The Protection of Machinery Spaces by means of the Local Application of Water Mist. Dr. Tim R. Nichols CPhys FIFireE

Similar documents
Application of BS 8489 to the Protection of Generator Enclosures. IWMA, BRE 22 nd March 2017 Dr Tim Nichols CPhys FIFireE

GUIDELINES FOR THE APPROVAL OF EQUIVALENT FIXED GAS FIRE-EXTINGUISHING SYSTEMS, AS REFERRED TO IN SOLAS 74, FOR MACHINERY SPACES AND CARGO PUMP-ROOMS

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

Watermist Fire Protection of Plant Rooms

26 June 2001 *** I:\CIRC\MSC\1007.DOC INTERNATIONAL MARITIME ORGANIZATION 4 ALBERT EMBANKMENT LONDON SE1 7SR

Safer.Smarter.Tyco. Watermist fire protection Technology you can trust

I wish I could protect my business with the most suitable Water Mist solution to fit my needs.

The Science Behind Water Mist Protection of Typical Building Hazards

POSITION PAPER ON WATER MIST FOR FIRE FIGHTING APPLICATIONS

Water Mist Fire Suppression

Water Mist Fire Protection Systems for the Protection of Industrial Oil Cookers. 8th March 2016 Dr Tim Nichols CPhys MIFireE

MORE THAN JUST FIRE PROTECTION

WATER MIST CONVENTION AND EXHIBITION

TN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco.

4 June This circular supersedes MSC/Circ.914. *** I:\CIRC\MSC\01\1272.doc

Method for testing the suppression performance of fire suppression systems installed in engine compartments of buses and coaches

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

FM Approvals & Water Mist Systems. Paul Bardsley Engineer, FM Approvals

MORE THAN JUST FIRE PROTECTION

tyco Fire & Safety RESEARCH VESSEL - NEW ORLEANS

The metering orifice is sized according to the type and percentage of concentrate used and is also secured with a stainless steel retaining ring)

Fire Protection for Printing Machines with High Pressure Water Mist

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES

HI-FOG for buildings. Technical introduction. Protecting people, property and business continuity. Jussi Tiainen

Australian Standard. Water mist fire protection systems System design, installation and commissioning AS

An Overview of Extinguishing Systems for Computer Equipment

Water Mist v Sprinklers

White Paper. The Victaulic Vortex Fire Suppression System Fire Suppression for Electrical and Electronic Applications

TECHNICAL NOTES. Literature Review on Hybrid Fire Suppression Systems. Peter Raia Michael J. Gollner University of Maryland

Can we use knowledge and experience from other sectors to prove Water mist s suitability for land applications? UK Water Mist Seminar 8th March 2016

Highly Protected Risks in Power Generation Stewart Kidd outlines the issues to consider when installing active fire suppression in power stations THE

The requirements of BS Watermist Fire System standard and how to demonstrate compliance

Proven Fire Fighting Efficiency for Large Transformers with High Pressure Water Mist

Technical Information

International Safety Guide Chapter 30 for Inland Navigation Tank-barges and Terminals. Chapter 30 FIRE-FIGHTING

Fixed fire protection solutions

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

VELMIST. System Mgły Wodnej Niskociśnieniowej

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017

The first tunnel fire. Benefits of fire


U.S. Coast Guard Research and Development Center 1082 Shennecossett Road, Groton, CT

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

ClassNK Technical Information No. TEC-0453 Attachment (1) to ClassNK Technical Information No. TEC-0453 Guidance on SOLAS Chapter II-2 as amended in 2

Zurich s experience case studies

What is HI-FOG? The natural enemy of fire

IMO. Resolution A.952(23) Adopted on 5 December 2003 (Agenda item 17) GRAPHICAL SYMBOLS FOR SHIPBOARD FIRE CONTROL PLANS

IMO FP 53 Report. Lloyd s Register report on the 53 rd session of IMO Fire Protection Sub-Committee. 16 th March, 2009

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS

The History of IWMA. 18th International Water Mist Conference will (IWMC) take place in London on 19th & 20th September 2018

Safer. Smarter. Tyco. I wish I had a flexible FM Approved Water Mist Solution to fit any industrial oil cooker.

FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS

RESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

Fire Suppression Systems

FEMA Recommendations for Protection of Curtained Limited Finishing Workstations using UL 1254 Listed Pre engineered Dry Chemical Systems

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES

Emergency shutdown systems. Procedures for bypassing ESD s

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

IMO INTERPRETATIONS OF FIRE PROTECTION-RELATED PROVISIONS OF THE HSC CODE

Low Pressure INNOVATIVE FIRE PROTECTION SOLUTIONS in the. Woodworking Industry INNOVATIVE FIRE PROTECTION. VID Fire-Kill. Denmark.

UNIFIED INTERPRETATION OF PROVISIONS OF IMO SAFETY, SECURITY, AND ENVIRONMENT-RELATED CONVENTIONS

Rick Seidel Fike Corporation Regional Sales Manager

and Sprinkler System in Resalat Tunnel of Tehran

Watermist Applications and Approvals

Fire Suppression. Water-Mist : A Revolutionary Green Technology in. - by Nimit Sheth TALL, SMART, SAFE BUILDINGS FOR SMART CITIES.

Fire Detection and Alarm System (FDAS) & Fire Detection and Suppression Systems (FDSS) for Buses - Requirements

Shipboard incinerators with capacities up to 4000 kw

4 August Islington Fire Protection Transpower NZ Limited

Moving Target: A Case Study in Providing Fire Protection Below a Reconfigurable Concert Hall Seating System. Part 1: Concept Design

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

NFPA 96, 2017 REVIEW SUMMARY

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

FIRE SUPPRESSION SOLUTIONS

BUS ENGINE COMPARTMENT FIRE PROTECTION SYSTEM FIREPRO TEST REPORT PEER REVIEW

- CONSTRUCTION FIRE SAFETY STANDARDS

Requirements for ships carrying hydrogen and compressed natural gas vehicles

Fire protection for buildings

CERTIFICATION BULLETIN

The development Of the new CEN standard For fire fighting foam systems EN13565 Part 2

SOLIT PROJECT: WATER MIST FIRE SUPPRESSION SYSTEMS AS PART OF THE TUNNEL SAFETY SYSTEM

CO 2 Fire Extinguishing Systems

SUPPRESS FLASHOVER OF GLASS-REINFORCED POLYESTER FIRE WITH WATER MIST INSIDE ISO 9705 ROOM

Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website:

TEST REPORT ON. TESTED FOR: Central States Manufacturing, Inc. 302 Jane Place Lowell, AR Phone: (800) Fax: (800)

Checklist For Life Safety

Fire protection on chemical manufacturing sites

WAS STARTED BY CARLOS BAHAMONDES MASAFIERRO

MIST FIRES AND EXPLOSIONS: FACT OR MYTH? Introduction

CERTIFICATE OF FIRE APPROVAL

Checklist For Building Inspection & Fire Safety

Loss Prevention Standards

IMO UNIFIED INTERPRETATIONS TO SOLAS CHAPTER II-2 AND RELATED FIRE TEST PROCEDURES

Building Standards Division. Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems

Test Report: ICL/H18/9039 Rev 1

RISK ENGINEERING GUIDELINE.

Performance Based Fire Protection With Water Mist

GASEOUS HYDROGEN SYSTEMS

BOC FS125 The Fire Extinguishing Solution

Transcription:

The Protection of Machinery Spaces by means of the Local Application of Water Mist Dr. Tim R. Nichols CPhys FIFireE

2017 Johnson Controls. All rights reserved. Tyco Fire Products LP is a subsidiary of Johnson Controls International Plc. ( JCI ) TYCO, Johnson Controls, and the product names listed in this document are marks and/or registered marks. Unauthorized use is strictly prohibited. The products and specifications published herein are for general evaluation and reference purposes only and are subject to change by JCI without notice. For the most up-to-date information, please visit www.tyco-fire.com. The information provided in this application paper should not be relied on as a substitute for professional advice concerning specific applications. ALTHOUGH JCI HAS ENDEAVORED TO ENSURE ITS ACCURACY, ALL INFORMATION HEREIN IS PROVIDED ON AN AS IS BASIS, WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED. Without limiting the foregoing, JCI does not warrant the accuracy, adequacy or completeness of any such information. All users of the information provided herein assume the risk of use or reliance on such information and JCI shall not be liable for any damages for such use including, but not limited to, indirect, special, incidental or consequential damages.

