Available online at ScienceDirect. Energy Procedia 52 (2014 ) Vishal Vadabhat, Rangan Banerjee

Similar documents
A study of Transient Performance of A Cascade Heat Pump System

Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

INDOOR HUMAN THERMAL COMFORT OPTIMAL CONTROL WITH DESICCANT WHEEL COOLING SYSTEM

Available online at ScienceDirect. Energy Procedia 70 (2015 ) Yanjun Dai*, Xian Li, Ruzhu Wang

Available online at ScienceDirect. Energy Procedia 109 (2017 ) 56 63

Continuous Commissioning: A Valuable Partner to Retrofit Projects

VARIABLE HEAT RECOVERY IN DOUBLE BUNDLE ELECTRIC CHILLERS. Richard J Liesen 1, Rahul J Chillar 2 1 University of Illinois at Urbana Champaign

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Performance of an Improved Household Refrigerator/Freezer

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

Experimental Investigation of a Heat Pump Assisted Fluidized Bed Dryer

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Available online at ScienceDirect. Energy Procedia 91 (2016 ) 35 41

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Performance Optimization of the Evaporative Condenser Design

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Pressure Enthalpy Charts

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Optimisation of cooling coil performance during operation stage for improved humidity control

Available online at ScienceDirect. Energy Procedia 78 (2015 )

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Don t Turn Active Beams Into Expensive Diffusers

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

Binoe E. ABUAN, Menandro S. BERANA, Ruben A. BONGAT. University of the Philippines Diliman, Quezon City, Philippines

Redesign of Bennett Hall HVAC System

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

2. CURRICULUM. Sl. No.

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

Enhancement of COP in Vapour Compression Refrigeration System

Performance evaluation of a liquid desiccant solar air conditioning system

Dehumidification: Energy Efficiency Comparisons

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

The Effect of Quantity of Salt on the Drying Characteristics of Fresh Noodles

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

HVAC Water chiller selection and optimisation of operation

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Optimizing Electric Humidifier Operation with an Air Side Economizer

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Experimental Investigation of a Multi Effect Membrane Based Regenerator for High Concentration Aqueous LiCL Solution as Desiccant

Numerical Simulation of Window Air Conditioner

Air Conditioning Clinic

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

MODELING OF THE SINGLE COIL, TWIN FAN AIR-CONDITIONING SYSTEM IN ENERGYPLUS

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

ScienceDirect. Development progress of critical equipment in the CSNS cryogenic hydrogen system

Seyedeh Sepideh Ghaffari 1 & Seyed Ali Jazayeri 2

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Simulation of Full-scale Smoke Control in Atrium

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Modified Air Cooler with Split Cooling Unit

Effect of Operating Parameters on the Performance of Direct Evaporative Cooler

PERFORMANCE EVALUATION OF TWO STAGE AIR COOLER IN DIFFERENT SPEED

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

White Paper Dehumidification in Humid Climates - A Theoretical Case Study

Improving operational effectiveness and reducing environmental impact

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Transcription:

Available online at www.sciencedirect.com ScienceDirect Energy Procedia 52 (214 ) 541 551 213 International Conference on Alternative Energy in Developing Countries and Emerging Economies Modeling of Demand Side Management Options for Commercial Sector in Maharashtra Vishal Vadabhat, Rangan Banerjee Department of Energy Science and Engineering,Indian Institute of Technology Bombay,Powai,Mumbai476,India Abstract There has been an unbalance between demand and supply of electricity in Maharashtra, a shortage of 2% peak power was reported in year 211-12. Demand side management (DSM) in the commercial sector (consuming about 12% of the state electricity) can help to bridge this gap. In this paper three DSM options namely global temperature adjustment (GTA), chilled water storage (CWS) and variable air volume system (VAVS) are evaluated to give potential energy savings and load shifting. Simulation of GTA model for a sample school building gave 21.3% saving in compressor work for a change of room settings from 23 C, 5% RH to 26 C, 4% RH. Model for CWS was simulated for an office building in Mumbai; the results showed a cooling load shifting of 1638TRh out of 275TRh was possible with an optimum tank size of 45kl. Simulation of VAVS for a sample school building showed fan energy savings of 68% over CAVS. 214 Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license 213 Published by Elsevier Ltd. Selection and/or peer-review under responsibility of the Research Center in (http://creativecommons.org/licenses/by-nc-nd/3./). Energy and Environment, Thaksin University. Selection and peer-review under responsibility of the Organizing Committee of 213 AEDCEE Keywords: Chilled water storage; Demand side management; Global temperature adjustment; Heat ventilation and air conditioning; Variable air volume system 1. Introduction Conventional power planning involves an increase in supply to meet the projected future demand. In India, an increase in electricity supply has not been able to keep pace with increase in demand, resulting in shortages. This gap between supply and demand can be bridged by DSM. DSM is a portfolio of measures on the demand side to modify load curves. In 211-12 the peak demand of Maharashtra was 2 MW with a shortage of 4 MW (2% of demand) [1]. This paper focuses on the commercial sector which includes offices, shopping malls, hospitals, hotels and consumes about 12% of total electricity [2]. This sector has a growth rate of 12% annually. Heat ventilation and air conditioning (HVAC) is a major electricity consuming end use in commercial buildings, consuming about 5-6% of total electricity. In this paper three DSM options namely GTA, VAVS, CWS for HVAC have been evaluated. These models are used to quantify energy savings and load shifting. 1876-612 214 Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/3./). Selection and peer-review under responsibility of the Organizing Committee of 213 AEDCEE doi:1.116/j.egypro.214.7.18

