C. All control equipment must have transient protection devices to comply with UL864 requirements.

Similar documents
SECTION FIRE ALARM SYSTEM PART 1 GENERAL

SECTION FIRE ALARM SYSTEMS

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

SECTION FIRE ALARM STANDARDS REVISED CONSTRUCTION STANDARD

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Hinesville First United Methodist Church SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

DIVISION 26 ELECTRICAL SECTION FIRE ALARM SYSTEM

Smoke Detector Activation of any smoke detector shall start the alarm verification mode.

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

A. This Section covers fire alarm systems, including initiating devices, notification appliances, controls, and supervisory devices.

SECTION FIRE ALARM

Fire Alarm System Fundamentals

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Addressable Fire Alarm Control Panel

LifeAlarm Fire Alarm Control Panels

Architect s Project Number of 12 Fire Alarm/Smoke Detection Systems District Master Specs 2013 Edition

Fire Alarm Acceptance Testing & On-Going Maintenance with The Joint Comm. Standards / Reporting. Prepared Especially for : OSFM TEC 2016

SECTION FIRE ALARM SYSTEMS

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

TrueAlarm Fire Alarm Systems

2. HVAC and smoke control systems; fire, smoke, and combination fire/smoke dampers. 5. Central control and monitoring system.

FIRE ALARM SYSTEM 1.1 GENERAL REQUIREMENTS

A. Provide addressable fire alarm system throughout the facility and supervise wet and preaction fire sprinkler system.

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Project No Belleville Fire Hall/Headquarters and Emergency Operations Centre Section Belleville, Ontario Page 1 of 10

FIRE DETECTION SYSTEM SPECIFICATION FOR MODEL XR200

1. Buildings on the Pullman campus are monitored by a Simplex 4120 FDA Network or a Siemens XLS Network.

Control/Communicator

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

1. Floor above/floor below notification. 2. Private alarm notification. 3. Not Used 4. Voice alarm notification. 5. Not Used.

SECTION ADDRESSABLE FIRE ALARM SYSTEM

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

Concerns: Affects: Dated: June 12, SECTION 1: GENERAL Scope Work Included... 3

TrueAlarm Analog Sensing

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

TrueAlarm Analog Sensing

Standard of Practice - Fire Alarm Systems. NOTE: Significant revisions or additions to the previous standards are highlighted in italics.

Voice Annunicated Fire Alarm System Page 1 of 26

TrueAlarm Analog Sensing

WINDOW & HVAC REPLACEMENT PEMBERTON TOWNSHIP BOE REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5450E

SECTION FIRE DETECTION AND ALARM

FIRE & LIFE SAFTEY STANDARD

Functional Performance Test

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

SECTION FIRE DETECTION AND ALARM

SECTION DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Lake County / Multi-Department Storage Facility / Project / December 12, 2016 SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

Rancho Cucamonga Fire Protection District Prevention Bureau Standard

SECTION FIRE ALARM INTEGRATED AUDIO VISUAL EMERGENCY COMMUNICATION SYSTEM

1.3 REFERENCE STANDARDS

DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM

The following information shall become and form part of the contract documents.

SECTION COMMON WORK RESULTS FOR SAFETY AND SECURITY 1.1 RELATED SECTIONS

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

Pakenham Branch Library Section MacFarlane Street MULTIPLEX FIRE ALARM SYSTEM Project No Page 1 of 12

University Design Standard Fire Alarm Systems

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

COUNTY OF KINGS KINGS COUNTY JAIL EXPANSION PHASE III

30.45 Electric Release PDRP-2001

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

MPC-6000 / MPC-7000 / RND-2

DESIGN & CONSTRUCTION GUIDELINES

Changes in NFPA

Specification/ Data Sheet

STATE OF NORTH CAROLINA

El Reno Fire Department Fire Alarm Plan Review Worksheet

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

good things in small packages

SECTION ADDRESSABLE FIRE ALARM SYSTEM

ONYX FirstVision Specification Interactive Firefighters Display

SECTION INTRUSION DETECTION

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

SECTION (13730) - INTRUSION DETECTION

FIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -

Section PERIMETER SECURITY SYSTEMS

Full Service Central Station Fire Alarm Listing Evaluation

B. Special Documentation Requirements. C. Materials and methods of Construction

SECTION SECURITY TESTING AND COMMISSIONING

Moreno Valley Fire Department Fire Prevention Bureau. New and Existing Fire Alarm & Signaling Systems Guideline

TrueAlert Notification Appliances

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

MANUAL OF DESIGN CRITERIA AND SPECIFICATIONS FOR FIRE DETECTION AND ALARM SYSTEMS PUBLIC SCHOOLS IN NEW MEXICO

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

Unified Fire Authority - Fire Prevention Bureau

FireSeeker Fire Alarm Control Panel Model FS-100 Installation, Operation, and Maintenance Manual

TrueAlarm ES Analog Sensing

109-B Concord Drive Casselberry, FL DynaFire.com INSPECTION AND TESTING FORM PER NFPA 72. Owner s Address: Owner's Phone Number:

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU PLAN REVIEW CHECKLIST FIRE ALARM SYSTEM INSTALLATION

1. The fire detection and alarm system (including the conduit) shall be a separate bid item and not part of the general electrical contract.

