Powerohm Resistors Digital HRG System

Similar documents
MPT Electric Fire Pump Controller

MPT Electric Fire Pump Controller

Across-the-Line SERIES MP300 Combined Manual and Automatic

Soft Start Series MP700 Solid State, Reduced Voltage

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

Single Phase Simplex SXL21=3, SXL24=3, SXH21=3, and SXH24=3

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Variable Frequency Drive SERIES MP800 VFD

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Beacon 410A Gas Monitor Operator s Manual

Microprocessor Based Wye-Delta Reduced Current Type Starting

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

Beacon 110 Gas Monitor Operator s Manual

Student Services & Classroom Addition. A. Section includes distribution panelboards and lighting and appliance branch-circuit panelboards.

GasScanner 4C. Four Channel Monitor. Operator s Manual. MINT-0280-XX Rev. A 02/25/08

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

Beacon 800 Gas Monitor Operator s Manual

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

www. ElectricalPartManuals. com GADD MKIII Ground Fault Indication System Instruction Manual Ground Fault Protection

VACUUM BREAKER MEDIUM VOLTAGE AUTOMATIC TRANSFER SWITCHES

21-light Remote Annunciator. Owner s Manual

T M. User Manual. MarinaGuard. Ground Fault Monitoring Panel For Marina Shore Power

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

MANUAL FOR MODEL MP600 HIGH VOLTAGE ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS

rev3 INSTALLATION & OPERATION MANUAL OIL CIRCULATING HEATING SYSTEM MODEL OSM

INSTALLATION, OPERATION AND MAINTENANCE MANUAL

PILOT SERIES MPT700TS

SYSTEM 2000 CHILLED WATER (CAC) EC SERIES -INSTALLATION OPERATIONS AND MAINTENANCE MANUAL-

SurgeBan. SurgeBan. Transient Suppression Systems. Installation, Operation and Maintenance Manual PN

Tachometer/Hourmeter/Trip. Installation and Operation Manual

AquaSaver DISPOSER CONTROL CENTER Installation Manual. Model AS-101K

SECTION AUTOMATIC TRANSFER SWITCHES

SECTION ISOLATED POWER SYSTEMS

EG Controls. SLIMVIEW 120 VOLT FLOAT SERIES DUPLEX PUMP CONTROL PANEL SPECIFICATION for CITY OF E G

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

SAFETY INFORMATION AND WARNINGS

AutoTest VSR (VSR-AT) (EU) Vane Type Waterflow Alarm Switch With Electronic Retard and Auto Test Feature

Installation, Operation and Maintenance Manual. RQ Series. Mold Temperature Control Units 0.75 to 7.5 hp and 0 to 24 kw

User s Manual. For the SHORE POWER CONNECTION MONITOR MODEL 9151

Flostop TS D7E and A8E. Operation Manual

www. ElectricalPartManuals. com GADP Ground Fault Indication System Instruction Manual Ground Fault Protection

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

Macurco DVP-120 / DVP-120M Detection and Ventilation Control Panel User Instructions

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 870 SERIES INDUSTRIAL CONTROL PANELS

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL G1000 AND H1000 SERIES ANNUNCIATORS

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

ELECTRIC FIRE PUMP CONTROLLER

Flopurge TS. Operation Manual

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

EXPERT TRI-STAR. Temperature controller. User s Manual

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

VSR-M REPLACEMENT Waterflow Switch for Globe Sprinkler Model UMC Manifold

INSTALLATION & OPERATION MANUAL

Spectron LSN (Life Safety Network) Suggested Specifications

OPERATION MANUAL MODEL LC2000 COPYRIGHT 2017 PNEUMERCATOR CO., INC EXPRESSWAY DRIVE NORTH HAUPPAUGE, NY 11788

EATON LMR Plus Electric Fire Pump Controllers

Installation and Maintenance Manual for Dimako NERM Panels REV 4. NERM Reference Manual NERM Panels 1 of 7

