Element D Services Heating, Ventilating, and Air Conditioning

Similar documents
Element Z General Design Requirements Existing Facilities Information

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

Steam Ancillary Equipment. Primary Steam System, Water Treatment and Auxiliary Steam System Equipment

Element Z General Design Requirements Existing Facilities Information

BuildingName The Description of the Project P DOCUMENTS

Water Fuel + Air for combustion Blowdown

RULE 3.23 NATURAL GAS-FIRED WATER HEATERS, SMALL BOILERS, AND PROCESS HEATERS (Adopted 10/03/2016)

SAMPLE SPECIFICATION FOR RIELLO ARRAY MODULATING BOILER

d. Portable water heaters used exclusively for underwater diving operations.

Moss MOSS TRAY DEAERATOR ECONOMICAL INDUSTRIAL DEAERATOR SYSTEMS

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

ClearFire Economizer Model ECF Integral or External. Addendum to manuals CFH and CFV

UNFIRED STEAM GENERATORS STANDARD EQUIPMENT

CONTENTS. B. System Design and Performance Requirements

Thermal Fluid Heaters

Boiler Condensate Return Basics. Presented by Steve Connor February 24, 2016

Existing Mechanical System Operation

PIP PNE00004 Steam Trap Guidelines

PRESSURE MOTIVE PUMP (PMP) APPLICATIONS

Tray ST5. Tray Type Deaerator Pressurized.005 cc/liter. industrialsteam.com

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

Boiler Basics. Design and operation

Revitalize Building Mechanical Systems (4619)

Deaerator. Specifications

Packaged Semi-Instantaneous Steam Fired Water Heater

PROPOSED October 15, 2013

Condensate Pumps Jones Boulevard Limerick Airport Business Center Pottstown PA Tel:

Silhouette. Feedwater Heater. Boiler Feedwater

Contact Information. Steven Potratz, P.E. WSU Facilities Services, Engineering Services Manager Phone

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

Clean Steam Generators

DIVISION FINNED WATER-TUBE WATER HEATERS

VCLEARFIRE. High-Efficiency, Commercial Steam Boiler Horsepower

Manufacturers Representatives Since Industrial Systems, Inc. Computer Support, Inc

BOILER APPLICATION GUIDE for:

EZ Plate Instantaneous

S AGE E NGINEERING A SSOCIATES, LLP

05/14/2012 BOILER TUNE UPS & REPLACEMENTS PRESENTATION BOILER BASICS FOR LARGE INDUSTRIAL FACILITIES. Mark Bergum, P.E.

.005 ATMOSPHERIC DEAERATOR

STEAM VALVE SUPPLY & SYSTEM DESIGN

Packaged Instantaneous Domestic Hot Water Generator Energy Source: Boiler Water

Element D Services Heating, Ventilating, and Air Conditioning

DEAERATORS .005 ATMOSPHERIC DEAERATOR

A Cover. steam & hot water ENERGY EFFICIENT

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

High Capacity Instantaneous Steam Fired Water Heater

DIVISION FINNED WATER-TUBE BOILERS

DIVISION 23 HVAC Hydronic Piping Systems

Rental Boiler Specifications (Nebraska Boiler)

Building Department Informational Handout

2016 Plumbing Supplemental Plan Review List

HCLEARFIRE. High-efficiency, modular steam boiler HP

USG Series. Unfired Steam Generators Generate Clean Steam With Boiler Steam or High Temperature Hot Water as the Energy Source

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

FINNED WATER-TUBE POOL HEATERS

District Heat Montpelier. Customer Training

Suggested Specifications Prestige Excellence 110

Energy Efficiency & Commercial Building Natural Gas Technologies. Presented by: Eric Burgis Energy Solutions Center

Energy Management and Controls

WATER-TUBE POOL HEATERS

Suggested Specification: Benchmark 1.5 Low NOx Gas-Fired Hydronic Boiler(s)

IN THE PULP AND PAPER INDUSTRY

007100S01 - PROGRAM DESIGN CRITERIA

DIVISION WALL-HUNG STAINLESS STEEL HEATING BOILERS

Super Boiler. > Gas Technology Institute Cleaver-Brooks Inc. May WHO WE ARE Gas Technology Institute

Originators of the Flexible Water Tube design

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

DUKE UNIVERSITY DESIGN GUIDELINES

Originators of the Flexible Water Tube design

1.1 This section applies to air handling units for HVAC Systems.

Cleveland Clinic Design Standards MECHANICAL SYSTEMS DESIGN GUIDELINES HVAC AIR DISTRIBUTION PART I - GENERAL 1.1 SUMMARY

