ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

Similar documents
ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

ISOMETER IR425. Insulation monitoring device for unearthed AC/DC control circuits (IT systems)

Residual current monitor RCM470LY/RCM475LY. for TN and TT systems (AC and pulsating DC currents)

LINETRAXX RCMA420. Residual current monitor for monitoring AC, DC and pulsed DC currents in TN and TT systems

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

ISOMETER isomed427p. Application Medical IT system in accordance with IEC , IEC , IEC and DIN VDE

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

LINETRAXX VMD420. Multi-functional voltage relay for 3(N)AC systems, frequency/overvoltage/undervoltage, phase, phase failure, asymmetry

Insulation fault evaluator EDS460-DG

1.7. Insulation fault evaluators EDS460/490 EDS461/491

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Remote alarm indicator and test combination MK2430

IT system floor-standing distribution

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

GM420. Digital Ground Continuity Relay For AC Systems. Technical Bulletin NAE /

Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Phone: Fax:

ISOMETER IRDH265 IRDH365

RCMA423-DM RCMA423-DM1C RCMA423-DM2C RCMA423-DM3C. Operating Manual

Operating Manual RCM420

LINETRAXX RCMS460-D/-L RCMS490-D/-L

Operating Manual VMD420

BENDER A-ISOMETER IRDH265 IRDH365

TM800. Remote alarm indicator and operator panels

Manual CME420. Multi-functional current relay, AC, overcurrent/undercurrent/ window discriminator function CME420_D00034_02_M_XXEN/05.

Bender GmbH & Co. KG. All rights reserved. Reprinting only with permission of the publisher. Subject to change! Photos: Bender archives

VME420 Voltage and frequency monitor

VME421H Voltage and frequency monitor

RCMA423. Residual current monitor for monitoring AC-, DC- and pulsed DC currents in TN- and TT systems Software-Version: D330 V1.0x.

RCMA423-DM1C Residual current monitor

CMD420 / CMD421 Series

ISOMETER IRDH375 IRDH375B

A-ISOMETER IRDH575. Operating Manual

Bender GmbH & Co. KG All rights reserved. Reprinting only with permission of the publisher. Subject to change! Photos: Bender archives.

RTA421. Technical Information. Limit alarm switch Alarm switch and power supply for monitoring current or voltage signals

PolyGard 2-channel Gas Controller MGC-03

Operating Manual MS220KA and MSR220KA

enproteko.com Specifications Ratings Item voltage to 24 VAC 5/6 Hz 24 VAC 5/6 Hz or 24 VDC Allowable voltage Characteristics 85% to 11% of power suppl

Line Isolation Monitor (LIM) LIM2000plus

T M LIM2010. Line Isolation Monitor (LIM) Technical Bulletin NAE /

LINETRAXX RCMS150. Residual current monitor type B with integrated measuring current transformers for earthed AC/DC systems (TN and TT systems)

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description

Monitoring Devices 11/1

DEB71. Earth Leakage Monitoring Relay. Benefits. Description

Connection. e. g. Pt100. reference limit. yellow Output I. Composition

Operating Manual MS220DA

Power Supply Display Module PSDM. Installation and Operation Manual

MK Series. Remote Indicators For Line Isolation Monitors and Fault Location. Technical Bulletin NAE /

02/11/2015

PolyGard Single Point Controller SPC-X3-20XX for refrigerant gases and vapours

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

PolyGard Single Point Controller SPC-X3-11XX for Toxic Gases and Oxygen

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-nA.

KHA6-GT*-Ex1. Thermocouple trip amplifiers. Composition. Hazardous area. Safe area. Function. 230 V AC 1-channel. Input EEx ia IIC

02/11/2015

Process Alarm Module RTA 421

PROTECT SRB 200EXi-1A

Parameterisable compact fault annunciator with permanent display

Universal fault annunciator for panel mounting

Additional Operating Instructions SITRANS F. Vortex flowmeters. SITRANS FX330 Ex-d.

Operating Manual TR600

Electronic Standard Devices. Annunciator Relay. MR 11 and MRE 11 MR 21 and MRE 21

7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for Infrastructure & Cities.