CONTENTS AUTOMATIC TRANSFER SWITCHES

Follett Performance Plus

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

PART GENERAL 1.01 SECTION INCLUDES

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2018

Model Gas Alarm Panel APPLICABILITY & EFFECTIVITY. This manual provides instructions for the following Sierra Monitor products:

THX-DL Data Logger USER & INSTALLATION MANUAL V

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

Installation Instructions

CONTENTS CONSIDERATIONS. General Plumbing Component Connection ILLUSTRATION. Control System CONFIGURATION. Voltage Verification CONNECTION

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Installation Instructions for the LatitudeTM Solaris Stick Light Models SL8C-xxx

DESCRIPTIVE AND INSTALLATION INSTRUCTION MANUAL FOR MODEL AH1000, BH1000, AND EH1000 SERIES ANNUNCIATORS

Beacon 200 Gas Monitor Operator s Manual. Part Number: RK Released: 6/6/08

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE STAND-ALONE FAAST LT MODELS FL0111E FL0112E FL0122E. 367 mm.

ESP TECHNOLOGIES LIMITED

PowerWave 2 Busway System

MODELS 304GC, 304GCX, 314GC, and 314GCX

MODELS ASHP, ASHH, ASUP, and ASUH

Service Manual Models: 1.0, 1.3, and 1.5

Installation and Operation Manual

Coolant Circulating Heating System Installation & Operation Manual

CAN bus-based I/O module, CIO relays Mounting Terminals and wiring Commissioning, using the utility software

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

Setup & Operation Index

D-TECT 3 IP. GJD260 IP Motion Detector

SECTION AUTOMATIC TRANSFER SWITCHES

CSP-204 CSP-208 CSP-104 CSP-108

FUSE PANEL Technical Practice N N/L9 10/10 GMT NEBS Level 3 Certified

CabLite Luminous Auto Light Control Installation Manual

i.c³ User Guide For Helmer i.series Ultra-Low Freezers A/A

Transcription:

Installation and Operating Instructions Powerohm Resistors Digital HRG System This manual provides general information, installation, operation, maintenance, and system setup information for the Powerohm Resistors Digital HRG System. Section Page Equipment Application 3 Installation 4 Operator Interface Device (OID) Use and Navigation 7 Equipment Operation 14 Measure Capacitance and Adjust Taps 16 Maintenance 18 Replacement Parts 20

2 Powerohm Resistors Digital HRG System History of Changes Rev. No. Date Description of Changes A September 2017 Initial Release

Equipment Application Powerohm Resistors Digital HRG System 3 Powerohm Resistors Digital HRG Systems are an economical means of improving a three-phase ungrounded power system by providing the following advantages: System Protection: Offers protection by providing a ground-to-neutral connection for a three-phase power system, while still allowing it to operate as an ungrounded system, When the neutral of a system is not grounded, the system is vulnerable to potentially damaging ground faults. Transient Over-voltage Reduction: A high resistance grounding system reduces the magnitude of transient over-voltages that may occur during arcing ground faults. High transient over-voltages may cause failure of equipment or insulation at locations on the system other than at the point of the fault. Ground Fault Detection Warning: Instantly provides a warning when the first ground fault occurs through an alarm signal. Form C contacts can be used to activate external alarms or annunciators. An audible horn and optional red warning beacon is available. Ground Fault Location Simplified: A pulsing contactor allows the ground fault location to be quickly located by use of a portable clamp-on current detector. The ease and swiftness of ground fault location eliminates the need to trace faults by opening and closing secondary feeders, branch circuits, and individual loads one at a time. Uninterrupted Service: A single line-to-ground fault left in operation may develop into a phase-to-phase fault, which is caused by the occurrence of a second ground fault on another phase before the first fault is cleared. Considerable damage may be caused by the high line-to-line fault current. The potential for quickly locating and removing faults before damage occurs to critical processes minimizes outages and costly manufacturing shutdowns. Improved Personnel Safety: Reduced transient over-voltages, equipment arcing, fault levels, insulation failures, and fault tracing through circuit isolation schemes decreases hazards to personnel.

