Space Coast Home Inspections LLC

Similar documents
Watson Home Inspection Services, LLC.

Axiom Property Inspections

Inspector Gadget Homes

1921 River Birch Dr., Shawnee, OK Inspection prepared for: Vicki Jager Date of Inspection: 7/27/2015 Time: 8am Weather: Sunny

MHI Services Inc. Property Inspection Report

Extra Mile Inspection, Inc.

Coast Home Inspection

Cascade Inspection Services, LLC

Troy's Home Inspection Services LLC

All In One Home Inspections

Asurity 1. Property Inspection Report S Gurd Rd., Hastings, MI Inspection prepared for: Beretta Lenos Real Estate Agent: Stan Labinski -

Inside Out Home Inspections

Bayshore House Inspections LLC

Jeff Brown Inspections

SPS Home Inspections, LLC

Hearth and Homes Inspections, llc

FAIRA TRANSPARENCY REPORTS th Ave NE B-3, Kenmore, WA March 28 th, 2017

Tennessee Valley Property Inspections

FAIRA TRANSPARENCY REPORTS Country Club Dr, B-203, Mill Creek, WA April 5 th, 2017

FAIRA TRANSPARENCY REPORTS. November 21, 2016

RW West Consultants. Property Inspection Report NE 199th St, Kenmore, WA Inspection prepared for: FAIRA/ Chris Ellis Real Estate Agent: -

Canadian Property Inspections

Final Phase Inspection

FAIRA TRANSPARENCY REPORTS Alaskan Way, 514, Seattle, WA 98101

FAIRA TRANSPARENCY REPORTS Brighton Pl, Mukilteo, WA 98275

FAIRA TRANSPARENCY REPORTS S 236th St, 10-5, Kent, WA 98032

RW West Consultants. Property Inspection Report

FAIRA TRANSPARENCY REPORTS NE 117th Pl, #F8, Kirkland, WA 98034

FAIRA TRANSPARENCY REPORTS W Manor Pl, #413, Seattle, WA August 25, 2017

FAIRA TRANSPARENCY REPORTS th St SW, Lynnwood, WA 98037

FAIRA TRANSPARENCY REPORTS nd Ave S, E-2, SeaTac, WA 98198

FAIRA TRANSPARENCY REPORTS Stone Ave N, #205, Seattle, WA 98133

FAIRA TRANSPARENCY REPORTS th St SW, 301, Lynnwood, WA May 31 st, 2017

The following report was prepared for the buyers of the home and property at 1400 Main St. Anywhere City, Tennessee. The inspection was conducted on

FAIRA TRANSPARENCY REPORTS S 272nd St, #39, Kent, WA September 1 st, 2017

FAIRA TRANSPARENCY REPORTS Greenwood Ave N, N304, Seattle, WA March 21, 2018

Inspection Report. 1 Inspection Way Orlando, FL Prepared for: Wanda Figueroa Prepared by: ACF Home Inspections Inc

FAIRA TRANSPARENCY REPORTS th St SE, Lake Stevens, WA June 14 th, 2017

FAIRA TRANSPARENCY REPORTS Hazel Loop SE, #D, Auburn, WA 98092

FAIRA TRANSPARENCY REPORTS Waverly Dr, Snohomish, WA May 10 th, 2017

Inspection Report. Prepared for: Tonia Mann. Property Address: 402 Leslie Court McDonough, GA Date: March 07, 2013

FAIRA TRANSPARENCY REPORTS Spruce Way, Lynnwood, WA August 21, 2017

FAIRA TRANSPARENCY REPORTS SE 265th St, Covington, WA October 10, 2017

FAIRA TRANSPARENCY REPORTS. November 21, 2016

Bay Wide Commercial and Home Inspection Thackeray Avenue/ Mail address Hayward, Calif TH AVENUE SAN LEANDRO, CALIFORNIA

