Product Data. Features/Benefits. AQUAZONE 50PCH,PCV Compact Water Source Heat Pumps with PURON Refrigerant (R-410A) 50 Hz

Similar documents
Product Data. Single-Package Horizontally Mounted Water Source Heat Pumps with Electronic

Product Data. Features/Benefits. Aquazone 50PSH, PSV, PSD Single-Stage Water Source Heat Pumps with PURON Refrigerant (R-410A)

Product Data. AQUAZONE 50HQP Large Capacity Horizontal Water Source Heat Pumps with PURON Refrigerant (R-410A) 6 to 10 Nominal Tons

Product Data. Features/Benefits Carrier s Aquazone WSHPs are an efficient, compact alternative for all boiler/tower and retrofit applications

Genesis Compact (GC) Series Submittal Data

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

Product Data. AQUAZONE 50VS Vertical Stack Water Source Heat Pump with PURON (R-410A) Refrigerant

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Engineered for flexibility and performance

GUIDE SPECIFICATIONS AQUARIUS ii

50 Series AQUAZONE Water Source Heat Pumps

McQuay. Vertical Water Source Heat Pump. FCV, FCG, FCW 036, 042 Vintage A. Last Manufactured: 1993

McQuay Enfinity TM. Horizontal & Vertical Water Source Heat Pump 1/2 to 5 Ton. Catalog

Catalog McQuay Enfinity Horizontal & Vertical Water Source Heat Pumps

EP Model. EP Model Water Source Heat Pump. ½ to 6 Ton

Product Data. Fig. 1 - Unit 50VR -A

Greensource Residential Water Source Heat Pumps. Simply Smart. i Series: SV Model. boschheatingandcooling.com

ENGINEERING SPECIFICATIONS

McQuay Horizontal Water Source Heat Pump 1/2 to 6 Ton

ENGINEERING SPECIFICATIONS

SECTION WATER-SOURCE UNITARY HEAT PUMPS

AAF. Water Source Heat Pump Ceiling Mounted. CCW Vintage E. Last Manufactured: Replacement Parts List No Revision D 08/2016

water to water heat pumps

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers

McQuay. Ceiling Concealed Horizontal Water Source Heat Pump. CCH, CCG, CCW 048, 060 Vintage A. Last Manufactured: 1995

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

AVAILABLE WITH ENERGY SAVING ECM MOTOR

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

RetroAire Model Number: 9,000 to 36,000 Btuh (2.6 to 10.5 kw)

GUIDE SPECIFICATIONS AQUARIUS ii

Reinventing Energy Efficiency

Catalog Enfinity Large Horizontal Water Source Heat Pumps with R-410A Refrigerant

Mammoth Water Source Heat Pumps

Tranquility 30 Two-Stage (TT) Series

McQuay. Large Vertical Water Source Heat Pump. LGP, LHP, LWP Vintage C. Last Manufactured: 1994

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

SECTION WATER-SOURCE UNITARY HEAT PUMPS

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

Enfinity Horizontal Ceiling Catalog Water Source Heat Pumps

SpaceKeeper Console (SKC)

Greensource iseries Water Source Heat Pumps. SV Model. Made in Florida boschheatingandcooling.com

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

Product Data. Features/Benefits. GEMINI 38AKS Commercial Air-Cooled Split Systems 50/60 Hz. 25 to 40 Nominal Tons (82.8 to 127.

DXair Pool Dehumidifiers

Tranquility Console (TRC) Series Submittal Data

Water Source Heat Pumps. Energy efficient heating and cooling commercial applications

THE TRANQUILITY 16 COMPACT (TC) SERIES

Product Data. Features/Benefits All in one package cooling efficiency, installation convenience and ease of accessibility allow for timesaving

Document # R01

Catalog SmartSource Two-Stage Horizontal & Vertical Water Source Heat Pumps

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

HEAT CONTROLLER, INC. HSS Series 1 1/2 to 5 Tons Indoor Split System Geothermal Heat Pumps

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

PAR5. Product Specifications

GT-PW (50YEW) Water-To-Water Series. WATER-TO-WATER PURON SYSTEMS SIZE 010 [10 kw]

Catalog SmartSource Compact Vertical Water Source Heat Pumps. Model GCV - Vertical Unit Sizes (1/2 thru 6 tons)

Product Data. Fig. 1 - Unit 50VG -A

1 to 5 Ton Vertical Wall Mount Air Conditioners Models AVPA

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Advance Product Data. Features/Benefits. 42WKN Hydronic Fan Coil Units

CAS. Product Specifications. COMMERCIAL SPLIT SYSTEMS CONDENSING UNITS R 410A, 6 to 12.5 TONS BUILT TO LAST, EASY TO INSTALL AND SERVICE

Advance Release September 2009

Tranquility Vertical Stack (TSM) Series

9 EER 1-5 Ton Vertical Packaged Wall Mount Air Conditioners

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

Enfinity Console Water Source Heat Pumps 1/2 to 1½ Ton

50VT--C Comfort 14 SEER Single--Packaged Heat Pump System with Puron

CXM/DXM. Application, Operation & Maintenance Instructions 97B0003N08 Revision: 01/10/05. CXM/DXM Digital Heat Pump Controllers.

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Product Data. Features/Benefits. 40QKB024,036 40QKE024,036,048 Cooling Only and Heat Pump In-Ceiling Cassettes. 2to4NominalTons

Product Data. Features/Benefits. 50TJ S Side Discharge Single-Package Rooftop Units 50/60 Hz 15 to 30 Nominal Tons

Manufacturer Update 2014 IGSHPA

K*ES120 DESCRIPTION TECHNICAL GUIDE SPLIT-SYSTEM EVAPORATOR BLOWERS 10 NOMINAL TONS EER 8.5 ACCESSORIES FIELD INSTALLED TABLE 1: ARI RATINGS*

FCC Fan-Coil Units High-Performance, Vertical

MAC-120HE-03 Air-Cooled Chiller

JCseries EVAPORATIVE CONDENSER. engineering data

DXM CONTROLS. DXM Digital Heat Pump Controllers. Application, Operation, & Maintenance. Table of Contents

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

VariCool VAV Engineering Guide

McQuay. Enfinity Vertical Water Source Heat Pump. WFCV, WFCW Design 1. Replacement Parts List No Revision D 03/2018

SPXB-HW Series Single Package Vertical Unit Cooling with Hot Water Heat 1 through 2 tons, up to 47,800 BTUH Heating

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

PAJ3. Product Specifications

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

50Hz AC, HP and Air Handler Units Up to 70 kw. Commercial Split Systems. Reliable, cost-effective and servicefriendly split systems inside and out

CA Model Water Source Heat Pump

EMBASSY SERIES SINGLE PACKAGE AIR CONDITIONERS (WATER-COOLED) C2ED060, 090, 120 & 180 5, 7-1/2, 10 & 15 Nominal Tons

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

Model 655A Sizes

50HJQ004, 005, 006, 007, 008 & 012 SINGLE-PACKAGE HIGH-EFFICIENCY HEAT PUMP UNITS WITH FIELD-INSTALLED ELECTRIC HEAT

From 230 tons to. Water-Source Heat Pump Products. Premium Performance Environmentally Friendly Superior Construction

607C- -A PREFERREDt SINGLE-PACKAGED HEAT PUMP SYSTEM WITH PURONR (R-410A) REFRIGERANT SINGLE AND THREE PHASE 2-5 NOMINAL TONS (SIZES 24-60)

T-CLASS Commercial Split Systems Up to 20-Ton TSA/TPA Models

Water Source Heat Pumps

Transcription:

Product Data AQUAZONE 50PCH,PCV009-060 Compact Water Source Heat Pumps with PURON Refrigerant (R-410A) 50 Hz 2.1 to 15.0 Nominal kw Single-package horizontally and vertically mounted water source heat pumps (WSHPs) with solid-state controls. Compact cabinet design Performance certified to AHRI/ISO/ ASHRAE 13256-1 Suitable for geothermal (with extended range option) and boiler/ tower use with an operating temperature range of -6.7 to 43.3 C Three service panels for compressor section Meets new ASHRAE 90.1 performance requirements Backward compatibility for replacing older units from various manufacturers Puron refrigerant (R-410A) Mute package for quiet operation CE Mark approval Features/Benefits Carrier s Aquazone WSHPs are an efficient, compact alternative for all boiler/tower and retrofit applications Operating efficiency Aquazone WSHP units offer cooling COPs (coefficients of performance) to 7 and heating COPs to 5. Copyright 2010 Carrier Corporation Form 50PC-C1PD

