Q700A,C, hermostat Subbases INSALLAION INSRUCIONS APPLICAION he Q700 hermostat Subbases provide electronic control of commercial Vac single or multistage heat pump or conventional heating and cooling systems. Select models have terminals for light emitting diodes LEs, remote temperature sensors and remote setback timer. he LE models have up to two field configurable LEs and up to two factory assigned LEs. Refer to able. All Q700 hermostat Subbases require a common wire to the supply power. able. escription of Q700 Subbases. Use Stages a Q700 700 System Heat Cool Figs. A or F Conventional or or 8-9 C E or F Heat pump, or or 0- E or F Heat pump or or 5 a epends on the model. RECYCLING NOICE If this control is replacing a control that contains mercury in a sealed tube, do not place your old control in the trash. Contact your local waste management authority for instructions regarding recycling and the proper disposal of the old thermostat. INSALLAION When Installing this Product.... Read these instructions carefully. Failure to follow the instructions can damage the product or cause a hazardous condition.. Check the ratings given in the instructions and on the product to make sure the product is suitable for your application.. Installer must be a trained, experienced service technician.. After completing installation, use these instructions to check out the product operation. CAUION isconnect power supply to prevent electrical shock or equipment damage. Location Subbase without Remote-Mounted emperature Sensor Install the subbase about 5 ft (.5m) above the floor in an area with good air circulation at average temperature. See Fig.. o not install the subbase where it can be affected by: drafts, or dead spots behind doors and in corners. hot or cold air from ducts. radiant heat from sun or appliances. concealed pipes and chimneys. unheated (uncooled) areas such as an outside wall behind the thermostat. Subbase with Remote-Mounted emperature Sensor(s) Install the subbase in an area that is accessible for setting and adjusting the temperature and settings. Install the remote-mounted sensor(s) about 5 ft (.5m) above the floor in an area with good air circulation at average temperature. See Fig.. o not mount the sensor(s) where it can be affected by: drafts, or dead spots behind doors and in corners. hot or cold air from ducts. radiant heat from sun or appliances. concealed pipes and chimneys. unheated (uncooled) areas such as an outside wall behind the thermostat. If more than one remote sensor is required, they must be arranged in a temperature averaging network consisting of two, three, four, five or nine sensors. See Fig. through 6. U.S. Registered rademark Copyright 996 Honeywell Inc. All Rights Reserved X-XX UL 69-09-
YES NO NO NO 5 FEE [.5 MEERS] M007 Fig.. ypical location of thermostat or remote-mounted sensor. 707G 707G 707C 707C 707C 707C M88 Fig.. wo 707G Sensors providing a 700/Q700 hermostat/subbase. M80 Fig.. Four 707C Sensors providing a 700/Q700 hermostat Subbase. 707C 707G 707G 707G 707C 707G 707G 707G M89 Fig.. wo 707C Sensors and one 707G Sensor providing a temperature averaging network for a 700/Q700 hermostat/subbase. M8 Fig. 5. Five 707G Sensors providing a 700/Q700 hermostat/subbase. 69-09
707C 707C 707C. Remove the subbase from the wall and drill two /6 inch holes in the wall (if drywall) as marked. For firmer material such as plaster or wood, drill two 7/ inch holes. Gently tap anchors (provided) into the drilled holes until flush with the wall.. Position the subbase over the holes, pulling wires through the wiring opening. 5. Loosely insert the mounting screws into the holes. 6. ighten mounting screws. 