"VIP 2" ADVANCED LUBRICATION CONTROLLER

Similar documents
Instruction & Maintenance Manual.

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

Refrigerated air dryers

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

100 Series Gas Ventilation Interlock System

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

M2500 Engine Controller Installation Manual

LMR Electric Fire Pump Controllers Features

LMR Electric Fire Pump Controllers Features

ABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual

Dixell Installing and Operating Instructions release 7.0

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

FX BLAST CHILLER ISO ISO 9001

PARAGON Commercial Refrigeration Controls

Engineers manual. Pass Through machines P500 P500 A P500 AS P500 A WS P500 AS WS. A- AirBreak WS Water Softener. AS Dual Rinse Element

- Data Brochure Addendum

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

FDF Foam Pump Controllers Features

EXTINGUISHING AGENT RELEASE MODULE

Centro-Matic Automated Lubrication Systems System Controls

PRODUCT INSTRUCTIONS. Fire Door Control Panel (FDCP) Stock Code Description Doc No: PI-115. Ellard Fire Door Control Panel Ellard Slave Repeater Unit

- Data Brochure Addendum

Controller Specification Sheet

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

Duct and Rough Service Carbon Monoxide Sensor

Digital Control Unit- Installation, Operation & Maintenance IMPORTANT INFORMATION

RTD TEMPERATURE SENSING SYSTEM

Dough Retarder Prover

Transfer Switch Features

Engineers manual. Under counter machines

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

RPM1600 Series Room Pressure Monitors

Application, Installation, Operation & Maintenance Manual

Servicing manual. 600 Series - 11S / 19S / 24S / 24C. Wall-mounted condensing gas boiler. For trade use

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Servicing manual. Wall-mounted condensing gas boiler 600 Series - 11S / 19S / 24S / 24C /2002 GB(EN) For trade use

H&O DIE SUPPLY, INC SPR-2000-JR. Programmable Fluid Controller Interstate 20 Kennedale, TX 76060

Forced draught gas burner

Transfer Switch Features

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

Engineers manual. Pass Through machines P500 P500 A P500 AS P500 A WS P500 AS WS. A- AirBreak WS Water Softener. AS Dual Rinse Element

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

ECO N DATE DESCRIPTION OF CHANGE CHG

AS950 REFRIGERATED SAMPLERS

BWAC Steuerung. Kochendwasser- Energiesparreinigung. Art.-Nr Version 1.0

PH / ORP Analyzers MODEL OPM223/253. Wedgewood Analytical Inc. Liquid Analytical Measurement & Control Specialists DESCRIPTION FEATURES APPLICATIONS

Chem-Trak Jr. Instruction Manual

GL-CO-RFG Channel Gas Leak Alarm System

ST Wiring diagram. Product description. Standard temperature controller. Order number

Models 4623, 4628 & 5999/980 USP<645> Conductivity Analyzers

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers

PHASE NON-COIN USER S MANUAL (S.A.F.E.)

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

LevControl LC PLUS OPERATING INSTRUCTIONS ALL OUR SYSTEMS COMPLY WITH DIRECTIVE 73/23 EEC - 89/336. Cod /0-12/97

LIEBERT LIQUI-TECT 460 KIT ZONE LEAK-DETECTION SENSOR WITH CABLE

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

1.1 REFERENCES.1 American National Standards Institute/National Fire Protection Association (ANSI/NFPA).1 ANSI/NFPA 20, Centrifugal Fire Pumps.

AS950 PORTABLE SAMPLERS

DCS2000 DEMENTIA CARE SYSTEM USER GUIDE. For Software Version 1.2 1

The Kryos LN2 Liquid Level Control & Cryogenic Temperature Control

Sentinel Kinetic MVHR RANGE

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

Operating Instructions

MTRA-FSP Level Control Relay. Installation & Operation Manual

CENTRO-MATIC - 278B. Model Controller Series C JAN Section - C8. Form Page. Indicates change

SMART EVO 2 - User Manual ELECTRICAL PANEL FOR 2 MOTORS

Wallace & Tiernan Controllers & Analysers ChemTrim Disinfection Controller

CONTROL DEVICE SLIDETRONIC HD

Instructions for the fan motor control system, SILVER C

SERVICE MANUAL WASHING WM-WD. Front loader. Platform. EWM1000 EWM1000plus EWM2000evo EWM3000new ENV06 11xx21xx 25xx/35xx

Type 8001 PRIME MOVER CONTROLS INC. ALARM ANNUNCIATOR TYPE8001 FEATURES SB 8001B

PRODUCTS. Operating Manual

Forced draught gas burner

Electronically controlled instantaneous water heater. CEX 9-U: C models. Installation instructions

CONTROL UNIT: REFERENCE MANUAL

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

CommStat 4 Controller

Intelligent Security & Fire Ltd

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL

CAN bus-based I/O module, CIO relays Mounting Terminals and wiring Commissioning, using the utility software

