Ventilation Planning for Mid-sized Japanese Commercial Kitchens and Calculation Method of Ventilation Rate Using Building Information Modeling

Similar documents
ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

AMOUNT OF MOISTURE PRODUCTION AND FIELD MEASUREMENT IN DRESSING ROOM

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

for commercial kitchen ventilation

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Passivhaus school kitchens

System Using Exhaust Heat from Residential GHPs

EFFECT OF PAG OIL CIRCULATION RATE ON THE HEAT TRANSFER PERFORMANCE OF AIR-COOLED HEAT EXCHANGER IN CARBON DIOXIDE HEAT PUMP SYSTEM

Energy-Saving Technology for Multi Split-Type Air-Conditioning Systems for Buildings

House Efficiency Survey Report

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

High-Temperature Cooling & Low-Temperature Heating AC System Evaluation of energy saving in an office in Tokyo

Commercial Kitchen Exhaust Requirements Kitchen Exhaust for Food Service Operations

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Model Change. models in total. General commercial kitchen Appliances & Equipment. August 2016 Edition

Itaru TAKAHASHI Ph.D 1 Akihiko KUROIWA 2

Mobile Vendors Bulletin

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

Top Runner Program IEA-4E

Webscraped Prices Comparison Method adopted for the PPI in Japan

Notable Changes in the Mechanical Codes

Study on water conservation by water saving fixtures

Comparative Study of Technological Trend between DAIKIN and Panasonic in the Field of Air Conditioner

MECHANICAL EXHAUST VENTILATION SYSTEMS OPERATIONAL GUIDELINES-REVISED 2003

ICE THERMAL STORAGE SYSTEM USING DYNAMIC ICE IN HERBIS OSAKA PHASE I AND II PROJECTS

MSYS 4490 AC Systems

LABEL PLEASE NOTE: ALL APPLICATIONS AND SITE PLANS MUST BE COMPLETED IN BLACK OR BLUE INK ONLY

REQUIREMENTS FOR HOOD PLANS

The mid-term Conference of IRE and NILIM Joint Research HELD IN TSUKUBA, JAPAN 3 rd October to 5 th October, 2017

Nest Learning Thermostat Summer 2012 Savings

Gas Range. New Power Cook. Power Cook. Deluxe. Standard. Outer Piping Soup Range Cool Kitchen Low Range

Importance of Alarm Management for Preventing Accidents which Lead to Environmental Pollution

K.F. Fong *, C.K. Lee, T.T. Chow

An experimental study of the impact of tunnel suppression on tunnel ventilation

Effective ventilation is necessary for the comfort

Development of Induction Heating Device for Corner of Bloom in Continuous Casting machine

Basic Hood Considerations The design process for a successful kitchen ventilation system starts when the engineering design HVAC team receives

PREDICTION OF THE ENERGY DEMAND IN THE JAPANESE RESIDENTIAL SECTOR IN 2030 BY RESIDENTIAL ENERGY END-USE MODEL

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

RESULTS FROM HOUSE APPLIANCE SAFETY AND DEPRESSURIZATION TESTS CONDUCTED ON SINGLE FAMILY HOUSES UNDERGOING SOUND INSULATION

Evaluation of Liquid Water Content in Thermal Efficient Heating Mechanism Using Water Vapor for Industrial Furnace

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2005

Feasibility study of the passive solar room dehumidifying system using the sorption property of a wooden attic space through field measurement

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

DEVELOPMENT OF A KILN DRIED WOOD SYSTEM USING HEAT PUMP TECHNOLOGY

Effectiveness of displaying energy consumption data in residential houses Analysis on how the residents respond

Institutions NUMBER: Food Service Safety And Sanitation

PERFORMANCE ANALYSIS OF GROUND SOURCE HEAT PUMPS FOR DOMESTIC HOT WATER SUPPLY IN THE LOW ENERGY HOUSE AND ITS APPLICATION

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

Compressor Explosion Accident at Pump-Down of Air Conditioners

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

HYBRID GAS HEAT PUMP WATER HEATER WITH THERMAL EFFICIENCY 120% 23rd World Gas Conference, Amsterdam Main Author. Atsuya Tajima Japan