4 Powerohm Resistors Digital HRG System Installation NOTICE Read these instructions thoroughly before installing and operating the controller. If there are still questions, contact your Powerohm Resistors factory representative for assistance. The system has been assembled and wired at the factory with the highest workmanship standards. All wiring and functions have been thoroughly tested to insure correct operation when properly installed. All national and local electric codes should be used for proper installation, wiring, and grounding of the system prior to startup. Receiving and Storage Immediately upon receipt, carefully unpack and inspect the system for damage that may have occurred in shipment. If damage or rough handling is evident, file a damage claim with the transportation carrier immediately. All packaged systems are suitable for prolonged storage. Always store the unit in the upright position (as shipped). Setting the crate on its side or top may cause damage to the resistor. Avoid stacking anything on top of the crate. NOTE It is recommended that the unit remain crated until it reaches the job site. Installation Instructions CAUTION To avoid risk of SERIOUS INJURY or DEATH, and to avoid damage to the system, READ THIS SECTION CAREFULLY. If questions or concerns still exist, contact the Powerohm Resistors factory for further clarification. Inspection Inspect the exterior of the enclosure for damage. Open the front door and inspect the resistor and control panel for damaged components. Medium voltage units have a step-down transformer in the bottom compartment; insure that the transformer is securely fastened and has not been damaged. Check all electrical connections to insure tightness

Powerohm Resistors Digital HRG System 5 NOTE If damaged parts are found, contact the factory immediately. Energizing the unit may damage the resistor and create a shock hazard to personnel. Handling Freestanding units are supplied with removable lifting eyes for use with an overhead crane. Do not attempt to move or lift the equipment at points other than the lifting eyes or skid base. Never position the unit on its side or top, which may cause damage to the unit. Wall mounted units and open panels should also be handled with care to prevent damage to extern components. Do not stack. Electrical Connections DANGER Electric shock may result in SERIOUS INJURY or DEATH. Electrical connections should be made by a qualified electrical engineer only. Refer to drawings supplied with the controller All national and local electric codes should be used for proper installation, wiring, and grounding of the system The installer is responsible for insuring no metallic foreign objects (such as drilling chips, etc.) fall inside the enclosure onto the electrical circuits. Failure to observe this could result in damage to the system and may void the warranty. Equipment Grounding To reduce the possibility of electrical shock, appropriate grounding practices must be adhered to. Prior to making any system connections, ground the equipment (a lug or ground strip is provided with all equipment). Insure that all ground conductors are sized per NEC and applicable standards. Line and Control Connections Refer to drawings supplied with the unit. Conduit entry for line connections are generally made through either the top or bottom of the enclosure to the proper internal terminals. A conduit entry drawing is available. Space is provided for line cables to run down the side without cable bends. Control power and auxiliary device connections are made to marked terminal blocks. Neutral Connection The neutral lead from the transformer (XO bushing) or generator is connected to a terminal strip or neutral terminal (refer to the supplied drawing for terminal location).

6 Powerohm Resistors Digital HRG System The connection is made directly to an internal terminal point via rigid conduit connected to the enclosure. On medium voltage units, the neutral cable is terminated to the transformer H1 terminal or a NEMA two-hole terminal with a compression type lug (customer supplied). Neutral conductor is sized per NEC 250. Location and termination of the conduit is the customer s responsibility. NOTE The factory supplied drawing identifies the neutral and ground connection points, and the proper connection is shown schematically. Delta Phase Connection The phase leads from the transformer or generator are connected to a terminal strip on low voltage units (refer to the supplied drawings for terminal locations). On medium voltage units the connection is made directly to the neutral deriving transformers via rigid conduit connected to the enclosure. The cables are terminated with a compression type lug (customer supplied) to the transformer H1 terminals. Location and termination of the conduit is the customer s responsibility. NOTE The factory supplied drawing identifies the phase and ground connection points. This grounding equipment is not phase rotation sensitive. Any phase can connect to any H1 terminal. Ground Connection The ground lead from the resistive element to ground may be connected one of two ways: 1. On low voltage units the connection is made directly to a control panel mounted ground bus. 2. Medium voltage units have separate grounds for the high voltage ground and a low voltage ground to the secondary of the step-down transformer(s). The HV ground connection is made directly to an internal ½ ground stud via rigid conduit connected to the enclosure. The ground terminal is labeled for easy identification. A compression type lug (customer supplied) is used for ground connection. The low voltage secondary ground connection is made directly to a control panel mounted ground bus. Location and termination of the conduit is the customer s responsibility. NOTE The factory supplied drawing identifies the neutral and ground connections.