NFPA 72 Code Changes vs 2013

FireSeeker Fire Alarm Control Panel Model FS-250 Installation, Operation and Maintenance Manual

The CWSI System CALL WITH QUESTIONS. RELY ON OUR KNOWLEDGE. DEPEND ON OUR EXPERIENCE. (800)

Transcription:

SECTION 28 31 11 - PART 1 - GENERAL 1.1 SCOPE & RELATED DOCUMENTS A. The work covered by this section of the specifications includes the furnishing of all labor, equipment, materials, and performance of all operations in connection with the installation of the Fire Alarm System as shown on the drawings and as herein specified. B. The requirements of the conditions of the Contract, Supplementary Conditions and General Requirements apply to the work specified in this section. C. The complete installation is to conform to the applicable sections of NFPA-72, Local Code Requirements and the National Electrical Code with particular attention to Article 760. D. The work covered by this section of the specifications is to be coordinated with the related work as specified elsewhere under the project specifications. 1.2 QUALITY ASSURANCE A. Each and all items of the Fire Alarm System shall be listed as a product of a SINGLE fire alarm system manufacturer under the appropriate category by Underwriters' Laboratories, Inc. (UL), and shall bear the "UL." label. All control equipment is to be listed under UL category UOJZ as a single control unit. Partial listing shall NOT be acceptable. B. The equipment and technical supervision furnished under this specification is to be provided directly by the existing equipment manufacturer/supplier, SimplexGrinnell. SimplexGrinnell shall provide all necessary network hardware and or software modifications as part of this contract. C. All control equipment must have transient protection devices to comply with UL864 requirements. 1.3 GENERAL A. Furnish and install a complete Fire Alarm System as described herein and as shown on the plans; to be wired, connected, and left in first class operating condition. The system shall be interfaced to communicate via network communications with the existing Simplex Fire alarm networked panels. The system shall use analog addressable initiating device circuits with individual device supervision, individual notification appliance circuit supervision, incoming and standby power supervision. Include control panels, network communication equipment, power supplies, remote annunciators, manual pull stations, automatic detection devices, addressable interfaces to sprinkler system devices, horns, strobes, remote control devices, wiring, connections to devices, outlet boxes, junction boxes, and all other necessary material for a complete operating system. 28 31 11-1 (45307035)

B. The fire alarm control panel shall allow for loading or editing special instructions and operating sequences as required. The system is to be capable of on-site programming to accommodate expansion, building parameter changes or changes as required by local codes. All software operations are to be stored in a non-volatile programmable memory within the fire alarm control panel. Loss of primary and secondary power shall not erase the instructions stored in memory. C. All panels and peripheral devices shall be the standard product of a single manufacturer and shall display the manufacturer's name on each component. The catalog numbers specified under this section are those of SIMPLEX as supplied by SimplexGrinnell and constitute the material and desired operating features that are to be furnished. 1.4 OPERATION A. Under normal condition, the front panel shall display a "SYSTEM NORMAL" message and the current time and date. B. Should an abnormal condition be detected, the appropriate LED (Alarm, Supervisory, or Trouble) shall flash. The panel audible signal shall pulse for alarm conditions and sound steadily for trouble and supervisory conditions. C. The panel shall have an eighty (80) character LCD display. The following information relative to the abnormal condition of a point in the system shall be displayed: 1. Custom location label describing the exact location of the device to include floor, room number (or nearest room number for corridor mounted devices). No two devices shall have the same location label. Provide forty (40) characters minimum to describe location information, this is in addition to the "type of device" and "status" requirements listed below. 2. Type of device (i.e. smoke, pull station, waterflow). Provide twenty (20) characters minimum to describe device type information. 3. Point status (i.e. alarm, trouble, sprinkler supervisory). Provide twenty (20) characters minimum to describe point status. D. Pressing the appropriate acknowledge button shall acknowledge the alarm or trouble condition. (The acknowledge, reset and bypass functions shall be passcode protected. Four levels of passcode protection shall be provided). If the user has insufficient privilege to acknowledge such conditions, a message shall indicate insufficient privilege but allow the user to view the points without acknowledging them. Should the user have sufficient privilege to acknowledge, a message will be displayed informing the user that the condition has been acknowledged. E. Alarm Silencing 1. Should the "Alarm Silence" button be pressed, all audible notification appliances shall be deactivated. Visual indicating appliances shall continue to flash until the system is reset. F. System Reset 1. The "System Reset" button shall be used to return the system to its normal state after an alarm condition has been remedied. The display shall step the user through the reset process with simple English language messages. Messages shall provide operator 28 31 11-2 (45307035)

