R&D ON HEAT PUMPS WITH NATURAL WORKING FLUIDS IN JAPAN

Similar documents
HFCs or the Old Refrigerants - what is the best Choice?

Alternatives in the AC & Chiller Sectors. Sukumar Devotta and Lambert Kuijpers OORG Refrigeration

Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Global Solutions for Ammonia Industrial Refrigeration

Development of CO2 Compressor and Its Application Systems

The Development of Heat Pump Water Heaters Using CO 2 Refrigerant

System Design, Commissioning, Operation

Current use of HFCs and HCFCs. Trends, alternatives and climate impact. YEREVAN, Armenia, May 18-19, International Institute of Refrigeration

Brazed Plate Heat Exchanger for CO Applications

Due to its low temperature glide about 1.5 approx. (75% less than R-407C and R-427A), it is suitable for a wide range of applications.

TYPICAL INITIAL OUTPUT OF A CO 2 HEAT PUMP

Main Anthropogenic Sources of Greenhouse Gases Refrigerants

REVERSIBLE R744 (CO 2 ) HEAT PUMPS APPLIED IN PUBLIC TRAINS

THE BIG FIVE NATURAL REFRIGERANTS IN DIFFERENT INDUSTRIAL APPLICATIONS. MAYEKAWA EUROPE S.A.,Leuvensesteenweg 605, 1930 Zaventem, Belgium

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

FACT SHEET 9 Large Air-Conditioning (air-to-air)

Japanese market and issue of Heat Pump Kenji Matsuda

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

A refrigeration system for supermarkets using natural refrigerant CO 2

Thermodynamics I. Refrigeration and Heat Pump Cycles

CO2 TRANSCRITICAL BOOSTER SYSTEMS

Environmentally friendly refrigeration systems for industrial use

This presentation is posted for public use. ACEEE does not endorse any product or service.

FACT SHEET 9 Large Air-Conditioning (air-to-air)

DEVELOPMENT AND EVALUATION OF HIGH PERFORMANCE, LOW GWP REFRIGERANTS FOR STATIONARY AC AND REFRIGERATION

Chapter 2. Alternatives to HCFCs and their Characteristics

RS-70 is suitable as a direct replacement for R-22 in low, medium and high temperatures in a great number of applications:

PHASE-IN of natural refrigerants. Prof. Dr. Armin Hafner NTNU Norway

Challenges and responses in refrigerant conversion

A Comparison Between Refrigerants Used In Air Conditioning

Transcritical CO2 Bottle Cooler Development

Daikin s Policy. and Comprehensive Actions on the Environmental Impact of

Actions to Control Emission of HFCs in Japan

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Transitioning to Alternatives and Challenges in Japan

HEAT PUMPS WITH HYDROCARBONS AS REFRIGERANTS FOR SMALL RESIDENTIAL BUILDINGS

Adsorption refrigeration system using waste heat

Refrigerants & Cooling in renovation buildings

Trends and Perspectives in Supermarket Refrigeration

Ammonia. Background on ammonia as a refrigerant

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

NATURAL REFRIGERANTS FOR HEAT PUMPS AND AIR-CONDITIONING SYSTEMS. Bernard Thonon Greth

CO 2. ECO Water Heaters. Energy efficient and environmentally friendly water and space heating. SANYO Air Conditioners. The natural choice.

IR-REVERSIBILITY ANALYSIS OF A SPLIT TYPE AIRCONDITIONER USING R600a AS REFRIGERANT

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

Industry co-operation on Natural Refrigerant technology development Kenji Matsuda

Mayekawa Mfg. Co., Ltd. Kuniaki Kawamura

Commercial CO 2 Refrigeration Systems

FACT SHEET 6 Transport Refrigeration

Current status of Japan s legislation on F-gases and RACHP using Low-GWP Refrigerants

Chapter 10. Refrigeration and Heat Pump Systems

Q. Which hydrocarbons can be used as a refrigerant? The following hydrocarbons can be used as a refrigerant in cooling & heating applications:

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% 23rd World Gas Conference, Amsterdam Main Author. Atsuya Tajima Japan

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Sub-Critical Operation of the CO2 Expander/ Compressor

Development of Environmentally Benign Heat Pump Water Heaters for the US Market

DEEPAK PALIWAL, S.P.S.RAJPUT

Description of the European standard EN 378: Refrigerating systems and heat pumps Safety and environmental requirements

we will examine only the vapour compression systems transfers to the Carnot cycle can serve as the initial model of the ideal refrigeration cycle.