Warnings, Safety Information and Guidance

Hydrogen Generator Model HPNM 2

ADE Gen4. Speech Dialler Engineering Information. Description. Features

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

FT60 Reduced Voltage - Autotransformer

THX-DL Data Logger USER & INSTALLATION MANUAL V

Series DCT1000DC Dust Collector Timer Controller Specifications Installation and Operating Instructions

ACT2-CS Convenience Store Controller

Oxygen (O2) Single-Point Gas Detection System

Pump-Down Controller MODEL 4052

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

VT4810 SINGLE / DUAL ZONE CONTROLLER INSTALLATION MANUAL

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Transcription:

1. DESCRIPTION: "VIP 2" ADVANCED LUBRICATION CONTROLLER with Integrated Air Pressure Sensor. The VIP2 Lubrication Controller has been designed as an extension to the standard VIP controller and offers features of the standard unit and several new options including the ability to monitor the air pressure in small Air/Oil system using an integrated pressure transducer. The connection to the pressure transducer is obtained simply by connected a 6mm nylon tube to the push-in fitting on the side of the panel. The addition of an separate output allows the control of a solenoid to shut-off the airflow in an alarm condition. The controller also has a priming function for aid the air-purge and priming of a small air/oil system. On applications that do not require an air pressure reading, the option can be disabled in the set- up menu and the controller can be used for other systems. INSTRUCTION AND PRODUCT DATA SHEET PATENTED 1639093 1639096 ENGLISH 2. SPECIFICATION: Power Consumption: 20 Watt Operating Temperature: -5C to +55C. INPUT CONTACTS: Power: Oil Level: Control Input: 110/230V AC Single Phase Level switch normally open/normally closed software selectable 12V Max. N.O. Pressure Switch. Micro/Reed Switch Proximity (NPN/PNP Autodetect) Air Pressure Transducer: Located internally and connected via 6mm push-in fitting. Connect 6mm nylon tube to air mixing chamber. 0.0 Bar Min - 7.0 Bar Max with increments of 0.1 Bar OUTPUTS: Pump/Drive Line: 110V/230V 5A 50/60 Hz. Air Solenoid: Alarm Output: 110V/230V 5A 50/60 Hz. Voltage free contact, Max 250V, 1A software selectable normally open/ normally closed ENCLOSURE: External Dimensions: 180 x 135 x 57mm Fixing Dimensions: 79 x 165 x (4 x M4 screws) Protection Grade: IP55 (note 6mm push-in fitting should be plugged if not used) FRONT PANEL DISPLAY & LEDS: Time/Option Display: Air Pressure Display: Alarm: Level: Pump ON: Air Low: 4 Digit Display 2 Digit Display. Indicates fault in the system. Following an alarm, the alarm code is displayed on the main display. Other LEDs may be active to help indentify nature of fault. Lit when a low level in tank condition occurs. Indicates that the pump is running Indicates the air low setting 1 C1046IE-09/98

FRONT PANEL MENU Parameter Screen Display Description Pump Cycle Time Pause Time/ Lubrication Interval This parameter is used to set (maximum) duration of Indicates the lubrication interval between lubrication cycles in hours and minutes. Keys used for setting Air High Air Low Used to set the maximum air pressure. Disable air monitoring functions Use to set the minimum air pressure allowed Nominal Air Pressure If using automatic loopback air pressure regulation, This value determines at what air pressure the controller will attempt regulation. Level Switch N.O/N.C Selection Level switch operates in a normally open state Level switch operates in a normally closed state TIMER : Timer function only. No monitoring is performed. Lubrication Cycle Operating Mode PS1 : Injector System Single Line(1). The Pressure switch is monitored to ensure that pressure is high at the end of the lubrication cycle and pressure is low prior to start of the Lubrication cycles selector for Progressive Systems. n=0-99 PS2: Injector System Single Line (2). Operates as above except that the lubrication cycle is terminated one second after oil pressure is achieved. SEP: Progressive divider mode. The controller monitors that within the specified pump on time the cycling input cycles 2n times (where n= number set in Parameter 2). Sets the number of progressive cycles when operating In SEP Mode (see parameter 1 set to 3) Air Servo Motor Regulator Function disubled. Enabled. The controller will pilot a servo motor to regulate the air pressure to the nominal air pressure setting. Servomotor Fault Delay s=0-90 Specifies the time delay (ss) in seconds before a servomotor fault condition occurs (disabled if parameter 3 is set to 0) Alarm Contact NO : Alarm Relay operates in a Normally Open State (Closed in alarm condition) NC : Alarm relay operates in a normally closed state (Opens in alarm condition) Note: The Key is used to move on to next parameter 2 VIP2 ADVANCED LUBRICATION CONTROLLER