assurance of the sequential steps (i.e.: "IN PROGRESS", "RESET COMPLETED", and "SYSTEM NORMAL") as they occur, should all alarm conditions be cleared. 2. Should an alarm condition continue to exist, the system will remain in an abnormal state. System control relays shall not reset. The panel audible signal and the Alarm LED shall be on. The display will indicate the total number of alarms and troubles present in the system along with a prompting to review the points. These points will not require acknowledgment if they were previously acknowledged. G. History Logging 1. In order to recreate a sequence of events in a fire or trouble investigation, the control panel shall store system abnormal conditions in three separate logs. Alarm activities shall be stored in an Alarm Log, sprinkler supervisory (tamper switch) activation in a Supervisory Log, and trouble events in a Trouble Log. The time and date of each occurrence must be included with each entry. These events shall be stored in a battery protected random access memory (RAM). In order to prevent re-occurring trouble and/or sprinkler supervisory conditions from overwriting other information, it is mandatory that each type of event be stored separately. Systems that are not equipped with separate logs, as described, shall include a UL listed fire alarm printer with battery back-up to record system activity including time and date of each occurrence. H. Walk Test with History Logging 1. The system shall be capable of being silently tested by one person. While in testing mode, the alarm activation of an initiating device shall be silently logged as an alarm condition in the historical data file. The panel shall automatically reset itself after logging of the alarm. 2. The momentary disconnection of an initiating or notification appliance circuit shall be silently logged as a trouble condition in the historical data file. The panel shall automatically reset itself after logging of the trouble condition. 3. Should the walk test feature be on for an inappropriate [programmable] amount of time, it shall revert to the normal mode automatically. 4. The control panel shall be capable of supporting up to eight (8) separate testing groups whereby one group of points may be in a testing mode and the other (non-testing) groups may be active and operate as programmed per normal system operation. After testing is considered complete, testing data may be retrieved from the system in chronological order to ensure proper device/circuit activation. I. System Trouble Reminder 1. Should a trouble condition be present within the system and the audible trouble signal silenced, the trouble signal shall resound at preprogrammed time intervals to act as a reminder that the fire alarm system is not 100% operational. Both the time interval and the trouble reminder signal shall be programmable to suit the owner's application. J. Smoke Sensor Operation 1. The smoke sensors shall automatically meet NFPA sensitivity testing requirements. 28 31 11-3 (45307035)

a. The control panel shall be listed as a calibrated sensitivity testing instrument that will automatically meet NFPA 72E Sensitivity Testing Requirements. The requirement to test the sensitivity of each detector within one year of installation and every alternate year thereafter as described in NFPA 72E shall not need to be performed manually. 2. The smoke sensors shall be smoke density measuring devices having no self contained alarm set-point. The alarm decision for each sensor shall be determined by the control panel. The control panel shall determine the condition of each sensor by comparing the sensor value to stored values. 3. The control panel shall maintain a moving average of the sensors smoke chamber value. The system shall automatically maintain a constant smoke obscuration sensitivity for each sensor and compensate for environmental factors such as dust accumulation. 4. The system shall automatically indicate when an individual sensor needs cleaning. When a sensor's average value reaches a predetermined value, a "Dirty Sensor" trouble condition shall be audibly and visually indicated at the control panel for the individual sensor. Additionally, the LED on the sensor base shall glow steady giving a visual indication at the sensor location. a. The smoke sensor shall not be operating at an increased sensitivity level due to the dust/dirt contamination. It shall continue to operate at the pre-set sensitivity level. 5. It shall be possible to program the control panel to automatically change the sensitivity settings of each sensor based on time-ofday and day-of-week. (For example, to be more sensitive during unoccupied times and less sensitive during occupied periods.) 6. The control panel shall have the capability of being programmed for a pre-alarm or two-stage function. This function shall allow a "pre-alarm" indication to occur when, for example, a 3% sensor reaches a threshold of 1.5% smoke obscuration. 7. The control panel shall have the capability to automatically log smoke obscuration levels at each individual sensor location, under normal conditions, for a 30-day period. The system shall then be adjusted to set individual sensor sensitivity levels slightly above the maximum obscuration recorded at each location. This will insure the earliest possible detection to smoke while eliminating false alarms caused by normal conditions in the area of each sensor. K. Network Communication Operation 1. Each node (building control panel, graphic command center) shall communicate to the next in a token ring configuration at 57.6 Kbaud via the campus fiber network. (The new FACP will be a new node on the existing campus network. Coordinate copper and /or fiber network interfaces as required.) 2. In the event that the path to the next node on the ring has experienced a communications failure, the node with possession of the token shall transmit it back in the direction from which it came to attempt to reach the next node by going around the ring in the opposite direction. At the same time, the status of the noncommunicating node shall be added into the token content. 3. The communication method shall be NFPA 72 style 7. Full communication between all nodes shall be maintained if an open occurs on the network communication lines. 4. Network time synchronization with seconds resolution accuracy shall be provided by designating one node as the network timekeeper. This node shall notify the network of authorized time and date changes. During periods without any time or date 28 31 11-4 (45307035)