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

The (Hot) Water Efficient Commercial Kitchen. Charles M. Bohlig East Bay Municipal Utility District

CONTROLLED GOODS AND THE APPLICABLE SAFETY STANDARDS PART I DOMESTIC OR HOUSEHOLD APPLIANCES AND SIMILAR ELECTRICAL APPLIANCES

Annual environmental performance evaluation of light and heat in daylight harvesting systems using Radiance and NewHASP

Development of Gas-Liquid Two-Phase Flow Distributor for Improving Energy Efficiency in Air-Conditioners

Industrial Heat Pumps and Their Application Examples in Japan

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

You will investigate the electrical consumption in your home over the course of TWO days (48 hour period).

Optimisation of cooling coil performance during operation stage for improved humidity control

FOOD SERVICE EQUIPMENT REBATES

Performance of an Improved Household Refrigerator/Freezer

SMART METERS ANSWER BOOK HOW YOU WHY ONTARIO WHAT ARE GETTING SMART ABOUT CAN START TO PREPARE NOW PAGE 6 TIME-OF-USE PRICES? PAGE 4 IS INTRODUCING

Innovative Energy Saving Proposal

General commercial kitchen Appliances & Equipment January 2018 Edition

Types of Detection. Fusible Link Detection - Most Common

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

User Manual PKPRC16. NutrichefKitchen.com

AN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

Residential Building Walls and Environment in Amman, Jordan

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

Experimental investigation of Hybrid Nanofluid on wickless heat pipe heat exchanger thermal performance

Survey on Cooling Costs and Related Factors for Apartments in an Urban. Area of Osaka

EcoCute. EcoCute 1. Product Outline. CO2 Heat pump water heater for commercial use

Lombard Fire Department Bureau of Fire Prevention COMMERCIAL HOOD & DUCT SYSTEMS

An Evaluation of Land Use Control in Hokkaido, Japan Kayoko Yamamoto

Development of Seismic-induced Fire Risk Assessment Method for a Building

Variable Ventilation for the Kitchen:

Specific Energy Consumption comparative study of Hot Air dryer and Heat Pump dryer for highland drying process Sayompon Srina

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

CITY OF BARTOW (COB)

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Efficiency of Application the Condensing Heat Utilizers in the Existing Boiler's Unit in Heat Power Station

Demand-Controlled Ventilation for Commercial Kitchen Ventilation

Hot Water Making Potential Using of a Conventional Air- Conditioner as an Air-Water Heat Pump

Leakage of Mildly Flammable Refrigerants into a Room

Home Fires Involving Heating Equipment

Museum Archive Dehumidification in Hot & Humid Climates

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

Transcription:

Ventilation Planning for Mid-sized Japanese Commercial Kitchens and Calculation Method of Ventilation Rate Using Building Information Modeling Osamu Nagase *, 1, 2, Yasushi Kondo 2, Hajime Yoshino 3, 2, Miwako Fujita, and Shunsuke Ogita 5 1 NIKKEN SEKKEI LTD 2-18-3 Iidabashi, Chiyoda-ku Tokyo, Japan nagaseo@nikken.jp 3 Nippon Institute of Technology -1 Miyanomi-cho, Minami Saitama-gun Saitama, Japan 2 Tokyo City University 1-28-1 Tamazutsumi, Setagaya-ku Tokyo, Japan Chubu Electric Power Company 1 Higashi-shincho, Higashi-ku, Aichi, Japan 5 TONETS CORPORATION 2-5-12 Kyobashi, Chuo-ku Tokyo, Japan ABSTRACT In the design of a commercial kitchen ventilation system, it is very important to maintain the capture efficiency of exhaust hoods and ensure smooth removal of heat, moisture, and odor. The capture efficiency is affected by the kitchen ventilation system and the cooking appliance usage condition. To identify an appropriate ventilation system design method for commercial kitchens in Japan, surveys were conducted as follows. The first survey was conducted on kitchen hoods, cooking appliances, and air supply openings in 35 midsized commercial electrical kitchens in Japan. In this survey, design drawings were collected, and field inspections were conducted. It is important to know the usage conditions and load factors of cooking appliances, which influence the capture efficiency. Therefore, the second survey was conducted to determine how cooking appliances were used. The load factors were studied based on the electricity consumption data of various cooking appliances used in ten mid-sized commercial kitchens in Japan. The design load factors are utilized to determine the conditions of the standard test method for the capture efficiency of exhaust hood and are the basic data for calculate cooling loads in kitchens. The proposed design method using the load factor can be referred to as smart kitchen ventilation. This study also demonstrates the application of Building Information Modeling (hereafter BIM) technology in commercial kitchens. Information on the cooking appliance and exhaust hood included in the BIM can be used to calculate the ventilation rate. This method can improve the design efficiency and reduce human error. The ventilation designer can compare the ventilation rate of several design methods, such as the conventional and proposed methods. In this study, an example procedure for ventilation rate calculation with BIM is demonstrated. Further, the scope for futures studies are discussed. KEYWORDS Electrical Commercial Kitchen, Actual Survey, Electricity Consumption, Design Load Factor, BIM 1 INTRODUCTION In commercial kitchens, a large amount of heat, water vapor, and oil mist are generated because of the cooking operation. The energy consumed in ventilation/air conditioning to remove them is very large [Kondo, Y. et al. 1]. It is very important to improve the capture efficiency of the exhaust hoods to maintain a healthy work environment for the kitchen staff. 19 P a g e

In Japan, the ventilation standard [MLIT, 215] of commercial kitchens has been based on the average velocity of the exhaust hood. While the standard is very simple, it may cause the overestimation of the ventilation rate. However, the circumstances of commercial kitchens have changed, such as diversification of cooking equipment and ventilation/air-conditioning systems. For these reasons, it is desirable to establish a standard test method for hood capture efficiency that reflects the actual condition of commercial kitchens. Ventilation/air conditioning systems should be designed based on these data. In this research, a ground situation survey was conducted to obtain basic data for appropriate conditions to be used in the standard test method of hood capture efficiency [JTCCM, 215]. The hood capture efficiencies determined using the standard test method can be used to realize healthy and comfortable work conditions with moderate ventilation rate. It is a smart ventilation method that considers the actual condition of the cooking operation and the HVAC system. In addition, the ventilation rate calculation tool using BIM can improve the design efficiency and reduce human error. 2 SURVEY METHOD 2.1 Ventilation system Survey items regarding kitchen specifications are shown in Table 1. A mid-sized kitchen of the company cafeteria was surveyed, in which to 8 meals are served during one mealtime. When sufficient design data could not be obtained, pictures of the air supply opening and the air conditioner were collected to understand the situation inside the kitchen. Figure 1 shows the location of 35 commercial electric kitchens in Japan. Table 1: Survey item of ventilation system (Survey period.11 213.2) Item Sub Item Contents Kitchen size Exhaust Hood Ceiling Air supply Floor space Ceiling height Size Type Overhang Heating equipment Type Installation position Number/Air volume Type Outside air Installation position Number/Air volume Cooking area Ceiling height Width, depth, height Island, wall-mounted Width, depth 2.2 Load factor of cooking appliances Cooking appliance type and arrangement VHS, BL, etc. Plan/elevation position Number of outlets, air volume PK, VHS, ceiling PAC, etc. Air conditioning Plan/elevation position Number of air inlets, air volume 2 15 2 1 Figure 1: Survey location 1 6 The load factor of various cooking appliances was surveyed in ten mid-sized commercial electric kitchens. Table 2 shows the outline of the surveyed kitchens. The measurement in winter was conducted for two weeks, while the power consumption data of the watthour meter installed in the appliances for ten days was examined. The electric power was measured at intervals of one second, and the average value for one minute was recorded. 11 P a g e