ISOMETER isopv1685rtu isopv1685p isopv1685pfr

Annunciator Relay MR 11 and MRE 11 MR 21 and MRE 21. Automation Equipment. Power Station Control Systems. Control Room Technology

RSWT. Three phase AC pumps and ventilators soft starter. Benefits. Description

IR5002. Operating Manual. Insulation monitoring device for IT DC systems V ISO Quality System Certified

SCHMIDT LED Measured Value Display MD Instructions for Use

Product overview. Alarm indicator, operator and display panels

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

GMA4100-DP. Control Panel. Operation Manual. Worldwide Supplier of Gas Detection Solutions

Combustible Gas Detection and Control System

Operating instructions Safety-monitoring module SRB 302X3. 1 About this document

Operating Manual MSF220V(VU)

Thermal Management Products & Accessories for Enclosures

VAMP 120 & 121. Arc flash detection units. Product picture

Ordering Key. Dielectric strength

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Overload relays. General descriptions. Configuration of the front

M15051) INSTRUCTION MANUAL

Interface and EOL Modules 8

FLAME AMPLIFIER MODULE 3001

Inductive Conductivity Measurement. Simultaneous display of conductivity/ resistance/salinity and temperature; large measurement symbol.

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

Monitoring Relays. 3RN1 Thermistor Motor Protection. For PTC sensors. 7/120 Siemens LV 1 T 2008

T M. User Manual LIM2010. Line Isolation Monitor

ABB Instrumentation. Specifications. COMMANDER 150 Universal Process Indicator. the 1 /8 DIN indicator to match all your display requirements

ISIS SAFETY SYSTEM Installation guide

INSTRUCTION MANUAL (ATEX / IECEx)

Operating instructions Safety-monitoring module SRB 302X3. 1. About this document. Content

OilSET-1000 (12 VDC)

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

EARTH FAULT METER MD-08

Vibracon LVL-A* Level limit switch for liquids, compact design

Oxygen (O2) Single-Point Gas Detection System

Transcription:

Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V IR1575_D00116_00_D_XXEN/05.2015

Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V Product description The ISOMETER of the IR1575 series monitor the insulation resistance of unearthed main circuits (IT systems) AC, 3(N)AC 0 480 V resp. DC 0 480 V. The AMP measurement method allows the Isometers to be used in systems with directly connected DC components. Taking the system leakage capacitances into account, the IR1575 automatically adapts itself to the existing system conditions in order to optimise the measuring time. An external supply voltage allows de-energised systems to be monitored too. Please note that the frequency range of the IR1575 is limited to DC, 30 420 Hz. For use in systems containing variable-speed drives, we recommend to use the IRDH275/375 version. ISOMETER IR1575 Device features Insulation monitoring for unearthed AC, AC/DC systems 0 480 V and DC systems 0 480 V Two separately adjustable response values 2 kω 1 MΩ AMP measurement method Automatic adaptation to the system leakage capacitance LEDs: Alarm 1/Alarm 2 Fault memory behaviour, selectable Connection monitoring system/earth Test and reset button Connection external test and reset button Two separate alarm relays with one changeover contact each N/O or N/C operation, selectable Backlit LC display Self monitoring with automatic alarm Plug-in terminals Enclosure for door mounting 96 x 96 mm Application AC or AC/DC main circuits AC/DC main circuits with directly connected DC components UPS systems, battery systems Heaters with phase control Installations including switch-mode power supplies Function When the insulation resistance between the system conductors and earth falls below the set response value, the alarm relays switch and the alarm LEDs light up. Two separately adjustable response values/alarm relays allow a distinction to be made between prewarning and alarm. The measured value is indicated on the LC display. The fault message can be stored. The fault memory can be reset by pressing the reset button. By pressing the test button, the function of the device as well as the connections to system and earth can be tested. When a fault occurs during this test, it will be signalled by alarm relay K2. The parameterisation of the device can be carried out via the LC display or the function buttons integrated in the front plate. Measurement method The ISOMETER s of the IR1575 use the AMP measurement method. Standards The ISOMETER of the IR1575 series complies with the requirements of the device standards: DIN EN 61557-8 (VDE 0413-8), EN 61557-8, IEC 61557-8, IEC 61326-2-4, DIN EN 60664-1 (VDE 0110-1), DIN EN 60664-3 (VDE 0110-3), ASTM F1669M-96 (2007), ASTM F1207M-96 (2007) Approvals 2 IR1575_D00116_00_D_XXEN/05.2015

