Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

Similar documents
RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

FIREFLY II PLUS RELEASE DEVICES INSTALLATION MANUAL

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

MODEL B2 INSTALLATION MANUAL

"SS90" SERIES CONTROLS MODEL C INSTALLATION MANUAL

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

RELEASE DEVICE CONTROLS

Cookson Company 1901 South Litchfield Road Goodyear, AZ Phone:

F I R E G A R D D C EXTENDED PERFORMANCE RELEASE DEVICE SAFE A N D SECURE

WARNING. Installation Tip: Try out this unit before installing onto a fire door system. Test and learn the release INTRODUCTION

MANUAL RESET ALARM RELEASE BOX

INSTRUCTION MANUAL. AlarmGard Chain Operator (Model FCA) AlarmGard Crank Operator (Model FKA)

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

M O D E L S FIREGARD BV EXTENDED PERFORMANCE RELEASE DEVICE

MANUAL RESET ALARM RELEASE

LiftMaster 300 Windsor Drive Oak Brook, IL LiftMaster.com

MANUAL RESET ALARM RELEASE

OWNER S MANUAL. Extended Performance Release Device. Models: Firefly III Plus, Firefly III Plus with Voiceboard

Hand Chain (Model FCF) &

AUTO RESET ALARM RELEASE BOX MODEL AR-C INSTRUCTION MANUAL

INSTALLATION & MAINTENANCE CORNELL FIREGARD CHAIN & ES ECO #1515 REVISION # 0000 FIREGARD CRANK OPERATORS BY: RICKM DATE: 3/23/2011

ACSI AO ELECTRIC LATCH RETRACTION CONTROLLER INSTALLATION INSTRUCTIONS I.D. 1089, REV. F

SP-1000X. Panic Device Power Controller Installation Guide. Rev

Conventional Releasing Control Panel

Installation Guide for AL600ULM. Multi-Output Access Control Power Supply Charger. Rev

Installation Guide for models:

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

PS1240x Series Dual Voltage Access Control Power Supply Systems Operating and Installation Instructions Rev D.01

Model 17A00 Expansion Enclosure

- 4 12VDC or 24VDC VDC or 24VDC - Eight (8) Fused Outputs - Eight (8) PTC Outputs. Installing Company: Service Rep.

MS-4012/4024 and CMS-4012/4024. Instruction Manual for the. Fire Alarm Control Panels

Public Safety DAS Annunciator Panel

Installation Guide for models:

DIVISION 8 OPENINGS SECTION OVERHEAD COILING FIRE DOORS. A. Section Metal Fabrications: Support framing and framed opening.

Installation Instructions. PS902 Power Supply. These instructions cover the following parts: PS902 Power Supply Specifi cations:

Installation Guide for AL300ULM. Multi-Output Access Control Power Supply Charger

RPSMLR2 RPSMLR2BB. Panic Device Power Controller Installation Guide LISTED. Rev

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Installation Guide for AL400ULM. Multi-Output Access Control Power Supply Charger

Series. Access Power Controllers. Installation Guide

TECHNICAL DATA OBSOLETE

Multiple Input and Output Modules

1 Description. 2 Specifications. HP600ULM Access Control Power Supply/Charger with Power Distribution Controller PN 52393:A 1/05/06 ECN

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

Installation Guide for AL800UL-ADA. NAC Power Extender. Rev

Operating & Maintenance Manual. Alert-4 Ethernet LCD Master Alarm

Specification/ Data Sheet

Model PAD-3 Distributed Power Module NAC Expander Installation, Operation, and Maintenance Manual

Multi-Output Access Control Power Supply Chargers VDC or 24VDC VDC or 4 24VDC.

AL600ULADA. NAC Power Extender. Installation Guide

ANSUL ANSUL AUTOMAN II-C RELEASING DEVICE

Single Doors FIREGUARD Series Use one Master Unit each door or one 2409 Support unit each door. Pairs of Doors

For a red enclosure add an R suffix to the part # e.g. eflow4na8dr. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

For a red enclosure add an R suffix to the part # e.g. eflow4na8r. Altronix Corp th St. Brooklyn, NY. Installing Company: Service Rep.

Multi-Output Access Control Power Supply Charger VDC or 24VDC VDC or 3 24VDC.