542 Vishal Vadabhat and Rangan Banerjee / Energy Procedia 52 ( 214 ) 541 551 2. Global Temperature Adjustment This section describes the global temperature adjustment (GTA) model. ASHRAE has defined comfort conditions for a range of 23-26 C and 45-6% RH. The main concept of GTA is to save energy by adjusting the room settings to the extremes of the comfort zone. GTA is a demand response strategy which is used to shave the peak demand. Recirculated air Room Fresh air Air on coil Cooling coil Air to room fan Fig1. Schematic for HVAC system with ventilation air As shown in the figure 1 the outside air and re-circulated air are mixed before entering the cooling and dehumidification coil. The state of the air leaving the coil depends on the room temperature and humidity settings. The model is formulated in two parts: Heat exchanger model Energy model for compressor 2.1. Heat exchanger model In the cooling and dehumidification coil there is heat as well as mass transfer. Energy estimation for these coils can be done by models based on effectiveness-ntu method. The effectiveness-ntu method is used for sensible heat exchanger. It can also be used for cooling and dehumidification coils but with some modification in the state variables. For sensible heat exchangers, the state variable is temperature, the capacity is the product of mass flow and fluid specific heat, and the overall transfer coefficient is the conventional overall heat transfer coefficient. For cooling and dehumidifying coils, the state variables are moist air enthalpy, the capacity has units of mass flow, and the overall heat transfer coefficient is modified to reflect enthalpy exchange [3]. The following equations are used to calculate the modified state variables. The flow chart for calculation is similar to figure 2. (2.1) is the saturated specific heat of air (kj/kg-k) is the enthalpy of saturated moist air at leaving temperature t wo ( C) of water through coil (kj/kg) is the enthalpy of saturated moist air at entering temperature of water t we ( C) through coil (kj/kg) (2.2) is the modified state variable for liquid specific heat (kg) m w is the mass flow rate of water through the coil (kg/s) C pw is the specific heat of water (kj/kg-k) (2.3)

Vishal Vadabhat and Rangan Banerjee / Energy Procedia 52 ( 214 ) 541 551 543 UA h is the modified (UA) product where U is the overall heat transfer coefficient (kw/m 2 -K) and A is the area of heat exchanger (m 2 ) The state of the air leaving the cooling and dehumidification coil with given temperature and humidity settings can be found from Q (cooling load) in (kw) and mass flow rate of air supplied to room m a in (kg/s) which is known from the air handling unit (AHU) rating. (2.4) (2.5) h acle and h aclo are the specific enthalpy of air entering and leaving the cooling and dehumidification coil respectively (kj/kg) The effectiveness of the cooling coil is defined as follows (2.6) When the settings of the conditioned space are changed h acle can be found out from the outside weather conditions and new settings but h aclo is unknown which is found by using following sets of equations. (2.7) By using NTU we can find the new effectiveness for the heat exchanger which in turn will be used to find h aclo. The effectiveness of cooling and dehumidification coil which is a cross flow heat exchanger is given by following equation: (2.8) is 2.2. Energy model for compressor (2.9) m ref is the mass flow rate of refrigerant (kg/s) (2.1) W c is the compressor work in (kw) and T s is the temperature at suction pressure (K) C m is the compression ratio (2.11) W m is the power consumption of the motor (kw). and are the efficiencies of motor and compressor respectively.