FAIRA TRANSPARENCY REPORTS. February 28 th, 2018

FAIRA TRANSPARENCY REPORTS Fairview Ave E, #304, Seattle, WA June 7 th, 2017

Excellent Home Inspection Services, LLC

FAIRA TRANSPARENCY REPORTS th Ave, Seattle, WA April 28 th, 2017

FAIRA TRANSPARENCY REPORTS NE 182nd St, C101, Kenmore, WA 98028

FAIRA TRANSPARENCY REPORTS SE Woody Creek Ln, Snoqualmie, WA October 12, 2017

FAIRA TRANSPARENCY REPORTS NE 108th St, Redmond, WA April 4 th 2017

FAIRA TRANSPARENCY REPORTS. March 14 th, 2017

1710 ANYWHERE DRIVE, MONTGOMERY, AL 36109

FAIRA TRANSPARENCY REPORTS S 248th Pl, Des Moines, WA March 12, 2018

FAIRA TRANSPARENCY REPORTS th Dr NE, Marysville, WA June 14 th, 2017

FAIRA TRANSPARENCY REPORTS th Ave S, A304, Des Moines, WA March 13, 2018

FAIRA TRANSPARENCY REPORTS SE 41st Ln, E203, Bellevue, WA April 7 th, 2017

FAIRA TRANSPARENCY REPORTS S 259th St, Des Moines, WA October 2, 2017

FAIRA TRANSPARENCY REPORTS

FAIRA TRANSPARENCY REPORTS. January 27 th, 2017

Amendment to the Inspection Report

FAIRA TRANSPARENCY REPORTS SE 240th Pl, Maple Valley, WA June 5th, 2017

FAIRA TRANSPARENCY REPORTS W Villa Monte Dr, Mukilteo, WA August 8 th, 2017

Inspector FX Field Forms

FAIRA TRANSPARENCY REPORTS th Ave SE, Bothell, WA 98012

fieldwork report contains the Functional

The Salvation Army Southern Territory OFFICERS QUARTERS PROPERTY INSPECTION FORM

FAIRA TRANSPARENCY REPORTS st Ave, #605, Seattle, WA June 2 nd, 2017

FAIRA TRANSPARENCY REPORTS Harbour Pointe Blvd, #301h, Mukilteo, WA 98275

FAIRA TRANSPARENCY REPORTS SE 279th St, Maple Valley, WA March 7, 2018

FAIRA TRANSPARENCY REPORTS Bothell Everett Hwy, D304, Bothell, WA February 6, 2018

Home Inspection Report

FAIRA TRANSPARENCY REPORTS. July 6, 2016

FAIRA TRANSPARENCY REPORTS NE 178th St, Lake Forest Park, WA May 2 nd, 2017

FAIRA TRANSPARENCY REPORTS th Dr NE, Lake Stevens, WA April 4th, 2017

Inspection Report 123 My Street Midland, GA

FAIRA TRANSPARENCY REPORTS st Pl SE, Sammamish, WA May 18 th, 2017

FAIRA TRANSPARENCY REPORTS th Ave S, Auburn, WA June 15 th, 2017

FAIRA TRANSPARENCY REPORTS th Ln NE, Issaquah, WA February 1, 2018

McKinney Inspection Company

FAIRA TRANSPARENCY REPORTS nd Ave SW, Burien, WA October 26 th, 2017

I. STRUCTURAL SYSTEMS

FAIRA TRANSPARENCY REPORTS Highland Dr, Bellevue, WA 98006

Inspection Report. Mr. Happy Homeowner. Property Address: Focal Point Home Inspection Ltd.

Inspecta-Homes 2469 University Avenue West St. Paul MN Ph#: (651)

Canadian Property Inspections

FAIRA TRANSPARENCY REPORTS. 405 SW 346th Pl, Federal Way, WA Nov 09th, 2015

FAIRA TRANSPARENCY REPORTS

FAIRA TRANSPARENCY REPORTS rd Pl SE, Maple Valley, WA April 4 th, 2017

Michael Newell Consulting

Steve Ramsey Home Inspections

FAIRA TRANSPARENCY REPORTS Interlake Ave N, Seattle, WA February 1, 2018

Home Inspection Report

Patriot Home Inspections

This Report Was Prepared For: Property Address Inspected:

Home Inspection Report

BISHOP HOME INSPECTIONS, LLC. Phone (269) / Fax (269) / Website: bishophomeinspection.