Table 2: Outlines of ten kitchens for the load factor study (Survey period.11 213.2) Kitchen A B C D E F G H I J Aichi Aichi Aichi Aichi Osaka Okinawa 73 72 135 96 88 9 2. 19 8: 1: 11/ 11/26 2. 8: 15: 213 1/9 1/2 11 2. 18 8: 1:3 11/28 12/ 2.3 3 6:3 1:3 12/13 12/27 2.5 13 6: 15: 11/5 11/16 2.6 15 15 6:3 15:3 12/13 12/27 5. kw(1) 12.3 kw(1) 16.2 kw(1) 26. kw(2) 8. kw(1) 5.3 kw(1) 21. kw(1) 13. kw(3) 5.5 kw(1) 12. kw(1) 18.5 kw(1) 3.6 kw(1) 11.9 kw(1) 12. kw(3) 23.2 kw() 15.3 kw(1) 15. kw(1). kw(2) 12. kw(1) 18.5 kw(1) 11.3 kw(1) 1.6 kw(2) 3. kw(2) 23.6 kw(3). kw(1) 2. kw(2) 5.9 kw(1) 11.3 kw(3) 12.8 kw(2) 3. kw(2) 2. kw(6). kw(2) Prefecture Hokkaido Kanagawa Toyama Shizuoka Floor space 129 163 113 72 [ ] 2. 2.3 3.6 2.6 Ceiling height [m] Design 6 8 25 Number of meals Operation 5 Operating time Cooking appliances (Total rated power [ Number]) Year Measurement Start End Number of operations Noodle boiler F l y e r Rice cooker IH cooktop Low range Tilting pan Steam convection Warmer table Dish washer Chinese range Soup kettle Griddle 7:3 16: 12/11 12/25 6:3 17: 12/5 12/18 2. kw(3) 15. kw(1) 32. kw(2) 16. kw(1).2 kw(1) 13. kw(1) 9.5 kw(1).5 kw(1).5 kw(1) 6. kw(1) 15. kw(1) 6: 1:3 11/19 12/7 1 6:3 1:3 2 12/6 12/28 15 18. kw(2) 23.1 kw(2) 6.1 kw(1) 12. kw(2) 7. kw(1) 6. kw(1) 15.3 kw(1) 3. kw(6) 26.6 kw(1) 8. kw(2). kw(1) 18. kw(2) 9. kw(1) 29. kw(2).3 kw(1).1 kw(1).5 kw(1) 1. kw(1) 8. kw(1) 9. kw(1) 18.5 kw(1) 9. kw(1) 3.1 kw(1) 9.3 kw(1) 6. kw(1). kw(1) 5. kw(1) 9.3 kw(1) 5.6 kw(1) 22.8 kw(1) 6.7 kw(1). kw(1) 12. kw(2) 11.7 kw(1). kw(1) The measurements were conducted during lunch time on weekdays. 3 SURVEY RESULTS OF THE VENTILATION SYSTEM 3.1 Kitchen Size Pretreatment 6 Special conditions do not count 2 2.2m未 満 2.3 2.3 2. 2.5 2.6 2.7 2.8 2.9 3. 3.m以 2. 2.5 2.6 2.7 2.8 2.9 3. 3.1 上 Ceiling height [m] Figure 2: Ceiling height of the kitchens 3.2 Cooking Washing Other average.2m2 15 5 1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35 average 2.5m 8 Floor area[m2] Number of kitchens The ceiling heights of the 35 kitchens are shown in Figure 2. These varied from 2. m to 2.5 m. The average height, without considering the uncommon height of over 3.1 m was 2.5 m. Figure 3 shows areas of preparation, cooking, pantry, washing, and others in the kitchen. The cooking area covers 56% of the entire kitchen. The preparation area and the washing area covers approximately 2% each. The floor area of the entire kitchen ranges from 5 m2 to m2, with an average value of.2 m2. Kitchen number Figure 3: Kitchen work area Overhang of Exhaust Hood The overhang size of exhaust hoods was calculated as shown in Figure (a). The average size of the overhang, excluding irregular, cases is shown in Figure (b). The mean size of the overhang for each cooking appliance ranges from 12 to 18 mm. However, in the survey carried out by ASHRAE [ASHRAE, 211] for U.S. kitchens, the overhang size was 23 to 6 mm, which is much larger than the results in Japan. 1111 P a g e