544 Vishal Vadabhat and Rangan Banerjee / Energy Procedia 52 ( 214 ) 541 551 The compressor work is calculated for current room settings by using equations (2.9) (2.11) directly. In case of changed settings the enthalpy of air leaving the coil is unknown. The heat exchanger model is used to find the effectiveness of the heat exchanger for changed room settings and outside conditions. Calculation flowchart of the model is given in the figure. The enthalpy of air leaving the coil is then calculated from the effectiveness. The compressor work for changed settings is then calculated and compared. 3. Variable air volume system model Central air conditioning systems generally use two types of air supply system: Constant air volume system (CAVS) Variable air volume system (VAVS) CAVS as name suggests supplies constant volume of air to the conditioned space irrespective of the cooling load. When the cooling load of the conditioned space reduces, CAVS varies its supply air temperature to match the cooling load. VAVS on the other hand vary its supply air volume flow rate at reduced load. The variable airflow volume is achieved by VAV boxes. The boxes have a modulating damper that throttles in response to the thermostat setting. When the indoor temperature conditions vary from the set point, the VAV box damper responds by restricting or increasing the supply air volume to the space. The air-handling unit serving the VAV distribution network is provided with a variable frequency drive (VFD) to alter the fan speed in relation to the airflow demand. Thus the fan power is less as compared to constant volume system. 3.1. Calculations for Model In VAVS system, it is necessary to find the mass of air supplied to the conditioned space at reduced loads to calculate the energy consumption of fan. Mass of air can be found out by using the heat exchanger model mentioned in subsection A of GTA model. The heat exchanger model is used to find the state of air leaving the cooling coil. The flowchart for calculation is shown below. The energy consumption of fan can be found from equations 3.1 and 3.2 [4]. (3.1) (3.2) P vavs is power consumption of fan for VAVS (kw) P cavs is power consumption of fan for CAVS (kw) are efficiencies of fan, motor and vfd. m a and m ar are mass flow rate of air supplied by VAV and CAV system respectively (kg/s) 3.2. Case Study for Model Mehmet Azmi et al [5] in their study have developed a model to quantify energy consumption of VAVS system. The data from [5] was used to verify the model developed in this paper. The study was carried out for a school building in Adana, Turkey. The cooling period was taken from April 21 to October 21 which covered 184 days. The building has three identical floors and a gross area of 1628 m 2. The hourly cooling load of the building was calculated for typical day of each month. The operation of building is from 8 hrs to 24 hrs. The weather data for Adana was obtained from [6]. The mass of air to be supplied to the space was assumed and then calculations were made according to the flow chart as shown in the figure2 given below.

Vishal Vadabhat and Rangan Banerjee / Energy Procedia 52 ( 214 ) 541 551 545 Variables as input: (UA), t wo, t we, Q, Weather data Calculating from above: (UA) h,c psat, h cle, m w Assuming initial value of m a and also setting small value of, k= Calculate leaving air enthalpy h aclo from equation (2.4) Calculate effectiveness of heat exchanger using (2.6) Calculate C l and NTU from equation (2.2),(2.7) Calculate new effectiveness by using NTU method use equation (2.8); Set as Calculate leaving state of air from equation (2.6) Set as Calculate new value of m a new from equation (2.4) k =k+1 set m a k = m a new No abs(m a k - m a new )<= Yes m a k = m a new Fig2. Flowchart for VAV model

546 Vishal Vadabhat and Rangan Banerjee / Energy Procedia 52 ( 214 ) 541 551 Table1. SYSTEM CHARACTERISTICS Air flow (kg/hr) Fresh air (m 3 /hr) Max cooling load (kw) Fan power (kw) 37348 71 131.1 26 Comfort conditions 26 C, 5%RH 4. Chilled water storage system The figure3 shows schematic of chilled water storage system. The water circuit and refrigerant circuits are shown separately. The chilled water storage system operates in two modes (1) Off peak mode (2) Peak mode 4.1. Off Peak Operation In the off peak mode, pump p1 is used to carry the warm water from the tank through the valve v1 to the chiller and store it at bottom of tank. Pump p2 is used to carry chilled water from the chiller to the cooling coils, according to the cooling load. Valve v2 allows passage of chilled water from the chiller. Thus the cooling load of the building is taken care by chiller in this mode. Following calculations are made during off peak operation (4.1) CCAP is capacity of chiller at off design conditions (kw), NCAP is nominal capacity of chiller (kw) and f cb is correction factor depends on outside weather condition [7]; it can be obtained from manufacturer s data. (4.2) PLR i is the part load ratio on chiller at i th hour. CL ci is cooling load taken care by chiller (kw) at i th hour. CL si is load on chiller for charging the chilled water in the storage tank. (4.3) E cei is the electrical energy consumed by the chiller in (kwh) during i th hour, t i is the time for which the chiller is working value of which is limited from -1 hour. EIR is energy input ratio at off design conditions [8]. (4.4) The values of a,b and c can be obtained from manufacturer s data. (4.5) m w2 is mass flow rate of water in (kg/s) handled by pump p2 during i th interval. t cr, t cs are temperature of water returning from chiller and supplied by chiller respectively ( C). (4.6) m w1 is mass flow rate of water in (kg/s) handled by pump p1 during i th interval. is difference in temperature between warm and chilled water stored in tank ( C). (4.7) (4.8)

