Classification Report BASEC Client Report No. Hubbell Inc. (Delaware) L1CPRT801-1 Classification Number of pages in this Report: 6 Issue Date 3 January 2018 Items Tested 1 sample of Copper Communication Cable Specification(s) BS EN 13501-6:2014 Authorised by: Issue Date: I McGuinness 3 January 2018 Laboratory Manager This Classification Report does not represent type approval or certification of the product. This Classification Report shall not be reproduced except in full, without written approval of the laboratory. British Approvals Service for Cables Presley House Presley Way Crownhill Milton Keynes MK8 0ES UK T: 01908 267300 F: 01908 267255 Notified Body No. 2661 E: mail@basec.org.uk W: www.basec.org.uk
Introduction This classification report defines the classification assigned to the product, Copper Communication Cable, in accordance with the procedures given in BS EN 13501-6:2014 CLASSIFICATION OF REACTION TO FIRE FOR ELECTRIC CABLES IN ACCORDANCE WITH BS EN 13501-6:2014 Sponsor: Hubbell Inc. (Delaware) Prepared for: Hubbell Inc. (Delaware), Premise Wiring Division, Suite 103, 23 Clara Drive, Mystic, CT 06355, USA Prepared by: British Approvals Service for Cables, Presley House, Presley Way, Crownhill Milton Keynes, MK8 0ES, United Kingdom Notified Body No. 2661 Cable Family Name: U/UTP Cat 6 24AWG LSZH Classification Report No. L1CPRT801-1 Classification Issue number: 1 Date of issue: 3 January 2018 This classification report consists of 6 pages and may only be used or reproduced in its entirety. Report Issue Date: 03/01/2018 Page 2 of 6
Details of classified product General The product U/UTP Cat 6 24AWG LSZH is classified in accordance with the procedures given in BS EN 13501-6:2014 and is defined as a copper communication cable according to BS EN 50575:2014+A1:2016. Product description The copper communication cable U/UTP Cat 6 24AWG LSZH is as described in the Sample details below. Traceability The test sample was selected by UL on behalf of BASEC and received on 14 April 2107 Sample details Parameter Test sponsor Contact address Details Hubbell Inc. (Delaware) Premise Wiring Division, Suite 103, 23 Clara Drive, Mystic, CT 06355, USA Cables submitted for test U/UTP Cat 6 24AWG LSZH (Sample 62) Trade Name 4 pair 24AWG U/UTP cable. Class 1 (solid) copper conductors, HD-PE insulation, NHFR filler, NHFR jacket OD = 6.0mm SPEEDCHANNEL 4 PR/24AWG LSZH Category 6 U/UTP Cable Report Issue Date: 03/01/2018 Page 3 of 6
Reports & results in support of this classification Reports Name of Laboratory Name of test sponsor Test reports Nos. Test method/field of application rules BS EN 50399:2011+A1:2016 BASEC Hubbell Inc. (Delaware) L1CPRT773 BS EN 60332-1-2:2004+A11:2016 BS EN 61034-2:2005+A1:2013 L1CPRT773a BS EN 60754-2:2014 Results Test method Parameter No. tests runs Continuous parameter Results Compliance parameters FS 1.09m 1.5m = B2ca compliant THR1200s 4.6MJ 15MJ = B2ca compliant 1 Peak HRR 15.5kW 30kW = B2ca compliant BS EN 50399:2011 +A1:2016 FIGRA 104.9W/s 150W/s = B2ca compliant TSP1200s 15.9m 2 50m 2 = s1 compliant 1 Peak SPR 0.06m 2 /s 0.25m 2 /s = s1 compliant Flaming droplets/particles 1 <10s Flaming <10s = d1 compliant BS EN 60332-1-2:2004 +A11:2016 BS EN 61034-2005 +A1:2013 H 1 82mm 425mm = Eca compliant Minimum transmission 1 80.8% 80% = s1a compliant BS EN 60754-2:2014 ph/conductivity 3 ph = 5.2*, conductivity = 0µS/mm* ph > 4.3 + conductivity <2.5µS/mm = a1 compliant * The least best result for all components tested Report Issue Date: 03/01/2018 Page 4 of 6
Classification and field of application Reference of classification This classification has been carried out in accordance with BS EN 13501-6:2014 Classification The communication cable in relation to reaction to fire behaviour is classified: B2 ca The additional classification in relation to smoke production is: The additional classification in relation to flaming droplets / particles is: s1a The additional classification in relation to acidity is: d1 The format of the reaction to fire classification for electric cables is: a1 Fire Behaviour Smoke Production Flaming Droplets Acidity B2 ca - s 1a, d 1, a 1 Reaction to fire classification: B2 ca -s1a,d1,a1 The classification assigned to the products in this report is appropriate to a declaration of conformity by the manufacturer within the context of system 1+ attestation of conformity and CE marking under the Construction Products Regulation. Report Issue Date: 03/01/2018 Page 5 of 6
Field of application This classification is valid for the copper communication cables described in Sample details and listed below: Brand Name Cable Identification Product Code Hubbell Inc (Delaware) U/UTP Cat 6 24AWG LSZH C6SCBZFRB22cc SPEEDCHANNEL 4 PR/24AWG, LSZH, Category 6 U/UTP Cable Reaction to Fire Classification B2 ca-s1a,d1,a1 This classification is valid for all end-use applications. Limitations This classification will be valid whilst; The test methods remain unchanged, The product standard or technical approval remains unchanged, Constructional or material modifications do not exceed limits of the field of application. The manufacturer has made a declaration, which is held on file, that the product placed in the marketplace, named in the product description section of this report and produced at the manufacturing plant listed therein, is exactly the same as the product that was tested. This classification document does not represent type approval or certification of the product. - - END OF REPORT - - - Report Issue Date: 03/01/2018 Page 6 of 6