FAIRA TRANSPARENCY REPORTS S 284th Ln, #H204, Federal Way, WA March 12, 2018

FAIRA TRANSPARENCY REPORTS th Ave SE, Renton, WA June 13 th, 2017

Transcription:

Cover Page Property Inspection Report 32908 Inspection prepared for: Melvin Jones & Melvin Jones Real Estate Agent: Anita Uhrmann - Caldwell Banker Date of Inspection: 12/16/2014 Time: 11am Age of Home: 8yrs Size: 2250 Weather: sunny Inspector: Donald Anderson License #HI7512

Report Summary Report Summary The summary below consists of potentially significant findings. These findings can be a safety hazard, a deficiency requiring a major expenses to correct or items I would like to draw extra attention to. The summary is not a complete listing of all the findings in the report, and reflects the opinion of the inspector. Please review all of the pages of the report as the summary alone does not explain all the issues. All repairs must be done by a licensed &bonded trade or profession. I recommend obtaining a copy of all receipts, warranties and permits for the work done. Kitchen Page 10 Item: 7 Cook top condition All heating elements operated when tested. When tested there was a electrical short sound. The unit is original and probably should be replaced Water Heater Page 17 Item: 5 Water Heater Condition Garage Page 19 Item: 10 Fire Door After running the hot water for several minutes the water heater base re filled with water. Recommend evaluation buy a licensed plumber. The door between the garage & house is not a fire rated door. @@@This may not have been required when originally built. Fire doors are fundamental to the integrity of fire barriers which provide resistance to the spread of fire, smoke, and toxic gasses. This means that should a fire occur in the garage, this door does not afford protection until fire-rescue people arrive. This door should be replaced with a fire rated door. Does Not Appear to be a Rated Fire Door Roof Page 22 Item: 7 Gutter Extensions / Splash blocks missing or insufficient: Install to divert water away from the foundation. Page 1 of 31

We appreciate the opportunity to conduct this inspection for you! Please carefully read your entire Inspection Report. Call us after you have reviewed your report, so we can go over any questions you may have. Remember, when the inspection is completed and the report is delivered, we are still available to you for any questions you may have, throughout the entire closing process. Properties being inspected do not "Pass" or "Fail. - The following report is based on an inspection of the visible portion of the structure; inspection may be limited by vegetation and possessions. Depending upon the age of the property, some items like GFI outlets may not be installed; this report will focus on safety and function, not current code. This report identifies specific noncode, non-cosmetic concerns that the inspector feels may need further investigation or repair. For your safety and liability purposes, we recommend that licensed contractors evaluate and repair any critical concerns and defects. Note that this report is a snapshot in time. We recommend that you or your representative carry out a final walk-through inspection immediately before closing to check the condition of the property, using this report as a guide. Page 2 of 31

1. Attendance 2. Home Type 3. Occupancy Inspection Details In Attendance: Selling Agent present No other parties present at inspection. Home Type: Single Family Home Occupancy: Occupied - Furnished Page 3 of 31

Interior Areas The Interior section covers areas of the house that are not considered part of the Bathrooms, Bedrooms, Kitchen or areas covered elsewhere in the report. Interior areas usually consist of hallways, foyer, and other open areas. Within these areas the inspector is performing a visual inspection and will report visible damage, wear and tear, and moisture problems if seen. Personal items in the structure may prevent the inspector from viewing all areas on the interior. The inspector does not usually test for mold or other hazardous materials. A qualified expert should be consulted if you would like further testing. 1. Bar 2. Cabinets 3. Ceiling Fans Operated normally when tested, at time of inspection. 4. Closets 5. Door Bell 6. Doors 7. Electrical Some outlets not accessible due to furniture and or stored personal items. 8. Security Bars 9. Smoke Detectors Operated when tested. 10. Stairs & Handrail Page 4 of 31