Vishal Vadabhat and Rangan Banerjee / Energy Procedia 52 ( 214 ) 541 551 547 E p1i and E p2i is electrical energy in (kwh) consumed by pump p1 and p2 respectively; both the pumps would run for 1hour in i th time interval. (4.9) E f is fan energy consumption (kwh); v f is rated volumetric flow rate of air (m 3 /s), is the pressure drop given by manufacturer, is the fan efficiency. Fan is assumed to be operating for 1 hour for interval i th time interval. Off peak hours are taken as 1pm to 6pm as tariffs are lowest during this period. It is assumed that if there are multiple chillers then they would operate at same PLR during off peak periods. 4.2. Peak Operation In peak mode, the warm water is cooled in the chiller and then pumped by p2 to the cooling coils through valve v2. Similarly chilled water stored in the tank is also pumped to cooling coils by pump p2, p1 is off. (4.1) Condenser v2 Chiller Warm Water Cold Water v1 Fig3. Schematic of chilled water storage system 4.3. Case Study The model was simulated for an office building in Mumbai. The system details are given below [9]. Time of use tariff (TOU) is used [1]. The total energy cost of chillers, fan, and pumps is minimized using constraints as shown below. Table2. HVAC system details for building Table3. Efficiencies of subsystems Chiller capacity (TR) Max cooling load (TR) Subjected to following constrains Cooling load (TRh) Pump1 head (m) Pump2 head (m) 11*2 17 275 12 2 p1 (%) p2 (%) m1 (%) m2 (%) f (%) 7 7 75 8 65

548 Vishal Vadabhat and Rangan Banerjee / Energy Procedia 52 ( 214 ) 541 551 5. Results 5.1. Global Temperature Adjustment (GTA) Model Results Model was simulated for an office building located in Nagpur for a typical day of April. The room settings were changed from 23 C, 5%RH to 26 C, 4%RH. The settings were changed from 1am to 6pm when the cooling load is at peak. The resulting change in the compressor work is plotted in figure5. The figure also shows variation in temperature with time. The energy consumption of compressor from 1am to 6pm was 544 kwh before GTA, after GTA it reduced to 429 kwh resulting in 21.6% energy savings. Before GTA After GTA Temperature (deg C) Compressor energy consumption (kwh) 5 4 3 2 1 2 4 6 8 1 12 14 16 18 2 22 24 Time (hrs) Fig4. Comparison of compressor work before and after GTA 5.2. Variable Air Volume System (VAVS) Model Results Fan energy consumption(kwh) 35 3 25 2 15 1 5 8 1 12 14 16 18 2 22 24 Hrs April May June July August September October CAV consumption Fig5. Fan energy consumption VAVS vs CAVS

Vishal Vadabhat and Rangan Banerjee / Energy Procedia 52 ( 214 ) 541 551 549 The above figure shows the comparison of VAV and CAV systems. The energy consumption of CAVS remains constant throughout the day and is 416 kwh for typical day of any month, whereas the energy consumption of VAVS varies hourly (with the cooling load). Figure6 shows the variation of energy consumption of VAVS for typical days of April and August. The energy consumption of VAVS for months from April to October is listed below. The total energy consumption of CAVS and VAVS are found to be 7696 kwh and 24497 kwh respectively. Thus VAVS consumes about 31.8% energy compared to CAVS. It is seen that energy consumption of VAVS is more than CAVS in August. This is because the efficiency of variable frequency drive is considered in calculation of fan power, also efficiency of motor at reduced speeds is lower as compared to base case (CAVS). Table4. Month-wise energy consumption VAVS vs CAVS Month Apr May Jun Jul Aug Sep Oct E c(kwh) 6656 12896 1248 12896 12896 1248 6656 E v(kwh) 1173 3434 3456 3571 697 3979 1914 E v/e c.176.266.276.276.54.318.287 5.3. Chilled Water Storage (CWS) Model Results The optimization of the objective function was carried out using OPTIM-TOOL in MATLAB. Active-set algorithm was used for this purpose. The results gave part load ratio values for the two chillers for each hour and also the time of operation of chillers in 1hour interval. These results were used to find size of storage tank. The results below show cooling load distribution by chiller and chilled water storage; it was found that out of 275TRh of cooling load 1638TRh is shifted to stored chilled water. The tank required for this purpose is 45kl capacity. Figure7 shows modification in load curve of chiller after the use of chilled water storage. The results showed peak demand shifting of 646.5kW which is almost 8% of total peak load. 2 Cooling Load (TRh) 15 1 5 Storage Chiller 1 3 5 7 9 11 13 15 17 19 21 23 Time (hrs) Electrical Energy Consumption (kwh) 25 2 15 1 5 Fig6. Hourly cooling load sharing by chiller and storage After Storage Before Storage 2 4 6 8 1 12 14 16 18 2 22 24 Time (hrs) Fig7. Hourly electricity comparison before and after storage