changes, the network timekeeper shall maintain network time synchronization by network communication once every 24 hours. In the event that the network timekeeper is unable to communicate the correct time, each node shall maintain its own local time and date reference using an internal, crystal controlled oscillator. 1.5 ALARM SEQUENCE A. The system alarm operation subsequent to the alarm activation of any manual station or automatic detection device is to be as follows: 1. All audible alarm notification appliances shall sound a temporal code pattern (.5 sec. on,.5 sec. off,.5 sec. on,.5 sec. off,.5 sec. on, 2.5 sec. off, then repeat) until silenced by the alarm silence switch at the control panel, remote annunciator or at the existing Campus Network Control Panel/Annunciator. 2. All visible alarm notification appliances [Xenon Strobes] shall display a continuous pattern until the system is reset. 3. All doors normally held open by door control devices shall release. 4. All egress doors normally locked by electric locking devices shall release. 5. The individual alarm device information shall be displayed on the local FACP and associated annunciators. This information shall also be transmitted via fiber-optic network communication across the existing fire alarm network to annunciate appropriately at other network panel locations. 6. The alarm is to be recorded with the time and date in the local control panel s alarm log as well as being recorded on other annuciated network panels. B. The alarm activation of any elevator lobby smoke detector shall, in addition to the operations listed above, send a signal to the elevator controller for a Fire Hat signal and recall the elevators according to the following sequence: 1. If the alarmed detector is on any floor other than the main level of egress, the elevator cabs shall be recalled to the main level of egress. 2. If the alarmed detector is on the main egress level, the elevator cabs shall be recalled to the predetermined alternate recall level as determined by the local authority having jurisdiction. C. Activation of any smoke detector in an elevator shaft or machine room shall send a signal to the elevator controller for a flashing Fire Hat signal. D. The activation of any elevator related heat detector shall, in addition to the operations listed above, activate the associated elevator shunt-trip breaker to remove power from the elevator. 1.6 NOTIFICATION APPLIANCE OPERATION A. The system shall provide for the synchronization and control of the audible and visible notification appliances on a common 2-wire circuit. The audible notification signal shall be in a temporal code pattern as described by NFPA 72 and shall remain active until the Alarm Silence switch is activated at the fire alarm control panel, remote annunciator panel, or network annunciator. The visible notification appliances (xenon strobes) shall be synchronized and shall remain active until the system is reset at either location. 28 31 11-5 (45307035)

1.7 SUPERVISION A. The disarrangement condition of any circuit shall not disrupt the operation of any other circuit. B. Each addressable initiating device and independently supervised circuit shall include a discrete panel readout to indicate disarrangement conditions. C. The incoming power to the system shall be supervised so that any power failure must be audibly and visibly indicated at the control panel and at the campus network annunciator. A green "power on" LED shall be displayed continuously while incoming power is present. D. The system batteries shall be supervised so that a low battery condition or disconnection of the battery shall be audibly and visibly indicated at the control panel and remote annunciator. E. The system shall provide for an operator to disable and enable each addressable device, indicating appliance circuit and each relay control circuit individually for maintenance or testing purposes. Device disabling capability shall be passcode protected and capable of being performed at the building control panel and from the existing campus network annunciator. F. If any addressable device is removed a "Device Missing" message along with the exact location of the missing device must be indicated at the fire alarm control panel, remote annunciator panel and campus network annunciator along with a system trouble indication. G. If more than one addressable initiating device is inadvertently programmed with the same address, a Duplicate Address error shall be displayed at the locations described. 1.8 POWER REQUIREMENTS A. The control panel shall be connected to a dedicated 120 VAC circuit originating from the load side of the main service of commercial power or the main distribution service of an isolated power plant located on the premises. The connection shall be made through an overcurrent protective device in an approved manner with the overcurrent protective device lockable and conspicuously identified with the designation Fire Alarm Supply.. B. The control panel shall contain one 24VDC, 4 AMP power supply as a minimum. Additional 4 AMP power supply or NAC panels shall be furnished as required to power the system with 20% spare capacity. C. The control panel shall contain four (4) Notification Appliance Circuits for alarm horns and strobes as a minimum. Notification Appliance Circuit Extender Panel(s) shall be furnished and installed as required to operate all notification appliances shown on the plans with 20% spare capacity per circuit for future additions. D. The system shall be provided with sufficient battery capacity to operate the entire system upon loss of normal 120 VAC power in a normal supervisory mode for a period of twenty-four (24) hours with five (5) minutes of alarm operation at the end of this period. The system shall automatically transfer to the standby batteries upon power failure. All battery charging and recharging operations shall be automatic. 28 31 11-6 (45307035)

E. All circuits requiring system operating power shall be 24VDC and shall be individually fused at the control panel. 1.9 SUBMITTALS A. Include bound equipment data booklets to include the following: 1. An indexed list of materials with mounting box requirements for each device. Each item shall reference a page number where detailed manufacturers data for that component can be located within the submittal. a. Product data for system components shall include UL listing information, detailed product data, dimensioned plans and elevations showing minimum clearances and installed features of devices. b. Where more than one product model is described on the manufacturers data sheet, the specific unit proposed shall be highlighted or otherwise identified. 2. When equipment other than that specified is submitted, a complete paragraph-by-paragraph comparison with the specification shall be included. 3. A detailed battery calculation document indicating each control panel component and peripheral device along with the following information: a. The quantity of each component b. The stand-by and alarm power requirements of each component c. Calculations to clearly indicate battery size needed to comply with the specification requirements. d. The size of proposed batteries. PART 2 - PRODUCTS 2.1 FIRE ALARM CONTROL PANEL A. Furnish and install a Simplex Model 4100U Fire Alarm Control Panel where shown on the drawings. Construction shall be modular with solid state, microprocessor based electronics. It shall display only those primary controls and displays essential to operation during a fire alarm condition. B. The Control Panel shall have an 80-character LCD display and perform all functions listed in this specification. The display shall be backlit for enhanced readability. So as to conserve battery standby power, it shall not be lit during an AC power failure unless an alarm condition occurs or there should be keypad activity. C. The Base Control Panel shall contain all necessary hardware and software required to monitor a minimum of 250 addressable devices and monitor and control three (3) 3Amp notification appliance circuits. It shall contain a minimum of four (4) programmable auxiliary relays and contain the circuitry to operate a serial controlled remote annunciator panel. The panel shall be expandable to monitor up to 2000 points. D. The control panel CPU shall allow for two on-board configuration programs. Two programs allow for reduced service programming time 28 31 11-7 (45307035)