Contents Introduction.... 2 Local Application.... 2 Extinguishing Options.... 3 Fire Test Protocols.... 3 CNPP TD2 fire test protocol.... 5 Conclusions.... 8 References:........................................................... 8

2 Introduction Water mist fire suppression systems originally designed for ships--have long been identified as a safe and reliable form of extinguishing fires on machinery. Yet, no matter how well designed, engineered and manufactured these systems may be, their safety and reliability depend on the utilization of fire test protocols to determine if they are suitable and approved for specific applications. Water mist fire suppression systems are not a one-size-fits-all solution. Despite this, designers-suppliers often mistakenly interpret an approval as applicable to all risks. The design of water mist systems is both technology and manufacturer dependent; therefore, verification can only be achieved if independent fire testing has been carried out by a published third party protocol. In addition, each protocol has limitations that need to be considered. There are two general categories of water mist test protocols: one in accordance to marine standards and the other in accordance to land standards. These requirements differ substantially. If a marine solution is applied to a landbased application, for example, this could result in inadequate protection. This paper will review the current protection options available for local applications and the correct solutions that should be adopted. Local Application In a local application system, a fixed supply of extinguishing media is discharged into a defined area that has no enclosure or is only partially enclosed. The fire risk is normally of Class B or Class K (See Table 1 below for examples). Application Fuel Type Fire Class Printing Presses Toluene B Industrial Fryers Canola Oil F (K outside of Europe) Generators Diesel B Transformers Oil B Engines Diesel B Table 1 Examples of local applications When protecting the total volume of an area, the effect on openings such as doors and windows needs to be considered; this is not the case in a local application design. Protection by a local application system is often preferred since, in many cases, the hazard is small in relation to the room in which it is contained. To provide a solution that totally floods the volume with extinguishing medium would not be economical. For the purposes of this paper, we consider only local application risks of Fire Class B, such as generators, transformers and industrial machinery. The protection of Class F (K) hazards differs greatly due to the high ignition temperatures of the oils. The latter is restricted to the protection of industrial deep fryers, a separate solution that Johnson Controls Fire Suppression provides.

