M3 M6 M10 TS6 T2 T5 TL3 TL6

Similar documents
HRS Heat Exchangers Instruction Manual

Instruction Manual Plate Condenser. AlfaCond 400/600/800. Part number

Channel plates Heat is transferred from one medium to the other through the thin channel plates.

eng ger fre Instruction Manual Plate Heat Exchangers spa M3 M6 M10 TS6 TL6 por ita swe dan fin dut rus pol Part number nor

Description. Main components. Lifting eyes To used for lifting and transport securing. Carrying bar Carries the cassettes and the pressure plate.

COPYRIGHT Alfa Laval Lund AB, 2012 How to contact Alfa Laval Contact details for all countries are continually updated on our website.

Instruction Manual - Plate Heat Exchangers

Titanium Plate Heat Exchanger. Installation & Operating Manual

AQUAS POOL PACKAGE INSTALLATION INSTRUCTIONS FOR MODELS: APN 1000, 1250, 1500, and 2000 AQUAS Pool Package

WesPlate. Operation, Maintenance & Installation Manual. Heat Exchanger. Models WP & WPDW

PLATE HEAT EXCHANGERS. Operation and Maintenance Manual

Instruction and Maintenance Manual. Spiral Heat Exchanger

Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers

Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010

The Alfa Laval. Cleaning procedures. for. HeatExchangers.

Rycroft Supapac Plate Heat Exchangers

Instruction Manual. Pharma-line ESE02198-EN Original manual

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW)

Evaporators. Direct Expansion Flooded Recirculated Over Feed

PLATE HEAT EXCHANGER

Operation of heat exchangers

4 route 147, C.P.33 Coaticook, Qc J1A 2S8

ANLAGENBAU HEAT EXCHANGER w w w. a nla g enba u-b oehm er. d e Version 05/2015

TopWing Ultra-Hygienic Rotary Lobe Pumps

Instruction Manual. Pharma-X ESE02197-EN Original manual

UniAir UniBraz UniCompact UniGasket UniSystem UniTwist UniWeld

USER AND MAINTENANCE MANUAL

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

Carry Out Maintenance Procedures

PLATE HEAT EXCHANGERS BETTER BY DESIGN

ECONOPLATE BARE PLATE HEAT EXCHANGERS

LONGONI ENGINEERING SRL

Aston Technology-Sondex A/S PHE - Design & Datalist V10A34 Aston Thomas McLaughlin 05/03/ ATESHEX S1 Item: 1

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

Installation of Glass Lined Equipment

OHM N PREPARATIONS & SUPPORT FOR A WATERTUBE BOILER Fax: P.O. Box 96. Russell, IL

WHEELED STORED PRESSURE

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual

UltraHeat Plate and Frame Heat Exchangers. Engineered for Excellence

BRAZED INSPECTED PLATE HEAT EXCHANGER SCAMBIATORI DI CALORE SALDOBRASATI ISPEZIONABILI CIESSE

INSTRUCTION MANUAL W-400

568X, 587X, 588X Series

PURPLE K POWDER EXTINGUISHERS INSTALLATION, OPERATION, MAINTENANCE AND RECHARGE MANUAL

Installation, Operation and Maintenance Instructions for Electric Storage Calorifier

Empty unit Cover Water Total weight 15 kg 8 kg 10 kg 33 kg

Secure hydraulic system performance. Smart solutions for cooling and cleaning hydraulic oil

OHMS ENTERPRISE Subsidiary of AIT Synergy Ventures SDN BHD

Where the tap has a removable aerator on the spout exit it can be removed and cleaned periodically to maintain optimum flow performance.

Plate Type Heat Exchangers. Operation and Maintenance Manual

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

OPERATION & MAINTENANCE INSTRUCTIONS

This chapter is devided into two sections:

APV ParaFlow Plate Heat Exchangers

INSTRUCTION MANUAL (English version) Water still

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Duke Manufacturing Co.