Number of kitchens Cooking appliances Exhaust hood Cooking appliance W/2 Cooking appliance Wall W/2 Cooking appliance D/2 D D [27%] [53%] [19%] [%] is the type ratio W Other Flyer Steam convection Tilting pan IH cooktop Rice cooker Noodle boiler Average depth :163mm Average width :12mm Depth Width 5 15 Overhang [ mm ] (a) Definitions of overhang size (b) Results of overhang size for appliances Figure : Survey of Overhang of Exhaust Hoods 3.3 Exhaust Air Volume Information on the exhaust air volume for the exhaust hood was obtained for 21 kitchens. Figure 5 shows the average velocity of exhaust hoods for each cooking appliance. The mean value of the average velocity of exhaust hood was.25 m/s. In many cases, the average velocity was within a range of.2 m/s to.3 m/s. Figure 6 shows the air change rate of 31 kitchens. The air change per hour was within the range of 3 to ACH for 26% of the kitchens. The average air volume of the ceiling exhaust was 16.3% of the total exhaust air volume. % 8% 6% % 2% % [m/sec]. -.5.1m/s 未満.1~.19m/s.3 -..2~.29m/s.2 -.3.3~.39m/s.1 -.2.~.9m/s. -.1.5m/s 以上 8 6 2 Other Washing 2 23 3 5 5 6 6 7 7 8 8 9 9 [Air change/ hour] Figure 5: Average Velocity of Exhaust Hood Figure 6: Air Change Rate of Kitchens 3. Type of Supply Opening and Supplied Air Temperature Figure 7 shows the type of supply openings. The universal type opening (hereafter VHS) was applied to 52% of the kitchens, while punker louver type (hereafter PK) was applied to 5% of kitchens. Packaged air conditioning mounted on the ceiling and PK are likely to cause air disturbance for the exhaust hood. They were installed in 22 kitchens, which is 63% of the whole. In 2 kitchens, which is approximately 6% of the whole, outside air was supplied without temperature control. This worsens the thermal condition. 1112 P a g e

Types of air supply Temperature controlled fresh air Outdoor air without temperature control Circulation of kitchen air Unknown 9% Other Supply and exhaust hood Nozzle Breeze line BL Punker louver PK VHS Ceiling hanging PAC 18% 12% 15% 5% "%" shown in the figure corresponds to 33 target kitchen 61% ratios 21% 5 15 2 Number of kitchens installed Figure 7: Type of Supply Openings SURVEY RESULTS OF LOAD FACTOR.1 Averaging Time for Load Factor Load factor [ ] The load factors with three averaging times, i.e., 1-min, 5-min, and -min are shown in Figure 8. The 1-min averaged load factor fluctuates greatly, making it difficult to determine the trend. Characteristics of the load factor can be determined when averaging is performed in 5 or minutes. However, as indicated by the dashed circle in Figure 8, when averaging in 5-min, the tendency slightly changes to show two peaks, while only one peak is observed when averaging in -min. The load factor should be averaged over a relatively short period of time. Therefore, 5-min is adopted as the averaging time for load factor in this paper. 1分間平均値 5分間平均値 分間平均値 75 Steam 5 Convection-1 Tilting pan 25 8: 9: : 11: 12: 7: 8: 9: : 11: 12: 7: 8: 9: : 11: 12: 7:Flyer-1 系列2 系列2 系列 系列 系列5 系列5 (a) 1- min average (b) 5-min average (c) -min average Figure 8: Load factors with three averaging times (Kitchen-B, 12/5).2 Deletion of Unnecessary Data The design load factor should cover the period when the required ventilation volume and air conditioning load are the maximum. The flyer and the warmer table consume most of the electricity at the beginning of the operation to heat oil and water to the target temperature. Although the load factor is high, the influence on thermal environment in the kitchen is low. Therefore, the time zone of the black portion shown in Figure 9 was deleted. 1113 P a g e