11. Window-Wall AC or Heat 12. Ceiling Condition 13. Patio Doors Materials: There are drywall ceilings noted. **Sliding Patio Doors** 14. Screen Doors 15. Wall Condition Materials: Drywall walls noted. 16. Fireplace 17. Window Condition Materials: Aluminum framed single hung window noted. Page 5 of 31

Bedrooms The main area of inspection in the bedrooms is the structural system. This means that all walls, ceilings and floors will be inspected. Doors and windows will also be investigated for damage and normal operation. Personal items in the bedroom may prevent all areas to be inspected as the inspector will not move personal items. 1. Locations 2. Cabinets Locations: Master#1 North East#1 South East#2 South East#3 3. Ceiling Fans 4. Closets Operated normally when tested, at time of inspection. The closet is in serviceable condition. 5. Doors 6. Electrical 7. Fireplace 8. Floor Condition 9. Security Bars 10. Smoke Detectors 11. Wall Condition No security bars are present in this room. The smoke detectors operated during the inspection. Materials: Drywall walls noted. Page 6 of 31

12. Window-Wall AC or Heat 13. Window Condition Materials: Aluminum framed single hung window noted. 14. Ceiling Condition Materials: There are drywall ceilings noted. 15. Patio Doors 16. Screen Doors Page 7 of 31

Bathroom Bathrooms can consist of many features from jacuzzi tubs and showers to toilets and bidets. Because of all the plumbing involved it is an important area of the house to look over. Moisture in the air and leaks can cause mildew, wallpaper and paint to peel, and other problems. The home inspector will identify as many issues as possible but some problems may be undetectable due to problems within the walls or under the flooring.. 1. Locations 2. Cabinets 3. Ceiling Condition 4. Counters 5. Doors Locations: Master Bathroom Main floor bath #2 6. Electrical 7. GFCI 8. Exhaust Fan No major system safety or function concerns noted at time of inspection. GFCI in place and operational The bath fan was operated and no issues were found. 9. Floor Condition 10. Heating Central heating and cooling noted in this room. At the time of the inspection, all appeared to be functioning and in serviceable condition. 11. Mirrors Page 8 of 31

12. Plumbing 13. Security Bars 14. Showers 15. Shower Walls 16. Bath Tubs Tub 17. Enclosure 18. Sinks 19. Toilets 0bserved as functional and in good visual condition. 20. Window Condition Materials: Aluminum framed single hung window noted. Spring is broken on master bedroom toilet room. but the window is still operating. Page 9 of 31

Kitchen The kitchen is used for food preparation and often for entertainment. Kitchens typically include a stove, dishwasher, sink and other appliances. 1. Cabinets 2. Counters 3. Dishwasher 4. Doors 5. Garbage Disposal 6. Microwave 7. Cook top condition 8. Oven & Range Operated. The dishwasher appears to be an older unit, and may have reached the end of its useful life. Sliding Door(s) are not securely installed on tracks. Operated - appeared functional at time of inspection. Built-in microwave ovens are tested using normal operating controls. Unit was tested and appeared to be serviceable at time of inspection. Leak and/or efficiency testing is beyond the scope of this inspection. If concerned, client should seek further review by qualified technician prior to closing. Electric cook top noted. All heating elements operated when tested. When tested there was a electrical short sound. The unit is original and probably should be replaced The upper and lower electric oven elements were tested at the time of inspection and appeared to function properly. These can fail at anytime without warning. No warranty, guarantee, or certification is given as to future failures. 9. Sinks Page 10 of 31

10. Drinking Fountain 11. Spray Wand 12. Hot Water Dispenser 13. Soap Dispenser 14. Trash Compactor 15. Vent Condition Materials: Recirculating 16. Window Condition 17. Floor Condition 18. Plumbing 19. Ceiling Condition Materials: There are drywall ceilings noted. 20. Security Bars 21. Patio Doors Page 11 of 31

22. Screen Doors 23. Electrical 24. GFCI 25. Wall Condition GFCI in place and operational. Materials: Drywall walls noted. Page 12 of 31