Features/Benefits (cont) All efficiency ratings stated are in accordance with standard conditions under AHRI (Air Conditioning, Heating and Refrigeration Institute U.S.A.)/ ISO (International Organzation for Standardization)/ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers) Standard 13256-1 and provide among the highest ratings in the industry, exceeding ASHRAE 90.1 Energy Standards. High quality construction and testing All units are manufactured to meet extensive quality control standards. An automated control system provides continuous monitoring of each unit and performs quality control checks as equipment progresses through the production process. Standard construction features of the Aquazone units include: Cabinet Heavy gage galvanized sheet metal cabinet construction enables part standardization (i.e., minimal number of parts) and modular design. Cabinet interior surfaces are lined with 12.7 mm thick, 24 kg/m 3 acoustic type insulation. Sheet metal surfaces are treated for maximum corrosion protection to ensure resilience for long term vitality. Compact cabinet dimensions fit tight space limitations in both horizontal and vertical configurations. Compressor Aquazone standard efficiency units include a rotary compressor in sizes 009 and 018 and a scroll compressor in size 024-060 units. Compressors are mounted on an isolated system (i.e., from the cabinet) that maximizes vibration isolation and Table of contents minimizes transmission to the unit structure. Blower and motor assembly Permanent split capacitor (PSC) threespeed blowers are provided with all units to satisfy many air distribution applications. Blower upgrades are available for high-static conditions. Fan speed control allows reduced sound operation. Blower motors operate at lower temperatures to help improve the reliability of the water source heat pump. Refrigeration/water circuit Most units have a sealed refrigerant circuit including a high-efficiency rotary or scroll compressor. Simplified refrigerant circuits provide easy maintenance, higher accuracy and excellent performance. Also standard are a reversing valve (4-way valve), water-torefrigerant coaxial (tube-in-tube) coil, TXV (thermostatic expansion valve), and enhanced aluminum fin/rifled copper tube air-to-refrigerant heat exchanger coil. AHRI/ISO Aquazone units have AHRI/ISO, NRTL (Nationally Recognized Testing Lab), or CSA (Canadian Standards Association) labels and are factory tested under normal operating conditions at nominal water flow rates. Quality assurance is provided via testing report cards shipped with each unit to indicate specific unit performance under cooling and heating modes. The 50PC units have CE MARK approval. Quiet operation Fan motor isolation and hermetic compressor springs provide sound Page Features/Benefits.......................................... 1-4 Model Number Nomenclature................................... 5 Physical Data............................................... 6 Options and Accessories..................................... 7-9 Dimensions............................................ 10,11 Selection Procedure......................................... 12 Performance Data....................................... 13-26 Electrical Data............................................. 27 Typical Piping and Wiring..................................... 28 Typical Control Wiring Schematics........................... 29-33 Application Data........................................ 34-38 Guide Specifications...................................... 39-42 isolation, cabinets are fully insulated to reduce noise transmission, low speed blowers are used for quiet operation through reduced outlet air velocities, and air-to-refrigerant coils are designed for lower airflow coil face velocities. A mute package is also available for extremely noise sensitive applications. Design flexibility Airflow configurations for horizontal units are available in four patterns including left or right return, and left, right, or back discharge. Horizontal units are field convertible from left or right discharge to back discharge. Vertical units are available in four airflow patterns including top discharge with front, right or left return. Standard water temperature range between 15.6 and 35 C offers maximum design flexibility for boiler/tower applications. Water flow rates as low as 2.41 L/s per kw assist with selection from a various range of circulating pumps. Factory-installed options are offered to meet specific design requirements. Safe, reliable operation Standard safety features for the refrigerant circuit include a high-pressure switch, low-pressure sensor to detect refrigerant loss. Equipment safety features include water loop temperature monitoring, voltage protection, water coil freeze protection, and standard electronic condensate overflow shutdown. All safety features are tested and run at the factory to assure proper operation of all components and safety switches. All components are carefully designed and selected for endurance, durability, and carefree day-to-day operation. The Aquazone unit is shipped to provide internal and external equipment protection. Shipping supports are placed under the blower housing and compressor feet. In addition, horizontal and vertical units are both mounted on oversized pallets with lag bolts for sturdiness and maximum protection during transit. Ease of installation The Aquazone unit is packaged for simple low cost handling and requires minimal installation. All units are prewired and factory charged with 2

refrigerant. Horizontal units include factory-installed hanger isolation brackets. Vertical units have an internally trapped condensate drain to reduce labor associated with installing an external trap for each unit. Water connections (FPT) and condensate drains (FPT) are anchored securely to the unit cabinet. Simple maintenance and serviceability The Aquazone WSHP units are constructed to provide easy maintenance. All units allow easy access to the compressor section from 3 sides with large removable panels. Additional panels allow access to the blower and control box sections. The blower housing assembly can be serviced without disconnecting ductwork from the dedicated blower access panel. Blower units come with permanently lubricated bearings for worryfree performance. Blower inlet rings allow blower wheel removal without having to remove the housing or ductwork connections. Electrical disconnection of the blower motor and control box is easily accomplished via quick disconnects on each component. Easy removal of the control box from the unit provides access to all refrigeration components. The refrigeration circuit is easily tested and serviced through high and low pressure ports integral to the refrigeration circuit. Maximum control flexibility Aquazone water source heat pumps provide reliable control operation using a standard microprocessor board with flexible alternatives for many direct digital controls (DDC) applications including the Carrier Comfort Network (CCN) controls and open protocol systems. Carrier s Aquazone standard unit solid-state control system, the Complete C, provides control of the unit compressor, reversing valve, fan, safety features, and troubleshooting fault indication features. The Complete C control is one of the most user friendly, low cost, and advanced control boards found in the WSHP industry. Many features are field selectable to provide the ultimate in field installation flexibility. The overall features of this standard control system include: 50-va transformer assists in accommodating accessory loads. Anti-short cycle timer provides a minimum off time to prevent the unit from short cycling. The 5-minute timer energizes when the compressor is deenergized, resulting in a 5-minute delay before the unit can be restarted. Random start relay ensures a random delay in energizing each different WSHP unit. This option minimizes peak electrical demand during start-up from different operating modes or after building power outages. High and low pressure refrigerant protection safeguards against unreliable unit operation and prevents refrigerant from leaking. Condensate overflow sensor is an electronic sensor mounted to the drain pan. When condensate pan liquid reaches an unacceptable level, the unit is automatically deactivated and placed in a lockout condition. The sensor recognizes 30 continuous seconds of overflow as a fault condition. High and low voltage protection provides safety protection from excessive or low voltage conditions. Automatic intelligent reset will automatically restart unit 5 minutes after shutdown if the fault has cleared. Should a fault occur 3 times sequentially, lockout will occur. Accessory output (24-v) is provided to cycle a motorized water valve or damper actuator with compressor in applications such as variable speed pumping arrangements. Performance monitor (PM) is a unique feature that monitors water temperatures to warn when the heat pump is operating inefficiently or beyond typical operating range. Field selectable switch initiates a warning code on the unit display. Water coil freeze protection (selectable for water or antifreeze) provides a field selectable switch for water and water/glycol solution systems which initiates a fault when temperatures exceed the selected limit for 30 continuous seconds. Air coil freeze protection (check filter operation) provides a field selectable switch for assessing excessive filter pressure drop. The switch initiates a fault when temperatures exceed the selected limit for 30 continuous seconds. Alarm relay setting is a selectable 24-v or pilot duty dry contact for activating a remote alarm. Electric heat option is an output provided on the controller for operating two stages of emergency electric heat. Service Test mode with diagnostic LED (light-emitting diode) allows service personnel to check the operation of the WSHP and control system efficiently. Upon entering Test mode, time delays speed up, and the Status LED flashes a code to indicate the last fault experienced. This mode provides easy fault diagnosis; based on the fault code that the status LED flashes, Carrier troubleshooting tables provide easy reference to typical problems. LED visual output indicates high pressure, low pressure, low voltage, high voltage, air/water freeze protection, condensate overflow, and control status via a LED panel. PremierLink controller adds reliability, efficiency, and simplification The PremierLink direct digital controller can be ordered as a factory-installed option. Designed and manufactured exclusively by Carrier, the controller can be used to actively monitor and control all modes of operation as well as monitor the following diagnostics and features: unit number, zone temperature, zone set point, zone humidity set point, discharge air temperatures, fan status, stages of heating, stages of cooling, outdoor-air temperature, leaving-air temperature, leaving water temperature, alarm status, and alarm lockout condition. This controller has a 38.4 kilobaud communications capability and is compatible with i-vu Open building automation system controls and CCN controls. The addition of the Carrier CO 2 sensor in the conditioned space provides ASHRAE 62-99 compliance and demand controlled ventilation (DCV). A DCV control strategy is especially beneficial for a water source heat pump system to minimize the energy utilized to condition ventilation air. In combination with energy efficient Aquazone units, DCV may be the most 3