Number of cooking appliances (a) Flyer (Kitchen-B) (b) Steam convection oven (Kitchen-B) (c) Warmer table (Kitchen-A) Figure 9: Load factor of cooking appliances (vertical axis: load factor, horizontal axis: time).3 Peak Period of Operating Appliances Figure shows the result of the peak period during which the load factor of each cooking appliance in kitchens reaches its peak value. There are variations in the peak period of fryers, electrical induction cookers, steam convection oven, and low ranges because the food items differ depending on the daily menu. However, the peak period was between 8 and 11 am, when the cooks prepared to serve lunch. The peak period of the rice cooker was between 9 and 11 am, that of the warmer table was between 11 am and 12 noon, while the dishwasher s was at 12 noon. Figure : Time variation of number of operating appliances. Calculation Procedure of Design Load Factor The proposed design load factor calculation procedure is shown below. (1) The one-hour average load factor for each cooking appliance was calculated and the peak period of one hour was determined. However, the time zone at the beginning of the operation is excluded for flyers and warmer tables. (2) The five-minute average load factor was calculated during the peak period. (3) The percentile value for all the 5-min average load factor data was calculated. The design load factor can be selected from the 9 th percentile value, the 95 th percentile value, or the th percentile value. The above procedure describes the design load factor of the cooking appliance alone. However, the design load factor for exhaust hood and the entire kitchen can be similarly calculated. In addition, the design load factor was assumed to be used for the calculation of heat load. Therefore, the hourly design load factor is appropriate for presenting in this paper..5 Design Load Factor 8 6 2 7 8 9 11 12 13 1 Times of Day Noodle boiler Flyer Rice cooker IH cooktop Low range Tilting pan Steam convection Warmer table Dish washer In this section, an example of the calculated results of design load factor is shown by using the data obtained from kitchens. 111 P a g e

Cumulative frequency[%] Cumulative frequency[%].5.1 Design Load Factor for Appliances The cumulative frequency of the five-minute average load factor of the cooking appliances is shown in Figure 11, while the cumulative value of the five-minute average load factor for each appliance and the design load factor for each cumulative value are shown in Table 3. The cumulative frequency of the load factor of the flyer shown in Figure 11 (a) varies for each device. As shown in Table 3, the 9 th percentile value of each device was 1% to 91%, while the design load factor of the 9 th percentile value was calculated to be 66%. In the case of the electrical induction cooker shown in Figure 11 (b), the cumulative frequency of the load factor varies greatly depending on the equipment. This is because the electrical induction cooker can cook various food items. The design load factor at the 9 th percentile value was calculated to be 72%. Load factor[%] Load factor[%] (a) Flyer (b) IH cooktop Figure 11: Cumulative frequency of load factor (5-min average) Table 3: Load factor for cooking appliances Kitchen A B C D E F G H I J Design load factor Cumulative 9 95 9 95 9 95 9 95 9 95 9 95 9 95 9 95 9 95 9 95 9 95 value [%] 2 Noodle boiler 5 6 76 76 99 99 - - 99 99 1 5 83 8 99 99 5 8 F l y e r 5 69 - - 1 68 - - 81 9 72 73 7 57 - - 66 75 3 1 8 6 2 フライヤ 2 6 8 12 Rice cooker 9 9 32 7 8 9 9 5 1 3 93 7 32 32 93 9 111 IH cooktop - - 35 1 2 85 95 58 72 72 9 112 Low range 65 7 7 51 92 93 99 99 8 8 51 6 79 98 5 Tilting pan 89 96 1 1 73 73 69 7 1 1 Steam eonvection 85 91 65 73 8 8 - - 38 53 52 75 96 3 92 95 97 97 8 92 6 Warmer table 111 111 99 1 1 1 - - 1 111 111 Dish washer - - 53 57 - - 93 9 91 92 2 3 6 65 72 76 98 1:When multiple devices are installed, one example is shown. 2:While the value should be %, it is over % because the real power exceeds the rated power. : Not in operation during measurement period. -:The load factor exceeds 113% because of measurement failure..5.2 Design Load Factor for Hood D H(No.1) H(No.2) I 8 6 2 Table shows the results of the hood in kitchen D, which include a fryer and two electrical induction cookers. Since the peak period of the two electrical induction cookers are the same from 9 to am, the peak period of the hood was 9 to am. However, since the peak periods of the flyers differ, the load factor of the hood is smaller than the load factor of the electrical induction cooker. The load factor at the 9 th percentile value is 58%. 電磁調理器 B(No.1) B(No.3) B(No.5) D(No.1) F(No.1) I(No.1) I(No.3) 2 6 8 12 I(No.5) B(No.2) B(No.) B(No.6) D(No.2) F(No.2) I(No.2) I(No.) 1115 P a g e