Industrial Heat Pumps and Their Application Examples in Japan

Thermodynamics II Chapter 5 Refrigeration

Ammonia Refrigeration & Scenario in Industrial Refrigeration. By Ramesh Paranjpey ASHRAE Fellow Life member

THE INSTITUTE OF REFRIGERATION

Transitioning to Alternatives and Challenges in Japan

HYDROCARBONS, HEAT PUMP, HOME LAUNDRY DRYER: ENVIRONMENT FRIENDLY APPLIANCE

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Assuring Reliability of Compressors Using HFC Refrigerants By Hideto NAKAO Mitsubishi Electric Corporation Amagasaki-City, Hyogo, Japan

Rotary type Oil-free Air Compressor General Catalogue. Oil-free Scroll Air Compressor Oil-free Claw Air Compressor

The lowest energy consumption when using R290 LBP fixed speed compressors in a plug in ice cream conservator

Performance of CO2 Cycles with a Two-Stage Compressor

Natural refrigerant trends in EU, Japan & North America

Member Briefing JAPAN

Homework Chapter2. Homework Chapter3

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA

NEW COPPER-BASED HEAT EXCHANGERS FOR R744 REFRIGERANT PART II: SYSTEM DESIGN AND CASE STUDIES

Commercial CO2 Refrigeration Systems. Guide for Subcritical and Transcritical CO2 Applications

"ETI-Z, GART-ZE/ZEI" Centrifugal Chillers using Low-GWP Refrigerants for Full Capacity Range

CHAPTER 1 INTRODUCTION

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

Variable refrigerant flow (VRF) systems

Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

High Efficiency Technologies for Small and Medium-Sized Air Conditioning Equipment Using R410A. Hitachi Appliances, Inc.

COMMERCIAL CO 2 HOT WATER HEAT PUMP FIELD TRIALS

Safety concerns for A2L refrigerants in AC service procedures

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

Compressor Explosion Accident at Pump-Down of Air Conditioners

The 10 th Three Associations Meeting JRAIA. The Japan Refrigeration and Air Conditioning Industry Association. August 31, 2016.

Centrifugal Chiller. GFG-S/SIT Series GXG-S/SIT Series GSG-S/SIT Series

DAIKIN Modular Inverter Air Cooled Chiller

PERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION

REFRIGERATION AND AIR CONDITIONING

Summary of Research Activities. Eckhard A. Groll Professor of Mechanical Engineering

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Transcription:

R&D ON HEAT PUMPS WITH NATURAL WORKING FLUIDS IN JAPAN E. Hihara, Professor, Institute of Environmental Studies, The University of Tokyo, 7-3-1 Hongo, Bunkyo-ku, Tokyo, Japan The conventional refrigerant R22 has been replaced by hydro-fluorocarbons, and the recovery and destruction system for fluorocarbons began operation in Japan. However, for future global warming prevention, it is said that conversion to natural working fluids will be required. In this paper, the overview of the research on the heat pumps using the natural working fluids in Japan is summarized. The carbon dioxide systems for mobile air conditioners and water heaters are actively researched. The heat pump water heaters operated in midnight were put on the market, and the spread is expected. Hydrocarbon heat pumps for air conditioning are not on the market from a viewpoint of safety. Only a small amount of refrigerators operated with isobutene is sold in Japan. Although the ammonia refrigerators are the ripened and reliable technology, the law requires expensive safety facilities, and therefore they are only used for the low-temperature warehouse or for the industrial use. 1. INTRODUCTION The energy consumption in the commercial and residential sector in Japan occupies 26% of the whole, and the growth is as large as the transportation sector. Figure 1 shows the transition of final energy consumption of each sector, in which final energy consumption in 1990 is set to 100. According to these consumption statistics, both the household use and the business use in the commercial and residential sector show growth higher than a whole average. About 40% of the cause of the growth of the household use is the increase in the number of households, about 30% is the increase in the power consumption of electric products, and about 30% is increase of the energy consumption for air conditioning. About 80% of the cause of the growth of the business use is increase of the floor area of business-use buildings, and the remainder is increase of the power consumption by the increase in information machineries and equipment. Since about 30% of energy consumption of the business use is used for air conditionings, the increase 160 140 120 100 80 60 40 20 Industrial Sector Household Use Business Use Passenger cars for private use Transportation Sector Total 0 1990 1991 1992 1993 1994 1995 1996 1997 1998 1999 Year Fig.1 Changes in final energy consumption by demanding sector in Japan 272