with one active program and one in reserve. The control panel shall remain fully operational during the configuration download process. E. The control panel shall be capable of operating on a "peer-to -peer network" with similar control panels to enable individual system expansion and the capability to monitor, control and program systems in different facilities from one central location. F. The control panel shall include an integral Digital Alarm Communicating Transmitter (DACT) to transmit fire alarm activation to an owner-selected central monitoring location. The communicator shall be UL 864 listed as conforming to the requirements of NFPA 71. It shall be listed as integral component with the fire alarm control panel. The communicator shall supervise (2) two telephone lines and be capable of seizing the telephone line and sending an alarm signal on one or both lines without the need of any additional equipment. The communicator shall be capable of transmitting to Silent Knight, Radionics or Ademco receiving stations. G. Provide cabinets of sufficient size to accommodate the aforementioned equipment. The cabinets shall be equipped with locks and transparent door panels providing freedom from tampering yet allowing full view of the various lights and controls. 2.2 NAC POWER EXTENDER PANEL(S) A. Furnish and install Simplex Model 4009-9201 Notification Appliance Circuit (NAC) Extender Panels as required to operate the alarm notification appliances where shown on the drawings. Allow for 20% spare capacity per circuit. Each power extender panel shall provide four (4) supervised notification appliance circuits and an 8 Amp power supply. The panel shall digitally communicate with the fire alarm control panel to provide for the synchronization and control of the audible and visible notification appliances on common 2-wire circuits. The audible notification signals (horns) shall sound in a temporal code pattern as described by NFPA 72 and shall remain active until the Alarm Silence switch is activated at the fire alarm control panel (or at the remote annunciator panel). The visible notification appliances (xenon strobes) shall be synchronized and shall remain active until the system is reset. The four circuits shall be individually software controlled from the fire alarm control panel. The panel shall monitor each of its' output circuits for trouble conditions and report back to the fire alarm control panel, by circuit, if a trouble occurs. Each panel shall be equipped with stand-by batteries sized to provide twenty-four (24) hours of standby followed by five (5) minutes of alarm operation. 2.3 REMOTE ANNUNCIATOR(S) A. Furnish and install a Simplex type 4603-9101 Alphanumeric LCD Remote Annunciator Panel where shown on the drawings. It shall operate from the Fire Alarm Control Panel using serial transmission techniques and shall require only a four-wire connection regardless of the number of annunciation zones or manual controls. An 80 character (2 Lines of 40) LCD display shall be included for annunciation of all system status changes including alarms, troubles, and supervisory service indications. Manual control switches with associated LED s shall be provided as an integral part of the annunciator for alarm acknowledge, trouble acknowledge, supervisory service acknowledge and alarm silence. System reset switch, display time switch, local audible alert and system master control enable switch shall also be provided 28 31 11-8 (45307035)