Fig 1. Fig 2. 3 C1046IE-09/98

3. INSTALLATION/OPERATION: 3.1 SETTING THE CONTROLLERS OPERATING PA- RAMETERS The settings are altered using the front panel menu (see page 2.). To access press the MODE Key for ten seconds.the following are the parameters in the Menu 3.2 PRIMING FUNCTIONS / PRIME PHASE 1 By holding The UP key for 10 seconds during normal operation the controller will enter Priming Stage 1. The duration of this priming phase is 10 minutes (remaining time is displayed on the main display) and the pump is cycled 1 second ON, 1 second OFF, to charge the oil injectors and eliminate air for the hydraulic oil circuit. During this phase the air solenoid (if connected) will remain in a closed position. After terimnating this phase, the controller will enter PRIME PHASE 2 3.3 PRIMING FUNCTIONS / PRIME PHASE 2 This phase is initiated following Phase 1 OR by holding the DOWN Key for 10 Seconds. The Pump is cycled as in PRIME PHASE 1 for 5 minutes (remaining time is displayed on the main display). During this phase the air solenoid (if connected) will be energised thereby allowing air flow. After terminating this phase, the controller will revert to Normal Operating Mode. 3.4 NORMAL OPERATING MODE. Normal operation will commence after power-up of the control starting with a During Normal Operating Mode the controller will control and monitor lubrication cycle at regular intervals as determined by the menu parameters (see sec 3.1) The LEDs show the status of the Inputs/Outputs of the controller. The alarm LED should NOT be lit. The main display will indicate time remaining until next lubrication cycle if in pause mode or cycle time during the The Digital Pressure Display displays the current air pressure of the system. No user intervention is required during normal operation. 3.5 ALARM CONDITION. During an alarm condition the Alarm LED will light and an Alarm Code will be displayed on the Main (4-digit) Display. See the Diagnostic Table for a description of possible alarm states. The Pump and air solenoid (if connected) will be deactivated when the controller enters any alarm condition. Following an alarm condition, the RESET button should be pressed after the fault has been cleared so the controller may return to normal operation. During Mode setting the Alarm Relay will be set active to avoid the machine operating with the lubrication system not operating. 3.6 ELECTRICAL CONNECTIONS AND CIRCUIT DETAILS: The controller can be wired on the terminal strip as shown in Fig. 1, or pre-wired with an Amp connector (Fig. 2) and connections for a typical Dropsa Air/Oil Lubrication System. Following the relevant wiring diagrams. 4. TEST PROCEDURES: The controller will self-diagnose on power-on and will display any errors on the 4-digit display. No testing is required or may be carried out by the user. 5. ORDERING INFORMATION: Part No.1639096 : 110/230V Box Version Internal Wiring Part No.1639093 : 110/230V Box Version with 2.5 m cable and Amp Connector, and cabling for typical Air/Oil injector System. 6. SPARES No user serviceable parts. 7. SAFETY REQUIREMENTS These controllers must be installed and operated in accordance with the requirements of this Instruction Sheet and should not be used for any purpose than that specified without the agreement of the suppliers. In addition to the need to observe general safety requirements the following specific hazards apply: Before installing or removing Advanced Lubrication Controllers from the system disconnect and isolate all power supplies. 8. OPERATING ENVIRONMENT Controllers must not be operated in excessively corrosive or aggressive environments. If in doubt, please contact our Technical Office. 4 VIP2 ADVANCED LUBRICATION CONTROLLER

9. DIAGNOSTIC TABLE: ALARM CODES DESCRIPTION OF FAULT ACTION A-07 In SEP Mode, the cycle input failed to trigger the correct amount of times within the cycle time. Check for correct operation of progressive divider valves. A-O1 A-O2 No parameters set (may indicate memory problem with microprocessor if alarm is given following successful installation of the unit.) Low Level Alarm. (Low Level LED will also be lit) Set parameters Oil level is low and requires refilling. Level Switch (parameter 0) may be set incorrectly if tank is full. A-08 Regulation Timeout Alarm (disabled if Parameter 3 = 0). The servo motor has not been able to regulate the air pressure to the correct setting within 2 minutes. Check for correct operation of servo motor and air line pressure. A-O3 In Mode PS1 or PS2, the system already had pressure before the cycle commenced, therefore not operating the injectors correctly. Check the pressure relief mechanism in the oil circuit is operating correctly. (Also perform checks as for A-03) A-O4 In Mode PS1 or PS2, The Pump failed to develop pressure within the specified Pump On Time. Check Correct operation of Pump/ Pressure Switch and make sure no filters are clogged in the system. A-O5 Air High Pressure (Air High LED will also be lit). The air pressure is lower than the air low setting. Check settings. Ensure fault was not caused by a broken Air/Oil line in the system causing pressure drop. AN ISO9001 APPROVED COMPANY A-06 Air low pressure (Air Low LED will also be lit). The air pressure is higher than the air low setting. Check settings. Ensure fault was not caused by a broken Air/Oil line in the system causing pressure drop. Copyright Dropsa - all rights reserved. Reproduction of any part of this document is strictly forbidden without prior consent from Dropsa. Dropsa reserve the right to withdraw or modify specifications without prior notice. 5 C1046IE-09/98