Use. The burner controls are certified to EN 230 and EN 298.

Similar documents
Use. Burner controls for use with forced draught gas or gas / oil burners of small to medium capacity in intermittent operation.

Burner Controls. Building Technologies HVAC Products

Gas Burner Controls. Building Technologies HVAC Products

LGA... Gas Burner Controls. Siemens Building Technologies Landis & Staefa Division

Burner controls. Building Technologies HVAC Products

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies Landis & Staefa Division

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

Oil Burner Controls LOA3... Building Technologies HVAC Products

LGA... Gas Burner Controls. Building Technologies Division

LOA2... LOA3... Oil Burner Controls. Siemens Building Technologies HVAC Products

LOA44.252A27. Oil Burner Control. Building Technologies HVAC Products

LAE10 LFE10. Use. Series 02

Oil Burner Controls LMO24... LMO44...

Oil Burner Controls LMO24... LMO44...

Flame Safeguards LFE10. Building Technologies HVAC Products

Flame Safeguards LFE10. Building Technologies HVAC Products

Oil Burner Controls LOA3... Building Technologies Division

UV Flame Supervision System

C Note! LGI16... Burner Controls. Building Technologies

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

Burner Management System

Infrared Flame Detectors

Product Range Overview

Building Technologies Division

QRA10... QRA53... QRA55...

Burner Management System

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

QRA10... QRA53... QRA55...

EUROBOX SERIES TYPES CM... SM... MM...

Flame detector. The QRA4.U is for use with the following types of burner control:

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

Flame detector. Building Technologies Division Infrastructure & Cities Sector

QRA10... QRA53... QRA55...

Building Technologies

Flame detector. The QRA4.U is for use with the following types of burner control:

EUROFLAT SERIES TYPES C... S... M...

LFL Series Burner Flame Safeguard Control

Program module for burner control LME71.000

Infrared Flame Detectors

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

DKG 972. Gas Burner Safety Control. For 2-stage atmospheric gas burners

Forced draught gas burner

EUROBOX SERIES TYPES CM...N SM...N MM...N

Burner Management System

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

MMI (40-34) Gas burner safty control

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

Basic unit with integrated air-fuel ratio control for forced draft burners

DMG 973. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners, facility to connect an air damper unit

MMG Gas burner safety control

DMG 970. Gas Burner Safety Control. For 2-stage forced draught and combi oil/gas burners

DKO 974/976 DKO 974 N/976 N. Oil Burner Safety Control

QRA10... QRA53... QRA55...

Basic unit with integrated fuel-air ratio control for forced draft burners LMV Building Technologies Division

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

Basic Unit with integrated Fuel / Air Ratio Control for Forced Draft Burners LMV Building Technologies

MICROFLAT SERIES TYPES C.../U T X

Forced draught gas burner

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

Part 3 Troubleshooting

Gas burner automatic safety control MMI / 811.1

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

Advanced Ultraviolet Burner Controller

SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SGU 930 SGU 930i. Control box

AUTOMATIC BURNER CONTROL SYSTEM SAFETY INFORMATION CONFORMITY

AUR300C, AUR350C. Advanced Ultraviolet Burner Controller

TWO STAGE HEAVY OIL BURNERS

Gas Burner Safety Control DMG 970

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

FIREYE M4RT1 FLAME SAFEGUARD CONTROLS DESCRIPTION

Eclipse Trilogy Flame Safeguard Modulating Sequences

Building Technologies Division Infrastructure & Cities Sector

MANUAL OF - INSTALLATION - OPERATION - MAINTENANCE LIGHT OIL BURNERS G4 - G6 G10 - G18 SINGLE STAGE

CODE MODEL TYPE PRESS 60 N 616 T PRESS 60 N 616 T80

CORONA BURNER CONTROLLER INSTRUCTION MANUAL RCF15 EXCLUSIVE FOR FLAME ROD. Corona Corporation

Interrupted Ignition Series Oil Primary Control

BGH Series Hot Surface Ignition Control

DOMESTIC HOT WATER Follow operational sequence

Quick Reference Guide. Application. Gas Furnaces Boilers Water Heaters Commercial Cooking. Features

