EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Similar documents
The Effect of Inner Grooved Tubes on the Heat Transfer Performace of Air-Cooled Heat Exchangers of Co2 Heat Pump System

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Air-Cooled Heat Exchanger Performance for R410A

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Global Journal of Engineering Science and Research Management

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Heat Transfer Characteristics and Heat Exchanger Performances for R407C Using Herringbone Heat Transfer Tube

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Effects of Oil on atranscritical Carbon Dioxide Air Conditioning Systems some experiences -

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

FROSTING BEHAVIOR OF FIN-TUBE HEAT EXCHANGER ACCORDING TO REFRIGERANT FLOW TYPE

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Development of Small-diameter Tube Heat Exchanger: Circuit Design and Performance Simulation

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant

Full and Partial Load Performances of RAC and CAC Heat Pump using R-32

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

Enhancement of Round Tube and Flat Tube- Louver Fin Heat Exchanger Performance Using Deluge Water Cooling

Low GWP Refrigerants for Air Conditioning Applications

PREDICTION OF THE PRESSURE DROP OF CO 2 IN AN EVAPORATOR USED FOR AIR COOLING ABSTRACT 1. INTRODUCTION 2. EXPERIMENTAL SET-UP AND PROCEDURE

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

MULTI-CHANNEL R134A TWO-PHASE FLOW MEASUREMENT TECHNIQUE FOR AUTOMOBILE AIR-CONDITIONING SYSTEM

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Performance Measurement of R32 Vapor Injection Heat Pump System

Performance of CO2 Cycles with a Two-Stage Compressor

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Study of R161 Refrigerant for Residential Airconditioning

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

NEW COPPER-BASED HEAT EXCHANGERS FOR R744 REFRIGERANT PART II: SYSTEM DESIGN AND CASE STUDIES

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Thermal Performance of a Loop Thermosyphon

Refrigerant Mass and Oil Migration During Start-up Transient

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12


Heat transfer property of refrigerant-oil mixture in a flooded evaporator: The role of bubble formation and oil retention

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Performance of window air conditioner using alternative refrigerants with different configurations of capillary tube

Feasibility Study of Condensation Heat Exchanger with Helical Tubes for a Passive Auxiliary Feedwater System

Evaluation and Development of Air-conditioners using Low GWP Refrigerant

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

A study on performance improvement of corrugated type total heat exchanger considering the structure of flow passage on surface

Effects of Non-Uniform Refrigerant and Air Flow Distributions on Finned- Tube Evaporator Performance

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Evaluation the Effect of Washing on the Heat Transfer Capacity and Air-Side Flow Resistance of Air Cooled Condensers

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Comparison of Oil Retention in R134a and CO 2 Climate Control Systems

Two Phase Flow Boiling Heat Transfer and Pressure Drop of Two New LGWP Developmental Refrigerants Alternative to R-410A

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

Investigation of Evaporator Performance with and without Liquid Overfeeding

Purdue e-pubs. Purdue University

Compressor Explosion Accident at Pump-Down of Air Conditioners

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Experimental performance evaluation of heat pump by using CO 2. as a refrigerant. IOP Conference Series: Materials Science and Engineering

Experimental Investigation of Elliptical Tube Bank Cross Flow Heat Exchanger with Inline Arrangement & 45 Angle of Attack

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

R&D ON HEAT PUMPS WITH NATURAL WORKING FLUIDS IN JAPAN

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

Enhancement of COP using Nanoadditives in Domestic Refrigerator

HFCs or the Old Refrigerants - what is the best Choice?

Experimental Analysis of Performance Characteristics of Mini Channel Heat Exchangers

Effect of magnetic field on the performance of new refrigerant mixtures

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

2. HEAT EXCHANGERS MESA

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Study on the Effect of Blade Angle on the Performance of a Small Cooling Tower

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Passive cooling of telecommunication outdoor cabinets for mobile base station

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

EFFECTS OF VARIABLES ON NATURAL CONVECTIVE HEAT TRANSFER THROUGH V-CORRUGATED VERTICAL PLATES

Study of solar-thermal collector assisted hybrid split air conditioner

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Design and Development of Water Cooled Condenser for Domestic Refrigerator

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

MAL-DISTRIBUTION MODEL OF HEAT EXCHANGERS IN MICRO CHANNEL EVAPORATOR

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Transcription:

- 1 - EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM Shun YOSHIOKA, Hyunyoung KIM, Kazushige KASAI, Daikin Industries, LTD., Kanaoka-cho, Kita-ku, Sakai, Osaka, Japan Abstract: In carbon dioxide (R744) heat pump systems, PAG oil is commonly used for lubrication of the compressor, while it is reported that the presence of oil is greatly influential on heat transfer performance due to its immiscibility against R744. This paper deals with an experimental study on the heat transfer performance of fin and tube heat exchangers working with R744 while taking the effect of PAG oil into account. The experimental apparatus was designed to enable control the oil circulation rate (OCR) independently by using an independent oil circulation line from the refrigerant circuit. Two types of heat exchangers with different tubes, smooth tube and internally grooved tube, have been tested while varying the OCR in the range from nearly zero to 5 wt %. It was found that the OCR change affects significantly in the heat transfer performance at the low range of OCR in both evaporation and gas cooling. The effect of the OCR, however, is different between the smooth tube and grooved tube. For understanding of these phenomena, the oil retention rate in each heat exchanger was measured. Key Words: heat exchanger, heat transfer, carbon dioxide, lubricant oil 1 INTRODUCTION In recent years, the problem of global warming is a one of great issue from an environmental point of view, and there have been many attempts to eliminate its cause. In the refrigeration and air conditioning field, there have been many studies in these regards. In the refrigeration industry, factors affecting global warming include not only emission of carbon dioxide in its operation, but also emission of refrigerant having global warming potential (GWP). Since the currently used freon refrigerant has a high GWP, many researchers are interested in using a natural refrigerant with low GWP. Carbon dioxide (R744) is one of the promising alternatives due to its low GWP. The refrigerating cycle using R744 operates in high pressure that is almost three times higher than that of R410A and forms trans-critical cycle. Since the highpressure side works above super-critical pressure, temperature gliding is displayed in its cooling process. By using these characteristics, this cycle has been successfully commercialized for hot water supply heat pump system in Japan. In designing a heat exchanger for a refrigerator or air conditioning system using R744, an understanding of the heat transfer performance is required. However, the heat transfer characteristics of R744 are greatly different from that of fluorocarbon due to a large difference of the working condition and its properties. Additionally, Polyalkylene glycol (PAG) is commonly used for lubricant of the compressor in R744 systems, while it is reported that the oil is relatively influential. A few experimental studies on the heat transfer characteristics of R744 in a horizontal single tube have been reported. Hihara and Dang (2007) have measured the boiling heat transfer characteristics in a smooth tube with 1 to 6mm in an inner diameter at 4.5-36kW/m 2 in heat flux and 360-1440kg/m 2 s in mass flux, and reported that the boiling heat transfer coefficient of R744 is strongly influenced by the heat flux but it is negligible for the mass flux in the pre-

- 2 - dryout region. Katsuta et al. (2007) have measured the boiling heat transfer characteristics with PAG oil in a smooth tube with 3mm in an inner diameter. They reported that the boiling heat transfer coefficient of two phase flow decrease with the presence of PAG. They suggested a correlation for the heat transfer coefficient with PAG in terms of the oil circulation rate (OCR). Higashiue et al. (2007) have measured the heat transfer characteristics of R744 with PAG in super critical gas cooling inside a inner micro-fin copper tube with 6mm in an outer diameter at 8 and 10MPa in pressure, 340-660kg/m 2 s in mass velocity and 0.06-2.26% in the mass percent concentration of PAG. They reported that the heat transfer coefficient in gas cooling decreases with the presence of PAG. However, the data provided from these open literatures are not sufficient in designing actual heat exchangers, since these data were obtained under different conditions of the range in which the heat exchanger is operated within the air conditioning system. In addition, it is necessary to take into account of the effect of inner surface geometry change caused by the mechanical tube expanding, which is essential in reducing the thermal contact resistance between fin collars and tubes. The objective of this study is to provide the experimental data on heat transfer in reference to designing heat exchangers applied to R744 heat pump systems. This paper deals with an experimental study on the heat transfer performance of fin and tube heat exchangers utilizing R744 as a refrigerant taking the effect of PAG into account. The experimental study for the heat transfer of fin and tube heat exchangers with two different types, smooth tube and grooved tube, at a varying the OCR was carried out. The heat transfer performance and oil retention rate of each heat exchanger for both evaporator and gas cooler was measured in order to understand the difference in heat transfer characteristics with a change in OCR and tube type. Environmental Chamber ΔP Air Chamber ΔP Test Section DB WB DB WB Blower Nozzle Air Sampler P T T ΔP Refrigerant Supply System (for evaporator test) Sub-Evaporator Compressor Accumulator Gas Cooler Sampling section for OCR Mass Flow Meter P Expansion Valve T Oil Separater Oil Separater Oil Pump Mass Flow Meter Air Refrigerant Oil DB : Dry bulb temperature (Pt100 sensor) WB : Wet bulb temperature (Pt100 sensor) T : Tempereture (Pt100 sensor) P : Pressure (Pressure gauge) ΔP : Pressure drop (Differencial pressure gauge) Figure 1: Schematic diagram of experimental apparatus