Powerohm Resistors Digital HRG System 7 Operator Interface Device (OID) Use and Navigation The Operator Interface Device (OID) provides visual indication of the alarms, status of system parameters, and an interface for adjusting set points to configure the Digital HRG. Drawing not to scale 1 2 6 Item Description 1 LCD Touchscreen 3 4 5 2 Home key This key will always return the on-screen window to the Home window. 3 Main Menu key This key will always return the on-screen window to the Main Menu window. 4 Alarm LED The LED will illuminate when an alarm occurs. 5 Pulser LED This LED will illuminate when the pulser to turned on 6 Pulser key This key will turn on and turn of the pulser. ATTENTION Touch one button at a time. Touching the touchscreen with multiple fingers may result in unintended operation.

8 Powerohm Resistors Digital HRG System Home Window Drawing not to scale 1 12:00 p.m. 2 4 Item Description 1 Window Status Bar Displays the date, time, and background activity such as downloading to a USB memory stick. 2 Current Panel Displays the neutral current and the fault current set point value. It will also blink PULSER ON when pulsing. 3 Voltage Panel Displays the neutral voltage and the voltage for all three phases. 4 Alarm Panel Displays the list of active and recent alarms. Touching a cleared alarm will remove it from the list. The panel will not be displayed if there are no active or recent alarms in the list. 3

Main Menu Window Drawing not to scale Powerohm Resistors Digital HRG System 9 2 3 12:00 p.m. 1 4 5 8 Item Description 1 Quick Start Begins the Quick Start set point configuration process for startup of system. 2 System Set Points Displays a list of all controller, motor, power, and alarm set points. 3 User Preferences Displays a list of all user preference set points. 4 Data Log Lists options for viewing the data log alarms, ground fault alarms, and diagnostic tests. 5 Diagnostics & Tests Lists options for calibrations, fault simulation, capacitive charging current test, and PCB info. 6 Devices Lists options for connected devices, such as Modbus and USB Memory Sticks. 7 About 8 Log In/Log Out 6 7

10 Powerohm Resistors Digital HRG System User Log In Navigating and viewing set point configurations is allowed at all times; however, changing any set point configuration requires the user password. The user password is shown below. This password is also on a label affixed to the enclosure door on the inside. When prompted for the user password, enter the following pin number: 1 2 3 3 3 3 Logging Out If there is no user activity on the OID for five minutes, the login state is automatically logged out. To manually log out From the Main Menu window, touch the Log Out button.

Configuring System Set Points Powerohm Resistors Digital HRG System 11 WARNING Adjustments should be performed by qualified personnel only. Touching the System Set Points button or the User Preference button on the Main Menu Window will load a new window with the following layout: Drawing not to scale 1 12:00 p.m. 2 3 Item Description 1 Back Button This button will return to the previous window. 2 Category List Contains a list of high level set point categories. Touching an item will populate the Settings List with category specific set points. 3 Settings List Contains a list of set points specific to the selected category. Touching an item will load the set point configuration window.

12 Powerohm Resistors Digital HRG System The set point configuration window has the following layout: Drawing not to scale 1 12:00 p.m. 2 3 4 5 6 Item Description 1 Set Point Name 2 Description of Set Point 3 Configuration Area This area is specific to the set point being configured. It consists of standard user interface controls, such as list boxes, radio buttons, and spin lists, which are used to modify the set point value. 4 Default button Loads the default value for the set point, but does not close the window. 5 Cancel button Cancels any changes and returns to the previous window. 6 Set button Saves all changes and returns to the previous window.