APS-300 SERIES DUAL VOLTAGE UL 294 LISTED ACCESS CONTROL POWER SUPPLIES

Installation, Operating and Maintenance Manual

AL800ULADA. NAC Power Extender. Installation Guide

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

AL400ULACM AL600ULACM - 4 amp - 12VDC or 6 amp. - Fused Outputs - Fused Outputs

Cimco Series 21. Series 21 - Specifications INDEX. Description. Operational Specification 2

ACSI Series 1550K-MD and 1550-MD Motor Drive Electric Latch Retraction

INSTALLATIONN GUIDE & OPERATION MANUAL

Wiring Instructions for the 2900 Series FIREGUARD Combination Door Closer-Holder and Releasing Device with Integral Smoke Detector

Booster Power Supply Manual

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

ACM8 Series UL Listed Sub-Assembly Access Power Controllers. Installation Guide. ACM8 - Eight (8) Fuse Protected Outputs

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

VIZOR Electronic Dry Pipe Accelerator (EDPA) Quick-Opening Device for Dry Pipe Systems General Description

DS160/161 Request To Exit PIR sensors Installation Instructions

TECHNICAL DATA. Humidity: 85% Relative Humidity (non-condensing) at 90 F (32 C) maximum.

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

FireNET Plus Wiring Instructions

Model 4001 Series Single Channel Controller

AL802ULADA. NAC Power Extender. Installation Guide. (See Application Guide for additional information)

ACM4 Series UL Listed Sub-Assembly Access Power Controllers

STATUS ALARM HISTORY ALARM RESET

30.45 Electric Release PDRP-2001

SAFETY INFORMATION AND WARNINGS

Wiring Instructions. Single Doors 99 Checkmate Series Use one or Master Unit each door or one or Support unit each door

MODEL EUR -5A AUTOMATIC SNOW/ICE MELTING SYSTEM CONTROL PANEL

SECTION OVERHEAD COILING FIRE DOORS 641 SERIES OVERHEAD COILING COUNTER FIRE DOORS

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Access Power Controllers with Power Supplies

10-175UL INSTALLATION. Power Supply UL. Access Control Power Supply/Charger. Installation and Specifications Manual

Power Supply Display Module PSDM. Installation and Operation Manual

- Four (4) Fused Outputs - Four (4) PTC Outputs. - Eight (8) Fused Outputs - Eight (8) PTC Outputs

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

8600 EMR SERIES. INSPK NO Rev.06/ INS NO. GENERAL DESCRIPTION

CM-RQE70 PIR REQUEST TO EXIT DETECTOR

ISIMET Utility Controller

CommStat 4. Controller for Redundant Telecom HVAC Systems PRODUCT DATA SHEET. Features and Benefits

Remote NAC Power Supply D7038

AL600ULX Series. Power Supply/Charger. Installation Guide

Conventional Smoke Detectors KFAPO

TS93 EMR WITH SMOKE DETECTOR

Transcription:

Firefly II Multi Voltage RELEASE DEVICES Firefly II & IIB-MV INSTALLATION MANUAL GENERAL DESCRIPTION: S/N The The Cookson Company Firefly II-MV time delay release devices are designed for use on rolling doors. All models are normally energized Fail-Safe Releasing Devices incorporating state of the art electronic control circuitry. The Firefly II-MV series release devices respond to emergency conditions generated by manual or automatic normally closed initiating devices and shall be used in conjunction with a temperature fuse link system. The Firefly II-MV series release device features include; world power source capability allowing the same unit to be used on 24VDC, 24VAC or 120VAC 50 or 60HZ., separate adjustable time delays for alarm and power loss, motor voltage sensing, form- C relay output, proximity/door edge input and trouble diagnostic capabilities. Models FFII and FFIIB can be wired for two or four wire configuration. *Check model label on unit to be installed to verify applicable features. CAUTION: Review all installation instructions, procedures, cautions and warnings contained within this manual prior to installing and/or servicing this product. As with all releasing device systems, maximum fire protection is provided when installed in accordance with factory specifications and used with fuse link systems. Fail-safe operation can only be provided with input power applied. DO NOT install this unit without fuse links. TEST SYSTEM AT LEAST ONCE EVERY 90 DAYS TO ASSURE PROPER OPERATION. MADE IN THE U.S.A. U.L. LISTED CANADIAN LISTED CSFM: 7300-1418:100 Installation and testing to factory specifications shall be performed by factory authorized personnel for proper operation in accordance with all of the latest National Fire Protection Association (NFPA), Underwriters Laboratories (UL), National Electrical Code (NEC), local, state, county, district and/or other applicable building and fire standards, guidelines, regulations and codes including, but not limited to, all appendices and amendments and the requirements of the local authority having jurisdiction (AHJ). TECHNICAL SUPPORT (602) 272-4244