MK 8706 / MB 8706 CONCEALED THERMOSTATIC SHOWER VALVE INSTALLATION GUIDE

The theory behind heat transfer

TECHNICAL DATA. Wet 26a. February 22, 2009

EXTREME HP-1 Reverse Osmosis System

F-CLASS MODEL M6L WET CHEMICAL FIRE EXTINGUISHER Installation, Operation, Recharge and Maintenance Manual

INFINITY FLUIDS CORPORATION

EXTREME 1 Reverse Osmosis System

INSTALLATION OF DURAVENT POLYPRO SINGLE WALL POLYPROPYLENE VENTING SYSTEMS

Steam Trap BK 45 BK 45-U BK 45-LT BK 46

HOSHIZAKI MODULAR CRESCENT CUBER MODELS KM-280MAH KM-280MWH INSTRUCTION MANUAL

INSTRUCTIONS FOR USE. To make the most of your new oven, read the user's instructions carefully and keep them on hand for consultation in the future.

Isolux Arsenic Removal Systems Central Treatment Systems Operation and Maintenance Manual

PARTS CLEANING AND DEGREASING

USER INSTRUCTION MANUAL. Autofill Water Boiler

TITAN FLOW CONTROL, INC.

OWNER'S SERVICE MANUAL NO INSPECTION, MAINTENANCE AND RECHARGE

569, 570, 571, 572 Series

SCHMIDT- BRETTEN GASKETED PLATE HEAT EXCHANGERS

Instruction Manual. Alfa Laval Agitator - ALT / ALTB ESE03504-EN Original manual

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

82. Siphon all gas out of the tank. 83. Disconnect the fuel filler and vent tube with a Phillips screwdriver.

569, 570, 571, 572 Series

Niles Steel Tank Hot Water Generator Installation and Operation Manual

USER MANUAL SPRAY GUN CLEANER - WATER BASED PAINTS UA400W CAUTION FOR WATER BORNE PAINTS ONLY

Why Clean? Sell more beer!

02 COOLING SYSTEM 02 COOLING SYSTEM COOLING SYSTEM INDEX. 1. General Specifications... 65

USE and MAINTENANCE INSTRUCTION MANUAL GRAVITY. WS-400 EVO LS-400 Entech. SPRAY GUN Series. en it fr es pt de se

SPIKA NG ICE MAKER MAINTENANCE

Installation, Operation and Maintenance Manual

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

Flanged Immersion Heaters

Instruction Manual, Toftejorg Rotary Spray Heads Toftejorg MultiMidget, Toftejorg MultiMagnum

MAINTAINING OPTIMUM PERFORMANCE

UltraHeat Plate and Frame Heat Exchangers. Engineered for Excellence

Brazed heat exchangers

Polaris PHEs vs. Shell-and-Tube Exchangers

SB Series Brazed Plate Heat Exchanger Installation Manual

Installation and servicing instructions

CHEST FREEZER HS225523

General Maintenance and Operating Instructions for Heat Exchangers

Hoshizaki America, Inc.

Akva Lux VX District heating substation for indirect heating and domestic hot water systems

Dishwasher Installation Instructions DW 24XT/DW 24XV

Air Cross 21 Installation and User Manual

Transcription:

DE Instruction Manual Plate Heat Exchangers M3 M6 M10 TS6 T2 T5 TL3 TL6 FR ES PT IT SV DA FI NL RU PL NO Part number 1644725-01 0810

Table of contents Table of contents Description... 1 Main components... 1 Function... 2 Semi-welded PHE... 2 Installation... 3 Requirements... 3 Lifting... 4 Raising... 4 Operation... 5 Start-up... 5 Unit in operation... 6 Shut-down... 6... 7 Cleaning-In-Place (CIP)... 7 Manual cleaning... 8 Pressure test after maintenance... 13 Regasketing... 14 How to contact Alfa Laval: Contact details for all countries are continually updated on our website. Please visit www.alfalaval.com and contact your local Alfa Laval Representative. Except for this Instruction Manual, the following documents are also included in this shipment: Plate Heat Exchanger (PHE) drawing Plate hanging list Parts list with exploded view drawing. Plate Heat Exchanger

Environmental compliance Environmental compliance AlfaLaval endeavours to perform its own operations as cleanly and efficiently as possible, and to take environmental aspects into considerattion when developing, designing, manufacturing, servicing and marketing its products. Unpacking Packing material consists of wood, plastics, cardboard boxes and in some cases metal straps. Wood and cardboard boxes can be reused, recycled or used for energy recovery. Plastics should be recycled or burnt at a licensed waste incineration plant. Metal straps should be sent for material recycling. During maintenance oil and wear parts in the machine are replaced. All metal parts should be sent for material recycling. Worn out or defective electronic parts should be sent to a licensed handler for material recycling. Oil and all non metal wear parts must be taken care of in agreement with local regulations. Scrapping At end of use, the equipment shall be recycleed according to relevant, local regulations. Beside the equipmnet itself, any hazardous residues from the process liquid must be considered and dealt with in a proper manner. When i doubt, or in absence of local regulations, please contact the local AlfaLaval sales company. Plate Heat Exchanger