55 Vishal Vadabhat and Rangan Banerjee / Energy Procedia 52 ( 214 ) 541 551 5.4. Effects of options on building load profile The effects of three DSM options on a hospital building load profile are discussed in this section. The hospital building is located in Mumbai. Certain assumptions are made for this purpose; it is assumed that HVAC consumes about 6% of total electricity of the building. The chiller and fan consumption are assumed to be 6% and 28% of total HVAC consumption respectively; using the results obtained in previous sections ; the change in the load profile of a hospital building with DSM options are shown. Demand(kW) Before GTA After GTA 3 25 2 15 1 5 2 4 6 8 11214161822224 Time (h) (a) Effect of GTA on building load profile Demand (kw) Before VAV After VAV 3 2 1 2 4 6 8 1 12 14 16 18 2 22 24 Time (h) (b) Effect of VAVS on building load profile Demand(kW) 4 3 2 1 Before CWS After CWS 2 4 6 8 1 12 14 16 18 2 22 24 Time (h) (c) Effect of CWS on building load profile Fig8. Effects of DSM options on building load profile 6. Conclusions The paper successfully combines modelling as well as case studies showing benefits of DSM options. This paper can be used to find the changes in the hourly electricity consumption pattern of commercial buildings on implementation of three DSM options (Variable air volume system, Global temperature adjustment and Chilled water storage system). The user can find changes in the consumption pattern of a building for any location just by changing local conditions in the models. HVAC consumes about 5% of the total electricity of the building. In this paper three DSM options for HVAC are modelled and the effect of these options on building load profile has been studied. The results show that 21% saving in compressor work can be achieved by changing the temperature and humidity settings of the conditioned space to extremes of comfort zone. The variable air volume system (VAVS) can save 52463 kwh of fan power consumption, which is equivalent to 68% energy savings as compared to constant air volume system. Case study for chilled water storage shows that peak load shifting of 8% can be achieved for optimal storage tank size. A tool is developed in this study which can be used to obtain potential energy savings and load shifting from any commercial building. This tool can be used for any region; the user has to input the local conditions to obtain potential savings from the DSM options. This tool can be used as a base to promote these three DSM options.

Vishal Vadabhat and Rangan Banerjee / Energy Procedia 52 ( 214 ) 541 551 551 Acknowledgement We are thankful to MERC and Tata Power for sharing their data and providing support. References [1] Load generation balance report; Government of India, Central Electric Authority, 18 th issue, 212-13 [2] Sharma HK., Kumar S., Jain S.; Energy Statistics, Central statistics office, Ministry of statistics and programme implementation, Government of India, 18 th issue, 211 [3] ASHRAE Handbook-Fundamentals; Energy Estimating and Modeling Methods, 29, pp 19.11-19.12 [4] Yao Y., Lian Z., Liu W., Hou Z., Wu M.; Evaluation program for the energy-saving of variable-air-volume systems, Applied Energy, Vol. 83, 26, pp 66-627 [5] Aktacir M., Buyukalaca O., Yilmaz T.; Life-cycle cost analysis for constant-air-volume and variable-air-volume airconditioning systems, Energy and Buildings, Vol. 39, 27, pp 558-568 [6] Weather data of Adana, Turkey; http://www.wunderground.com/global/stations/17352.html, last accessed on 17 th March 213 [7] Hajiah A., Krarti M.; Optimal control of building storage systems using both ice storage and thermal mass- Part I: Simulation environment, Energy Conversion and Management, 212 [8] Meyer M., Emery A.F.; Optimal control of an HVAC system using cold storage and building thermal capacitance, Energy and Buildings, Vol. 23, 1995, pp 19-31 [9] Ashok S.; Industrial Load Management, PhD Thesis, Indian Institute of Technology, Bombay, 22 [1] Maharashtra State Electricity Distribution Company Limited; High Tension Tariff Booklet, 1 st October, 26.