 5. Select "2" with Ú, "ON" flashes. 6. Press OK, "ON" will be displayed constantly. 7. Ending output selection: Press ä. 48

Matching the control unit the heating system Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) The control unit must be matched the equipment level of the system. Various system components are recognised aumatically by the control unit and the relevant codes are adjusted aumatically. For the selection of an appropriate scheme, see the following diagrams. For coding steps, see page 64. System version 1 One heating circuit without mixer A1, with/without DHW heating, with low loss header 7 5 6 1 2 8 qp 4 3 9 ID: 4605139_1103_02 1 Videns 200-W 2 Outside temperature sensor (only for weather-compensated control units) or Vitrol 100 (only for constant temperature control units) 3 Boiler circuit pump 4 Circulation pump for cylinder heating 5 DHW cylinder 6 Cylinder temperature sensor 7 Heating circuit without mixer A1 (heating circuit 1) 8 Heating circuit pump A1 9 Low loss header 49 Service

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) qp Flow temperature sensor, low loss header Function/system components Code Adjust Group Operation with LPG 82:1 "General"/1 System with low loss header and without DHW circulation pump: Heating circuit pump A1 connection at extension "General"/1 AM1, terminal A1 System with low loss header and with DHW circulation pump: Heating circuit pump A1 connection at extension "General"/1 AM1, terminal A1 DHW circulation pump connection at internal extension "General"/1 H1 or H2 System with low loss header 04:0 "Boiler"/1 50

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) System version 2 One heating circuit with mixer M2, with/without DHW heating, with low loss header 7 1 2 8 9 5 6 qp qe qq M 4 3 qw ID: 4605140_1103_02 1 Videns 200-W 2 Outside temperature sensor 3 Boiler circuit pump 4 Circulation pump for cylinder heating 5 DHW cylinder 6 Cylinder temperature sensor 7 Heating circuit with mixer M2 (heating circuit 2) 8 Temperature limiter restrict the maximum temperature of underfloor heating systems 9 Flow temperature sensor M2 qp Heating circuit pump M2 qq Extension kit for one heating circuit with mixer M2 qw Low loss header qe Flow temperature sensor, low loss header Service 51

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Function/system components Code Adjust Group Operation with LPG 82:1 "General" System only with one heating circuit with mixer with extension kit for mixer (without unregulated heating circuit) With DHW cylinder 00:4 "General" Without DHW cylinder 00:3 "General" System with DHW circulation pump DHW circulation pump connection at internal extension "General" H1 or H2 System with low loss header 04:0 "Boiler" System version 3 One heating circuit with mixer M2, with system separation, with/without DHW heating 7 5 6 1 8 9 2 qp qq qp qw M 4 3 ID: 4605141_1103_02 1 Videns 200-W 2 Outside temperature sensor 3 Boiler circuit pump 52 4 Circulation pump for cylinder heating 5 DHW cylinder 6 Cylinder temperature sensor

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 7 Heating circuit with mixer M2 (heating circuit 2) 8 Temperature limiter restrict the maximum temperature of underfloor heating systems 9 Flow temperature sensor M2 qp Heating circuit pump M2 qq Heat exchanger for system separation qw Extension kit for one heating circuit with mixer M2 Function/system components Code Adjust Group Operation with LPG 82:1 "General" System only with one heating circuit with mixer with extension kit for mixer (without unregulated heating circuit) With DHW cylinder 00:4 "General" Without DHW cylinder 00:3 "General" System with DHW circulation pump DHW circulation pump connection at internal extension H1 or H2 "General" Service 53

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) System version 4 One heating circuit without mixer, one heating circuit with mixer M2 (with extension kit), one heating circuit with mixer M3 (with extension kit) and low loss header (with/without DHW heating) 7 qp 9 qr qe 1 2 qt 5 6 qo 8 qw M qq qz qu M 4 3 qi ID: 4605142_1103_02 1 Videns 200-W 2 Outside temperature sensor 3 Boiler circuit pump 4 Circulation pump for cylinder heating 5 DHW cylinder 6 Cylinder temperature sensor 7 Heating circuit without mixer A1 (heating circuit 1) 8 Heating circuit pump A1 9 Heating circuit with mixer M2 (heating circuit 2) qp Flow temperature sensor M2 qq Heating circuit pump M2 qw Extension kit for one heating circuit with mixer M2 qe Heating circuit with mixer M3 (heating circuit 3) qr Temperature limiter restrict the maximum temperature of underfloor heating systems qt Flow temperature sensor M3 qz Heating circuit pump M3 qu Extension kit for one heating circuit with mixer M3 qi Low loss header qo Flow temperature sensor, low loss header 54