Description Description Main components Frame plate Carrying bar Carries the channel plates and the pressure plate. Bolt protection Support column Tightening bolts Press the channel plates together. Connections Holes through the frame plate, permitting the media to enter into the heat exchanger. Threaded studs around the holes secure the pipes to the apparatus. Metallic or rubber-type linings may be used to protect the holes against corrosion. Connections can also be pipes for welding or threaded. Pipe connections Channel plates Heat is transferred from one medium to the other through the thin channel plates. The number of plates determines the total heat transfer surface. Guiding bar Keeps the channel plates in line at their lower end. Pressure plate Moveable steel plate. In some cases pipes may be connected to the pressure plate. Protective sheets In the USA mandatory, in other countries optional. Plate Heat Exchanger 1

Description Function The plate heat exchanger consists of a pack of corrugated metal plates with portholes for the passage of the two fluids between which heat transfer will take place. The plate pack is assembled between a frame plate and a pressure plate and compressed by tightening bolts. The plates are fitted with a gasket which seals the channel and directs the fluids into alternate channels. The plate corrugation promotes fluid turbulence and supports the plates against differential pressure. M3, M6, M10, TS6 Principle of plate pack arrangement M3, M6, M10, TS6 T2, T5 The A-plate is a plate hanging with the chevron pointing downwards. The A-plate is a plate hanging with the chevron pointing upwards. The B-plate is a plate hanging with the chevron pointing upwards. The B-plate is a plate hanging with the chevron pointing downwards. Semi-welded PHE For certain plate sizes there are semi-welded plates (Cassettes) available. The function of the semi-welded PHE is the same as that of the conventional PHE. Chapters Installation and Operation of this manual are applicable to full extent. Chapter is fully applicable when it comes to the parts Cleaning-in-Place and Pressure test after maintenance and partially applicable for the remaining part. To cover the specific requirements of the semi-welded PHE a separate additional manual has been made. 2 Plate Heat Exchanger

Installation Installation Requirements Pipes Caution! Make sure the pipe connections are locked when working on the piping. Turning of the connections will damage the gaskets on the end plate and cause leakage. Multi-pass units: Connections on the pressure plate It is important that the plate pack has been tightened to the correct measurement (check against drawing) before the pipe is connected. Elbow To make it easier to disconnect the plate heat exchanger, an elbow should be flanged to the connection in the pressure plate, directed upwards or sideways, and with another flange located just outside the contour of the heat exchanger. Space 600 mm minimum free space is needed for lifting plates in and out. Drip tray Depending on the type of fluid in the PHE and the type of installation, a drip tray (drainage box) may be nesessary to avoid damages on personnel and equipment. Shut-off valves To be able to open the heat exchanger, shut-off valves should be provided in all connections. Before connecting any piping, make sure all foreign objects have been flushed out of the system. When connecting the pipe system make sure the pipes do not subject the plate heat exchanger to stress or strain. To avoid water hammer, do not use fastclosing valves. Foundation Install on a flat foundation giving enough support to the frame. Safety valves should be installed according to current pressure vessel regulations. If PHE surface temperature is expected to be hot or cold, the PHE should be isolated. It is recommended that protective sheets are used to cover the PHE. For each model, design pressures and temperatures are marked on the identification plate. These must not be exceeded. Plate Heat Exchanger 3

Installation Lifting Warning! Never lift by the connections or the studs around them. Straps should be used when lifting. Place straps according to picture. Raising 1 Place two timber beams on the floor. 4 Place straps around one bolt on each side. 2 Lift the heat exchanger off pallet using e.g. straps. 5 Lift the heat exchanger off the timber beams. 3 Place the heat exchanger on the timber beams. 6 Lower the heat exchanger to horizontal position and place it on the floor. 4 Plate Heat Exchanger