Design and Construction Standards SECTION PLUMBING EQUIPMENT

DIVISION FINNED WATER-TUBE BOILERS

ENERVEX VHX VORTEX HEAT RECOVERY CENTER

DATE PRODUCT WAS INTRODUCED TO THE CANADIAN MARKET: September 2018

NHS Sustainable Development: 14 th February Reduce Energy Consumption Through Steam System Modernisation. National Key Account Manager

DIVISION FINNED WATER-TUBE WATER HEATERS

GESTRA. Product Overview. The optimum components for every application

CCLEARFIRE CONDENSING FIRETUBE BOILER DESIGNED FOR MAXIMUM HYDRONIC SYSTEM EFFICIENCY 500 TO 3,300 MBTU

WATER-TUBE POOL HEATERS

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

Commercial Semi-Instantaneous Water Heaters

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

FINNED WATER-TUBE POOL HEATERS

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

SECTION STEAM CONDENSATE PUMPS

GAS/LOW NOx SERIES. High or Low Pressure Steam Boiler. The most versatile industrial steam boiler in the world

Open System Condensate receiver tank of cylindrical. design type SDR A with highpressure

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Commercial Applications

APPENDIX L ALTERNATE PLUMBING SYSTEMS

Plate Water Heaters Brazed Plate Water Heaters-BPH Series Plate and Frame Water Heaters-PFH Series

Typical Specifications For: ADVANTUS TM DOMESTIC HOT WATER SUPPLY Models AV(W)0500 AV(W)4000

Condensate Recovery and Return System SDR A

Product overview. the optimum components for every application

THE PRESSURIZED CONDENSATE RECOVERY SYSTEM:

University of Delaware

XTHERM, TYPE WH - MODELS 1005A- 2005A DIVISION COMMERCIAL, WATER-TUBE, CONDENSING GAS DOMESTIC WATER HEATERS

Proudly assembled in U.S.A

Transcription:

PART 1 - GENERAL 1.01 OVERVIEW A. This section includes criteria for the design of building heat generating systems including all isolation valves and steam piping and fittings, steam specialties, control valves, steam pressure pumps and shell and tube heat exchangers. B. Refer to Design Guideline Element D3044 for waterside distribution requirements. C. Where applicable for satellite locations, HVAC heating water and domestic hot water shall be produced using high efficiency (condensing style, long life, cast iron, etc.) natural gas fired heaters/boilers. D. Where steam generation is required/chosen due to existing systems, process needs, or district distribution, pursue high efficiency heat recovery systems (i.e., 2-stage flue gas recovery) for steam generating equipment to achieve high efficiency condensing operation. Intent is to limit inefficient steam generation where possible by using highly efficient steam generating systems. E. Consideration of facility operations with respect to dual-fuel and emergency operation is required when using condensing style boilers/heaters. Refer to Design Guideline Element D3026 for water heating and distribution requirements. PART 2 - DESIGN CRITERIA 2.01 GENERAL A. Boiler fuel selection and system design will be in accordance with the ASHRAE Handbooks and NFPA Standards. B. Boiler steam will be used as a heating medium for the following applications: 1. Heating Hot Water 2. Food Service (non-contract, as applicable) 3. Domestic Hot Water 4. Humidification (Clean) Steam (using an unfired boiler) 5. Autoclaves and sterilizers (verify quality of steam and whether plant or clean steam is required). C. Provide gas and oil meters for the boiler installation. ODG120908 1 OF 6