- 3-2 EXPERIMENT 2.1 Experimental apparatus Figure 1 shows the schematic diagram of the experimental apparatus. This apparatus consists of a refrigerant supply system, an air chamber that can control air velocity for the test heat exchanger, and an environmental chamber that can control air temperature and humidity to adjust each experimental condition. The refrigerant supply system, which has a compressor for the R744 super critical cycle, was designed enabling control R744 conditions such as the pressure, temperature, quality, and mass flow rate flowing into the test heat exchanger. In addition, it is able to control the PAG oil circulation rate (OCR) by using a separated oil circulation line, which is prepared independently from the refrigerant circuit. 2.2 OCR measurement It is known that PAG flows separately from the R744 main flow, since PAG is almost immiscible against R744. In addition, the flow pattern of the mixture will vary with the refrigerant condition. Therefore, it seems that the accurate measurement of the OCR is not easy. Several methods for measurement of the OCR of PAG in R744 circuit have been reported so far. Higashiue et al. (2007) used the method of immediately collecting the refrigerant in the refrigerant circuit. They prepared a sampling tube with two normally opened air actuated valves at both ends and a bypass loop with a normally closed actuated valve in the refrigerant circuit, and reversed each valve at the same time while driving the system and measured weight of refrigerant and oil. Gao and Honda (2006) used the method that measures quantities of the oil visually at the place after an evaporator. They set up a sightglass chamber that was able to observe the behaviour to which oil fell in the droplet, and counted fall frequency and size of the oil droplet during a certain time interval. In this study, the OCR was measured by collecting the refrigerant into the sampling tank, which was set in the circuit, referring to ASHRAE standard (1996). The measuring point is the line just next to the gas cooler and before the expansion valve in both the evaporator test and the gas cooler test. In that point, pressure and temperature of the refrigerant is about 10MPa and 20 to 30 C respectively, and the density of PAG becomes near that of R744. Therefore, it is seemed that the oil flows relatively homogeneously in R744, and it is able to be caught the oil and R744 accurately. Incidentally, the oil behaviour in the refrigerant before the point can be observed in a tube type sight glass. To collect the refrigerant, considering the oil retention in the connecting tube, the vacuumed sampling tank and another sub-tank was set above the main flow tube as shown in figure 2. And then, the refrigerant was caught into the sampling tank just after cleaning the connecting tube by using the sub-tank. The volume of the sampling tank is 150cc, and an electronic scale was used to measure the weight. Sub- Tank (75cc) Sanpling Tank (150cc) from gas cooler Sighit glass Refrigerant flow to expansion valve Figure 2: Details in OCR sampling section

- 4-2.3 Test heat exchanger Table 1 shows the specifications of the test heat exchangers. The test heat exchangers are composed of copper tubes with a 7mm outer diameter and aluminium fins with a 0.1mm thickness, which are generally used in actual air conditioners. In order to evaluate detailed R744 heat transfer characteristics of a heat exchanger in this study, two types of heat exchangers with different shaped tubes were prepared, one with smooth surface tubes, and the other with inner grooved tubes that have micro fins for enhancing heat transfer generally utilizing Fluorocarbon refrigerant. Tube Table 1; Specification of test heat exchangers Type Smooth tube Grooved tube Fin Outside diameter mm 7.0 7.0 Bottom wall thickness mm 0.9 0.6 Number of grooves - - 60 Fin height mm - 0.15 Apex angle deg - 60 Lead angle deg - 18 Type Wavy fin (hydrophilic coated) 21 18.2 Size Fin pitch mm 1.3 W H D mm 400 252 36.4 W D H Fin pitch Step Row - 12 2 Air Refrigerant (R744) Table 2; Experimental conditions Evaporator Gas cooler Dry bulb / Wet bulb C 27 / 19 20 / 15 Velocity V a m/s 1.0 1.0 Pressure P MPa 4.18 10.00 Inlet quality x i - 0.2 - Super heat temp. T sh K 3.0 - Inlet temperature T i C - 90 Outlet temperature T o C - 30 Flow pattern Parallel flow Oil (PAG) Oil circulation rate OCR wt% 0~5 Counter flow