707C 707C 707C WIRING 707C 707C 707C All wiring must comply with local electrical codes and ordinances. Refer to Fig. 9 through 5 for typical hookups. A letter code is located near each terminal for identification. CAUION isconnect power before wiring to prevent electrical shock or equipment damage. M8 Fig. 6. Nine 707C Sensors providing a 700/Q700 hermostat/subbase. Subbase Installation he subbase can be mounted horizontally on the wall or a in. x in. wiring box. Position the subbase horizontally on the wall or on a in. x in. wiring box.. Position and level the subbase (for appearance only). he thermostat will function properly even when not level.. Use a pencil to mark the mounting holes. See Fig. 7.. Loosen the terminal screws on the back of the thermostat and connect the system wires. See Fig. 8. IMPORAN Use 8 gauge, color-coded thermostat cable for proper wiring.. Securely tighten each terminal screw.. Push excess wire back into the hole.. Plug the hole with nonflammable insulation to prevent drafts from affecting the thermostat. WIRES HROUGH WALL WALL FOR WRAPAROUN INSERION SRIP 7/6 IN. ( MM). FOR SRAIGH INSERION SRIP 5/6 IN. (8 MM). M86 Fig. 8. Proper wiring technique. WALL ANCHORS () B O G Y X W CONACOR HEA OR COIL RH RC LES Fig. 7. Mounting the subbase. MOUNING HOLES MOUNING SCREWS M65 HEA L (HO) POWER SUPPLY. PROVIE ISCONNEC MEANS AN OVERLOA PROECION AS REQUIRE. M8A Fig. 9. ypical hookup of Q700A0 in a one-stage heat and one-stage cool conventional system. 69-09
RC O Y Y G X W W B RH L (HO) CONACOR CONACOR HEA HEA HEA REMOE EMPERAURE REMOE SEBACK IMER L (HO) CAUION: EQUIPMEN AMAGE WILL OCCUR IF POWER IS CONNECE O HE ERMINALS. POWER SUPPLY. PROVIE ISCONNEC MEANS AN OVERLOA PROECION AS REQUIRE. JUMPER RC ERMINAL O RH ERMINAL WHEN INSALLE ON A SYSEM WIH ONE RANSFORMER. M87A Fig. 0. ypical hookup of Q700A00 in a two-stage heat and two-stage cool conventional system with two transformers. B O W G X Y R X W E G X Y X R HEA HEA CONACOR EQUIPMEN MONIOR L (HO) M088 HEA EM. H. CONACOR EQUIPMEN MONIOR L (HO) POWER SUPPLY. PROVIE ISCONNEC MEANS AN OVERLOA PROECION AS REQUIRE. M8A Fig.. ypical hookup of Q700C0 in a one-stage heat and one-stage cool heat pump system. Fig.. ypical hookup of Q700 in a one-stage heat and one-stage cool heat pump system. X W O B W G E Y R X AUX. HEA HEA EQUIPMEN MONIOR IMER HEA EM. H. CONACOR L (HO) M089 Fig.. ypical hookup of Q700C06 in a two-stage heat and one-stage cool heat pump system. Includes remote temperature sensor and remote setback timer. 69-09
X O E G B W W Y Y X X X X R 5 HEA CONACOR EQUIPMEN MONIOR REMOE EMPERAURE EM. H. HEA HEA CONACOR EQUIPMEN MONIOR L (HO) REMOE SEBACK IMER 5 CAUION: EQUIPMEN AMAGE WILL OCCUR IF POWER IS CONNECE O HE ERMINALS. POWER SUPPLY. PROVIE ISCONNEC MEANS AN OVERLOA PROECION AS REQUIRE. EM. HEA OES NO CYCLE. O URN OFF HE EM. HEA, GO O SYSEM SELECION AN CHOOSE HEA. SELEC MOELS HAVE LES. X AN X NEE O BE JUMPERE O ERMINAL X. M85A Fig.. ypical hookup of Q700C008 in a two-stage heat and two-stage cool heat pump system. Includes remote temperature sensor and remote setback timer. B X O E G W Y Y X X X R CONACOR EQUIPMEN MONIOR REMOE EMPERAURE HEA EM. H. AUX. H. CONACOR EQUIPMEN MONIOR L (HO) REMOE SEBACK IMER CAUION: EQUIPMEN AMAGE WILL OCCUR IF POWER IS CONNECE O HE ERMINALS. POWER SUPPLY. PROVIE ISCONNEC MEANS AN OVERLOA PROECION AS REQUIRE. SELEC MOELS HAVE LES. X NEES O BE JUMPERE O ERMINAL X. M8B Fig. 5. ypical hookup of Q700C07 in a three-stage heat and one-stage cool heat pump system. Includes remote temperature sensor and remote setback timer. Mounting hermostat on Subbase Mount the thermostat on the subbase after the subbase is installed.. Engage tabs at the top of thermostat and subbase. See Fig. 6.. Press lower edge of case to close and latch. NOE: o remove the thermostat from the wall, first pull out at the bottom of the thermostat; remove top last. IMPORAN Refer to the thermostat installation instructions for Installer Setup, Settings, Installer Self-est and roubleshooting information. A. ENGAGE ABS A OP OF HERMOSA AN. B. PRESS LOWER EGE OF CASE O LACH. M6799A Fig. 6. Mounting thermostat on subbase. 5 69-09