Features/Benefits (cont) energy efficient approach ever developed for a water source heat pump system. The PremierLink peer-to-peer, Internet ready communicating control is designed specifically for constant volume (CV) and variable volume and temperature (VVT ) applications. This comprehensive controls system allows water source heat pumps to be linked together to create a fully functional HVAC (heating, ventilation, and air conditioning) automation system. Contact factory for Rohs (restriction of hazardous substances) compliance. Open protocol for diverse control The LON controller option is ideal when building automation requires interoperability across diverse control platforms. This LONMark* compliant offering can operate as stand-alone or as a part of Local Operating Network (LON) via the LonWorks* FTT-10 Free Topology communication network. Pre-engineered application specific to Aquazone water source heat pumps and digital wall sensors communicating over Sensor Link (S-Link) communication protocol completes a system of networked control. Humidity control Aquazone 50PCH,PCV units provide very good latent capacity and are an excellent choice for controlling humidity within a zone in many applications. The latent capacity of the units can be increased based on zone conditions with the use of fan speed control and a humidistat. The Deluxe D controls option provides fan speed control based on relative humidity and is an effective, low-cost means of controlling humidity. Puron refrigerant (R-410A) Puron refrigerant (R-410A) is a nonchlorine based refrigerant. Puron refrigerant characteristics, compared to R-22, have: Binary and near azeotropic mixture of 50% R-32 and 50% R-125. Higher efficiencies (50 to 60% higher operating pressures). Non-ozone depleting potential and low global warming potential. Virtually no glide. Unlike other alternative refrigerants, the two components in Puron refrigerant have virtually the same leak rates. Therefore, refrigerant can be added if necessary without recovering the charge. *Registered trademark of the Echelon Corporation. 4

Model number nomenclature 50PCH,PCV 50PCV 024 F C C 7 0 1 3 0 Aquazone Compact Water Source Heat Pump with Puron Refrigerant (R-410A) 50PCH Horizontal Configuration 50PCV Vertical Upflow Configuration Unit Size 009 030 060 015 036 018 042 024 048 Airflow Configuration Return Discharge Blower Motor 50PCH Units A Right Left PSC HS B Right Back PSC C Right Back PSC HS D Left Right PSC HS E Left Back PSC F Left Back PSC HS S Left Right PSC Z Right Left PSC 50PCV Units F Front Top PSC G Right Top PSC HS H Front Top PSC HS L Left Top PSC M Left Top PSC HS R Right Top PSC Control C Complete C Microprocessor Control D Deluxe D Microprocessor Control L Complete C with LON M Deluxe D with LON P Complete C with PremierLink Control *Available on sizes 009-036 only. Available on sizes 030-060 only. Water Circuit Options 0 None Operating Range/Sound Option 1 Extended Range ( 6.7 to 43.3 C) 2 Extended Range with Mute Package 3 Standard Range (15.6 to 35.0 C) 4 Standard Range with Mute Package Packaging 1 Domestic Revision Code 0 Current Revision Voltage 7 220/240-1-50* 9 380/420-3-50 HS High Static LON LonWorks Open System Protocol PSC Permanent Split Capacitor Heat Exchanger Options A Copper with E-Coated Air Coil C Copper (Std) J Cupronickel with E-Coated Air Coil N Cupronickel A50-8563 5

Physical data IPT Internal Pipe Thread PSC Permanent Split Capacitor PHYSICAL DATA 50PCH,PCV UNITS 50PCH,PCV UNIT 009 015 018 024 030 036 042 048 060 COMPRESSOR (1 each) Rotary Scroll REFRIGERANT TYPE R-410A Factory Charge (kg) 0.52 0.99 1.22 1.22 1.36 1.42 1.98 2.10 2.32 PCS FAN MOTOR AND BLOWER Fan Motor Type...Speeds PSC...3 Fan Motor (W) (hp) 75 ( 1 / 10) 124 ( 1 / 6) 124 ( 1 / 6) 187 ( 1 / 4) 560 ( 3 / 4) 373 ( 1 / 2) 560 ( 3 / 4) 560 ( 3 / 4) 746 (1) Blower Wheel Size (D x W) (mm) 127 x 127 52 x 127 254 x 254 279 x 254 WATER CONNECTION SIZE IPT (in.) 1/ 2 3/ 4 1 HORIZONAL UNITS Air Coil Dimensions (H x W) mm 254 x 381 406 x 559 508 x 635 508 x 635 508 x 711 508 x 711 (1) 508 x (1) 508 x Standard 25 mm Throwaway Filter (Qty) (mm) 254 x 457 406 x 635 406 x 635 457 x 635 457 x 635 or (2) 508 x or (2) 508 x 610, (1) 508 610, (1) 508 356 356 x 356 x 356 Weight (kg) Operating 47 69 72 86 89 92 99 119 138 Packaged 52 72 74 88 92 95 102 123 129 Corner Weight kg Left-Front* 17 24 25 28 30 34 37 44 47 Right-Front* 11 16 17 18 19 21 23 27 29 Left-Back 10 15 16 18 18 20 22 26 28 Right-Back 9 14 14 15 15 17 18 21 23 VERTICAL UNITS Air Coil Dimensions (H x W) (mm) 254 x 381 508 x 438 610 x 552 610 x 718 Standard 25 mm Throwaway Filter (Qty) (mm) 254 x 457 508 x 508 610 x 610 (1) 356 x 610, (1) 457 x 610 Weight (kg) Operating 47 69 72 86 89 92 99 119 126 Packaged 52 72 74 88 92 95 102 123 129 *Front is control box end. NOTE: All units have grommet compressor mountings, TXV (thermostatic expansion valve), and 1 / 2-in. and 3 / 4-in. electrical knockouts. *Front is control box end. 50PCH UNIT CORNER WEIGHTS (kg) 50PCH UNIT SIZE TOTAL LEFT-FRONT* RIGHT-FRONT* LEFT-BACK* RIGHT-BACK* 009 48 17 11 10 9 015 69 24 16 15 14 018 72 25 17 16 14 024 79 28 18 18 15 030 83 30 19 18 15 036 92 34 21 20 17 042 99 37 23 22 18 048 119 44 29 26 21 060 126 47 29 28 23 6