of floor area results in the increasing energy consumption. Since we pursue a continued comfortable life, the energy consumption is continuously growing, and huge amount of energy is spent on the air conditioning. For global warming prevention, the Law Concerning Rational Use of Energy calls for energy conservation of home electronics in Japan. The energy-conservation standards of the air conditioners for both heating and cooling purposes by the revised Law Concerning Rational Use of Energy enforced in 1999 are shown in Table 1 (ECCJ 1999). The air temperature conditions in the performance test are the standard cooling conditions and the standard heating conditions specified in the Japanese Industrial Standard B8616 or C9612, as shown in Table 2. The arithmetic average of the COPs by the both tests is asked to exceed the values in Table 1. The COP target values of business-use air-conditioners are fairly lower than those of residential air-conditioners. When this energy-conservation standard was established, the business-use air-conditioners had the low concern about energy saving compared with the home air-conditioners, and the inverter was not introduced. The business-use air-conditioners with which average COP exceeds 4 are put on the market now, and the consumer's concern about energy conservation is increasing. Type of air conditioner Non-ducted and window-mounted type Non-ducted and wall-mounted type Non-ducted types other than the above Ducted type air conditioners Multi-type air conditioners that separately control the operation of indoor units Table 1 Standard energy consumption efficiency. Cooling capacity More than 2.5 More than 3.2 More than 4.0 2.5 kilowatts but kilowatts but kilowatts but kilowatts 3.2 kilowatts 4.0 kilowatts 7.1 kilowatts or less or less or less or less 2.85 More than 7.1 kilowatts 5.27 4.90 3.65 3.17 3.10 3.96 3.96 3.20 3.12 3.06 3.02 3.02 3.02 4.12 3.23 3.07 Table 2 Standard air temperature conditions specified in JIS C9612 and B8616. Indoor air Outdoor air Test Dry bulb temperature Wet bulb temperature Dry bulb temperature Wet bulb temperature Standard cooling test 27 C 19 C 35 C 24 C Standard heating test 20 C - 7 C 6 C For another measure of global warming prevention, a duty of the refrigerant recovery at the time of air-conditioner abandonment was imposed in Japan. As for the refrigerant used for the business-use air-conditioners and the automobile air-conditioners, a duty of recovery and destruction was imposed by the fluorocarbon recovery and destroying law from 2002. As for the refrigerant used for the residential air-conditioners, the similar duty was imposed by the law requiring the recycling of home appliances from 2001. Although the air-conditioner 273

manufacturers are making the system for collecting fluorocarbons and not revealing to the atmosphere, it is not easy for them to recover completely. Since the possibilities of HFC refrigerants are indefinite, the concern about natural working fluids is increasing. Although the conventional refrigerant R22 has been replaced by the HFC refrigerant, the expectation for natural working fluids is growing especially in European countries. When the refrigerant recovery at the time of abandonment does not progress in Japan, introduction of natural working fluids may have to be considered. An advantage of natural working fluids is their low GWP. However, if the COP of the heat pump using a natural working fluid is remarkably inferior compared with the conventional refrigerants, such as R22, the carbon dioxide emissions accompanying the power consumption under operation will increase. It is necessary to secure the reservation of safety and the high COP in using a natural working fluid. In this paper, the outline of the natural working fluids research in Japan is introduced. Table 3 summarizes the current status of each natural working fluid. Carbon dioxide Neither toxic nor flammable Negligible pressure drop Suitable for temp. booster Propane Isobutene Table 3 Summary of natural working fluids Advantages Faults Application Low COP Water heater High pressure (10MPa) Mobile A/C Mineral oil can be used. COP is similar to R22. Ammonia COP is higher than R22. High heat transmission High latent heat Water Neither toxic nor flammable High COP Vacuum operation Flammable International standards are required. Toxic and flammable Copper material cannot be used. Safety facility is expensive. Large compressor High pressure ratio High initial cost Cold district heating Refrigerator Vending machine Commercial refrigerator Chillers for industrial use Chiller for industrial use Ice-maker Air Neither toxic nor flammable Low COP in A/C use Low-temperature warehouse 2. CARBON DIOXIDE Since carbon dioxide does not have toxicity or inflammability, it has been developed as a working fluid for automobile air-conditioners. The major manufacturer of automobile air-conditioners Denso Corporation and Mitsubishi Heavy Industries independently developed scroll type compressors. Since a difference between high-pressure and low-pressure of carbon dioxide cycle is large, loss by leak is large and big thrust load acts on a thrust bearing. Mitsubishi Heavy Industries developed a new bearing in which the thrust load is reduced by adding high-pressure oil from the back. The compressor efficiency is shown in Fig. 2 (Hirao et al. 2000). The research on the heat pump water heater operated with carbon dioxide progressed, and three manufacturers had put residential systems on the market in 2002. Figure 3 shows an advantage of CO 2 for heat pump water heaters using a temperature-entropy chart. The critical temperature of CO 2 is 31.1 C, and thus the cooling process is in the supercritical state. The cooling device is called a gas cooler instead of a condenser, because no phase change occurs in the gas cooler. The fluid temperature in the gas cooler becomes low even if the pressure is kept 274