Extinguishing Options Historically, the two choices of extinguishing media for local application protection have been gas solution, i.e. carbon dioxide (CO 2 ) or water solution, i.e. water spray. Carbon dioxide is designed according to the standards NFPA 12, BS5306 Part 4, ISO 6183 or CEA 4007. Water spray is designed according to the standards NFPA15 and FM 4-1N. Water mist was introduced in the marine industry as a safer alternative to CO 2, which still today is utilized on marine vessels and can be harmful to people. Carbon Dioxide Carbon dioxide extinguishes the fire through the dilution of oxygen. It offers minimum cooling effect, and nozzles need to be directed appropriately for the gas to exclude all oxygen around the combustible surfaces. Since extinguishment is only achieved through reduction in oxygen, the duration of the discharge must be long enough to allow the combustibles to cool below their ignition temperature. Deep-seated fires (those that contain a large amount of residual heat beneath the surface) are normally outside of the practical use of carbon dioxide. The gas is also subject to air movements and therefore cannot be used in ventilated environments. Water Spray Water spray (deluge) systems extinguish the fire by physically separating the combustible with the water so that no contiguous combustion path can form. Water discharges in large quantities providing substantial cooling. Sufficient allowance for bunding to contain the discharged water/combustible and suitable drainage need to be provided for. Since the application is at medium or high velocity the system can function in high airflows, and is therefore suitable for outdoor use. Water Mist Water mist systems extinguish the fire through a combination of dilution of oxygen at the flame front and direct cooling. Their performance is dependent on the layout of nozzles and configuration of the risk. There are no design standards detailing how a water mist system must be designed. Performance criteria and limitations are detailed in third party fire test protocols. Because water mist is affected by ventilation, which must be shut down prior to activation, this system is not suitable for outdoor applications. 3 Fire Test Protocols Fire test protocols are methods used to determine the suitability and approval of water mist for a given application. The first fire test protocol for water mist protection of local applications was published by the International Maritime Organisation (IMO) - IMO MSC/Circ 913 and was later updated and re-designated IMO MSC/Circ 1387. For land-based applications, there are three published fire test protocols: FM 5560 Appendix I; BS 8489 Part 4 (based on the FM protocol); and the French approvals authority CNPP TD2. Each fire test protocol has limitations, and it is important that these limitations are taken into account. As mentioned previously, often, designer-suppliers mistakenly interpret the approval as suitable for all application risks. The limitations of these fire test protocols are as follows: IMO 1387 fire test protocol IMO 1387 was introduced as a first stage intervention to extinguish a fire on board a ship. The goal of designing the protocol around the extinguishment of spray fires from an engine casing was for the local application to be initiated without shutting down the entire engine room. Fire tests are undertaken in an enclosure 100m 2 with a ceiling height of at least 5m. There are 10 test configurations (five undertaken at maximum height, and five undertaken at a 1m height). The approval is for extinguishment to occur within five minutes with no re-ignition. The test protocol is limited to exposed spray fires only. There are no tests on pool fires or concealed fires.

4 As per concept, the design protocol provides primary protection only and requires that a secondary (flooding) protection system be used. This requirement is necessitated by the fact that many water mist applications on land have been installed without a secondary protection system, which seriously compromises the security of the system. A mandated requirement is a minimum 20-minute discharge: many systems are designed with a discharge of a few minutes with no safety factor. Additional requirements include mandatory interlocks for electrical, fuel, lubrication and ventilation shutdown; and suitable containment of the release of flammable liquids. FM5560 fire test protocol The FM5560 fire test protocol (Appendix I) is a land application test. The enclosure has to be a minimum of 500m 3 volume and at least 5m high. There are 23 tests that include: square pool fires (four tests including minimum and maximum nozzle height) channel pool fires (four tests including minimum and maximum nozzle height) spray fires (four tests including minimum and maximum nozzle height) combined pool and spray fires (five arrangements at maximum nozzle height) obstructed pool fire (two tests including minimum and maximum nozzle height) combined pool and spray fires with an external ignition source (two tests including minimum and maximum nozzle height) The pass approval is to extinguish the fire in all tests. The minimum discharge time is 10 minutes or double the worst case extinguishing time. Similar to IMO 1387, other requirements include mandatory interlocks for electrical, fuel, lubrication and ventilation shutdown; and suitable containment of the release of flammable liquids. The BS8489 Part 4 test protocol has been developed from FM5560 and is essentially the same fire test.

CNPP TD2 fire test protocol The CNPP TD2 fire test protocol was established by the French approval body, is a land application test and is based around an actual mock-up. 5 Figure 1 Photo of the Mock-Up of the CNPP TD2 Fire Test The protocol s seven test configurations include: pool fires (two off); large burning spray fire; small burning spray fire; small burning fuel leak fire; large burning fuel leak that could turn into a pool fire; and a cable tray fire. The pass approval is to extinguish the fire in all tests. The minimum discharge time is 10 minutes or double the worst case extinguishing time. Other requirements include mandatory interlocks for electrical, fuel, lubrication and ventilation shutdown; and suitable containment of the release of flammable liquids. In summary, the marine IMO 1387 only permits protection of exposed spray fires, where as FM5560 and CNPP TD2 allow the protection of risks with the potential occurrence of spray fires (exposed or obstructed) and pool fires (exposed or obstructed), as well as electrical fires essentially all potential fire events on land. Since the latter approvals cover all eventualities, a secondary fire protection system is not mandated. Development Programme at CNPP Many years ago, JCI obtained marine approvals in accordance with IMO 1387 for both its low pressure AquaMist ULF and high pressure AquaMist FOG water mist systems. As part of JCI s on-going product development and to prove the differences between IMO 1387 approved systems and land application protocols, JCI undertook the CNPP TD2 tests in 2015. A total of 58 tests were completed, including testing the nozzles approved to IMO 1387. The generator mock-up has a dimension of 5m(length) x 2m(width) x 2m(height). Installed instrumentation included thermocouples, heat flux gauges, pressure sensors and a flow meter. Cameras were used for recording. The fuel package was diesel and fire scenarios varied in fire power: 3MW for the pool fires, 3MW for the spray fires and 2.4MW for the burning leakage fires.