Settings and Maintenance of the CombinAir

Building Technologies Division

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

24 VAC Intermittent Pilot Gas Ignition Control

UV - flame detector dual fuel burners for intermittent burner operations

24 VAC Direct Spark Gas Ignition

Grant UK VortexBlue. 21, 26 and 36kW Blue Flame Oil Boiler Range. Supplementary Installation, Servicing and User Instructions

Old documentation - Only for your information! Product is not available anymore!

Technical Data. General specifications Switching element function DC Dual NC Rated operating distance s n 3 mm

INSTALLATION, OPERATING AND SERVICING INSTRUCTIONS BG 2000-S (V13) RU PL DE IT ES NL EN 1 662Y0600 A

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

BOSCH CONDENS 5000W ZSB18-2A

Blue-flame Detectors

Gas-Gebläsebrenner Brûleur gaz à air soufflé Forced draught gas burner Gasventilatorbrander Quemador de gas de aire soplado

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

CATALOGUE PRODUITS - CSA - CSI - CSM - CSS - CSS2 - P16 - P19 - P20 - P25 - UV DETECTOR

21D83M-843 Integrated Single Stage Furnace Control Replacement Kit INSTALLATION INSTRUCTIONS

Burner control unit BCU 370

GAS FIRED ATMOSPHERIC ELECTRONIC VERSION kw

Transcription:

7 421 SO 9001 Burner Controls G2... Burner controls for the supervision of single- or two-stage forced draught gas or gas / oil burners of small to medium capacity (typically up to 350 kw) in intermittent operation. The burner controls are certified to E 230 and E 298. They carry the CE mark based on the directives for gas appliances and electromagnetic compatibility. The G2... and this data sheet are intended for use by OEs which integrate the burner controls in their products. Use Burner controls of the G2... range are used for startup and supervision of single- or two-stage gas or gas / oil burners in intermittent operation. The flame is supervised with a detector electrode or UV flame detector QRA... (with ancillary unit AGQ2...A27). G21... / G22... in the same housing replace burner controls GB21... / GB22... (refer to «Type summary») and, with the help of the respective adapters, burner controls F7... and F1... (refer to «Ordering»). Application-specific features Detection of undervoltages Air pressure supervision with function check of air pressure monitor during startup and operation Electric remote reset ndication of error code and flame signal by means of EDs in the lockout reset button Precise program times thanks to digital processing of signals Available versions G21... / G22... G25... For unlimited burner capacities (output on startup 120 kw) ocking in the event of loss of flame during operation For burner capacities 120 kw Three repetitions in the event of loss of flame during operation andis & Staefa Division CC17421E December 04, 1998 1/16

Warning notes To avoid personal injury, damage to property or the environment, the following warning notes should be observed! t is not permitted to open, interfere with or modify the unit! Before performing any wiring changes in the connection area of the G2..., the burner control must be completely isolated from the mains supply! Check wiring and all safety functions! Risk of explosion Press lockout reset button / operating button only manually (applying a force of no more than 10 ), without using any tools or pointed objects! Check the connecting wires of the air pressure monitor for short-circuits (terminals 3, 6 and 11)! Engineering notes ounting notes nstallation notes Check the electromagnetic compatibility with adjacent components! On applications with actuators, the actuator does not feed a position checkback signal to the burner control. The actuator running times must be matched to the burner control's program. An additional safety check of the burner with the actuator must be made! The relevant national safety regulations must be complied with! ocate the ignition and detector electrode such that the ignition spark cannot arc over to the detector electrode! Risk of electric overloads the ignition spark cannot adversely affect ionization supervision! nstallation and commissioning work may only be carried out by qualified staff! Observe the permissible length of the detector cables! Refer to «Technical data» Always run ignition cables separate from the unit and other cables while observing the greatest possible distances! Before putting the burner control into operation, check wiring carefully! nstall switches, fuses, earthing, etc., in compliance with local regulations! The connection diagrams shown apply to burner controls with earthed neutral. n the case of ionization current supervision in networks with non-earthed neutral, terminal 2 must be connected to the earth conductor via an RC unit (part no. ARC 4 668 9066 0)! Do not exceed the maximum permissible switching capacity of the connection terminals! o mains voltage may feed back to the control s output terminals from an external supply or source. When checking the functioning of devices controlled by the burner control (gas valves, etc.), the burner control may never be plugged in! n the case of burners with no fan motor, an AGK25 must be connected to terminal 3 of the burner control, or else the burner cannot reliably be started up! For safety reasons, feed the neutral conductor to the neutral distributor on the plug-in base, or to terminal 2, and from there to the various devices (fan, ignition transformer and gas valves) or to an external neutral distributor! Example 2 3 7 4 5 7421a16/0398 2/16 CC17421E December 04, 1998 andis & Staefa Division