Wiring diagram Operating elements Wiring diagram Mains connection ISOMETER IR1575 1 U S 2 1 2 3 4 5 6 7 8 9 10 3 4 1 - TEST button: to call up the self test Arrow up button: Parameter changes, scroll 2 - RESET button: to delete alarm and fault messages Arrow down button: Parameter changes, scroll 3 - MENU button: to call up the menu system Enter button: to confirm parameter changes 4 - LC display 2 x 16 characters 5 - Alarm LED 1 lights: insulation fault, first warning level reached 6 - Alarm LED 2 lights: insulation fault, second warning level reached 7 - External test button T1/T2 (N/O contact) 8 - External reset button R1/R2 (N/C contact or wire jumper). When the terminals are open, the fault message will not be stored. 9 - Alarm relay. Alarm 2 10 - Alarm relay. Alarm 1 5 6 1 - Supply voltage U S (see nameplate) 6 A fuse protection recommended: A0 - A1 = AC 88 264 V, DC 77 286 V A0 - A2 = AC 340 460 V 2 - Separate connection of E and KE to PE 3 - Connection to the AC system to be monitored: connect terminals L1, L2 to conductor L1, L2. 4 - Connection to the DC system to be monitored: Connect terminal L1 to conductor L+, terminal L2 to conductor L- 5,6 - Connection to the 3AC system to be monitored: Connect the terminals L1, L2 to neutral conductor N or terminals L1, L2 to conductor L1, L2. IR1575_D00116_00_D_XXEN/05.2015 3

Technical data Insulation coordination acc. to IEC 60664-1 Rated insulation voltage AC 500 V Rated impulse withstand voltage/pollution degree 4 kv/3 Voltage ranges Nominal system voltage AC, 3(N)AC 0 480 V, DC 0 480 V Nominal frequency f n DC, 30 420 Hz Supply voltage U S see ordering information Power consumption 5 VA Response values Response value R an1 (Alarm 1) 2 kω 1 MΩ Response value R an2 (Alarm 2) 2 kω 1 MΩ Relative uncertainty 0 + 20 %/min. +2 kω Response time t an at R F = 0.5 x R an and C e = 1 μf 5 s Hysteresis 25% Measuring circuit Measuring voltage U m ±20 V Measuring current I m (at RF = 0 Ω) 170 µa Internal DC resistance R i 119 kω Impedance Z i at 50 Hz 14 kω Permissible extraneous DC voltage U fg DC 680 V Permissible system leakage capacitance 60 μf Displays Display backlit LC display Characters (number of characters, height) 2 x 16 (4.5 mm) Display range, measured value 1 kω 5 MΩ Operating uncertainty (1 10 kω) ± 1 kω Operating uncertainty (10 kω 5 MΩ) ± 10 % Outputs Test and reset button internal/external Switching elements Number of switching elements 2 x 1 changeover contact Operating principle N/C operation/n/o operation Factory setting N/O operation Contact class IIB (IEC 60255-0-20) Rated contact voltage AC 250 V/DC 300 V Making capacity AC/DC 5 A Breaking capacity 2 A, AC 230 V, cos phi 0.4 0.2 A, DC 220 V, L/R = 0.04 s Contact rating at DC 24 V 2 ma (50 mw) Environment Shock resistance IEC 60068-2-27 (device in operation) 15 g/11 ms Bumping IEC 60068-2-29 (transport) 40 g/6 ms Vibration resistance IEC 60068-2-6 (device in operation) 1 g/10 150 Hz Vibration resistance IEC 60068-2-6 (transport) 2 g/10 150 Hz Ambient temperature (during operation) -10 +55 C Ambient temperature (during storage) -40 +70 C Climatic class acc. to DIN IEC 60721-3-3 3K5 Connection Connection plug-in terminals Connection properties rigid/flexible 0.2 /4/0.2 2.5 mm² flexible with ferrules without/with plastic sleeve 0.25 2.5 mm² Conductor sizes (AWG) 24 12 Tightening torque 0.5 0.6 Nm (4.3 5.3 lb-in) Other Operating mode continuous operation Mounting position display-oriented Degree of protection, internal components (DIN EN 60529) IP30 Degree of protection, terminals (DIN EN 60529) IP20 Mounting panel mounting Flammability class UL94 V-2 Documentation number D00116 Weight 400 g 4 IR1575_D00116_00_D_XXEN/05.2015

Measuring time Dimension diagram Dimensions in mm t an [s] R f C e [µf] Ordering information Design Standard Increased shock and vibration resistance 1) Absolute values 1) Supply voltage U S AC DC Type Art. No. 88 264 V 340 460 V 77 286 V IR1575-435 B 9106 4000 16 72 V 10.2 84 V IR1575-434 B 9106 4003 88 264 V 340 460 V 77 286 V IR1575W-435 B9106 4000W IR1575_D00116_00_D_XXEN/05.2015 5

Bender GmbH & Co. KG P.O. Box 1161 35301 Gruenberg Germany Londorfer Strasse 65 35305 Gruenberg Germany Tel.: +49 6401 807-0 Fax: +49 6401 807-259 E-Mail: info@bender.de www.bender.de BENDER Group IR1575_D00116_00_D_XXEN / 05.2015 / pdf / Bender GmbH & Co. KG, Germany Subject to change! The specified standards take into account the version that was valid at the time of printing.