Options and accessories ITEM FACTORY-INSTALLED OPTION FIELD-INSTALLED ACCESSORY Aquazone Thermostats X Ball Valves X Cupronickel Heat Exchangers X Deluxe D Control System X E-Coated Airside Coil X Extended Range Units X Filter Rack X Full Filter Frame X Fire-Rated Hoses X High-Static Blower X Hose Kit Assemblies X LONMark Compliant Controller X PremierLink Controller X PremierLink Accessories X Remote Sensors (CO 2, Humidity Sensors) X Solenoid Valves X Sound Attenuation (Mute) Package X Y Strainers X Factory-installed options Cupronickel heat exchangers are available for higher corrosion protection for applications such as open tower, geothermal, etc. Consult the water quality guidelines for proper application and selection of this option. Deluxe D control system provides the same functions as the Complete C control system while incorporating additional flexibility and functions including: Thermostat input capabilities accommodate emergency shutdown mode and night setback (NSB) with override potential. Night setback from low temperature thermostat with 2-hour override is initiated by a momentary signal from the thermostat. Compressor relay staging is used with dual stage units (units with 2 compressors and 2 Deluxe D controls) or in master/slave applications. Boilerless electric heat control system allows automatic changeover to electric heat at low loop water temperature. Intelligent reversing valve operation minimizes reversing valve operation for extended life and quiet operation. Thermostat type select (Y, O or Y, W) provides the ability to work and select heat pump or heat/cool thermostats (Y, W). Reversing valve signal select (O or B) provides the selection for heat pump O/B thermostats. Dehumidistat input provides fan control for dehumidification operation. Multiple units on one thermostat/wall sensor provides communication for up to three heat pumps on one thermostat. Boilerless changeover temperature provides the selection of boilerless changeover temperature set point. Accessory relays allow configuration for multiple applications including fan and compressor cycling, digital night setback (NSB), mechanical night setback, water valve operation, and outside air damper operation. E-coated airside coil is available for highly corrosive environments. This is an excellent option for coastal areas, marine applications or other areas in which corrosion may be an issue. Extended range units insulate the coaxial coil to prevent condensation, and therefore potential dripping problems, in applications where the entering water temperature is below the normal operating range (less than 15.6 C). Units are capable of operating at a range of 6.7 to 43.3 C. High-static blower increases airflow at various static pressure conditions, providing even more flexibility to the high blower performance offered by the standard models. LONMark compliant controller contains the factoryloaded Aquazone water source heat pump application for an interoperable control solution. PremierLink controller is compatible with the Carrier Comfort Network (CCN) and other building automation systems (BAS). This control allows users the access and ability to change factory-defined settings, thus expanding the function of the standard unit. Sound attenuation package (mute package) is available for applications that require especially low noise levels. With this option, a double application of sound attenuating material is applied to the internal divider, side panels, top and bottom panels. Sound attenuating material is also added to the fan housing. Spring isolation is added to the compressor mounting. The mute package in combination with standard unit noise reduction features (i.e., as mentioned previously) provide sound levels and noise reduction to the highest degree. Field-installed accessories Aquazone thermostats are both attractive and multifunctional, accommodating stand-alone water source heat pump installations. Programmable 7-day thermostat offers 2-stage heat, 2-stage cool, auto changeover, copy command, 4 settings per day, fully electronic, 24 vac, backlit LCD, keypad 7

Options and accessories (cont) lockout, no batteries required, 5-minute compressor protection, NEVERLOST memory, 3 security levels, and temperature display in degrees F or C. Programmable 7-day light-activated thermostat offers the same features as the 7-day programmable thermostat and also includes occupied comfort settings with lights on and unoccupied energy savings with lights off. Programmable 7-day flush-mount thermostat offers same features as the 7-day programmable thermostat including locking coverplate with tamper proof screws, flush to wall mount, holiday/vacation programming, set point limiting, dual point with adjustable deadband, O or B terminal, and optional wall or duct-mounted remote sensor. Programmable 5-day thermostat offers 2-stage heat, 2-stage cool, auto changeover, 5-minute built-in compressor protection, locking cover, temperature display in degrees F or C, keypad lockout, backlit display, 5-1-1 programming, O or B terminal, dual set point with adjustable deadband, configurable display, self-prompting program, and 4 settings per day. Non-programmable thermostat offers 2 heat stages, 2 cool stages, auto changeover, 5-minute built in compressor protection, locking cover, temperature display in degrees F or C, keypad lockout, large display, backlit display, O or B terminal, dual set point with adjustable deadband, and a backplate with terminals. Ball valves (brass body) used for shutoff and balancing water flow. The valves are available with memory, memory stop, and pressure temperature ports. The valves are UL-listed (Underwriters Laboratories [U.S.A. standard]) brass body, ball and stem type with Teflon* seats and seals and are available in five sizes (12.7, 19.0, 25.9, 31.75, 38.1 mm). Filter rack (50.8 mm) is available in place of the standard 25.4 mm return air filter to enhance the filtration system of the water source heat pump. The 50.8 mm filter rack does not include filters. Fire-rated hoses are 61 cm long and have a fixed MPT on one end and a swivel with an adapter on the other end. Hose kits have both a supply and return hose and are stainless steel or galvanized. Five sizes are available (12.7, 19.0, 25.9, 31.75, 38.1 mm). Full filter frame is available in place of the standard 25.4 mm return air filter. The frame includes a locking door to facilitate filter changes and cleaning without disrupting duct connections. Frames are available in 25.9 and 50.8 mm sizes. Hose kit assemblies provide all the necessary components to hook up a water-side system. Supply hose includes a ported ball valve with pressure/temperature (P/T) plug ports, flexible stainless steel hose with swivel and nipple. Return hose includes a ball valve, preset automatic balancing valve (l/s) with two P/T ports, flexible stainless steel hose with a swivel and nipple, balancing valve, and low-pressure drop water control valve. PremierLink accessories provide a fully integrated WSHP DDC system. Accessories include supply air temperature sensors (with override and/or set point adjustment), communicating room sensors, CO 2 sensors (for use in demand controlled ventilation), and linkage thermostats (to control multiple units from one thermostat). Remote sensors are available for Aquazone flush-mount thermostats and for wall (wired and wireless) or duct mounted applications. LON wall sensors are available in 3 models: sensor only, sensor with status override indicator, and sensor with set point, status adjustment override, and digital LCD display. Solenoid valves (brass body) offer 6.5 watt coil, 24 volt, 50/60 Hz, and 7.5-va with slow operation for quiet system application. Three sizes are available. Y strainers (bronze body) are Y type strainers with a brass cap and a stainless steel strainer screen. Maximum operating pressure rating of strainers is 400 psig. Strainers are available with blow down valves. Six sizes are available. *Teflon is a trademark of E. I. du Pont de Nemours and Company. 8

R AQUAZONE THERMOSTATS Carrier Pm AUTO COOL HEAT COOL AUTO HEAT 7-DAY PROGRAMMABLE/ LIGHT-ACTIVATED PROGRAMMABLE 7-DAY PROGRAMMABLE FLUSH MOUNT LON WALL SENSORS 5-DAY PROGRAMMABLE/ NON-PROGRAMMABLE SENSOR ONLY SENSOR WITH OVERRIDE SENSOR WITH SET POINT ADJUSTMENT, OVERRIDE AND DIGITAL LCD 9

Dimensions 50PCH UNITS HORIZONAL AIRFLOW 2' [61cm] Service Access Front BSP Straight Discharge O LEFT RETURN M P CSP N Blower Outlet A Optional 2' [61cm] Service Access Note: Choose either back or straight discharge Air Coil Side Left Return Back Discharge Left Return Back Discharge C 1 / 2" AA [12.7mm] 3.3" Knockout [83.8mm] Low Voltage 1 / 2" [12.7mm] Knockout 0.7" [17.8mm] 3 BB Condensate 3 / 4" IPT N V Blower Outlet Supply 3 / 4" [19.1mm] Knockout Front O M BSP 1.1 [27.9mm] G K J 2 H CAP 1 A Front-View Note: Blower service panel requires 2 service access Unit Hanger Detail Model U [ ] V [ ] W[ ] 009 34.1 [86.6] 21.1 [53.6] 16.9 [42.9] 015-030 43.1 [109.5] 22.2 [56.4] 18.0 [45.7] 036-042 47.1 [119.6] 22.2 [56.4] 18.0 [45.7] 048-060 54.1 [137.4] 26.2 [66.5] 22.0 [55.9] U BSP L F E N Right Return AA 3.3" [83.8mm] D 0.7" [17.8mm] BB Condensate 3 / 4" IPT W Blower Outlet M RIGHT RETURN Back Discharge C Air Coil Side N 2' [61cm] Service Front Access Optional 2' [61cm] Service Access CSP Straight Discharge Note: Choose either back or straight discharge Blower Outlet O A Right Return Back Discharge CSP P M BSP Front Left Return Straight Discharge L O Right Return Straight Discharge Front T S Q Air Coil 1.75 [44.5mm] Air Coil Q S T C R CSP C R B Left Return Left View - Air Coil Opening Front Front B Right Return Right View - Air Coil Opening A50-8568 50PCH UNIT SIZE OVERALL CABINET A Width B Depth C Height WATER CONNECTIONS 1 2 3 Loop In Loop Out Cond 3 / 4-in. IPT D E F G AA BB NOTES: 1. All dimensions are metric (cm) unless stated otherwise. 2. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service. 3. Horizontal units shipped with filter bracket only. This bracket should be removed for return duct connection. 4. Discharge flange and hanger brackets are factory installed. 5. Condensate is 3 / 4-in. (19.1 mm) IPT copper. 6. Blower service panel requires 2 ft (610 mm) service access. 7. Blower service access is through back panel on left or right discharge units or through panel opposite air coil on back discharge units. 50PCH009-060 UNITS Size (FPT) (in.) H 1 / 2-in. Low Voltage ELECTRICAL KNOCKOUTS J 1 / 2-in. K 3 / 4-in. DISCHARGE CONNECTIONS DUCT FLANGE ( 2.5 mm) L M Supply Height N Supply Width O P RETURN CONNECTION USING RETURN AIR OPENING 009 48.5 86.6 27.9 24.3 2.7 3.8 2.7 8.4 0.7 1/ 2 20.6 13.0 5.4 1.9 22.7 17.0 13.3 3.3 41.0 25.0 2.7 1.5 015 51.1 109.5 43.2 38.4 3.4 8.1 3.5 8.4 1.8 1 / 2 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 38.1 2.8 2.5 018 51.1 109.5 43.2 38.4 3.4 10.4 3.5 8.4 1.8 1/ 2 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 38.1 2.8 2.5 024 51.1 109.5 46.5 41.7 3.4 11.3 3.5 8.4 1.8 3/ 4 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 41.4 2.8 2.5 030 51.1 109.5 46.5 41.7 3.4 7.8 3.5 8.4 1.8 3 / 4 30.8 23.2 15.6 6.6 33.8 25.1 10.5 3.3 58.4 41.4 2.8 2.5 036 51.1 119.6 53.3 48.5 3.4 13.4 3.5 8.4 1.8 3/ 4 41.0 33.3 25.7 6.3 40.9 27.9 7.7 6.4 65.8 48.3 2.8 2.5 042 51.1 119.6 53.3 48.5 3.4 11.3 3.5 8.4 1.8 3/ 4 41.0 33.3 25.7 6.3 40.9 27.9 7.7 6.4 65.8 48.3 2.8 2.5 048 61.2 137.4 53.3 48.5 3.4 11.1 3.5 8.4 1.8 1 41.0 33.3 25.7 9.5 41.0 34.8 10.3 3.2 91.2 48.3 2.8 2.5 060 61.2 137.4 53.3 48.5 3.4 9.7 3.5 8.4 1.8 1 41.0 33.3 25.7 4.4 46.0 34.8 10.3 3.2 91.2 48.3 2.8 2.5 Low Voltage Supply Q Return Depth R Return Height AIRFLOW CONFIGURATION Code Return Discharge D or S Left Right E or F Left Back A or Z Right Left B or C Right Back BSP Blower Service Panel CAP Control Access Panel CSP Compressor Service Panel FPT Female Pipe Thread S a50-8568 T 10