on the annunciator. To prevent unauthorized operation of the control switches, the enable switch shall be key operated and be used to enable the other control switches. The Annunciator shall also be provided with a power on indicator and five programmable auxiliary control switches and associated LED indicators. All wiring to the Remote Annunciator shall be supervised by the fire alarm control panel for opens, shorts and ground faults. 2.4 PERIPHERAL DEVICES A. MANUAL STATIONS: Furnish and install Simplex type 4099-9001 Single Action Addressable Manual Pull Stations where shown on the drawings. Stations shall be constructed of high impact red lexan and shall operate with or without glass rod. Station shall contain a key lock keyed identical to the control panel to be used for resetting the station. Once activated, the pull station handle shall remain at a 90-degree angle from the front of the station to provide visual indication as to which pull station was activated. Manual stations shall be suitable for semi-flush or surface mounting. Where stations are to be surface mounted, the enclosures shall be provided by the manufacturer. Stations shall be semi-flush mounted wherever possible. B. SMOKE SENSORS: Furnish and install Simplex Model 4098-9714 TrueAlarm Smoke Sensors with Model 4098-9792 base where shown on the drawings. Sensors shall be of the photoelectric type and shall communicate actual smoke chamber values to the system control panel. The sensors shall be listed to UL Standard 268 and shall be documented compatible with the control equipment to which they are connected. The sensors shall be listed for both ceiling and wall mount applications. The sensitivity of each individual detector shall programmable from the control panel. The sensors shall automatically compensate for the accumulation of dust and dirt to maintain operation at their programmed sensitivity level as these contaminates accumulate. The control panel shall identify the need for individual sensors to be cleaned before the contamination affects their sensitivity. In order to assist maintenance personnel, the control panel shall report sensors that are almost dirty so that these units can be serviced at the same time as sensors reporting a dirty condition. The sensors shall be documented to automatically meet NFPA sensitivity testing requirements. C. HEAT SENSORS: Furnish and install Simplex Model 4098-9733 TrueAlarm Heat Sensors with Model 4098-9792 base where shown on the drawings. They shall be a combination rate-of-rise and rate compensated fixed temperature sensor of which both operations are self-restoring. The sensor's small thermal mass shall allow an accurate up-to-date temperature reading of each sensor to be logged at the control panel. The rate of rise operation shall be selectable in either a 15-degree per minute or a 20-degree per minute rate of temperature rise. The fixed temperature principle shall operate entirely independent of the rate of rise principle and shall be selectable for either 135 degrees or 155 degrees Fahrenheit. The heat detectors shall be UL listed to standard 521 for sixty (60) foot spacing at the 135-degree setting and forty (40) foot spacing at the 155-degree setting. D. DUCT SMOKE SENSORS: Furnish and install Simplex Model 4098-9756 Duct Housings with type 4098-9714 TrueAlarm sensors where shown on the drawings. The sensors shall meet the requirements of UL Standard 268A and shall be documented compatible with the control equipment to which they are connected. The addressable duct smoke sensors shall digitally communicate analog information to the control panel to be 28 31 11-9 (45307035)

analyzed. The sensor input is stored and tracked as an average value with an alarm or abnormal condition being determined by comparing the sensor s present value against it s average. Monitoring each sensor s average value provides a software filtering process that compensates for environmental factors (dust, dirt, etc.) and component aging, providing an accurate reference for evaluating new activity. The result is a significant reduction in the probability of false or nuisance alarms caused by shifts in sensitivity. The duct housing shall contain a red LED, which shall pulse to indicate power-on and glow continuously to indicate an alarm or a sensor trouble condition. It shall also contain a relay driver output that is supervised for opens, shorts, and ground faults for control of the remote relay, described below. The duct smoke sensor shall obtain 24VDC-operating power from the fire alarm control panel. It shall utilize a cross sectional sampling principle by which a sampling tube is extended across the duct to continuously sample the air movement through the duct, after which the sampled air is returned to the duct via an exhaust tube. Sampling tubes shall be properly sized for the duct in which they are installed. The housing shall include a magnetic test location to enable the sensor to be electronically tested in place without removing the housing cover. Additionally, the housing shall include smoke test ports to enable actual smoke testing without removing the housing cover. 1. REMOTE RELAY: Furnish and install a Simplex Model 4098-9843 Remote Relay in a separate electrical box within three (3) feet of each AHU control panel or other device (damper, etc.) being controlled. The relay operation shall be software programmable and supervised by the fire alarm control panel for opens, shorts, and ground faults per NFPA 72, Section 3-9.2.1. The relay shall contain SPDT contacts rated at 10 amps @ 120VAC for unit shutdown/control. 2. REMOTE TEST STATION: Furnish and install a Simplex type 2098-9806 Remote Alarm Indicator with Test Keyswitch for each duct smoke sensor. The unit shall be mounted in a separate single gang electrical box in a visible/accessible location within twenty (20) feet of the duct smoke sensor or where indicated on the plans when applicable. The station shall provide a remote indication of the alarm condition of the associated smoke sensor and a key-operated switch for testing. Note: Duct smoke sensors and accessories are to be furnished and wired to the fire alarm system by the electrical contractor to insure compatibility with the system. The housings are to be installed in the HVAC system and wired for proper AHU/Damper shutdown operation from the remote relay location to the control unit by the mechanical contractor. The electrical contractor shall turn the housings over to the mechanical contractor upon delivery for installation. E. WATERFLOW AND OS&Y MONITOR SWITCHES: Waterflow and OS&Y Monitor Switches shall be furnished and installed under other sections of these specifications but shall be wired and connected to the Fire Alarm System by the Electrical Contractor. F. INDIVIDUAL ADDRESSABLE MODULE (IAM): Furnish and install Simplex Model 4090-9001 Individual Addressable Modules as required. The units shall provide location specific addressability to non-addressable devices such as waterflow, sprinkler tamper switches, and kitchen suppression systems, furnished by others, by monitoring normally open dry contacts. Closure of the monitored contact shall initiate an alarm or supervisory condition, as required. An open in the initiating circuit will cause a trouble to be reported at the fire alarm control panel. Units shall mount in a standard single gang electrical box. 28 31 11-10 (45307035)