Electrical connection of ionization current and UV detectors t is important to achieve practically loss-free signal transmission Cable length may not exceed 20 m ever run the detector cable together with other cables ine capacitances reduce the magnitude of the flame signal Use a separate cable nsulation resistance Between detector electrode and ground: minimum 50 Ω Soiled detector electrode holders reduce insulation resistance, thus supporting creepage currents Earth the burner in compliance with the relevant regulations; earthing the boiler alone does not suffice Observe the polarity Burner controls G2... detect wrong polarity of live and neutral, in which case they initiate lockout at the end of «TSA» echanical design Burner controls G2... Plug-in design like predecessor type GB2... (refer to «Dimensions») Housing made of impact-proof, heat-resistant plastic Housing accommodates the - control of the microcontroller with PCB relay for load control - electronic flame signal amplifier (ionization) - lockout reset button with integrated red fault indication lamp and green flame signal lamp Plug-in base ade of impact-proof, heat-resistant plastic Available with screw terminals AGK11 Cable entry optionally - from the front or laterally by means of cable gland holders AGK65 or cable holders AGK66 - from below through two holes of 16.2 mm dia. Provided with catches on the two narrow sides which engage in the burner control's housing - must audibly click when plugging in the G2... - to disengage, a screwdriver must be slightly tilted in the guiding slots; then, the burner control slightly lifts For length and width of plug-in base and positions of fixing holes, refer to «Dimensions» andis & Staefa Division CC17421E December 04, 1998 3/16

Type summary The type references contained in the following table refer to G2... with no plug-in base and with no flame detector. For ordering information on bases and other accessories, refer to «Ordering». Type of flame detector Type reference G2... tw s max. t1 s min. TSA s max. t3n s ca. t3 s ca. t4 s ca. t10 s min. t11 s ¹) max. t12 s ¹) max. Behaviour in the event of flame failure during operation Burner controls for pre-purging with low flame air volume, without actuator control Detector electrode () G21.130A27 2) 8 7 3 2.6 2 8 5 - - ockout or G21.230A27 3) 8 20 3 2.6 2 8 5 - - ockout UV detector QRA... G21.330A27 3) 8 30 3 2.6 2 8 5 - - ockout with G21.350A27 3) 8 30 5 4.6 2 10 5 - - ockout AGQ2...A27 G21.550A27 3) 8 50 5 4.6 2 10 5 - - ockout Burner controls for pre-purging with nominal air volume, with actuator control Detector electrode () G22.130A27 2) 8 7 3 2.6 3 8 3 12 12 ockout or G22.230A27 3) 8 20 3 2.6 3 8 3 16.5 16.5 ockout UV detector QRA... G22.233A27 8 20 3 2.6 3 8 3 30 30 ockout with G22.330A27 3) 8 30 3 2.6 3 8 3 12 11 ockout AGQ2...A27 G22.330A270 3)4) 8 30 3 2.6 3 8 3 12 11 ockout Burner controls for pre-purging with low flame air volume, without actuator control Detector electrode () G25.230A27 8 20 3 2.6 2 8 5 - - ax. 3 repetitions or G25.330A27 8 30 3 2.6 2 8 5 - - ax. 3 repetitions UV detector QRA... G25.350A27 8 30 5 4.6 2 10 5 - - ax. 3 repetitions with AGQ2...A27 egend tw Waiting time t4 nterval «TSAEnde-» or «-R» t1 Checked pre-purge time t10 Specified time for air pressure signal TSA gnition safety time t11 Programmed opening time for actuator «SA» t3 Pre-ignition time t12 Programmed closing time for actuator «SA» t3n gnition time during «TSA» 1) ax. running time available for actuators «SA» 3) Also suited for use with direct fired air heaters 2) Also suited for use with flash-steam generators 4) Without integral fuse; use only in connection with bases AGK86... or with an external microfuse of max. 6.3 A (slow) 4/16 CC17421E December 04, 1998 andis & Staefa Division