50PCV UNITS VERTICAL UPFLOW P N Field Installed Discharge Flange Access Panels Standard Filter Bracket O Q Air Coil & Front Side Top View-Front Return Air Coil P N N B P BSP ASP O Q Front Air Coil Side Air Coil Side Front O A M CSP CAP Opptional 2' [61cm] Service Access Left Rtn (Right Rtn Opposite Side) Top View-Right Return Top View-Left Return U R S U S R 2' [61cm] Service Isometric View 1.00 [25.4 mm] Air Coil Air Coil T T BSP C Front CSP Right Return Right View - Air Coil Opening Back C Back AIRFLOW CONFIGURATION Code Return Discharge F or H Front Top L or M Left Top G or R Right Top CSP Left Return Left View - Air Coil Opening Front Supply 3/4" [19.1 mm] HV Knockout Low Voltage 1/2" [12.7 mm] LV Knockout Low Voltage 1/2" [12.7 mm] LV Knockout CSP CAP L K J 2 3 1 Front-View ASP Alternate Service Panel BSP Blower Service Panel CAP Control Access Panel CSP Compressor Service Panel G E I D Condensate 3/4" IPT H F A50-8569 50PCV009-060 UNITS 50PCV UNIT SIZE OVERALL CABINET WATER CONNECTIONS ELECTRICAL KNOCKOUTS A Width B Depth C Height 1 2 3 D E F G Loop In Loop Out H I Size (FPT) (in.) J 1 / 2-in. K 1 / 2-in. L 3 / 4-in. Low Voltage Low Voltage Supply M DISCHARGE CONNECTION DUCT FLANGE INSTALLED 2.5 mm N O Supply Width P Supply Depth Q R RETURN CONNECTION USING RETURN AIR OPENING S Return Depth T Return Height U 009 48.5 48.5 27.9 3.6 4.1 24.1 4.3 15.6 4.1 1 / 2 7.3 14.9 22.5 22.7 12.9 22.9 22.9 14.0 5.3 41.1 25.1 1.9 015 54.6 54.6 99.1 4.8 3.6 35.1 3.6 20.6 3.6 1 / 2 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 53.1 1.9 018 54.6 54.6 99.1 4.8 3.6 32.8 3.6 20.6 3.6 1 / 2 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 53.1 1.9 024 54.6 54.6 101.6 4.8 3.6 35.1 3.6 20.6 3.6 3 / 4 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 53.1 1.9 030 54.6 54.6 101.6 4.8 3.6 38.6 3.6 20.6 3.6 3 / 4 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.6 5.8 46.5 53.1 1.9 036 54.6 66.0 114.3 4.8 3.6 39.9 3.6 20.6 3.6 3 / 4 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.1 5.8 57.9 60.7 1.9 042 54.6 66.0 114.3 4.8 3.6 42.0 3.6 20.6 3.6 3 / 4 10.5 18.1 25.7 16.1 9.5 35.6 35.6 13.1 5.8 57.9 60.7 1.9 048 61.0 82.6 116.8 4.8 3.6 42.2 3.6 20.6 3.6 1 10.5 18.1 25.7 17.4 18.4 40.6 45.7 13.1 5.8 74.4 57.0 1.9 060 61.0 82.6 116.8 4.8 3.6 43.7 3.6 20.6 3.6 1 10.5 18.1 25.7 17.4 18.4 40.6 45.7 13.1 5.8 74.4 57.0 1.9 NOTES: 1. All dimensions are metric (cm) unless stated otherwise. 2. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service. 3. Front and side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available. Except on PCV015-030 with front return. 4. Discharge flange is field installed. 5. Condensate is 3 / 4-in. IPT. 11

Selection procedure (with 50PCH024 example) I II III IV Determine the actual cooling and heating loads at the desired dry bulb (db) and wet bulb (wb) conditions. Given: Total Cooling (TC)...................5.9 kw Sensible Cooling (SC)................4.3 kw Entering-Air Temperature db............ 27 C Entering-Air Temperature wb............ 18 C Determine the following design parameters: Entering water temperature, water flow rate (L/s), airflow (L/s), water flow pressure drop and design wet and dry bulb temperatures. Airflow should be between 40 and 60 L/s per kw. Unit water pressure drop should be kept as close as possible across units to make water balancing easier. Enter the 50PCH024 Performance Data tables and find the proper indicated water flow and water temperature. For example: Entering Water Temperature............ 30 C Water Flow (Based upon 6.7 C rise in temperature).......... 0.284 L/s Airflow.......................... 240 L/s Select a unit based on total cooling and total sensible cooling conditions. Enter tables at the design water flow and water temperature. Read the total and sensible cooling capacities. NOTE: Interpolation is permissible, extrapolation is not. For example: Enter the 50PCH024 performance table at design water flow and water temperature. Read total cooling, sensible cooling and heat of rejection capacities: Total Cooling.....................5.94 kw Sensible Cooling.................. 4.92 kw Heat of Rejection..................7.53 kw Read the heat capacity. If the heat capacity exceeds the design criteria, it is acceptable. NOTE: It is quite normal for water source heat pumps to be selected on cooling capacity only since the heating output is usually greater than the cooling capacity. Determine the correction factors associated with the variable factors of dry bulb and wet bulb using the correction factors tables found in this book. V VI Using the following formulas to determine the correction factors of dry bulb and wet bulb: a) Corrected Total Cooling = tabulated total cooling x wet bulb correction x airflow correction. b) Corrected Sensible Cooling = tabulated sensible cooling x wet/dry bulb correction x airflow correction Determine entering air and airflow correction using the correction factors tables found in this book. The nominal airflow for 50PCH024 is 274 L/s. The design parameter is 240 L/s. 230/307 = 88% of nominal airflow Use the 88% row in the Airflow Correction table. The entering air temperature wb is 18 C. Use the 18 C row in the Entering Air Correction table. Using the following formulas to determine the correction factors of entering air and airflow correction: Table Ent Air Airflow Corrected Corrected Total Cooling = 5.94 x 0.9681 x 0.9837 = 5.66 Corrected Sensible Cooling = 4.92 x 1.1213 x 0.9393 = 5.18 Corrected Heat of Rejection = 7.53 x 0.9997 x 0.9826 = 7.40 Compare the corrected capacities to the load requirements established in Step I. If the capacities are within 10% of the load requirements, the equipment is acceptable. It is better to undersize than oversize as undersizing improves humidity control, reduces sound levels and extends the life of the equipment. Calculate and assess the water temperature rise. Calculate the water temperature rise and assess the selection using the following calculation: Actual Temperature Rise = Correction Heat of Rejection L/s x 4.16 For example, using the Corrected Heat of Rejection from the last step: Actual Temperature Rise = 7.40 0.284 x 4.16 = 6.26 C If the units selected are not within 10% of the load calculations, review what effect changing the gpm, water temperature and/or airflow will have on the corrected capacities. If the desired capacity cannot be achieved, select the next larger or smaller unit and repeat Steps I through VI. 12