6 Figure 2 Pool Fire Tests (the tray positions are in red) For the pool fire tests, the pool fire on the upper tray (1m 2 ) above the mock-up was 1.1MW, and the pool fire on the lower tray (2.4m 2 ) under the mock-up was 3MW. Figure 3 Spray Fire Tests (spray location is indicated by the red arrow) For the spray fire tests, the small spray was 480kW 590kW, and the large spray was 2.3MW 3MW.

7 Figure 4 Burning Leak Tests (the green arrows indicate the two diesel injection points) For the burning leak fire tests, the small leak was 410kW, and the large leak was 1.9 2.4MW. Figure 5 Cable Fire Tests (cable trays are in red) For the cable fire tests, the set-up partially obstructed the cable trays. The large (horizontal tray) had a fire load consisting of heptane (59MJ) and cables (23 quantity of 80cm length weighing 9kg, equivalent to 378MJ). The small (vertical tray) had a fire load consisting of heptane (29MJ) and cables (23 quantity of 60cm length weighing 7kg, equivalent to 294MJ).

8 The tests were repeated with different nozzle types. Additionally, changes were made to angles, distance, height, k-factor and discharge pressure. The first test results on IMO 1387 nozzles showed that the design could not extinguish the concealed pool fires. In fact, the tests could only be successfully passed through the addition of a foam concentrate in the water mist supply. The k-factor and, hence, flow were higher than that required for the IMO 1387 tests, so more water is required, and nozzle spacing is less. A combination of droplet sizes is necessary to cool the surroundings and displace the oxygen. Larger droplets penetrate the fire plume due to the increased momentum. In reviewing the solutions from competing products approved to CNPP TD2, we identified that every solution has required the use of foam and that no pure water mist system is currently available. Conclusions In order to pass the local application fire tests for a combination of fire scenarios, additional nozzles, increased flow and the addition of foam additive are required. This increases the cost of the system above the commonly used IMO 1387 solution. However, these tests confirm that the IMO 1387 solution should not be used for land-based applications unless the limitations and restrictions of the type of fire that can be extinguished are clearly documented and accepted by the user. In this case, a secondary protection system would also be required, mitigating any possible (misguided) cost savings and complicating system management. In summary, in accordance with the approval requirements, all systems must be supplied with approved components as tested in the fire protocols. References: FM5560 (2016) Approval Standard for Water Mist Systems Appendix I fire Tests for Water Mist Systems for the protection of Local Application Systems. BS8489 Part 4 (2016) Fixed fire protection systems Industrial and commercial Watermist Systems BS 8489-4:2016 Part 4: Fire performance tests and requirements for water mist systems for local applications involving flammable liquid fires.

9 Dr. Tim R. Nichols CPhys FIFireE Dr. Tim R. Nichols holds a Ph.D. in Physics. He undertook postdoctoral work in Japan before returning to the UK to join the fire industry in January 1991. He has held posts in research, product development, sales and international management, and now serves as Sales Director, Special Hazards, Engineered Systems & Water Mist for Europe & Africa at Johnson Controls. He is a member of British and CEN standard committees for water mist systems. Nichols has written several papers and a book on fire extinguishing systems, is an expert witness, and has been involved in the design and supply of several prestigious and large engineering projects protected by water mist systems. He is a Fellow of the Institution of Fire Engineers and a Chartered Physicist.