Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland. Evaluation of task air conditioning system with convection, conduction, and radiation

Similar documents
AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality

Human response to thermal environment in rooms with chilled beams

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Experimental study of a novel dew point indirect evaporative cooler

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

EFFECTS OF EXTREMELY LOW HUMIDITY ON COMFORT AND FATIGUE OF JAPANESE OCCUPANTS

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

Experimental Study to Evaluate Smoke Stratification and Layer Height in Highly Ventilated Compartments

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

Center for the Built Environment October 2013

AMOUNT OF MOISTURE PRODUCED INSIDE BATHROOM AND APPURTENANT CHANGING ROOM

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Indoor Thermal Environment of Residential Buildings in Three Cities of China

Thermal Comfort with Convective and Radiant Cooling Systems

Study on water conservation by water saving fixtures

Heat Exchanger Shelves For Better Temperature Control Of Food In Open-Type Display Cases

Comfort and health-indoor air quality

Experimental study of space cooling using ceiling panels equipped with capillary mats

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

A Novel Approach for the Thermal Management. of PC Power Supply

Survey on Cooling Costs and Related Factors for Apartments in an Urban. Area of Osaka

Experimental Study on Crawl-Space Heating with Thermal Storage using Heat Pump

Development Of A Low-Cost Heat Pump Water Heater For Residential Applications

STUDY ON A FLOOR SUPPLY AIR CONDIGIONING SYSTEM WITH THERMAL ENERGY STORAGE USING GRANULATED PCM

A Study on the Effects of Urban Landscape on Citizen s

THERMAL VACUUM TESTS OF A FIVE WATT PSEUDO CHIP SEM-X ELECTRONIC MODULE CLAMPED IN A SATELLITE BOX

Poultry Housing Tips Radiant Tube Heater Floor Heating Patterns Volume 17 Number 5 April, 2005

A study of radiant cooling for a room with daytime application in tropical climate

A Study on the Characteristics of Planning within Analyzing of Exterior Space in Mixed-use Development 1

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Module 1: Introduction to Radiant Cooling. Pierre Jaboyedoff

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

Experimental study of fan coil assisting radiant floor heating system

How to ensure Thermal Comfort in buildings with CFD

The Low-Temperature Radiant Floor Heating System Design and Experimental Study on its Thermal Comfort

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement

Development of Gas-Liquid Two-Phase Flow Distributor for Improving Energy Efficiency in Air-Conditioners

Evaluation of Fill Power Conditioning Methods

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Ergonomic Assessments of the Melni BD2HL-S Mechanical Lug Connector and the Traditional Crimped Lug Connector

Secador Automatic Desiccator. vs. Comparable Competitor

Temperature Distribution of Rotary Heat Recovery Units

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

OIL AND GAS INDUSTRY

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

SURVEY ON THE OCCUPANT BEHAVIOR RELATING TO WINDOW AND AIR CONDITIONER OPERATION IN THE RESIDENTIAL BUILDINGS

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

Comparison of Thermal Comfort by Radiant Heating and Convective Heating

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

Osaka City New Supply of Office Buildings & Office Stock Pyramid 2015

Conductive Heating Technologies for Medical Diagnostic Equipment. Russell Strehlow, Manager of Research and Development, Minco

FORM ACCL-PC1 ACCL WITNESS TEST PROCEDURE AND CHECKLIST

Optimisation of cooling coil performance during operation stage for improved humidity control

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

U.S. Fire Department Profile 2015

Electric radiator tests

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

EXPERIMENTAL STUDIES CONCERNING WATER MIST FIRE SUPPRESSION IN VENTILATED CLOSED SPACES

The Participant will select one of the two Approval Categories (below) and submit the appropriate documentation.

Analysis and Evaluation of a Passive Evaporative Cool Tower in conjunction with a Solar Chimney

The Affect Differentiating ph Levels and Visible Light. Spectrums have on the Rudbeckia Hirta

Case Study. A Geothermal Energy Generation Facility Embraces Infrared. Polymer Window Inspections. Overview: iriss.com

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Hot-air heating of family houses with accumulation of energy in the floor

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Mold Infestation in Buildings of Warm Humid Climate Case Studies

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

Landscape planning for a safe city

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Applied Energy 83 (2006)

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Soil-Structure Interaction of a Piled Raft Foundation in Clay a 3D Numerical Study

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

Comparison of radiant and convective cooling of office room: effect of workstation layout