Operation Operation Start-up If several pumps are included in the system, make sure you know which one should be activated first. 3 4 If there is a valve at the exit, make sure it is fully open. Open the vent and start the pump. Adjustments of flowrates should be made slowly in order to avoid the risk of water hammer. Open Water hammer is a shortlasting pressure peak that can appear during start-up or shutdown of a system, causing liquids to travel along a pipe as a wave at the speed of sound. This can cause considerable damage to the equipment. 5 Open the valve slowly. 1 Check that measurement A is correct. For A, see enclosed PHE-drawing. Open slowly 2 Check that the valve is closed between the pump and the unit controlling the system flowrate. 6 When all air is expelled, close the vent. Closed Close Open 7 Repeat steps 1 6 for the second media. Plate Heat Exchanger 5

Operation Unit in operation Adjustments of flowrates should be made slowly in order to protect the system against sudden and extreme variations of temperature and pressure. During operation, check that media temperatures and pressures are within the limits stated on the PHE-drawing Shut-down 1 If several pumps are included in the system, make sure you know which one should be stopped first. Slowly close the valve controlling the flowrate of the pump you are about to stop. Close no leakages appear due to faulty tightening of the plate pack or to defective or damaged gaskets support column, carrying bar and guiding bar are kept clean and greased the bolts are kept clean and greased. 2 3 4 When the valve is closed, stop the pump. Repeat steps 1 2 for the other side. If the heat exchanger is shut down for several days or longer, it should be drained. Draining should also be done if the process is shut down and the ambient temperature is below freezing temperature of the media. Depending on the media processed, it is also recommended to rinse and dry the heat exchanger plates and connections. No leakage Clean and greased Always consult your local Alfa Laval Representative for advice on new plate pack dimensions if you intend to change number of plates selection of gasket material if operating temperatures and pressures are permanently changed, or if another medium is to be processed in the PHE. 6 Plate Heat Exchanger

Cleaning-In-Place (CIP) The Cleaning-In-Place (CIP) equipment permits cleaning of the plate heat exchanger without opening it. If CIP cannot be done, cleaning must be performed manually, see section Manual cleaning. CIP performs cleaning of fouling and descaling of lime deposits passivation of cleaned surfaces to reduce susceptibility to corrosion neutralization of cleaning liquids before draining. Follow the instructions of the CIP equipment. CIP equipment CIP model Maximum number of plates M3 M6 M6-M M10-B M10-M TS6-M CIP 20 90 89 62 40 27 56 CIP 40 178 124 81 53 110 Cleaning liquids Cleaning liquid AlfaCaus AlfaPhos AlfaPass AlfaNeutra Description A strong alkaline liquid, for removing paint, fat, oil and biological deposits. An acid cleaning liquid for removing metallic oxides, rust, lime and other inorganic scale. An alkaline liquid for passivation (inhibition of corrosion). A strong alkaline liquid for neutralization of AlfaCarbon or AlfaPhos before drainage. Plate Heat Exchanger 7

Manual cleaning Warning! To avoid hand injuries owing to sharp edges, protective gloves should always be worn when handling plates and protective sheets. Opening Warning! If the heat exchanger is hot, wait until it has cooled down to about 40 C (104 F). 1 Drain the plate heat exchanger. 2 Inspect the sliding surfaces of the carrying bar and wipe clean. Inspect 8 Plate Heat Exchanger

3 Mark the plate assembly on the outside by a diagonal line. Mark See also point 5 under part Closing. 4 Measure and note down the dimension A. 6 Open the plate pack by letting the pressure plate glide on the carrying bar. If plates are to be numbered, do this before removing the plates. Plates need not to be removed if cleaning is done using only water, i.e. without cleaning agent. 5 Loosen and remove all bolts except the 4 at the positions indicated below. Use these remaining 4 bolts to open the plate pack according to the following scheme. Step Bolt No. To dimension Remove the plates 1 1 2 3 4 1,05A 2 1 2 or 3 4 Opening Be careful so that the plate and pressure plate are always in parallel. Skewing of the pressure plate during opening must not exceed 10 mm (2 turns per bolt) across the with and 25 mm (5 turns per bolt) vertically. Warning! The plate pack may still contain a small residual amount of liquid after draining. Depending on the type of product and type of installation special arrangments, e.g. drainage box, may be necessary to avoid damages on personnel and equipment. Plate Heat Exchanger 9