Ordering Burner control refer to «Type summary» Flame detectors Detector electrode delivered by others UV detector QRA... refer to data sheet 7714 Plug-in base with screw terminals Cable gland holder For inserting in the plug-in base For 5 x Pg11, one each on the narrow sides, three on the wide side Cable holder For inserting in the plug-in base With six knockout holes for cable entries (without cable tension relief) - 1 x 8.8 mm dia. and 1 x 17 mm dia. (laterally) - 3 x 7 mm dia. (on the front) - 1 x rectangular opening 6 x 20 mm (on the front) Pedestal For increasing the height to that of the F... or F7... (refer to «Dimensions») AGK11 AGK65 AGK66 AGK21 RC unit ARC 4 668 9066 0 For supervision of the ionization current in networks with non-earthed neutral PTC resistor (AC 230 V) To generate load on terminal 3 (used with burners with no fan motor, e.g. atmospheric gas burners) AGK25 Ancillary unit for UV supervision Can be fitted under the plug-in base; for dimensions, refer to «Dimensions» Actuators (refer to data sheet 7808) Actuators (refer to data sheet 7804) Actuators (refer to data sheet 7806) AGQ2.1A27 (cable length 500 mm) AGQ2.2A27 (cable length 300 mm) SQ3... SQ7... SQ9... Service adapter KF8872 For checking the functioning of the burner controls on the burner plant Functional check with indicator lamps ote: with no load on the output terminals, the respective indicator lamp may light up! Detector current measurement with jacks of 4 mm dia. Test case KF8843 ¹) For checking the functioning of the burner controls away from the burner ¹) With extended type connector for use with G... Adapter / replacement types o rewiring required ew type of burner control Adapter type Predecessor type G21... with adapter KF8853-K F7... KF8880 F1... / 1...-F G22... with adapter KF8853-K F7... KF8880 F1... andis & Staefa Division CC17421E December 04, 1998 5/16

Technical data G2... Operating voltage AC 230 V +10 % / -15 % Weight - Burner control approx. 158 g ains frequency 50 Hz -6 %...60 Hz +6 % - Plug-in base AGK11 approx. 80 g - AGK65... approx. 12 g Power consumption 12 VA - AGK66... approx. 12 g Primary fuse max. 10 A (slow) Degree of protection P 40 ounting position optional ax. cable length terminals 8 and 10 20 m Environmental conditions nput current at terminal 12 max. 5 A Transport EC 721-3-2 Climatic conditions class 2K2 dentification code to E 298 Temperature range -40...+60 C G21... / G22... F T X Humidity < 95 % r.h. G25... F T C X echanical conditions class 22 Operation EC 721-3-3 CE conformity Climatic conditions class 3K5 According to the directives of the European Union Temperature range -20...+60 C Electromagnetic compatibility EC Humidity < 95 % r.h. 89 / 336 EEC incl. 92 / 31 EEC Condensation, formation of ice and ingress of water are not permitted! Directive for gas appliances 90 / 396 EEC Terminal rating At cos ϕ 0.6 At cos ϕ = 1 - Terminal 3 max. 2.7 A (15 A during max. 0.5 s) max. 3 A - Terminals 4, 5 and 7 max. 1.7 A max. 2 A - Terminal 10 max. 1 A max. 1 A 6/16 CC17421E December 04, 1998 andis & Staefa Division