1.1. SYSTEM MODELING

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

APPLICATION OF HEAT PUMP SYSTEM FOR ECO-FRIENDLY VEHICLES

UBC Social Ecological Economic Development Studies (SEEDS) Student Report


American Society of Heating, Refrigerating and Air-Conditioning Engineers

A WEB-BASED SIMULATION TOOL ON THE PERFORMANCE OF DIFFERENT ROOFING SYSTEMS

Transcription:

Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland Paper ID 0009 ISBN: 978-83-7947-232-1 Evaluation of task air conditioning system with convection, conduction, and radiation Misa Imazu 1,*, Shin-ichi Tanabe 1, Jiannan Liu 2, Kazuki Furumoto 2, Riho Matsuzaki 2, Miki Iijima 2, Kenji Fujino 3, Daisuke Hatori 3, Nobuhiro Hirasuga 3, Shun Kato 3, Shiori Sasahara 4, Hiroki Iwata 5 1 Waseda University, Tokyo, Japan 2 Former Waseda University, Tokyo, Japan 3 Mitsubishi Jisho Sekkei Inc., Tokyo, Japan 4 Taksago Thermal Engineering Co., Ltd., Tokyo, Japan 5 TOYOX Co., Ltd., Toyama, Japan * Corresponding email: imazu@tanabe.arch.waseda.ac.jp SUMMARY In this study, a subjective experiment was conducted to evaluate thermal sensation and comfort, and usage of newly developed task conditioning system in different ambient temperatures. Gender differences were shown in task usage, and individual differences were significant at higher ambient temperatures. Data of how one uses task conditioning are crucial under practical use and when evaluating overall energy conservation, considering both task and ambient conditioning systems. KEYWORDS task usage, individual controlling, gender differences, steady rate, non-steady rate 1 INTRODUCTION Diversity in the working style of office workers and thermal constitution has becomes more conspicuous in recent years, causing diversity in thermal sensation and comfort. Task ambient conditioning systems are being recognized as a technology to improve the thermal comfort of office workers. In this study, a newly developed task conditioning system named task desk was used. The purpose of this study is to evaluate how the task desk is used under different ambient conditions and to evaluate thermal comfort. 2 MATERIALS/METHODS 2.1 Task Desk Figure 1 shows the image of task desk. Task desk is installed with three different types of personal conditioning systems (PCSs), depending on different modes of heat transfer: convective, conductive, and radiative. All of the PCSs are cooled by water at 16 C, which is supplied by pipes connected to each desk.

A. Convective PCS Two fans are installed in the front screen. The ambient air is induced by the inlet port and cooled by the cooling coils, which are cooled by cooling water. The cooled air is then supplied to the user by the outlet port. This PCS cools the user by the cooled air, which is expected to hit the upper body. Users can choose the three levels of air capacity supplied: OFF/Weak/Strong. At the Weak level, the cooled air hits the users arms, and at the Strong level, it hits the head and chest. Users cannot choose the temperature of the supplied air. B. Conductive PCS A cooling panel is installed on top of the desk surface, and the cooling water is directly supplied to the panel. This PCS is expected to cool the users by convective heat transfer when contact between the cooling panel and users arms occurs. Users can either choose ON/OFF of this PCS by the water supply and cannot change the surface panel temperature. C. Radiative PCS The same cooling panel used in the conductive PCS is installed under the desk surface, and it is expected to cool the users thighs by radiation. Users can either choose ON/OFF of this PCS and cannot change the surface panel temperature. A. Top View A. Convective PCS (outlet) B. Bottom View Strong/Weak: 53 m 3 /h / 73 m 3 /h A. Convective PCS (inlet) B. Conductive PCS Surface temperature: 22 o C C. Radiative PCS Surface temperature: 18 o C Figure 1. Image of Task Desk and each PCS installed. 2.2 Subjective Experiment A subjective experiment was conducted to evaluate thermal comfort and task usage of each PCS under three different ambient temperatures: 26 C, 28 C, and 30 C. This experiment was conducted in a research laboratory where a radiant conditioning system was used as the ambient conditioning system. In this room, both water and air supplied radiant cooling panels are used. Heating elements are set to simulate an office room. Figure 2 shows the image of the research laboratory and the location of the desks. Water supplied radiant cooling panel (50 %) Air supplied radiant cooling panel (2 %) Blank panel Lighting panel Heating element (Large) Heating element (Small) Figure 2. Image of the research laboratory and desk locations.