Manual cleaning of opened units Caution! Never use hydrochloric acid with stainless steel plates. Water of more than 330 ppm Cl may not be used for the preparation of cleaning solutions. It is very important that carrying bars and support columns in aluminium are protected against chemicals. Be careful not to damage the gasket during manual cleaning. Deposits removable with water and brush Plates need not to be removed from the plate heat exchanger during cleaning. Remove deposits using a soft brush and running water. 1 2 Rinse with water using a high pressure hose. Deposits not removable with water and brush Plates must be removed from the plate heat exchanger during cleaning. Brush with cleaning agent. 1 2 Rinse with water. 10 Plate Heat Exchanger

Cleaning agents Incrustation, scaling Concentration max 4 % Temperature max 60 C (140 F) Incrustation Scaling Sediment Cleaning agent Calcium carbonate Corrosion products Nitric acid Calcium sulphate Metal oxides Sulfamic acid Silicates Silt Citric acid Alumina Diatomic organisms and their excrement of various colours Phosphoric acid Complexing agents (EDTA, NTA) Sodium polyphosphates Cleaning agents Biological growth, slime Concentration max 4 % Temperature max 80 C (176 F) Biological growth Slime Bacteria Nematodes Protozoa Sodium hydroxide Sodium carbonate Cleaning agent Cleaning effect can be considerably increased by the addition of small quantities of hypochlorite or agents for the formation of complexes and surfactants. Cleaning agents Oil residues, asphalt, fats Oil residues Asphalt Fats Deposit Cleaning agent Paraffinic naphta-based solvent (e.g. kerosine). Gaskets in EPDM rubber qualities swell in these media. Contact time should be limited to 30 minutes. Caution! The following solutions should not be used: Ketones (e.g. Acetone, Methyletylketone, Methylisobutylketone Esters (e.g. Ethylacetate, Butylacetate) Halogenated hydrocarbons (e.g. Chloro-thene, Carbon tetrachloride, Freons) Aromatics (e.g. Benzene, Toluene). Plate Heat Exchanger 11

Closing 1 2 Check that all the sealing surfaces are clean. Brush the threads of the bolts clean, using a steel wire brush. Lubricate the threads with a thin layer of grease, e.g. Gleitmo 800 or equivalent. 5 Press the plate assembly together. Tightening is done in two steps, see figures below. Be careful so that the frame plate and the pressure plate are always in parallel. Step Bolt No. To dimension 1 1 2 or 3 4 1,10A 2 1 2 3 4 A Tighten the two diagonal pair of bolts alternately until the plate package measures 1,10A. 3 Attach gaskets to the plates or check that all the gaskets are properly attached. If the gasket is wrongly positioned, it will show by the fact that it rises out of the gasket groove or that it is positioned outside the groove. 4 Insert the plates with the herring bone pattern positioned in alternate directions and with the gaskets turned towards the frame plate. After that bolts are tightened alternately and diagonally, as shown in the figure below. 12 Plate Heat Exchanger

Finally the middle pair of bolts, and upper and lower bolts are tightened. Pressure test after maintenance Before start-up of production, whenever plates or gaskets have been removed, inserted or exchanged, it is strongly recommended to perform a pressure test to confirm the internal and external sealing function of the PHE. At this test, one media side at the time must be tested with the other side open to the atmosphere. The pressure testing shall be performed at a pressure equal to the operating pressure of the actual unit but never above the design pressure as stated on the nameplate. The recommended test time is 10 minutes. Please note that PHE units for refrigeration applications and units with media not mixable with water must be dried after hydrostatic pressure testing. The actual measurement must never be less than the A-dimension. Please consult the local office/representative of the supplier for advice on the pressure testing procedure. 6 If the plates are correctly assembled, the edges form a honeycomb pattern, see picture below. Plate Heat Exchanger 13

Regasketing 1 Open the plate heat exchanger according to page 8, and remove the plate that is to have a new gasket. Glued gaskets Separate gluing instructions will be delivered together with the glue. 2 Remove the old gasket. 3 Assure that all sealing surfaces are dry, clean and free of foreign matter. 4 Attach the clip-on gasket to the plate. Slip the gasket prongs under the edge of the plate. Make sure the two gasket prongs are in correct position. 5 Proceed with the next plate to be regasketed until all plates in need of regasketing are done with. 6 Close the plate heat exchanger according to page 12. 14 Plate Heat Exchanger