Flame supervision with detector electrode Detector voltage across terminals 1 and 2 or ground (AC voltmeter Ri 10 Ω) Switching thresholds (limit values) At mains voltage U = AC 230 V AC 115...230 V Switching on (flame on) DC ammeter, Ri 5 kω) DC 1 µa Switching off (flame off) DC ammeter, Ri 5 kω) DC 0.5 µa Requested sensor current for reliable operation 2 µa ax. short-circuit current across terminals 1 and 2 or ground (AC ammeter, Ri 5 kω) AC 50 µa ote: With the same flame quality, the detector current with G2... is lower than with GB2...! Flame supervision takes place by making use of the conductivity and rectifying effect of hot flame gases. The flame signal amplifier responds only to the DC current component of the flame signal. A short-circuit between detector electrode and ground causes the burner to initiate lockout easuring circuit G2... 1 7421v01/0598 + - + C For detector currents, refer to «Technical data». egend C Electrolytic capacitor 100...470 µf; DC 10...25 V Detector electrode icroammeter (Ri max. = 5000 Ω) andis & Staefa Division CC17421E December 04, 1998 7/16

Flame supervision with AGQ2...A27 and UV detector QRA... Operating voltage AC 230 V +10 % / -15 % ax. permissible cable lengths QRA... to AGQ2...A27 20 m ains frequency 50 Hz -6 %...60 Hz +6 % (separate cable) AGQ2...A27 to G2... 20 m Environmental conditions Transport EC 721-3-2 Weight Climatic conditions class 2K2 AGQ2...A27 approx. 140 g Temperature range -40...+60 C QRA... refer to data sheet 7714 Humidity < 95 % r.h. echanical conditions class 22 ounting position optional Operation EC 721-3-3 Climatic conditions class 3K5 Degree of protection P 40 Temperature range -20...+60 C Humidity < 95 % r.h. Power consumption 4.5 VA At mains voltage U AC 220 V AC 240 V Detector voltage at QRA... (with no load) To the end of «t10» and after a controlled shutdown DC 400 V DC 400 V From the beginning of «t1» DC 300 V DC 300 V Detector voltage oading by DC meter Ri > 10 Ω To the end of «t10» and after a controlled shutdown DC 380 V DC 380 V From the beginning of «t1» DC 280 V DC 280 V DC current detector signals with UV detector QRA... min. required max. possible easurement made on UV detector 200 µa 500 µa For UV detector QRA..., refer to data sheet 7712 Ancillary unit AGQ2...A27 When used in connection with burner controls G2..., the UV ancillary unit AGQ2...A27 is required. Using circuitry (A) or (B), the quench test on ageing UV detectors can be made in two different ways: egend Type of circuitry: (A) Operation with a permanent line UV test at twice the supply voltage across the UV cell on startup and after a controlled shutdown (B) Operation with a controlled line UV test at twice the supply voltage on startup only, during the interval between controlled startup and air pressure signal o voltage at the UV cell after a controlled shutdown o full substitute for mode (A) described above since an aged UV cell can regenerate itself Connection diagram G2... 12 2 * 11 (B) (A) 1 7421a11/0598 br bl rt sw AGQ2...A27 sw bl AGQ2.1A27 AQG2.2A27 QRA + - easurement circuit easurement made on UV detector AG Q 2...A27 QRA + - sw bl sw bl - C + + G2... 1 2 7421v02/0598 egend C Electrolytic capacitor 100...470 µf; DC 10...25 V bl blue icroammeter Ri max. 5000 Ω sw black QRA... UV detector gr grey 8/16 CC17421E December 04, 1998 andis & Staefa Division