G. AUDIBLE/VISIBLE UNITS: Furnish and install Simplex type 4903-9418 Synchronized Audible/Visible Units where shown on the drawings. The visible portion of the appliances shall provide 75 cd illumination and have a flash rate of 1 Hz over the entire operating voltage range as required by the Americans with Disabilities Act (ADA). 15/75 candela devices will not be considered as equal. The output of the audible portion of the appliance shall be rated at 91dBA at 10 feet. The notification appliances shall be UL listed to Standards 1971 and 464. The specified control panel shall provide for the synchronization and control of the audible and visible portions of these devices on a common 2-wire circuit. The audible notification signal shall be in a temporal code pattern as described by NFPA 72 and shall remain active until the Alarm Silence switch is activated at the fire alarm control panel (or at the remote annunciator panel). All visible notification signals (xenon strobes) shall be synchronized and shall remain active until the system is reset. The units shall be labeled with the word "FIRE" in a contrasting color and the height of each character shall be a minimum of 5/8". In its' quiescent state, the word "FIRE" shall be visible. The devices shall semi-flush mount directly to standard single gang, double gang, and 4 square electrical boxes without the use of special adapters or trim rings. Where indicated on the drawings, include Simplex Model 4905-9998 protective wire guards. H. VISUAL ONLY UNITS: Furnish and install Simplex type 4904-9332 Synchronized Visible Units where shown on the drawings. The appliances shall provide 75 cd illumination and have a flash rate of 1 Hz over the entire operating voltage range as required by the Americans with Disabilities Act (ADA). 15/75 candela devices will not be considered as equals. The notification appliances shall be UL listed to Standard 1971. The specified control panel shall provide for the synchronization and control of the system audible and visible notification appliances on a common 2-wire circuit. The audible notification signal shall sound in a temporal code pattern as described by NFPA 72 and shall remain active until the Alarm Silence switch is activated at the fire alarm control panel (or at the remote annunciator panel). The visible notification signals (xenon strobes) shall be synchronized and shall remain active until the system is reset. The units shall be labeled with the word "FIRE" in a contrasting color and the height of each character shall be a minimum of 5/8". In its' quiescent state, the word "FIRE" shall be visible. The devices shall semi-flush mount directly to standard single gang, double gang, and 4 square electrical boxes without the use of special adapters or trim rings. Where indicated on the drawings include Simplex Model 4905-9998 wire guards. I. DOOR HOLDERS: Furnish and install Simplex type 2088 Series Door Holders where shown on the drawings. The units shall be rated for a minimum of 25 lbs. of holding force and shall be wall or floor mounted as indicated on the drawings. They shall be powered from the Fire Alarm Control Panel by a fused 24VDC circuit and shall release the door on any alarm. J. INDIVIDUAL ADDRESSABLE MODULE (IAM): Furnish and install Simplex Model 4090-9001 Individual Addressable Modules to monitor nonaddressable devices as required. The units shall provide location specific addressability to non-addressable devices such as waterflow, sprinkler tamper switches and kitchen suppression systems. The module shall be capable of sensing normal, open circuit, short circuit, and current limited conditions. With the proper end-of-line and current limiting resistors, dual functions such as tamper switch and waterflow switch monitoring can be determined and communicated by a single addressable point. Units shall mount in a standard single gang electrical box. 28 31 11-11 (45307035)

K. ADDRESSABLE CONTROL RELAYS (RELAY IAM): Furnish and install Simplex Model 4090-9002 Addressable relay module. The relays shall operate on the ID NET circuit only and shall not require 24vdc to operate. The relay module shall provide SPDT contacts rated at 2 amps @ 24vdc for transient suppressed loads. The relay assembly shall mount to a standard 4 inch square electrical box. The electrical contractor shall provide a standard box cover. PART 3 - EXECUTION 3.1 INSTALLATION, GENERAL A. All fire alarm system conductors shall be installed in conduit. Wire sizes and types shall be per manufacturer recommendations. B. Install system according to NFPA Standards referenced in Parts 1 and 2 of this Section. C. Fire Alarm Power Supply Disconnect: Paint red and label "FIRE ALARM." Provide with lockable handle or cover. 3.2 EQUIPMENT INSTALLATION A. Existing Fire Alarm Equipment (If Applicable): Maintain fully operational system. As new equipment is installed, label it "NOT IN SERVICE" until operational. Remove tags from new equipment when put into service and tag existing fire alarm equipment "NOT IN SERVICE" until removed from the building. B. Equipment Removal (If Applicable): After acceptance of the new fire alarm system, remove existing, disconnected fire alarm equipment and restore damaged surfaces. Remove from the site and legally dispose of the material. C. Manual Pull Stations: Mount semi-flush in recessed back boxes with operating handles 44 inches above finished floor or as indicated. D. Smoke Detectors: Install ceiling-mounted detectors in center of corridors or as indicated on the drawings but not less than 4 inches (100 mm) from a side wall to the near edge. Install detectors located on the wall at least 4 inches (100 mm) but not more than 12 inches (300 mm) below the ceiling. For exposed solid joist construction, mount detectors on the bottoms of the joists. On smooth ceilings, install detectors not over 30 feet (9 m) apart in any direction. Install detectors no closer than 5 feet (1500 mm) from air registers. E. Audible Alarm-Indicating Devices: Install not less than 80 inches above the finished floor nor less than 6 inches (160 mm) below the ceiling. Install bells and horns on flush-mounted back boxes with the device-operating mechanism concealed behind a grille or as indicated. Combine audible and visual alarms at the same location into a single unit. F. Visual Alarm-Indicating Devices: Install at 80 inches (2000 mm) above the finished floor or 6 inches (150 mm) below the ceiling, whichever is lower. 28 31 11-12 (45307035)