Adiabatic efficiency 100 90 80 scroll measurement Scroll analysis Wobble analysis 70 60 50 0 1000 2000 3000 4000 Compressor speed (1/min) Fig.2 Efficiency of prototype CO 2 scroll compressor by Mitsubishi Heavy Industries. constant. Therefore, by using a countercurrent gas cooler, irreversible loss in the gas cooler can be reduced. Average COP of the products is 3.0. These heat pump water heaters have less energy consumption and less carbon dioxide emissions than a conventional gas combustion water heater. The heat pump water heater makes hot water using cheap midnight electric power, stores hot water in a tank, and hot water is used in the daytime. In order to proliferate and to promote high-efficiency hot water systems, the government assists a part of installation expense of this system, and therefore it is very economical. Table 4 shows the summary of the developed CO 2 compressors. Figure 4 shows the performance of Denso s compressor, where the COP for heating is the ratio of heat rejection at the gas cooler to the compression work (Saikawa et al. 2000). Figure 5 shows the comparison between single-stage compression and two-stage compression by Sanyo Electric (Sato et al. 2002). The COPs are normalized by the value at 80Hz of compressor speed for single-stage compression. For two-stage compression the compression ratio at each stage is so small that the leakage from the compression parts is also small. Resultantly the COP of two-stage compression is higher than that of single-stage compression especially in low compressor speed region. Table 5 summarizes the specification of the Daikin Industries heat Tap water 3 4 Gas cooler Throttle Evaporator Ambient air Hot water 2 Compressor 1 2 9MPa 3.5MPa 3 4 Heat-sink Heat-source 1 Fig.3 An advantage of CO 2 for heat pump water heater. 275

COP for heating COP ratio 4.5 4 3.5 3 2.5 1.2 1.1 1 0.9 single-stage compression two-stage compression 2 2000 3000 4000 5000 6000 7000 Compressor speed (1/min) Fig. 4 Efficiency of CO 2 compressor by Denso Corporation. Suction and discharge pressures are 9.8 and 3.9MPa, respectively. Superheating is 10 C. pump water heater (Daikin 2002). 0.8 50 60 70 80 90 100 110 Compressor speed (1/s) Fig. 5 Efficiency of CO 2 compressor by Sanyo Electric. Suction and discharge pressures are 9 and 3MPa, respectively. Suction gas temperature is 35 C. Table 4 Specifications of CO 2 compressors for water heater. Manufacturer Denso Corporation Sanyo Electric Daikin Industries Type of compressor Scroll type Two-stage rolling piston type Single-stage swing type Motor type DC motor-inverter DC motor-inverter DC motor-inverter Size 137 x 285 118 x 217 126 x 265 Swept volume (cm 3 ) 3.3 2.89 3.4 Table 5 Specifications of Daikin Industries heat pump water heater Rated heating capacity 4.5kW Power consumption 1.21kW COP at standard condition (*) 3.72 Sound in operation 45dB Water tank capacity 370L or 300L Hot-water temperature in tank 65 ~ 90 C Hot-water supply temperature 36 ~ 48 C Range of ambient temperature -10 ~ 43 C (*)Ambient temperature: 16 CDB/12 CWB, tap water temperature: 17 C, hot water temperature: 65 C Fig. 6 Daikin Industries heat pump water heater 3. HYDROCARBONS It is very hard to use hydrocarbons as a working fluid for air-conditioners due to its inflammability. Although isobutene operated refrigerators are widely used in Northern Europe and Germany, they were not sold in Japan until last year. Of course, some Japanese 276