Functions G21... / G25... G22... SB / R / W / GP A A B B C D 12 10 3 7421d05/0498 SB / R / W / GP A A B B C D 12 10 3 7 7 4 SA 9 5 4 P 11 (R) 5 FS 1 P 11 tw t10 t1 t3 t3n TSA 400 ms t4 8 FS tw t1 t3 t3n t12 TSA t10+t11 400 ms t4 1 8 7421d06/1098 egend A Start command (switching on by «R») B-B nterval for establishment of flame C Operating position of burner reached C-D Burner operation D Controlled shutdown by «R» Burner is immediately shut down Burner control is immediately ready for new startup A Fault status signal (alarm) Fan motor BV... Fuel valve R Control thermostat / pressurestat Remote reset button SA Actuators FS Flame signal SB Safety limit thermostat GP Gas pressure monitor W imit thermostat / pressure monitor P Air pressure monitor gnition transformer R oad controller Prerequisites for startup Undervoltage Checked intermittent operation Reversed polarity protection Control program in the event of fault Resetting the G2... Burner control is reset All contacts in the line are closed Fan motor or AGK25 is connected Air pressure monitor «P» is in idle position o undervoltage Safety shutdown in the event the mains voltage is lower than typically AC 160 V a restart is made when the mains voltage exceeds AC 195 V After no more than 24 hours of continuous operation, the burner control initiates a safety shutdown, followed by a restart. f the connections of line (terminal 12) and neutral (terminal 2) have been exchanged, the burner control will initiate lockout at the end of «TSA». f a fault occurs, all outputs will immediately be deactivated (< 1 s) On restoration of power, a restart will be made with the full program sequence f the operating voltage drops below the undervoltage threshold (for threshold, refer to «Functions»), a restart will be made with the full program sequence f there is a premature faulty flame signal during «t1» ockout f the contact of the air pressure monitor «P» has welded in the working position: prevention of startup and, after 8.5 seconds, lockout f the contact of the air pressure monitor «P» has welded in the idle position: lockout at the end of «t10» f there is no air pressure on completion of «t10» ockout f the burner does not ignite by the end of «TSA» ockout f flame is lost during operation G21... / G22... lockout G25... three repetitions When lockout occurs, the burner control can immediately be reset! n that case, keep lockout reset button depressed for a minimum of 0.5 seconds and a maximum of 3 seconds! andis & Staefa Division CC17421E December 04, 1998 9/16

Connection diagram G21... / G25... G21.../25... 12 2 10 8 3 6 11 7 9 4 5 1 1) ¹) Wire link required only with GB21..., not with G21... / G25... 0 A P 7421a06/0598 Application examples Control of actuators of two-stage or two-stage modulating burners. Checked pre-purging «t1» with low flame air volume. Exactly the same low flame actuator positions during startup and operation! For information about actuators «SA»: G2... 5 R O/OFF 12 4 SA SB/ 7421a07/1098 RV SQ3...: refer to data sheet 7808 SQ7...: refer to data sheet 7804 SQ9...: refer to data sheet 7806 G21.../22.../25... 12 2 10 8 3 6 11 9 7 4 5 1 (*) P A G 21.../22.../25... 12 2 10 8 3 6 11 9 7 4 5 1 A P GP/ SB R R 0 (*) * 1 2 6 7 5 4 3 b1 b2 B a a3 a b b S a b a2 a V b A a b SQ3...121... / two-stage control * ote: with two-stage modulating burners (with gas regulation damper «RV»), and the dotted connection between terminals (*) are not required V 7421a03/1098 RV K KP K V u t1 V V t 7421d03/1098 0 1 2 5 3 6 4 K2 + V a b D a b - + C3 K1 C31 V S a b a b R32 R1 a b SA 7421a08/1098 SQ91.140... / two-stage control K G21.../22.../25... 12 2 10 8 3 6 11 7 4 5 1 P A GP/ SB R 8 4 1 5 3 2 7 6 0 a1 c1 b2 KP V V K B A b1 a2 C V 7421a09/1098 zu t1 TSA t4 t SQ7...244 / two-stage control 10/16 CC17421E December 04, 1998 andis & Staefa Division