G. Remote Alarm Indicators/Test Switches: Locate in the public space immediately adjacent to the device they monitor. H. Fire Alarm Control Panel (FACP): Surface mount with tops of cabinets not more than 6 feet (1800 mm) above the finished floor. I. Remote Annunciator: Arrange as indicated, with the top of the panel no more than 6 feet (1800 mm) above the finished floor. 3.3 WIRING INSTALLATION A. Wiring Method: Install wiring in metal raceway according to Division 16 Section "Raceways." Conceal raceway except in unfinished spaces and as indicated. B. Wiring Within Enclosures: Install conductors parallel with or at right angles to the sides and back of the enclosure. Bundle, lace, and train the conductors to terminal points with no excess. Mark each terminal according to the wiring diagrams of the system. Make all connections with approved crimp-on terminal spade lugs, pressure-type terminal blocks, or plug connectors. C. System Wiring: For the low-voltage portion of the fire alarm system, install No. 14 AWG conductors and 75-deg C insulation in wet, damp, or dry locations. For line-voltage wiring, install No. 12 AWG size with insulation rated 75 deg C minimum. D. Color Coding: Color-code fire alarm conductors differently from the normal building power wiring. Use one color code for alarm circuits wiring and a different color code for supervisory circuits. Colorcode audible alarm-indicating circuits differently from alarminitiating circuits. Use different colors for visual alarm-indicating devices. Paint fire alarm system junction boxes and covers red. E. Wiring to Central Station Transmitter: 1-inch conduit between the FACP and the central station transmitter connection as indicated. Install number of conductors and electrical supervision for connecting wiring as required to suit central-station monitoring function. 3.4 FIELD QUALITY CONTROL A. Manufacturer's Field Services: Provide services of a factory-employed service representative to supervise the field assembly and connection of components and the pretesting, testing, and adjustment of the system. B. Pretesting: Upon completing installation of the system, align, adjust, and balance the system and perform complete pretesting. Determine, through pretesting, the conformance of the system to the requirements of the Drawings and Specifications. Correct deficiencies observed in pretesting. Replace malfunctioning or damaged items with new and retest until satisfactory performance and conditions are achieved. Prepare forms for systematic recording of acceptance test results. C. Report of Pretesting: After pretesting is complete, provide a letter certifying the installation is complete and fully operable, including the names and titles of the witnesses to the preliminary tests. D. Final Test Notice: Provide a 10-day minimum notice in writing when the system is ready for final acceptance testing. 28 31 11-13 (45307035)

E. Minimum System Tests: Test the system according to the procedures outlined in NFPA 72H, Chapters 2 and 4, and NFPA 72E, Chapter 8. Minimum required tests are as follows: 1. Verify the absence of unwanted voltages between circuit conductors and ground. 2. Megger test all conductors other than those intentionally and permanently grounded with electronic components disconnected. Test for resistance to ground. Report readings less than 1-megohm for evaluation. 3. Test all conductors for short circuits utilizing an insulationtesting device. 4. Verify the control unit is in the normal condition as detailed in the manufacturer's operating and maintenance manual. 5. Test each initiating and indicating device for alarm operation and proper response at the control unit. 6. Test the system for all specified functions according to the manufacturer's operating and maintenance manual. Systematically initiate specified functional performance items at each station including making all possible alarm and monitoring initiations and using all communications options. For each item, observe related performance at all devices required to be affected by the item under all system sequences. Observe indicating lights, displays, signal tones, and annunciator indications. F. Retesting: Correct deficiencies indicated by tests and completely retest work affected by such deficiencies. Verify by the system test that the total system meets the Specifications and complies with applicable standards. G. Report of Tests and Inspections: Provide a written record of inspections, tests, and detailed test results in the form of a test log. Submit log upon the satisfactory completion of tests. 3.5 CLEANING AND ADJUSTING A. Cleaning: Remove paint splatters and other spots, dirt, and debris. Touch up scratches and mars of finish to match original finish. Clean the unit internally using methods and materials recommended by manufacturer. B. Occupancy Adjustments: When requested within one year of date of Substantial Completion, provide on-site assistance in adjusting sound levels and adjusting controls and sensitivities to suit actual occupied conditions. Provide up to three visits to the site for this purpose. 3.6 DEMONSTRATION A. Provide the services of a factory-employed service representative to demonstrate the system and train Owner's maintenance personnel as specified below. 1. Train Owner's maintenance personnel in the procedures and schedules involved in operating, troubleshooting, servicing, and preventive maintaining of the system. Provide a minimum of 4 hours' training. 2. Schedule training with the Owner at least seven days in advance. 28 31 11-14 (45307035)

3.7 WARRANTY A. The contractor shall warrant the completed fire alarm system wiring and equipment to be free from inherent mechanical and electrical defects for a period of one (1) year from the date of the completed and certified test. B. The equipment manufacturer shall make available to the owner a maintenance contract proposal to provide a minimum of two (2) inspections and tests per year in compliance with NFPA-72H guidelines. END OF SECTION 28 31 11 28 31 11-15 (45307035)