Cooking equipment Table : Load factor for exhaust hood (Kitchen D) Peak period Cumulative percentile 9% 95% % Flyer (6 kw) 11 1 68 Electrical induction cooker (5 kw) 9 2 3 Electrical induction cooker (3 kw) 9 3 3 Exhaust hood 9 58 6 67.5.3 Design Load Factor for Kitchen Table 5 shows the load factor at the peak period, the th percentile values in each kitchen, and the design load factor. The peak period varied depending on the kitchen. However, the peak period for many kitchens was from 9 to am. The load factor at 9 th percentile values was within the range of 2% to %, while the design load factor was 38%. The 95 th percentile value was 3% and the th percentile value was 6%. Table 5: Load factor for kitchens Kitchen A B C D E F G H I J Design load factor Peak period 9 9 12 13 11 11 8 9 9 9 9 11 - Percentile value 9% 1 2 26 2 38 3 25 36 38 95% 27 3 5 1 38 7 7 27 1 3 99% 6 32 1 5 8 7 58 9 3 5 5 % 5 33 2 57 5 5 6 51 35 56 6 5 CALCULATION TOOL FOR VENTILATION RATE USING BIM 5.1 Ventilation calculation tool A flow chart of the ventilation calculation tool proposed in this paper is shown in Figure 12. The BIM software was developed by Autodesk Revit, while Dynamo was used to create an automatic calculation tool. Figure 13 shows a part of the Dynamo visual program screen. By importing information on kitchen appliances, the exhaust hood is automatically placed above the necessary cooking appliances. The designer changes the hood type and size to complete the 3-dimensional model, equipment list, and ventilation volume list. Figure 12: Flow chart of the ventilation calculation tool 1116 P a g e

3 Figure 13: Dynamo's visual program screenshot (3 and are shown in Figure 12) 5.2 Method of calculation Table 6 presents three methods for calculating ventilation in Japan. Ⅰ. Ministry of Land, Infrastructure, Transport and Tourism Standards [MLIT, 215] are commonly used in Japan. Calculations are based on 1) theoretical waste gas volume and electric capacity, 2) the hood face wind velocity, and 3) the air change rate of the kitchen. The maximum value among the three methods should be selected. As a result, it is often determined using 3) the hood face wind velocity. Ⅱ. Standard of Japan Testing Center for Construction Materials [JTCCM, 217] shows a calculation method to maintain appropriate air environment in the kitchen. This method focuses on air pollutants from the cooked product and combustion exhaust gas. The calculated ventilation rate maintains the hood capture efficiency at over 9%. Ⅲ. Standard of Japan Electro-Heat Center [JEHC, 217] is dedicated to the commercial electric kitchen. Calculation is based on the rated power and the required ventilation rate coefficient, which is listed for the typical hood shape and cooking appliance. In methods II and III, the temperature of the air supplied should be controlled to maintain good indoor thermal conditions. These methods also strongly encourage the reduction of air disturbance caused by the air supplied to the thermal plume over the cooking equipment. Ⅰ MLIT Standard Commonly used Table 6: Standards for ventilation rate in Japan Keyword for calculation method 1) Gas usage/ Rated power 2) Surface wind velocity of hood 3) Air change rate Maximum ventilation from 1) to 3) Ⅱ JSTM JSTM V 6271:217 Design load Factor, appropriate air quality, capture efficiency Ⅲ JEHC JEHC3-217 Electric kitchen, required ventilation rate coefficient, rated power 5.3 Calculation example Figure 1 shows a kitchen where the ventilation amount was estimated. The floor area is 76 m² and the ceiling height is 2.5 m. Figure 15 shows a diagram of the operational steps of the ventilation amount calculation tool. Numbers in the figure are the numbers in the flowchart 1117 P a g e