- 5-2.4 Experimental condition Table 2 shows the experimental conditions. Each value was adjusted to actual operating conditions for the heat exchanger of an inside unit of an air conditioner. The OCR is varying within the range from nearly zero to 5wt%. The refrigerant pressure is adjusted at the vapor side in each test, therefore, that is outlet side in the evaporator test, or inlet side in the gas cooler test. The refrigerant outlet condition such as the super heated temperature in the evaporator test or outlet temperature in the gas cooler test is adjusted by changing the refrigerant flow rate. Controlling to adjust these experimental conditions in each test, data of the heat transfer rate and pressure drop of the air and refrigerant are measured after confirmation of a constant state. The heat transfer rate is calculated from the air side enthalpy and flow rate, which is confirmed less than ± 3% difference from the calculated value at the refrigerant side enthalpy and flow rate in each test. 3 EXPERIMENTAL RESULT AND CONSIDERATION 3.1 Experimental result of heat transfer rate Figure 3 shows the experimental results. Heat transfer performances against oil circulation rate were measured under the conditions of evaporator and gas cooler. In the evaporator test shown on Figure 2(a), it is clear that the heat transfer performance decreases as OCR increases in both and. Especially, that of using grooved tubes decreases as much as 13% at only 0.5wt% oil mixture, and approaches to that of using smooth tubes. In the gas cooler test shown on Figure 2(b), it is found that the performance of doesn t change against OCR, however, decreases greatly and becomes less than that of at more than 0.4wt% of OCR. From these experimental results, it is confirmed that the OCR change affects significantly on the heat transfer performance at the low range of OCR. Heat transfer rate Q [kw] 3.0 2.8 2.6 2.4 2.2 Evaporator P =4.18MPa, T sh =3K, x i =0.2 2.0 Heat transfer rate Q [kw] 3.6 3.4 3.2 3.0 2.8 2.6 Gas cooler P =10MPa, T i =90, T o =30 2.4 (a) Evaporator test (b) Gas cooler test Figure 3: Heat transfer rate versus oil circulation rate 3.2 Heat transfer coefficient of R744 The heat transfer performance of the heat exchanger mainly consists of the heat transfer coefficient of the air side and that of refrigerant side. Because the heat transfer coefficient of the air doesn t change with the change of the OCR, the deterioration of the heat transfer rate of the heat exchanger is caused by the deterioration of the heat transfer coefficient of the

- 6 - refrigerant flowing inside of the tube. Using data from the heat transfer rate shown on Figure 3, to calculate refrigerant heat transfer coefficient was attempted. Using a calculation tool which can calculate heat transfer performance of air-cooled heat exchangers by the tube by tube method, and installing an air side heat transfer coefficient that had been measured in advance by using Wilson-plot method, the refrigerant heat transfer coefficient was calculated to match the calculation value of the heat transfer rate and pressure drop to the corresponding experimented value. To determine the shape of the refrigerant heat transfer coefficient against the quality or the temperature of the refrigerant, it was decided to utilize Gnielinski (1976) correlation to single-phase region and Kandlikar (1990) correlation to two-phase region by multiplied moderate coefficient. Using this calculation method, two-phase mean heat transfer coefficient in evaporator and single-phase mean heat transfer coefficient in gas cooler was calculated. Figure 4 shows the calculated heat transfer coefficient of refrigerant divided by that of oil less. It is found that the effect of OCR on the heat transfer coefficient is different between the smooth tube and grooved tube. The heat transfer coefficient of grooved tube decreases to a half with over 1wt% of OCR, however, it is found that the smooth tube doesn t change so significantly with OCR. Deterioration ratio of heat transfer coefficient hr /hr 0 1.4 1.2 1.0 0.8 0.6 0.4 0.2 Evaporator P =4.18MPa, T sh =3K, x i =0.2 Smooth tube Grooved tube 0.0 (a) Evaporator test Deterioration ratio of heat transfer coefficient hr /hr0 1.4 1.2 1.0 0.8 0.6 0.4 0.2 Gas cooler P =10MPa, T i =90, T o =30 Smooth tube Grooved tube 0.0 (b) Gas cooler test Figure 4: Heat transfer coefficient of refrigerant versus oil circulation rate 3.3 Oil retention in heat exchanger In order to investigate the decline of heat transfer performance of heat exchanger by oil mixture, the oil retention rate in the heat exchangers were measured. In each test, after confirmation of the constant state, ball valves set up on each end of the test heat exchanger make refrigerant flow intercepted at the same time. The test heat exchanger is detached from the system, and R744 in the heat exchanger is emitted, and the heat exchanger is measured the weight and calculated oil quantity. Furthermore, taking the oil quantity corresponding to refrigerant quantity from that value, oil retention rate m [g/m 2 ] is calculated as: Refrigerant flow Oil quantity corresponding to refrigerant quantity (OCR) Ball valve Measured oil quantity Oil retention Figure 5: Measurement of oil retention rate in heat exchanger