Powerohm Resistors Digital HRG System 13 Quick Start The quick start feature is used to sequentially configure the primary system set points without having to navigate through the onscreen menu. The following set points are configured: TBD. Refer to Main Menu Window, Item 1, on page 9 above. To perform a quick start: 1. From the Main Menu window, touch Quick Start. 2. Configure each set point one at a time, pressing the Next button to move to the next set point. 3. A summary will be displayed after the last set point has been configured. Press the Save button to save all set points. 4. The window will return to the Main Menu window. NOTE Canceling the Quick Start process will discard all changes. Set Point List System Set Point Window Pulser Settings Pulse Rate Current Trip Settings Current Trip Alarm Option Pulse Current Ground Fault Time Delay Voltage Trip Settings Line Voltage Connections Voltage Trip Alarm Options Ground Fault Voltage Level Ground Fault Time Delay Aux Programs Aux Program 1 48 User Preference Window User Preferences Language GUI Theme Temperature Unit Date Format Time Format Idle Timeout Change User Password Date & Time Set Date Set Time Daylight Saving Time Option DST Start Date DST End Date Screen Settings Brightness LCD Auto Dim Calibrate Touch Screen

14 Powerohm Resistors Digital HRG System Equipment Operation Always refer to the drawings supplied with your Digital HRG equipment to review design parameters. Drawings will include initial set up instructions pertaining to your specific unit. They will also include resistor tap information, alarm contact detail, and power connection requirements. Contact your Hubbell Powerohm Resistors factory representative if you need assistance. Standard equipment operation is as follows: Normal Operation Under normal operating conditions there is no ground fault present on the system and only a small capacitance charging or magnetizing current flows. During this condition, there is no appreciable voltage present across the resistor. An illuminated green indicating light, located on the front door, verifies normal operating conditions and proper control power. Ground Fault Condition During a ground fault condition a red indicating light, located on the front door, will illuminate, the horn will sound, the Ground Fault alarm message will be displayed on the OID, and the alarm contacts will activate. The horn may be silenced by pressing the alarm silence icon on the OID. All other alarm indicators will remain activated until the ground fault is removed. During a ground fault, voltage will appear across the resistor. The voltage across the resistor will be sensed by the 59G relay. The resistor is designed to limit the ground fault current to a low, acceptable value. Multiple taps are included with the resistor to adjust the fault current to a value slightly greater than the system magnetizing current. The resistance taps can be factory set or adjusted at time of equipment installation, and when additional loads are added to the system in the future. Ground Fault Location To locate the ground fault, activate the pulse contactor by pressing the PULSE key, located on the OID. This activates a cycle of 1 60 pulses per minute (user configured) to alternate the ground fault current between the fault and pulse current settings. A portable clamp-on ammeter (optional) can be used to follow the fluctuating fault current through the system to the location of the fault source. After removing the ground fault, press the PULSE key again to stop the pulsing cycle.

Powerohm Resistors Digital HRG System 15 The Ground Fault alarm message on the OID will display Touch to Clear. Touching the message will remove it from the onscreen list of active and recent alarms. Once all alarms have been cleared, the horn will turn off and the remote alarm indicators will clear, and the green indicating light will illuminate to indicate that the system has returned to normal. HRG System Test To test the system under normal operating conditions: 1. From the Main Menu window, touch Diagnostics & Tests. 2. From the Diagnostics & Tests window, touch Simulate Fault. 3. Logon with the user password if prompted. 4. A confirmation message will be displayed; touch Yes to begin the test. The test will last for 2 5 seconds and it will cause a ground fault alarm, including illuminating the red indicating light, sounding the horn, displaying the Ground Fault alarm message on the OID, and activing the remote alarm contacts. The horn may be silenced by pressing the alarm silence icon on the OID. When the test is complete, the Ground Fault alarm message on the OID will display Touch to Clear. Touching the message will remove it from the onscreen list of active and recent alarms. Once all alarms have been cleared, the horn will turn off and the remote alarm indicators will clear, and the green indicating light will illuminate to indicate that the system has returned to normal