(Figure 12) and a screenshot of that process is shown. By changing the exhaust hood information, the ventilation volume is calculated in real time. Thus, one can proceed with the design while checking. The ventilation volumes of the three calculation methods are displayed in Table 7. The ventilation rate calculated by method I may be overestimated.. Figure 1 Kitchen used for the calculation example ② ③ ④ ④ Figure 15: Diagram of the operational steps (③ and ④ are shown in Figure 12) Table 7: List of ventilation rates Kitchen appliance Ventilation volume [m3/h] Exhaust hood Notes Ⅰ. MLIT Ⅱ. JSTM Ⅲ. JEHC Place Width Depth No. 1 No. 2 A 1.65 m 1.5 m IH cooktop/8. kw Flyer/6. kw 1,871 1,871 1,22 B 1. m 1. m Steam convection/.1 kw Noodle boiler/6.1 kw 1,37 871 77 C.8 m.85 m Noodle boiler/6.1 kw 73 73 35 D 1. m.8 m Dish washer/6.1 kw 86 2 32 E 1.95 m 1. m Low range/5. kw Rice cooker/1.2 kw 2,6 1,696 962 F 2. m 1. m Rotary pot/13.5 kw Steam Convection/15.3 kw 2,851 1,556 1,36 exhausttasks 51 351 Ceiling surface 5.Ceiling Future 5,95 3,865 Total 6,882 1118 P a g e

Unfortunately, methods II and III have been developed recently and do not provide sufficient information for all cooking appliances. If sufficient information becomes available in the future, these methods will become popular in Japan. Particularly, if a database of hood capture efficiency for various cooking appliances under various conditions based on the standard test method [JTCCM, 215] is constructed, the appropriate designing of kitchen ventilation can be achieved. The improvement of BIM library and the addition of adequate information on cooking appliances in BIM are also recommended. 6 CONCLUSIONS The ventilation systems of commercial kitchens in Japan were surveyed through questionnaires and by obtaining drawings. Additionally, based on the measured power consumption of kitchen equipment, the calculation method of the design load factor such as the unit of the cooking appliance or the entire kitchen was examined and a calculation example was shown. The ventilation calculation tool introduced in this paper is expected to improve the design efficiency and remove human error. This method can not only be applied to kitchens, but to research facilities where many draft chambers are used. In the future, it is possible to further develop the calculation tool of the ventilation rate to cover the entire building. 7 ACKNOWLEDGEMENTS We would like to thank the building administrators and cooperators of the kitchens we surveyed. 8 REFERENCES Kondo, Y. et al. (1). Energy Consumption and HVAC System in Commercial Kitchens. SHASE Vol.75, No. 9, pp.761 77. MLIT (215). Building facility design standard. pp.532 535/Ministry of Land, Infrastructure, Transport and Tourism Supervision. JTCCM (215). Measurement method for capture efficiency of exhaust hoods in commercial kitchens. JSTM- V-621/Japan Testing Center for Construction Materials. JTCCM (217). Calculation method of ventilation rate to keep appropriate air quality in commercial kitchens. JSTM-V-6271/Japan Testing Center for Construction Materials. ASHRAE (211). ASHRAE Handbook HVAC Applications, Chapter 33 Kitchen Ventilation/American Society of Heating, Refrigerating and Air-Conditioning Engineers JEHC (217). Ventilation equipment design guidelines for commercial kitchen facilities. JEHC3/Japan Electro-Heat Center. 1119 P a g e