Connection diagram G22... G22... 12 2 10 8 3 6 11 7 4 5 9 1 SA 0 A P 7421a15/0598 Application examples 12 G2... 5 9 4 7421a19/1098 Control of actuators of two-stage or two-stage modulating burners. Checked pre-purging «t1» with nominal load air volume. R SA RV For information about actuators «SA»: SQ3...: refer to data sheet 7808 SQ7...: refer to data sheet 7804 SQ9...: refer to data sheet 7806 SB/ G22... 12 2 10 8 3 6 11 9 5 7 P R A 4 1 * G22... 12 2 10 8 3 6 11 9 5 7 4 1 P R A * 0 SA * 8 1 2 7 5 6 3 4 9 R3 K2 C2 + D - + R2 C1 R1 K1 S C3 SQ3...151... or SQ3...251... * ote: with two-stage modulating burners (with gas regulation damper «RV»), and the dotted connection between terminals (*) are not required V 7421a13/1098 RV K KP K u t1 t4 TSA t 7421d04/0498 0 6 8 10 2 R3 1 3 7 9 R1 K2 C2 K1 + D - + C3 R2 S C1 SA SQ90.220... / two-stage modulating control 7421a14/0598 RV K G 22... G22... 12 2 10 8 3 6 11 5 9 7 4 1 12 2 10 8 3 6 11 9 5 7 4 1 A P R A P R 1 2 5 4 1 3 2 8 6 7 4 5 1 3 2 8 6 7 0 a1 c1 b2 KP V V 0 a1 b2 C A b1 a2 B V 7421a17/1098 K zu t1 TSA t4 t A b1 a2 B V 7421a18/1098 SQ7...454 / two-stage control, single-wire control SQ7...424 / two-stage control, two-wire control andis & Staefa Division CC17421E December 04, 1998 11/16

Other application examples Burner without fan assistance and without «P» Burner with fan control via auxiliary contactor with «P» 2 3 11 6 AGK 7421a04/1098 * 12 2 3 11 6 AGK25 P 7421a05/0398 * ote: different from GB2... egend AGK25... PTC resistor P Air pressure monitor A Fault status signal (alarm) R oad controller BV... Fuel valve Fan motor Dbr... Wire link S Synchronous motor Remote lockout reset button ominal load Detector electrode QRA... UV detector FS Flame signal R Control thermostat / pressurestat GP Gas pressure monitor RV Gas regulation damper ain switch SA Actuator SQ... K1...4 nternal relays SB Safety limit thermostat K ow flame t Time K Air damper W imit thermostat / pressure monitor KP Air damper position gnition transformer 12/16 CC17421E December 04, 1998 andis & Staefa Division

Operating concept Burner control has initiated lockout Red fault ED on A Burner control in operation Green flame signal ED on FS Reset Press lockout reset button for 0.5...3 s Diagnosis of cause of fault Wait > 10 s Press lockout reset button for > 3 s Read blink code of red fault ED «Error code table» Restart Press lockout reset button for 0.5...3 s Read flame establishment time Press lockout reset button for > 3 s Read blink code of green flame signal ED «Error code table» Diagnosis of cause of fault After lockout, the red fault ED is steady on. For reading the cause of fault, refer to the blink code given in the following table: FS Red ED on A ~ ED on (waiting time > 10 s) Fault Press lockout reset button for > 3 s Blink code Off Approx. 3 s Blink code ~ Error code table Blink code 2 x 3 x 4 x 5 x 7 x 8...17 x... 18 x 19 x 20 x Possible cause o establishment of flame at the end of «TSA» Faulty or soiled detector electrode Faulty or soiled fuel valves Poor adjustment of burner Air pressure monitor does not close «P» faulty «P» incorrectly adjusted Fan motor does not run Air pressure monitor does not open or extraneous light on burner startup «P» faulty «P» incorrectly adjusted Extraneous light during pre-purging Or internal device fault oss of flame during operation Poor adjustment of burner Faulty or soiled fuel valves Short-circuit between detector electrode and ground Free Air pressure monitor opens during pre-purging or operation «P» incorrectly adjusted Four times loss of flame during operation (G25) Faulty output contact Wiring error External power supply on output terminal nternal device fault During the time the cause of the fault is diagnosed, the control outputs are deactivated. The burner remains shut down Exception: fault status signal «A» at terminal 10 The burner is switched on only after a reset is made. Press lockout reset button for 0.5...3 seconds andis & Staefa Division CC17421E December 04, 1998 13/16