Performance data 50PCH, PCV UNIT SIZE NOTES: 1. Cooling capacities based on 27 C db and 19 C wb entering air temperature. 2. Heating capacities based on 20 C db and 15 C wb entering air temperature. 3. Ground loop heat pump ratings based on 15% menthol antifreeze solution. 4. All ratings based upon operation at lower voltage of dual voltage rated models. ASHRAE/AHRI/ISO 13256-1 CAPACITY RATINGS WATER LOOP HEAT PUMP GROUND WATER HEAT PUMP GROUND LOOP HEAT PUMP COOLING 30 C HEATING 20 C COOLING 15 C HEATING 10 C COOLING 25 C HEATING 0 C CAPACITY COOLING COP CAPACITY COP CAPACITY COOLING COP CAPACITY COP CAPACITY COOLING COP CAPACITY 009 2.11 3.8 2.75 4.1 2.43 6.0 2.33 3.8 2.23 4.5 1.87 3.3 015 3.48 4.4 4.11 4.9 4.04 7.0 3.42 4.3 3.60 4.9 2.63 3.5 018 4.16 4.1 5.10 4.9 4.95 6.9 4.08 4.3 4.42 4.6 3.30 3.3 024 5.97 4.1 6.93 5.0 6.73 6.4 5.84 4.3 6.27 4.7 4.50 3.5 030 7.08 4.1 8.54 4.9 7.99 6.2 7.20 4.3 7.28 4.6 5.69 3.6 036 8.69 4.2 10.99 4.7 9.75 6.4 9.12 4.2 8.89 4.6 7.20 3.5 042 10.10 4.0 12.82 4.6 11.57 6.0 10.70 4.0 10.21 4.4 8.34 3.4 048 12.02 4.1 13.59 5.0 13.68 6.3 11.31 4.3 12.35 4.5 8.85 3.6 060 14.97 4.1 18.73 4.6 16.78 6.1 15.56 4.0 15.14 4.6 12.28 3.3 COP 13

Performance data (cont) Dry Bulb Coefficient of Performance Entering Air Temperature (C) Energy Efficiency Ratio Entering Water Temperature (C) Heating Capacity Heat of Extraction Heat of Rejection Latent Heat Leaving Water Temperature Sensible Capacity Total Capacity Wet Bulb Water Pressure Differential 50PCH,PCV009 121 L/S NOMINAL AIRFLOW WATER/BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C EWT (C) Flow WPD (L/s) (kpa) TC SC HR EER HC HE LAT COP 0.07 12.9-5.0 0.11 17.3 0.14 28.5 1.71 0.54 1.17 31.7 3.2 0.0 0.07 0.11 0.14 8.2 13.5 23.4 2.53 2.60 2.63 1.74 1.73 1.73 0.34 0.32 0.30 2.88 2.92 2.93 7.4 8.2 8.6 1.82 1.90 1.94 0.55 0.55 0.56 1.27 1.35 1.36 32.5 33.0 33.3 3.3 3.4 3.5 db COP EAT EER EWT HC HE HR LAT LWT SC TC wb WPD 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 0.07 0.11 0.14 0.07 0.11 0.14 0.07 0.11 0.14 0.07 0.11 0.14 0.07 0.11 0.14 0.07 0.11 0.14 0.07 0.11 0.14 0.07 0.11 0.14 0.07 0.11 0.14 5.8 11.2 20.2 4.4 9.6 18.0 3.5 8.5 16.3 2.9 7.6 15.0 2.4 7.0 13.9 2.1 6.4 13.0 1.8 6.0 12.3 1.6 5.6 11.6 1.4 5.2 11.1 2.45 2.52 2.55 2.35 2.43 2.46 1.70 1.72 1.72 1.67 1.70 1.70 2.03 2.11 2.15 1.90 1.99 2.03 1.76 1.86 1.90 1.62 1.72 1.76 1.47 1.57 1.62 1.73 1.74 1.74 1.72 1.73 1.73 2.25 2.33 2.37 2.14 2.23 2.27 1.63 1.66 1.68 1.58 1.62 1.64 1.52 1.57 1.59 1.44 1.50 1.52 1.35 1.41 1.44 0.38 0.35 0.34 0.42 0.39 0.38 0.47 0.43 0.42 0.52 0.48 0.46 0.57 0.53 0.51 0.63 0.59 0.57 0.68 0.64 0.62 0.74 0.70 0.68 0.81 0.77 0.75 2.83 2.87 2.89 2.78 2.82 2.84 2.72 2.76 2.79 2.66 2.71 2.73 2.60 2.64 2.67 2.53 2.58 2.60 2.45 2.50 2.53 2.37 2.42 2.45 2.28 2.33 2.36 6.4 7.2 7.6 5.6 6.2 6.6 4.8 5.4 5.7 4.1 4.6 4.9 3.6 4.0 4.2 3.0 3.4 3.6 2.6 2.9 3.1 2.2 2.4 2.6 1.8 2.0 2.2 2.04 2.13 2.17 2.25 2.35 2.41 2.46 2.57 2.63 2.67 2.78 2.84 2.87 2.98 3.04 3.05 3.17 3.22 0.56 0.57 0.57 0.58 0.58 0.59 0.59 0.60 0.61 0.61 0.62 0.63 0.63 0.64 0.65 0.65 0.66 0.67 1.47 1.56 1.60 1.67 1.77 1.82 1.87 1.97 2.02 2.06 2.16 2.22 2.24 2.34 2.40 2.40 2.51 2.56 34.0 34.6 34.9 35.4 36.1 36.5 36.9 37.6 38.0 38.3 39.1 39.5 39.7 40.5 40.9 40.9 41.7 42.1 3.6 3.7 3.8 3.9 4.0 4.1 4.1 4.3 4.3 4.4 4.5 4.5 4.6 4.7 4.7 4.7 4.8 4.8 NOTES: 1. Interpolate is permissable; extrapolation is not. 2. All entering air conditions are 27 C db and 19 C wb in cooing and 20 C db in heating. 3. Table does not reflect fan or pump power connections for AHRI/ ISO conditions. 4. All performance data is based upon the lower voltage of dual voltage rated units. 5. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 6. Operation below 4 C EWT is based on 15% methanol antifreeze solution. 7. Operation below 16 C EWT requires optional insulated water/ refrigerant circuit. 8. See performance correction tables for operating conditions other than those listed above. 9. Shaded area refers to calculations required to determine if heating water flow is sufficient for the non-antifreeze systems. 14