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Function/system components Code Adjust Group Operation with LPG 82:1 "General" System only with two heating circuits with mixer with extension kit for mixer (without unregulated heating circuit) With DHW cylinder 00:8 "General" Without DHW cylinder 00:7 "General" System without DHW circulation pump Heating circuit pump A1 connection at internal extension "General" H1 or H2 System with DHW circulation pump Heating circuit pump A1 connection at extension "General" AM1, terminal A1 DHW circulation pump connection at internal extension "General" H1 or H2 System with low loss header 04:0 "Boiler" System version 5 Multi boiler system with several heating circuits with mixer and low loss header (with/without DHW heating) 1 2 3 qw 8 9 qe qr 1 5 6 qi qq M qp qt qz M Service 7 4 4 qu ID: 4605016_1103_04 55

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) 1 Videns 200-W 2 Vitronic 300-K 3 Outside temperature sensor 4 Boiler circuit pump 5 DHW cylinder 6 Cylinder temperature sensor 7 Circulation pump for cylinder heating 8 Heating circuit with mixer M2 (heating circuit 2) 9 Flow temperature sensor M2 qp Heating circuit pump M2 qq Extension kit for one heating circuit with mixer M2 qw Heating circuit with mixer M3 (heating circuit 3) qe Temperature limiter restrict the maximum temperature of underfloor heating systems qr Flow temperature sensor M3 qt Heating circuit pump M3 qz Extension kit for one heating circuit with mixer M3 qu Low loss header qi Flow temperature sensor, low loss header Required codes Address Multi boiler system with Vitronic 300-K 01:2 Note Codes for multi boiler system, see Vitronic 300-K installation and service instructions. Adjusting the heating curves (only for weather-compensated control units) The heating curves illustrate the relationship between the outside temperature and the boiler water or flow temperature. To put it simply: The lower the outside temperature, the higher the boiler water or flow temperature. The room temperature, in turn, depends on the boiler water or flow temperature. Settings in the delivered condition: Slope = 1.4 Level = 0 Note If the heating system includes heating circuits with mixers, then the flow temperature of the heating circuit without mixer is higher by a selected differential (8 K in the delivered condition) than the flow temperature of the heating circuits with mixers. The differential temperature is adjustable via coding address "9F" in the "General" group. 56

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) Boiler water or Flow temperature in C 90 80 70 60 50 40 3.0 3.2 3.4 2.6 2.8 2.4 2.2 Slope 2.0 1.8 1.6 1.4 1.2 1.0 0.8 0.6 0.4 30 0.2 35 30 25 20 15 10 5 Set room temperature in C 10 5 0-5 -10-15 -20-25 Outside temperature in C -30 Slope setting ranges: Underfloor heating systems: 0.2 0.8 Low temperature heating systems: 0.8 1.6 Standard set room temperature 90 A Selecting the set room temperature Individually adjustable for each heating circuit. The heating curve is offset along the axis of the set room temperature. When the heating circuit pump logic function has been enabled, the curve modifies the starting and spping characteristics of the heating circuit pump. C D 26 + 20 B -20 E Example 1: Change in the standard set room temperature from 20 26 C Service A Boiler water temperature or flow temperature in C B Outside temperature in C C Set room temperature in C 57

Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) D Heating circuit pump "OFF" E Heating circuit pump "ON" Changing the standard set room temperature Operating instructions Changing the slope and level Individually adjustable for each heating circuit. 90 3.5 Reduced set room temperature C D 90 A +20 14 5 B -20 E Example 2: Change in the reduced set room temperature from 5 C 14 C A Boiler water temperature or flow temperature in C B Outside temperature in C C Set room temperature in C D Heating circuit pump "OFF" E Heating circuit pump "ON" Changing the reduced set room temperature Operating instructions Boiler water or flow temperature in C A B +20-20 Outside temperature in C 1.4 0.2 A Changing the slope B Changing the level (vertical parallel offset of the heating curve) Extended menu: 1. å 2. "Heating" 3. Select heating circuit. 4. "Heating curve" 5. "Slope" or "Level" 6. Select heating curve according the system requirements. 58

Connecting the control unit the LON Commissioning, inspection, maintenance Further details regarding the individual steps (cont.) The LON communication module must be plugged in. Note The data transfer via the LON can take several minutes. Note In the LON system, the same subscriber number cannot be allocated twice. Only one Vitronic may be programmed as fault manager. Single boiler system with Vitronic 200-H and Vicom 300 (example) Set the LON subscriber numbers and further functions via code 2 in group "General" (see following table). Boiler control unit Vitronic 200-H Vitronic 200-H Vicom LON LON LON Subscriber no. 1 Code "77:1" Control unit is fault manager Code "79:1" Control unit transmits the time Code "7b:1" Control unit transmits outside temperature Set code "97:2" LON subscriber fault moniring Code "9C:20" Subscriber no. 10 Code "77:10" Control unit is not fault manager Code "79:0" The control unit receives the time Set code "81:3" Control unit receives outside temperature Set code "97:1" LON subscriber fault moniring Code "9C:20" Subscriber no. 11 Set code "77:11" Control unit is not fault manager Code "79:0" The control unit receives the time Set code "81:3" Control unit receives outside temperature Set code "97:1" LON subscriber fault moniring Code "9C:20" Subscriber no. 99 Device is fault manager Device receives the time Service 59