In this experiment, eight males and seven females in their twenties were chosen. The clothing level was 0.48 clo for males and 0.44 clo for females, which are normal clothing levels for office workers during summer in Japan. Table 1 shows the measurement items. Measuring of ambient environment and the verification of the task desk was conducted to verify if the PCSs were at the temperatures shown in Figure A, and the ambient temperatures were controlled through the experiment. Table 1. Measurement items Measurement items Location No. of points Measuring interval Ambient temp., humidity ( C, %) Air temp. of convective PCS (inlet) ( C) 1.1 m above floor Inlet of fan Air temp. of convective PCS (outlet) ( C) Surface temp. of conductive PCS ( C) Surface temp. of radiative PCS ( C) Outlet of fan Panel surface Panel surface 1 1 min Before the experiment was performed, a questionnaire about gender, likes/dislikes of air conditioning, and body condition was distributed to each subject. First, a step exercise that was to simulate a 15-min walk at 2.0 met, was conducted in an outside air chamber, which was set at 30 C. This step exercise was to simulate a situation where an office worker returns from a hot outdoor environment during summer. Then, the subjects were to enter the research laboratory and answer the questionnaire about their thermal sensation and comfort. The experiment began with all of the PCSs set at OFF. Subjects were allowed to arrange the PCSs once every 15 min and to report how they were arranged. Thermal sensation and comfort were reported at 1, 3, 6, 9, 12, 15, 30, 45, 60, 75, and 90 min after the experiment started. After the experiment, subjects were asked to answer the questionnaire about the PCSs. Data in the 0 30 min range were analyzed as data in the non-steady rate, indicating that the metabolic rate was not stable, and that in the 45 90 min range were analyzed as data in the steady rate. 3 RESULTS 3.1 PCS Usage Figure 3 shows the percentage of PCS usage in different ambient temperatures. The upper graphs show the PCS usage of males, and the lower graphs show the PCS usage of females. Convective PCS(Strong) Convective PCS(Weak) Conductive PCS Radiative PCS Male Femal 0-15 15-30 30-45 45-60 60-75 75-90 0-15 15-30 30-45 45-60 60-75 75-90 0-15 15-30 30-45 45-60 60-75 75-90 nonsteady steady nonsteady steady nonsteady steady 30 C 28 C 26 C Figure 3. PCS usage at different ambient temperatures (Upper: male, Lower: female) (n=15).

A. Differences between ambient temperatures When the ambient temperature was 30 C, the PCS usage of the convective PCS was 100 %, both for males and females. The usage of the radiative PCS was almost 100 % for both genders, both in steady and non-steady rate. All of the subjects used the PCS more at 30 C, compared to 28 C and 26 C. Thus, this can prove PCSs are needed for many subjects to improve their thermal sensation and comfort. When the ambient temperature was 28 C, the usage of the convective PCS was 100 % for males in steady rate. The usage of the conductive PCS was higher for males, which was approximately double that of females. When the ambient temperature was 26 C, the usage of the convective PCS for females dramatically dropped in steady rate. The usage of the PCS dropped for both genders when the ambient temperature was lower; however, the male used the convective and conductive PCS more as compared to females. B. Differences between PCSs For all ambient temperatures, the usage of the convective PCS was higher for males compared to females, and the usage of the convective PCS (Strong) dropped at 26 C. The usage of the conductive PCS significantly dropped for females in steady rate. The usage of the radiative PCS was higher compared to other PCSs in all conditions, and there were no significant drops for females as seen in the usage of other PCSs. This proved that convective and conductive PCSs were able to improve thermal sensation and comfort more quickly as compared to radiative PCSs. 3.2 Thermal Sensation and Comfort Table 2 shows the scale of thermal sensation and comfort, Figure 4 shows the average changes in thermal sensation and comfort, and Figure 5 shows the percentage change in thermal sensation and comfort. Table 2. Scale of thermal sensation and comfort Value -3-2 -1 0 Thermal sensation Thermal comfort Very cold Very uncomfortable Cold Uncomfortable Slightly cold Slightly uncomfortable Neutral Neutral Value +1 +2 +3 Thermal sensation Slightly hot Hot Very hot Thermal comfort Slightly comfortable Comfortable Very comfortable A 30 C 28 C A 26 C non-steady steady non-steady steady thermal sensation thermal comfort Figure 4. Average changes in thermal sensation and comfort.