50PCH,PCV015 192 L/S NOMINAL AIRFLOW WATER/BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C EWT (C) Flow WPD (L/s) (kpa) TC SC HR EER HC HE LAT COP 0.12 8.8-5.0 0.18 15.0 0.24 26.3 2.52 0.80 1.72 30.86 3.16 0.0 0.12 0.18 0.24 6.6 12.2 22.1 4.32 4.36 4.38 3.13 3.14 3.15 0.55 0.50 0.48 4.86 4.87 4.86 7.92 8.68 9.07 2.73 2.86 2.92 0.81 0.82 0.82 1.92 2.04 2.10 31.79 32.32 32.61 3.37 3.48 3.54 db COP EAT EER EWT HC HE HR LAT LWT SC TC wb WPD 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 0.12 0.18 0.24 0.12 0.18 0.24 0.12 0.18 0.24 0.12 0.18 0.24 0.12 0.18 0.24 0.12 0.18 0.24 0.12 0.18 0.24 0.12 0.16 0.24 0.12 0.18 0.24 5.3 10.5 19.4 4.4 9.3 17.5 3.8 8.5 16.0 3.4 7.8 14.8 3.0 7.2 13.9 2.8 6.8 13.1 2.5 6.3 12.5 2.3 6.0 11.9 2.1 5.7 11.4 4.23 4.30 4.33 4.10 4.20 4.24 3.95 4.07 4.12 3.78 3.91 3.97 3.59 3.73 3.80 3.38 3.53 3.60 3.16 3.31 3.39 2.94 3.09 3.17 2.71 2.86 2.94 Dry Bulb Coefficient of Performance Entering Air Temperature (C) Energy Efficiency Ratio Entering Water Temperature (C) Heating Capacity Heat of Extraction Heat of Rejection Latent Heat Leaving Water Temperature Sensible Capacity Total Capacity Wet Bulb Water Pressure Differential 3.09 3.12 3.13 3.04 3.08 3.09 2.97 3.02 3.04 2.91 2.96 2.98 2.83 2.89 2.92 2.76 2.81 2.84 2.67 2.73 2.76 2.58 2.64 2.67 2.49 2.55 2.58 0.60 0.56 0.54 0.67 0.62 0.59 0.73 0.68 0.66 0.80 0.75 0.72 0.88 0.82 0.80 0.96 0.90 0.87 1.04 0.99 0.96 1.13 1.07 1.04 1.23 1.17 1.14 4.83 4.86 4.87 4.77 4.82 4.84 4.68 4.75 4.78 4.58 4.66 4.70 4.47 4.55 4.59 4.34 4.43 4.48 4.21 4.30 4.35 4.07 4.16 4.21 3.94 4.03 4.07 7.00 7.71 8.09 6.16 6.81 7.15 5.39 5.97 6.29 4.70 5.21 5.49 4.08 4.53 4.77 3.52 3.91 4.13 3.03 3.36 3.55 2.59 2.88 3.04 2.20 2.45 2.58 3.10 3.25 3.33 3.47 3.64 3.73 3.84 4.02 4.12 4.20 4.40 4.51 4.55 4.77 4.89 4.90 5.13 5.26 0.84 0.84 0.85 0.86 0.87 0.87 0.88 0.89 0.89 0.90 0.91 0.91 0.92 0.93 0.93 0.93 0.94 0.95 2.27 2.40 2.48 2.61 2.77 2.85 2.96 3.13 3.23 3.30 3.49 3.59 3.64 3.84 3.96 3.97 4.19 4.31 33.39 34.00 34.35 34.98 35.68 36.07 36.55 37.34 37.77 38.10 38.97 39.44 39.64 40.57 41.09 41.14 42.14 42.69 3.71 3.84 3.92 4.05 4.19 4.27 4.37 4.52 4.61 4.67 4.84 4.93 4.97 5.15 5.24 5.26 5.44 5.54 NOTES: 1. Interpolate is permissable; extrapolation is not. 2. All entering air conditions are 27 C db and 19 C wb in cooing and 20 C db in heating. 3. Table does not reflect fan or pump power connections for AHRI/ ISO conditions. 4. All performance data is based upon the lower voltage of dual voltage rated units. 5. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 6. Operation below 4 C EWT is based on 15% methanol antifreeze solution. 7. Operation below 16 C EWT requires optional insulated water/ refrigerant circuit. 8. See performance correction tables for operating conditions other than those listed above. 9. Shaded area refers to calculations required to determine if heating water flow is sufficient for the non-antifreeze systems. 15

Performance data (cont) Dry Bulb Coefficient of Performance Entering Air Temperature (C) Energy Efficiency Ratio Entering Water Temperature (C) Heating Capacity Heat of Extraction Heat of Rejection Latent Heat Leaving Water Temperature Sensible Capacity Total Capacity Wet Bulb Water Pressure Differential 50PCH,PCV018 230 L/S NOMINAL AIRFLOW WATER/BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C EWT (C) Flow WPD (L/s) (kpa) TC SC HR EER HC HE LAT COP 0.14 17.7-5.0 0.21 27.2 0.28 46.5 2.94 0.94 2.01 30.60 3.14 0.0 0.14 0.21 0.28 13.8 22.6 39.4 5.48 5.67 5.78 4.13 4.18 4.20 0.65 0.58 0.54 6.12 6.25 6.32 8.48 9.83 10.67 3.19 3.33 3.41 0.96 0.96 0.97 2.24 2.37 2.44 31.51 32.01 32.28 3.34 3.45 3.51 db COP EAT EER EWT HC HE HR LAT LWT SC TC wb WPD 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 0.14 0.21 0.28 0.14 0.21 0.28 0.14 0.21 0.28 0.14 0.21 0.28 0.14 0.21 0.28 0.14 0.21 0.28 0.14 0.21 0.28 0.14 0.21 0.28 0.14 0.21 0.28 11.4 19.6 34.8 9.9 17.6 31.5 8.7 16.1 28.9 7.8 14.8 26.9 7.1 13.8 25.3 6.5 13.0 24.0 6.1 12.3 22.8 5.6 11.6 21.8 5.3 11.1 20.9 5.25 5.44 5.53 5.02 5.20 5.30 4.78 4.97 5.06 4.54 4.72 4.82 4.28 4.47 4.57 4.00 4.20 4.30 3.70 3.91 4.02 3.37 3.60 3.70 3.02 3.25 3.36 4.04 4.12 4.15 3.93 4.02 4.06 3.80 3.90 3.95 3.66 3.77 3.82 3.51 3.62 3.68 3.35 3.47 3.52 3.18 3.30 3.36 3.0 3.12 3.19 2.79 2.93 2.99 0.73 0.66 0.63 0.81 0.74 0.71 0.9 0.83 0.79 0.99 0.92 0.88 1.08 1.01 0.97 1.19 1.11 1.07 1.30 1.22 1.18 1.43 1.34 1.30 1.56 1.48 1.43 5.97 6.10 6.16 5.83 5.94 6.01 5.68 5.79 5.85 5.52 5.64 5.70 5.36 5.48 5.54 5.19 5.31 5.38 5.00 5.13 5.20 4.80 4.94 5.01 4.58 4.72 4.80 7.22 8.24 8.85 6.20 7.00 7.47 5.34 6.00 6.37 4.60 5.15 5.46 3.95 4.42 4.68 3.37 3.78 4.00 2.84 3.20 3.40 2.36 2.68 2.85 1.93 2.20 2.35 3.62 3.79 3.88 4.06 4.25 4.35 4.50 4.71 4.84 4.94 5.18 5.32 5.38 5.66 5.81 5.82 6.13 6.29 0.98 0.99 1.00 1.01 1.02 1.03 1.03 1.05 1.05 1.06 1.07 1.07 1.08 1.09 1.10 1.10 1.11 1.12 2.64 2.79 2.88 3.05 3.23 3.33 3.46 3.67 3.78 3.88 4.12 4.25 4.30 4.57 4.71 4.73 5.02 5.17 33.06 33.65 33.98 34.63 35.32 35.7 36.21 37.00 37.43 37.80 38.69 39.18 39.39 40.39 40.93 41.00 42.09 42.69 3.68 3.81 3.88 4.01 4.16 4.24 4.35 4.51 4.60 4.67 4.85 4.95 5.00 5.19 5.30 5.31 5.52 5.63 NOTES: 1. Interpolate is permissable; extrapolation is not. 2. All entering air conditions are 27 C db and 19 C wb in cooing and 20 C db in heating. 3. Table does not reflect fan or pump power connections for AHRI/ ISO conditions. 4. All performance data is based upon the lower voltage of dual voltage rated units. 5. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 6. Operation below 4 C EWT is based on 15% methanol antifreeze solution. 7. Operation below 16 C EWT requires optional insulated water/ refrigerant circuit. 8. See performance correction tables for operating conditions other than those listed above. 9. Shaded area refers to calculations required to determine if heating water flow is sufficient for the non-antifreeze systems. 16