manufactures were exporting the HC compressors to Europe. Last year the Japan Electrical Manufacturers' Association (JEMA) decided upon an independent standard for HC refrigerators in Japan. This standard was not attested by the governmental institute, but the guideline for the production of HC refrigerators was given. Taking the feature of Japanese refrigerators and living situation into account, JEMA proposed the standard, which was a little different from the IEC standard for flammable refrigerant (IEC335-2-24). (1) The object of this standard is limited to the refrigerator below 800 liters of the rated internal volume. (2) The amounts of filling refrigerant for forced convection type refrigerators must be less than 100g, while that for natural convection type refrigerators must be less than 150g. The forced convection type refrigerators, in which cold air is circulated by a fan, are in use in Japan. (3) The restriction of the electric heater for defrosters is added. (4) The cooling piping in a warehouse must be dual structure. Electrical appliances must have explosion-proof construction. From the beginning of 2002 Matsushita Electric Industrial and Toshiba started to sell HC refrigerators in Japan. HC refrigerators will gain a certain amount of market share in the near future. Introduction of ice thermal storage equipment is progressing for electric power load equalization in Japan. Zeneral Heatpump Industry and Chubu Electric Power jointly developed a heat pump chiller, which used propane as a working fluid in 1999 (Shiba and Atsumi 2002). This machine has the following functions; generation of the hot water and cold water for air-conditioning, generation of the ice which uses cheap electric power at midnight, and the hot-water supply. By performing simultaneously ice thermal storage operation and hot-water supply operation, it is designed in the summer to perform the efficient exhaust heat recovery operation. In order to minimize the leakage of the refrigerant to the air at the accident, the refrigerant system is divided into several suitable units. The specification of the minimum unit is summarized in Table 6. Table 6 Specifications of the minimum unit of ice thermal storage heat pump chiller. Cooling capacity 17.3kW Refrigerant Propane Ice storage capacity 13.4kW Filling refrigerant 5kg Heating capacity 19.7kW Size of chiller 1.7x0.8x1.8m Hot water capacity 17.3kW Size of ice storage tank 2.0x2.5x1.5m Type of compressor Semi-hermetic reciprocating Output power of compressor 5.5kW 4. AMMONIA Since utilization of ammonia is the ripened technology, there is no serious technical problem for spread. The efficiency of refrigeration equipment using a secondary coolant is equal to or higher than fluorocarbon equipments. But safety facilities are required and make it high cost due to its inflammability and toxicity. The followings are the research items for further spread. (1) Curtailment of the amount of filled refrigerant By using soluble lubricant PAG, small tube piping, and heat transfer enhancement, the size of heat exchangers can be made small. Brazed plate heat exchangers are used abundantly. (2) Curtailment of the leakage 277

Development of hermetic compressors is one of the most important technologies to prevent ammonia from revealing. Since copper cannot coexist with ammonia, in order to make a hermetic compressor, a canned motor has been used. But the efficiency of canned motor is low. Currently a canless motor, in which aluminum wire is used, is developed. Maekawa Mfg. is a leading company of production of compressors for ammonia in the world. Maekawa Mfg. newly developed a high-efficiency semi-hermetic canless screw compressor for ammonia refrigerant (Maekawa 2000). Aluminum is used for wire in motor, and Teflon is used as material for insulator. It is reported that the efficiency of canless motor is 92%, which is similar to an open type motor, and is higher than a canned motor by about 7%. Figure 8 compares the performance of ammonia refrigerator with that of R22. The vertical axis is the ratio of the COP of ammonia refrigerator to that of R22. In high and medium temperature region the COP of ammonia system is higher than that of R22 by about 10%. Fig. 7 Semi-hermetic canless screw compressor for ammonia by Maekawa Mfg. 1.2 1.1 Single-stage compression Double-stage compression 1 0.9 0.8-30 -25-20 -15-10 -5 0 5 Evaporating temperature (C) Fig. 8 Comparison of the refrigerator performance between ammonia and R22. 278

5. CONCLUSION An overview of research and development of heat pumps for natural working fluids in Japan is given. There are many compressor suppliers in Japan. Development of compressors for natural working fluids is actively undertaken. In the future, when the use of HFC refrigerant will be regulated, the role of Japanese companies will become more important. REFERENCES Daikin Industries Catalog, 2002. ECCJ 1999. http://www.eccj.or.jp/law/e_machine/aircon.html. Hirao T., Mizukami H., Takeuchi M., Taniguchi M., 2000. Development of air conditioning system using CO 2 for automobile, Proc. 4 th IIR Gustav Lorentzen Conference on Natural Working Fluid at Purdue, pp. 193-200. Maekawa Mfg. 2000. http://www.mycomj.co.jp/eindex/can.html. Saikawa M., Hashimoto K., Kobayakawa T., Kusakari K., Ito M., Sakakibara H., 2000. Development of prototype of CO 2 heat pump water heater for residential use, Proc. 4 th IIR Gustav Lorentzen Conference on Natural Working Fluid at Purdue, pp. 51-57. Sato K., Matsumoto K., Yamasaki H., 2002. The development of carbon dioxide hermetic compressor for heat pump water heater systems, Refrigeration, Vol. 77, No. 893, pp. 193-197. Shiba Y., Atsumi T., 2002. A heat pump chiller using propane as refrigerant applicable to the ice storage system, Refrigeration, Vol. 77, No. 893, pp. 221-225. 279