16 Powerohm Resistors Digital HRG System Measure Capacitance and Adjust Taps WARNING Testing for system capacitance leakage current requires that all system loads be connected. Take all necessary safety measures and follow safety practices to avoid injury. Instructions Preconditions 1. Connect and turn on the high resistance ground system with the factory settings or the settings based on calculations. 2. All normal loads need to be connected or their contribution to the system capacitance will not be measured. 3. Verify that no ground faults are indicated by the controller. Clear any ground faults before proceeding. Calculate System Capacitance 1. Press the MENU key on the OID. 2. On the Main Menu window, press the Diagnostics & Tests icon. 3. On the Diagnostics and Tests window, press the Charging Current icon. 4. Logon with the user password if prompted. 5. A confirmation message will be displayed; touch Yes to begin the test. At this point, the system will automatically calculate the system capacitance. The calculation will take 2 5 seconds. Once complete, a message will be displayed indicating the charging current. Use the calculated charging current to adjust the Fault Current system set point. A value 10 percent higher than the charging current is recommended. Refer to the factory supplied drawings to determine which resistor taps to set for the fault current and pulse current. CAUTION Isolate the controller with the disconnect switch before adjusting the resistor taps. Note that medium voltage systems do not disconnect the high voltage neutral connection to the step-down transformer, which will still feed voltage to the terminal strip and line side of the disconnect switch.

Annual Adjustments Powerohm Resistors Digital HRG System 17 The above test to measure the system capacitance leakage current should be performed annually, as over time additional loads may be added to the system. Maintaining the fault setting higher than the system capacitance leakage current allows the HRG to limit transient overvoltages, should an arcing fault develop on the system. Fault current settings higher than recommended by the drawing allows more damage to occur at the point of fault and may subject personnel at the point of fault to injury. If you have questions on this procedure, contact the Hubbell Powerohm Resistors factory.

18 Powerohm Resistors Digital HRG System Maintenance The Digital HRG requires monthly inspections for damage to insure that the resistor is still capable of protecting the system. Damage may occur from lightning, earthquakes, overloads, or extended service life. The following procedure is recommended for field inspections: 1. Isolate the high resistance grounding system with the disconnect switch. Note that medium voltage systems do not disconnect the high voltage neutral connection to the step-down transformer, which will still feed voltage to the terminal strip and line side of the disconnect switch. For complete protection the system must be de-energized. These precautions are recommended to prevent a shock hazard to maintenance personnel and to prevent the system from being operated without proper grounding. 2. Inspect and test the control panel. 3. Carefully check the resistor assembly for cracked ceramics or damaged insulators. A Megger or Hi-Pot test is the most reliable method of ensuring that the porcelain insulation is still providing the necessary electrical isolation. Ground connections must be disconnected to perform this test. 4. Check the resistive element for continuity. An ohmmeter reading made between the neutral and the ground side of the resistor should be within 10% of the drawing values. If the resistance of the element is more than 15% off from the nameplate value, the resistors should be replaced. 5. Check all internal connections for tightness. Check wiring for signs of damage from heat or overloads. 6. Drawings can be supplied by email or fax if we are furnished with complete nameplate information. Finally check the mounting bolts for tightness. CAUTION Maintenance work should be performed by qualified electrical personnel in compliance with national and local safety regulations. NEC requires qualified and trained electrical personnel to be available to supervise operation of this equipment.

Powerohm Resistors Digital HRG System 19 Notes

20 Powerohm Digital HRG System Replacement Parts For replacement parts, contact your local Powerohm Resistors office or the Hubbell Powerohm Resistors factory at: Telephone: (800) 838-4694 Email: sales@powerohm.com Technical Support Telephone: (336) 434-2800 ext. 183 Email: info@powerohm.com www.powerohm.com Hubbell Industrial Controls, Inc. 4301 Cheyenne Drive, Archdale NC 27263 USA Tel: (336) 434-2800, Fax: (336) 434-2801 www.hubbell-icd.com Powerohm Resistors 5713 13 th Street, Katy TX 77493 USA Tel: (859) 384-8088, Fax: (859) 384-8099 Printed in USA