Thermal comfort: Hot side Neutral side Cold side Thermal sensation: Comfortable side Neutral side Uncomfortable side Thermal Sensation Thermal Comfort time [min] time [min] time [min] non-steady steady non-steady steady non-steady steady 30 C 28 C 26 C Figure 5. Percentage change in thermal sensation and comfort (n=15). In this experiment, the scale shown in Table 2 was used to analyze thermal sensation and comfort. For thermal sensation, Very cold and Cold were regarded as Cold side, where Slightly cold, Neutral, and Slightly hot were Neutral side, and Hot and Very hot were Hot side. For thermal comfort, Very uncomfortable and Uncomfortable were regarded as Uncomfortable side, whereas Slightly uncomfortable, Neutral, and Slightly comfortable were Neutral side, and Comfortable and Very comfortable were Comfortable side. On an average, there were no significant differences between ambient temperatures in average thermal sensation and comfort in steady rate, as shown in Figure 4. Thermal sensation was approximately neutral in ambient temperature at 30 C and 28 C, and slightly cold at 26 C. Thermal comfort improved throughout the experiment for all ambient temperatures, scoring approximately +1. However, there were differences in the percentage change of thermal sensation and comfort, as shown in Figure 5. When the ambient temperature was 30 C, there were approximately 10 % of Hot side in steady rate, whereas 0 % at 28 C and 26 C. In addition, there were 50 75 % of Comfortable side at 30 C, whereas 65 90 % at 28 C and 26 C. This proves that the use of the PCSs can improve one s thermal sensation and comfort at 30 C; however, it cannot reach to the same level as when the temperature is 28 C or 26 C. Regarding Figure 3, many subjects did not use PCSs at 26 C. However, though thermal comfort still scores approximately the same or higher level at 28 C. This proves that using PCSs at 28 C can improve one s thermal sensation and comfort to the same or higher level as when PCSs are not used at 26 C. As shown in Figures 4 and 5, by using PCSs at 30 C, the average thermal comfort can score the same or higher level as that at 28 C and 26 C; however, the percentage of each side varied. Thus, it can be estimated that individual differences were significant at higher ambient temperatures, and there were a certain number of subjects feeling hot and uncomfortable at steady rate.

3.3 Opinions on PCSs Figure 6 shows the opinions on which PCS had the most cooling effect and which was the most favorable. 30 C 28 C 26 C Convective PCS Conductive PCS Radiative PCS Did not use PCS percentage [%] percentage [%] PCS which had the most cooling effect Most favorable PCS Figure 6. PCS which had the most cooling effect and the most favorable PCS (n=15). The conductive PCS was reported as having the highest cooling effect among all PCSs. In addition, more subjects favored convective PCS at higher ambient temperatures. The opposite trend was shown for convective PCS, where more subjects favored the PCS at lower ambient temperatures. Few answered the radiative PCS as having most cooling effect, thus only a few answered they favoured. It can be guessed that many subjects could not feel a large cooling effect because of the position of the panel. The thighs are covered with clothes which made it difficult for subjects to feel the cooling. By several subjects, it was reported that they were not satisfied with the radiative PCS because of the small cooling effect. 4 DISCUSSION The results show that the way subjects arrange each PCS varies between genders. Each subject arranged the PCS to improve their thermal sensation and comfort, and in average, achieved same level of comfort regardless of ambient temperatures. However, it was shown that the use of PCS at 30 C cannot prevent all of the subjects from feeling hot. 5 CONCLUSIONS In this study, we evaluated thermal sensation and comfort and the task usage of PCSs. There were differences between genders on how and which PCS is used. In addition, individual differences about thermal sensation and comfort were significant under higher ambient temperatures. How task conditioning systems are used is dependent on the individuals, and knowing how these are used is an important information when operating, and saving the total energy consumption. In this study, variation between genders were shown however, further studies about the differentiation within genders are needed for optical operation. 6 REFERENCES Hatori et al., 2015. Design and Verification of the Advanced Office Part 1~5. In: Summaries of technical papers of annual meeting / Society of Heating, Air-Conditioning and Sanitary Engineers of Japan (in Japanese), 5-24 pages. Ohta et al., 2010. Effects of Environmental Selection Option on Thermal Comfort. In: Summaries of technical papers of annual meeting / Society of Heating, Air-Conditioning and Sanitary Engineers of Japan (in Japanese), Yamaguchi, 1115-1118 pages. Zhang et al., 2008. Comfort, Perceived Air Quality, and Work Performance in a Low-Power Task-Ambient Conditioning System. Ph.D. Thesis, Center for the Built Environment (CBE), University of California, Berkley, 16-18, 32-41 pages.