- 7 - M m = 0 ρr OCR V 1000 100 A i (1) where M 0 is measured oil quantity [g], ρ r is density of refrigerant [kg/m 3 ], V is inner volume [m 3 ], and A i is inner surface area of heat exchanger [m 2 ]. Figure 6 shows the results of oil retention rate versus OCR. From this figure, it can be found that a large quantity of oil remains in the heat exchanger with a slight oil mixture. Furthermore, it is found that oil retention rate of is larger than that of, especially that of gas cooler is larger, and the variation of the oil retention rate becomes small with over 1wt% of OCR. From these results, it can be supposed that the oil retention rate in the tube of the heat exchanger can possibly be a factor of deterioration of the refrigerant heat transfer coefficient shown on Figure 4. It is found that the deterioration of the heat transfer coefficient of the grooved tube with higher oil retention rate is larger than that of the smooth tube. Oil retention rate m [g/m 2 ] 100 80 60 40 20 0 Evaporator P =4.18MPa, T sh =3K, x i =0.2 Oil retention rate m [g/m 2 ] 100 80 60 40 20 0 Gas cooler P =10MPa, T i =90, T o =30 (a) Evaporator test (b) Gas cooler test Figure 6: Oil retention rate in heat exchanger versus oil circulation rate 4 CONCLUSION For the design of the air-cooled heat exchanger in R744 heat pump system, the heat transfer performance of fin and tube heat exchangers flowing R744 with PAG oil. From the analysis of the experimental results, it can be found that the heat transfer performance of the fin and tube heat exchanger declines greatly by accumulating PAG oil in the tube when R744 including slight PAG oil emitted from the compressor flows into the heat exchanger. Therefore, it can be found that it is necessary to pay attention to the effect of PAG oil circulation rate on the heat transfer performance in designing heat exchangers. 5 REFERENCES Hihara, E. and Dang, C. 2007. Boiling heat transfer of carbon dioxide in horizontal tubes, Proceedings of ASME-JSME Thermal Engineering Summer Heat Transfer Conference, Vancouver, Canada, HT2007-32885 Katsuta, M., Okuma, K., Kishi, S., and Miyachi N. 2007. The evaporating heat transfer characteristics on refrigeration cycle of CO 2 in the refrigerator oil mixture state, Proceedings of 2007 JSRAE Annual Conference, E103 (in Japanese)

- 8 - Higashiue, S., Kuwahara, K., Yanachi, S. and Koyama, S. 2007. Experimental investigation on heat transfer characteristics of supercritical carbon dioxide inside a horizontal micro-fin copper tube during cooling process, Proceedings of ASME-JSME Thermal Engineering Summer Heat Transfer Conference, Vancouver, Canada, HT2007-32724 Gao, L. and Honda, T. 2006. Flow and heat transfer characteristics of refrigerant and PAG oil in the evaporator of a CO 2 heat pump system, Proceedings of 7 th IIR-Gustav Lorentzen Conference on Natural Working Fluids, Trondheim, Norway ANSI/ASHRAE Standard 41.4-1996 (RA 2006). Standard Method for Measurement of Proportion of Lubricant in Liquid Refrigerant, American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc., Atlanta. Gnielinski, V. 1976. New equations for heat and mass transfer in turbulent pipe and channel flow, International Chemical Engineering, Vol.16, pp.359-368. Kandlikar, S.G. 1990. A general correlation for saturated two-phase flow boiling heat transfer inside horizontal and vertical tubes, Transactions of the ASME, Journal of Heat Transfer 112, pp.219-228.