1. Locations Laundry 2. Cabinets 3. Counters 4. Dryer Vent 5. Electrical 6. GFCI 7. Exhaust Fan None present. 8. Gas Valves 9. Wash Basin 10. Floor Condition 11. Plumbing 12. Wall Condition Materials: Drywall walls noted. Page 13 of 31

13. Ceiling Condition Materials: There are drywall ceilings noted. 14. Security Bars 15. Doors 16. Window Condition Page 14 of 31

Heat/AC The heating, ventilation, and air conditioning and cooling system (often referred to as HVAC) is the climate control system for the structure. The goal of these systems is to keep the occupants at a comfortable level while maintaining indoor air quality, ventilation while keeping maintenance costs at a minimum. The HVAC system is usually powered by electricity and natural gas, but can also be powered by other sources such as butane, oil, propane, solar panels, or wood. The inspector will usually test the heating and air conditioner using the thermostat or other controls. For a more thorough investigation of the system please contact a licensed HVAC service person. 1. Heater Condition 2. Heater Base 3. Enclosure 4. Venting 5. Gas Valves 6. Refrigerant Lines Materials: The home has a dual pack unit. 7. AC Compress Condition Compressor Type: Electric Location: The compressor is located on the exterior east. Appeared functional at the time of inspection. The typical temperature differential split between supply and return air in an air conditioner of this type is 15-20 degrees F. This system responded and achieved an acceptable differential temperature of @@ degrees F. 8. Air Supply 9. Registers The return air supply system appears to be functional. Page 15 of 31

10. Filters 11. Thermostats Location: Located in a filter grill in a hall area wall. Digital - programmable type. Functional at the time of inspection. Page 16 of 31

1. Base 2. Heater Enclosure Water Heater The water heater based has standing water in it it should be drained and cleaned. The water heater enclosure is stained. We recommend cleaning. 3. Combusion 4. Venting 5. Water Heater Condition Heater Type: Gas Location: The heater is located in the garage. After running the hot water for several minutes the water heater base re filled with water. Recommend evaluation buy a licensed plumber. 6. TPRV 7. Number Of Gallons 40 gallons Page 17 of 31

8. Gas Valve 9. Plumbing Appears functional. Materials: PVC 10. Overflow Condition Materials: PVC 11. Strapping Page 18 of 31

1. Roof Condition Garage 2. Walls 3. Anchor Bolts The anchor bolte were inspected and appear to be serviceable. 4. Floor Condition 5. Rafters & Ceiling 6. Electrical 7. GFCI 8. 240 Volt There are no 240 volt outlets visible in this room. 9. Exterior Door 10. Fire Door The door between the garage & house is not a fire rated door. @@@This may not have been required when originally built. Fire doors are fundamental to the integrity of fire barriers which provide resistance to the spread of fire, smoke, and toxic gasses. This means that should a fire occur in the garage, this door does not afford protection until fire-rescue people arrive. This door should be replaced with a fire rated door. Does Not Appear to be a Rated Fire Door Page 19 of 31

11. Garage Door Condition 12. Garage Door Parts 13. Garage Opener Status Chain drive opener noted. 14. Garage Door's Reverse Status Eye beam system present and operating. 15. Ventilation 16. Vent Screens 17. Cabinets 18. Counters 19. Wash Basin Page 20 of 31

1. Electrical Panel Electrical Location: East side of the house. Location: Located in the garage. No major system safety or function concerns noted at time of inspection at main panel box. 2. Main Amp Breaker 150 amp 3. Breakers in off position 0 4. Cable Feeds 5. Breakers 6. Fuses There is an overhead service drop noted. There is an underground service lateral noted. Materials: Copper non-metallic sheathed cable noted. All of the circuit breakers appeared serviceable. Page 21 of 31

1. Roof Condition 2. Flashing Roof Materials: Asphalt shingles noted. No major system safety or function concerns noted at time of inspection. 3. Chimney 4. Sky Lights 5. Spark Arrestor 6. Vent Caps 7. Gutter Extensions / Splash blocks missing or insufficient: Install to divert water away from the foundation. Page 22 of 31