50PCH,PCV024 274 L/S NOMINAL AIRFLOW WATER/BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C EWT (C) Flow WPD (L/s) (kpa) TC SC HR EER HC HE LAT COP 0.19 17.9-5.0 0.28 31.1 0.38 55.4 4.18 1.34 2.84 32.63 3.12 0.0 0.19 0.28 0.38 14.9 26.9 48.5 7.23 7.36 7.43 5.48 5.53 5.54 0.95 0.89 0.87 8.18 8.26 8.29 7.57 8.23 8.56 4.54 4.74 4.85 1.47 1.48 1.48 3.07 3.26 3.37 33.71 34.32 34.65 3.09 3.21 3.27 db COP EAT EER EWT HC HE HR LAT LWT SC TC wb WPD 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 0.19 0.28 0.38 0.19 0.28 0.38 0.19 0.28 0.38 0.19 0.28 0.38 0.19 0.28 0.38 0.19 0.28 0.38 0.19 0.28 0.38 0.28 0.38 0.19 0.19 0.28 0.38 13.0 24.2 44.0 11.6 22.2 40.6 10.6 20.7 38.0 9.8 19.4 35.9 9.2 18.4 34.1 8.6 17.5 32.7 8.1 16.8 31.3 7.7 16.1 30.2 7.4 15.6 29.3 7.03 7.19 7.26 6.81 6.99 7.07 6.57 6.76 6.85 6.30 6.51 6.61 6.02 6.23 6.34 5.71 5.94 6.05 5.39 5.63 5.74 5.05 5.30 5.42 4.70 4.95 5.08 Dry Bulb Coefficient of Performance Entering Air Temperature (C) Energy Efficiency Ratio Entering Water Temperature (C) Heating Capacity Heat of Extraction Heat of Rejection Latent Heat Leaving Water Temperature Sensible Capacity Total Capacity Wet Bulb Water Pressure Differential 5.41 5.47 5.50 5.31 5.39 5.42 5.20 5.29 5.33 5.08 5.17 5.22 4.95 5.05 5.09 4.82 4.92 4.96 4.69 4.79 4.83 4.56 4.66 4.70 4.43 4.53 4.57 1.04 0.97 0.94 1.14 1.06 1.02 1.26 1.17 1.12 1.39 1.29 1.24 1.55 1.43 1.37 1.72 1.59 1.53 1.92 1.78 1.70 2.15 1.98 1.91 2.41 2.22 2.13 8.07 8.16 8.20 7.95 8.05 8.09 7.82 7.92 7.97 7.69 7.79 7.84 7.56 7.66 7.71 7.43 7.53 7.58 7.31 7.40 7.45 7.20 7.28 7.32 7.10 7.17 7.21 6.76 7.41 7.74 5.97 6.59 6.91 5.22 5.80 6.10 4.53 5.06 5.34 3.89 4.36 4.62 3.31 3.74 3.96 2.80 3.17 3.37 2.35 2.67 2.84 1.95 2.23 2.38 5.16 5.40 5.53 5.78 6.06 6.22 6.40 6.72 6.88 7.01 7.34 7.52 7.58 7.92 8.09 8.11 8.44 8.60 1.50 1.51 1.52 1.53 1.55 1.56 1.57 1.58 1.59 1.60 1.62 1.63 1.64 1.66 1.67 1.67 1.69 1.70 3.66 3.89 4.01 4.25 4.52 4.66 4.84 5.13 5.29 5.41 5.72 5.88 5.95 6.26 6.42 6.44 6.74 6.89 35.58 36.31 36.72 37.48 38.32 38.79 39.35 40.30 40.80 41.18 42.18 42.71 42.92 43.93 44.45 44.52 45.49 45.97 3.44 3.57 3.64 3.78 3.92 4.00 4.09 4.24 4.32 4.38 4.53 4.61 4.64 4.78 4.85 4.86 4.98 5.04 NOTES: 1. Interpolate is permissable; extrapolation is not. 2. All entering air conditions are 27 C db and 19 C wb in cooing and 20 C db in heating. 3. Table does not reflect fan or pump power connections for AHRI/ ISO conditions. 4. All performance data is based upon the lower voltage of dual voltage rated units. 5. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 6. Operation below 4 C EWT is based on 15% methanol antifreeze solution. 7. Operation below 16 C EWT requires optional insulated water/ refrigerant circuit. 8. See performance correction tables for operating conditions other than those listed above. 9. Shaded area refers to calculations required to determine if heating water flow is sufficient for the non-antifreeze systems. 17

Performance data (cont) Dry Bulb Coefficient of Performance Entering Air Temperature (C) Energy Efficiency Ratio Entering Water Temperature (C) Heating Capacity Heat of Extraction Heat of Rejection Latent Heat Leaving Water Temperature Sensible Capacity Total Capacity Wet Bulb Water Pressure Differential 50PCH,PCV030 343 L/S NOMINAL AIRFLOW WATER/BRINE COOLING - EAT 27/19 C HEATING - EAT 20 C EWT (C) Flow WPD (L/s) (kpa) TC SC HR EER HC HE LAT COP 0.24 10.3-5.0 0.35 18.2 0.47 32.7 5.28 1.64 3.64 32.75 3.23 0.0 0.24 0.35 0.47 8.3 15.5 28.2 8.69 8.77 8.79 6.19 6.17 6.14 1.18 1.11 1.08 9.87 9.88 9.87 7.36 7.88 8.13 5.68 5.91 6.03 1.80 1.82 1.83 3.87 4.08 4.20 33.71 34.26 34.56 3.15 3.24 3.29 db COP EAT EER EWT HC HE HR LAT LWT SC TC wb WPD 5.0 10.0 15.0 20.0 25.0 30.0 35.0 40.0 45.0 0.35 0.47 0.24 0.24 0.35 0.47 0.24 0.35 0.47 0.24 0.35 0.47 0.24 0.35 0.47 0.24 0.35 0.47 0.24 0.35 0.47 0.24 0.35 0.47 0.24 0.35 0.47 7.0 13.7 25.3 6.1 12.5 23.2 5.4 11.5 21.6 5.0 10.7 20.3 4.5 10.1 19.2 4.3 9.6 18.3 4.0 9.1 17.5 3.7 8.8 16.8 3.5 8.4 16.2 8.52 8.66 8.71 8.29 8.47 8.55 8.00 8.22 8.32 7.67 7.92 8.04 7.31 7.58 7.71 6.92 7.20 7.34 6.51 6.79 6.94 6.09 6.37 6.52 5.66 5.95 6.09 6.16 6.19 6.19 6.07 6.14 6.16 5.93 6.04 6.08 5.77 5.89 5.95 5.58 5.72 5.78 5.38 5.52 5.60 5.18 5.32 5.39 4.97 5.11 5.18 4.77 4.90 4.97 1.28 1.20 1.17 1.38 1.30 1.26 1.51 1.41 1.37 1.64 1.54 1.49 1.80 1.68 1.63 1.98 1.85 1.79 2.18 2.03 1.97 2.40 2.25 2.17 2.66 2.48 2.40 9.80 9.86 9.88 9.67 9.77 9.81 9.51 9.63 9.69 9.32 9.46 9.53 9.11 9.26 9.34 8.89 9.05 9.12 8.68 8.83 8.90 8.49 8.62 8.69 8.32 8.43 8.49 6.68 7.21 7.47 5.99 6.51 6.78 5.32 5.82 6.08 4.67 5.15 5.40 4.06 4.50 4.73 3.50 3.90 4.11 2.99 3.34 3.53 2.53 2.84 3.00 2.13 2.39 2.54 6.39 6.66 6.81 7.11 7.44 7.61 7.85 8.22 8.42 8.59 8.99 9.21 9.31 9.74 9.96 10.00 10.44 10.67 1.86 1.87 1.88 1.90 1.92 1.93 1.94 1.96 1.98 1.99 2.01 2.02 2.03 2.06 2.08 2.08 2.12 2.14 4.53 4.79 4.93 5.21 5.52 5.68 5.91 6.25 6.44 6.60 6.98 7.18 7.28 7.68 7.89 7.92 8.33 8.53 35.42 36.09 36.45 37.18 37.96 38.39 38.96 39.85 40.33 40.74 41.71 42.23 42.48 43.51 44.06 44.16 45.22 45.78 3.44 3.55 3.62 3.74 3.87 3.94 4.04 4.18 4.26 4.32 4.47 4.55 4.59 4.73 4.80 4.81 4.93 4.99 NOTES: 1. Interpolate is permissable; extrapolation is not. 2. All entering air conditions are 27 C db and 19 C wb in cooing and 20 C db in heating. 3. Table does not reflect fan or pump power connections for AHRI/ ISO conditions. 4. All performance data is based upon the lower voltage of dual voltage rated units. 5. Performance stated is at the rated power supply; performance may vary as the power supply varies from the rated. 6. Operation below 4 C EWT is based on 15% methanol antifreeze solution. 7. Operation below 16 C EWT requires optional insulated water/ refrigerant circuit. 8. See performance correction tables for operating conditions other than those listed above. 9. Shaded area refers to calculations required to determine if heating water flow is sufficient for the non-antifreeze systems. 18