1. Provide a gas meter at the building(s). Install oil meters in both the supply line and the return line of each storage tank. 2. Each boiler, or set of identical boilers, must be equipped with a natural gas totalizer for each boiler, or each set of identical boilers, in accordance with 30 TAC 117.213(a) and 30 TAC 117.479(a). 3. If the boilers to be installed have a maximum capacity less than 40 MMBTUs/hr, then it is acceptable by TCEQ to design one flow meter for a set of identical boilers. D. Safety relief vent piping shall be extended above the roof, and shall be independent of the other steam vent piping. To avoid long safety relief valve discharge piping, safety relief valves may be located close to the terminal point if there is no shut-off valve between the PRV and the safety relief valve. E. Steam relief vent piping located downstream of safety relief valves shall be designed per ASME standards. F. Steam service from a local boiler or from a central plant boiler shall be reduced to the proper working pressures at the individual heat exchangers, prior to the control valve. Provide twostage pressure reducing valve station when reducing high pressure steam to low pressure steam service. G. Steam condensate will be collected at the receivers and pumped back to the deaerator and boiler. H. Each steam pressure reducing station will have a minimum of two air loaded steam pressurereducing valves. One steam pressure-reducing valve will be sized to provide 1/3 of the required steam capacity and the second steam pressure-reducing valve will be sized to provide 2/3 of the required steam system capacity. I. The number of condensate pumping systems and deaerator provided will be determined based on condensate loads. Redundant pressure reducing valves will not be provided, but each pressure reducing station will have a manual normally closed bypass valve. Each pressure reducing station shall have a normally open isolation valve located at upstream of each strainer and downstream of each pressure regulator. J. Heating hot water shall be produced by steam to hot water heat exchangers. The A/E shall allow for a minimum of two steam to hot water shell and tube heat exchangers to handle the heating hot water load. Each exchanger shall be capable of heating the hot water from 120 degrees F to 150 degrees F, at the required flow rate (gpm) to heat the building. K. Select equipment such that one heat exchanger provides 100 percent redundant capacity based on peak design load. L. Steam pipe sizing shall not exceed 80 feet per second. M. Steam relief vents shall be extended to the highest building roof. ODG120908 2 OF 6

N. Design steam distribution system for minimum ¾ inch pipe size. Design steam and condensate piping with loops, bends, and offsets to allow for thermal expansion and keep stresses within allowable limits of the piping material. O. The piping, fittings, valves and steam specialties used on a low pressure chemically untreated steam distribution system shall be manufactured from Type 304 stainless steel. Humidification steam is produced by an unfired steam boiler. P. Avoid using expansion joints or ball joints if possible. Q. Steam traps shall be readily available for ease of maintenance. For renovation project, the A/E shall confirm with Owner to determine if the existing steam condensate system is utilizing (Steam Eye) a monitoring system that detects and identifies failed steam traps. R. Depending on the size of the installation and the pressure at which steam is generated, use boiler accessories such as feedwater heaters to increase the steam generation cycle efficiency where applicable. S. Use blowdown separator/recovery units where possible to preheat make-up water to boiler system/deaerator where possible. Size blowdown separator/recovery unit to reduce blowdown water temperature below 120F prior to discharge of water to sanitary drainage system without the addition of potable water. T. Use flue gas recovery heat exchangers to preheat boiler feed water (and/or serve other heating loads where applicable). Use two-stage flue gas recovery (condensing) where possible to further increase boiler efficiency. Where recovery systems result in condensing of flue gases, design the boiler system with appropriate venting materials, proper sloping, and sufficient removal of condensate. Second stage of heat recovery may be associated with lower temperature heat requirements (e.g., HVAC heating hot water, domestic hot water, desiccant reactivation, etc.). U. Consider the application of vent condensers as another means to recover waste heat. A deaerator vent is a typical application for a vent condenser. V. The blowers on large capacity steam boilers often produce excess pressure at part load conditions. While blowers have increased in size due to reduced emissions requirements, there may be an opportunity to acquire some energy savings by using variable-frequency drives. Consider application of VFDs on boilers that have long operating hours at part- load, particularly when loads are at or below 50 percent fire. W. Meter all building steam supply, hot water supply, condensate return, and hot water return lines if steam is being supplied by a central plant steam system. X. Fuel oil storage tanks are to meet all EPA and applicable State, city codes and technical standards. ODG120908 3 OF 6

PART 3 - SPECIAL CONTRACT DOCUMENT REQUIREMENTS 3.01 GENERAL A. The A/E shall include a schematic of the steam boilers and associated equipment, in the Contract Documents. The boiler(s) and steam distribution system including controls shall be shown on a control diagram. The control diagram shall be complete with, but not limited to, the following: 1. Isolation valves 2. Control valves 3. Pressure and temperature gauges 4. Boiler blowdown cooler and piping 5. Flash tank 6. All steam piping specialties 7. Make up water treatment system (for boilers) 8. Chemical feeder 9. Make up or feedwater controls (interface with boiler) 10. Pressure reducing stations 11. Condensate receivers 12. Deaerator 13. Condensate tank 14. Feed water pumps 15. Flow control and measuring devices 16. Flue gas monitoring system and controls (interface with boiler) 17. Variable frequency drives (if used) 18. Heat exchangers with water side temperature controls. B. Boilers that serve Vivarium space heating, cagewash hot water, and steam for autoclaves shall be on emergency power. Refer also to Section D3000 for additional emergency power requirements. ODG120908 4 OF 6