nterrogation of flame establishment time Green ED on FS A This function measures the flame establishment time with ionization supervision. With the AGQ2..., this function cannot be used. n the running position, the green flame signal ED is steady on. The flame establishment time is read in the running position according to the following sequence: ED on Press lockout reset button for > 3 s Blink code Off Blink code ~ Operation Approx. 3 s ~ When reading the flame establishment time, the burner is put out of operation. Reading is in the form of a blink code as multiples of 0.4 s. Diagnostics table Blink code Flame establishment time with «TSA» = 3 s 1 x 0.4 s 2 x 0.8 s Flame establishment time with «TSA» = 5 s 0.4 s 0.8 s 7 x 2.8 s 2.8 s 12 x --- 4.8 s The flame establishment time is the period of time from the moment opens to the moment the flame signal is detected for the first time The flame establishment time remains stored for one startup sequence and is reascertained the next time the burner is started up During the period of time the flame establishment time is interrogated, the fault status outputs are deactivated: Burner remains shut down t is restarted only after a reset is made Press lockout reset button for 0.5...3 seconds ote: f ignition and ionization electrode are not correctly located, ignition effects may lead to incorrect measurements. 14/16 CC17421E December 04, 1998 andis & Staefa Division

nternal diagram G21... / G25... T Control of microcontroller EK RESET 7421a01e/1298 A red FS green K4 FSV K1 K2 K3 12 2 10 7 3 4 5 8 6 11 1 Si / A P G22... T Control of microcontroller EK RESET 7421a02e/1298 A red FS green K4 FSV K1 K2 K3 12 2 Si / 10 A 7 3 9 4 5 R 8 6 11 P 1 SA egend EK ockout reset button (internal) T Power section FSV Flame signal amplifier Si Fuse andis & Staefa Division CC17421E December 04, 1998 15/16

Dimensions Burner control Dimensions in mm 9 62,5 5,5 1 230 V~ 50-60 Hz 25 25 88 91 TSA 3 sec. 12VA P40 CE - 0085AT0010 22 9550 46,5 62 7421m01/0398 41,5 Burner control with plug-in base AGK11... and cable gland holders AGK65... (can be inserted in the base) FS A < 3 sec. Reset > 3 sec. Diagn. Plug-in base 1 2 3 4 5 6 7 8 9 10 11 12 7421m02/0398 Ø 5,4 31 32 4 17 23,5 Ø 16,2 A 11 Ø 4,5 24 24 30 30 C B AGK11... Plug-in base with screw terminals Hatched: position of cable gland holder or cable holder «B»: holes for cable entry «31», «32»: auxiliary terminals : neutral terminals, connected to neutral input (terminal 2) Underneath: 4 earth terminals, joining a lug for earthing the burner andatory: (AGK11...) Connection of earthing lug «C» and fixing screws in «A» to the burner ground (using a metric screw with a lockwasher or similar) Ancillary unit AGQ2...A27 27,5 90,5 60 220 69 6 Type reference Dimensions A B AGQ2.1A27 500 19 AGQ2.2A27 300 34 18 65,6 4 5,4 5,4 13 7421m04/0398 A B 6 1998 andis & Staefa Produktion GmbH 16/16 CC17421E December 04, 1998 andis & Staefa Division