1. Access 2. Structure Scuttle Hole located in: Garage area Attic 3. Ventilation 4. Vent Screens 5. Duct Work 6. Electrical Most areas not accessible due to insulation. 7. Attic Plumbing 8. Insulation Condition Page 23 of 31

9. Chimney 10. Exhaust Vent Page 24 of 31

1. Doors 2. Window Condition Exterior Areas Components appeared in satisfactory condition at time of inspection. Some window screens damaged. 3. Siding Condition 4. Eaves & Facia 5. Exterior Paint 6. Stucco Page 25 of 31

1. Slab Foundation Foundation Concrete slab not visible due to floor coverings. 2. Foundation Perimeter No leaks were observed at the time of the inspection. There was a minor stairs step crack very minor. Monitor caulk and paint. 3. Foundation Walls 4. Cripple Walls Cracks / Holes (1/4" or less) present in: foundation / floor / ext. wall. Consider sealing them to prevent water infiltration. Generally speaking, cracks that are less than 1/4" are not commonly regarded as being structurally significant. 5. Ventilation 6. Vent Screens 7. Access Panel Page 26 of 31

8. Post and Girders 9. Sub Flooring 10. Anchor Bolts 11. Foundation Electrical 12. Foundation Plumbing 13. Sump Pump 14. Ducting Page 27 of 31

Grounds 1. Driveway and Walkway Condition Materials: Concrete driveway noted. Concrete sidewalk noted. Moderate cracks in sidewalk. Repair and / or monitor for expansion and development of trip hazards. 2. Grading No major system safety or function concerns noted at time of inspection. 3. Vegetation Observations Prune or remove any plants that are in contact or proximity to home to eliminate pathways of wood destroying insects. 4. Gate Condition Materials: The gate is made of ok of vinyl material Page 28 of 31

5. Patio and Porch Deck 6. Stairs & Handrail 7. Grounds Electrical 8. GFCI GFCI receptacles are in good condition. 9. Main Gas Valve Condition Materials: East side. 10. Plumbing Materials: There was no visible exterior plumbing to the house at the time of inspection. Outside water pressure was good 11. Water Pressure 12. Pressure Regulator 13. Exterior Faucet Condition 14. Balcony 15. Patio Enclosure There is 1 turn screen it looks like homeowner repair buthas been repaired 16. Patio and Porch Condition Materials: The patio/porch roof is the same as main structure. Page 29 of 31

17. Fence Condition 18. Sprinklers Page 30 of 31

Residential Earthquake Hazards Report Yes No N/A Don't Know Yes No N/A Don't Know Yes No N/A Don't Know 1. Is the water heater braced, strapped, or anchored to resist falling during an earthquake? 2. Is the house anchored or bolted to the foundation? 3. If the house has cripple walls: a. Are the exterior cripple walls braced? Yes No N/A Don't Know Yes No N/A Don't Know Yes No N/A Don't Know Yes No N/A Don't Know Yes No N/A Don't Know Yes No N/A Don't Know Yes No Don't Know Yes No Don't Know b. If the exterior foundation consists of unconnected concrete piers and posts, have they been strengthened? 4. If the exterior foundation, or part of it, is made of unreinforced masonry, has it been strengthened? 5. If the house is built on a hillside: a. Are the exterior tall foundation walls braced? b. Were the tall posts or columns either built to resist earthquakes or have they been strengthened? 6. If the exterior walls of the house, or part of them, are made of unreinforced masonry, have they been strengthened? 7. If the house has a living area over the garage, was the wall around the garage dooropening either built to resist earthquakes or has it been strengthened? 8. Is the house outside an Alquist-Priolo Earthquake Fault Zone (zones immediately surrounding known earthquake faults)? 9. Is the house outside a Seismic Hazard Zone (zone identified as susceptible to liquefication or landsliding)? EECUTED BY: (Seller) (Seller) Date I acknowledge receipt of this form, completed and signed by the seller. I understand that if the seller has answered No to one or more questions, or if seller has indicated a lack of knowledge, there may be one or more earthquake weaknesses in this house. (Buyer) (Buyer) Date Page 31 of 31