C. Texas Commission on Environmental Quality Nitrogen Oxide Emission Compliance Requirements: 1. Emissions standards for any new boiler with a maximum rated capacity equal to or greater than 100 MMBtu/hr: i. 0.020 lb Nitrogen Oxides (NO x) per MMBtu; and ii. 400 ppmv carbon monoxide (CO), at 3.0 percent O2 dry basis. Reference: 30 TAC 117.206(c)(1)(A) and 30 TAC 117.206(e). a. A/E must inform the Owner s Project Manager to contact the Owner s EH&S department, if a unit of the above size will be installed. A unit of this size may trigger some additional federal requirements under Title 40 of the Code of Federal Regulations (40 CFR) as well as state and federal permitting requirements under 30 TAC 116 or 122. 2. Emissions standards for any new boiler with a maximum rated capacity equal to or greater than 40 MMBtu/hr, but less than 100 MMBtu/hr: i. 0.030 lb NO x per MMBtu; and ii. 400 ppmv carbon monoxide (CO), at 3.0 percent O2 dry basis. Reference: 30 TAC 117.206(c)(1)(A) and 30 TAC 117.206(e). a. A/E must inform the Owner s Project Manager to contact the Owner s EH&S department, if a unit of the above size will be installed. A unit of this size may trigger some additional federal requirements under Title 40 of the Code of Federal Regulations (40 CFR) as well as state and federal permitting requirements under 30 TAC 116 or 122. D. Emissions standards any new boiler with a maximum rated capacity less than 40 MMBtu/hr but greater than 2.0 MMBtu/hr: i. 0.036 lb NOx per MMBtu (or alternatively, 30 ppmv NOx, at 3.0 percent O2 dry basis); and ii. 400 ppmv carbon monoxide (CO), at 3.0 percent O2 dry basis. Reference: 30 TAC 117.206 (c)(1)(c, 30 TAC 117.206(e)(1), 30 TAC 117.475(c)(1)(A) and, 30 TAC 117.475(i)(1). E. Emissions standards any new boiler with a maximum rated capacity greater than 400,000 Btu/hr, but less than or equal to 2.0 MMBtu/hr: i. 30 ppmv NOx at 3.0 percent O2 dry basis; or ii. 0.037 lbs NOx per MMBtu of heat input. Reference: 30 TAC 117.465(a)(4)(A). F. Emissions standards any new boiler with a maximum rated capacity greater than 75,000 Btu/hr, but less than or equal to 400,000 Btu/hr: i. 40 ng NOx per J of heat output; or ii. 55 ppmv NOx at 3.0 percent O2 dry basis. Reference: 30 TAC 117.465(a)(3)(A). G. Emissions standards any new boiler with a maximum rated capacity less than or equal to 75,000 Btu/hr: i. 10 nanograms (ng) NOx per Joule(J) of heat output; or ii.15 ppmv NOx at 3.0 percent O2, dry basis. Reference: 30 TAC 117.213(a) and 30 TAC 117.479(a). H. The boiler must be able to achieve the applicable low Nox emission standards, as indicated above, 100 percent of the time. Flue gas recirculation or any other technology that will not obtain low Nox emissions 100 percent of the time is not acceptable. ODG120908 5 OF 6

PART 4 - PRODUCTS 4.01 GENERAL A. Refer to Owner s Master Construction Specifications. These are available on the Owner s Design Guidelines website: http://www2.mdanderson.org/depts/cpm/standards/specs.htm B. Fire tube boilers are preferred for large scale building projects that have a large demand requirement for medium pressure steam. The fire tube boiler would provide steam to autoclaves, unfired boilers for sterilizers, converters for building hot water, and to steam hot water heaters for domestic hot water. C. Specify condensing boilers for smaller scale buildings that utilize hot water re-heat. Design Guideline Element D3044 Hot Water Distribution, provides additional information that applies to the use of this type of boiler. PART 5 - DOCUMENT REVISION HISTORY Issue Date Revision Description Revisor 01-01-07 Initial Adoption of Element Rev. 1 05-17-07 Re-Numbered Element From D302001 to D3025 DOS Rev. 2 Rev. 3 Rev. 4 Rev. 5 Included sustainability requirements throughout document based upon TGCE's evaluation. (Paragraphs 1.01 C; 1.01 D; 1.01 E; 2.01J; 2.01 S; 2.01 T & 3.01B) JCD END OF ELEMENT D3025 ODG120908 6 OF 6