INSTALLATION INSTRUCTIONS - To be performed by factory authorized personnel only. The following installation procedures must be followed to assure performance of the release device to factory standards. SECTION A. MOUNTING PROCEDURE (Figure 1) 1. The release device shall be mounted on a vertical surface with chain end link exiting side of enclosure as illustrated in figure 1. The unit may be rotated 90 degrees CW for a direct vertical pull. 2. Release device enclosure shall be mounted with minimum #10 size fastening screws or bolts for securing to structures other than masonry. Masonry applications shall utilize 1/4" or greater anchors or studs as required to ensure proper mounting strength. 3. Release device and associated hardware [sash chain or 1/16 cable, eyebolts, fuse links (DO NOT install this unit without fuse links), turnbuckles] shall be installed as per door manufacturers recommendations (figure 1 typical installation configuration). Note should be taken that the end link direction of pull is perpendicular to the enclosure side. An eyebolt installed at a distance of 18 to 24 inches from the release device should adequately redirect sash chain pull as illustrated in figure 1. 4.Complete hardware installation by connecting fuse links, sash chain, S-hooks and turnbuckles as required. Push reset lever in direction of arrow on label to allow insertion of end link through release device side opening. Push end link completely in and release reset lever to latch end link. Remove sash chain slack by adjusting turnbuckle. Do Not exceed 40 lbs. maximum pull rating on release device. SECTION B. Smoke Detectors. When installing smoke detectors with this unit refer to NFPA 72-1993 and NFPA 80, for instructions concerning proper placement and detection coverage. End of line devices (relays) must be installed in accordance with U.L. 864. See electrical connections figure 4. Verify detector placement with Final AHJ. SECTION C. ELECTRICAL CONNECTIONS - All models (Figure 4-4 wire operation, figure 4A - 2 wire operation) Installation of all wiring and connections shall be performed in accordance with, but not limited to, the latest NFPA, U.L. and N.E.C. standards. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material, wiring gauge related to power capacity requirements and circuit length and wiring methods. The following wiring instructions can configure the unit for independent delay on alarm and power loss using four wires or a single adjustable delay using only two wires. Use steps 1-2-3-4 for 4 wire operation. *Use 1-2-3 for 2 wire operation. See Figure 4, page 3A for 4 wire dual delay wiring and Figure 4A, page 3B for 2 wire single delay wiring 1. Turn off power supply before beginning. 2. Verify voltage rating of release device to power source being utilized. 3. Connect 24 volt power source inputs to MV circuit board, screws 1 & 2. On 24VDC units observe proper polarity by placing positive (+) wire to screw 1. 120 VAC use TB3. TB3 screw 3 shall be utilized for earth ground where applicable. 4. Normally closed initiating devices (smoke detectors)- remove jumper from screws 1 & 2 (Alarm loop will not function if jumper is not removed). Connect wiring from N/C initiating device alarm loop to TB1 screws 1 & 2 (see NFPA 72-1993 and NFPA 80 for proper placement of smoke detectors). NOTE: Alarm loops cannot be series or parallel connected between TB1 of multiple release devices. OPTIONS: FFIIB-MV only. *Close Limit Detection (Lower limit/proximity switch) -This option interfaces to electrical contact type lower limit sensing devices and/or magnetic proximity type switches. If the electrical contact has toggled states from its N/O condition to a closed condition (TB1-5&6) indicating the door edge has made contact with desired down position, the release device logic will prevent the solenoid from energizing on alarm, thereby eliminating any damage which may result to the door from the release device attempting to close the already lowered door. This option only works as long as power is available to unit. Fail-safe operation shall be maintained under all operating conditions. Continued on page 3 2

* TYPICAL INSTALLATION FIGURE 1 RELEASE DEVICE End link Fuse link Fuse link Ceiling Sash chain or cable Thru wall conduit * Actual configuration may differ. This unit may be rotated 90 degrees CW for a vertical pull. See door manufacturer recommendations and NFPA 80 for use of this product with specific door. DO NOT install this unit without fuse links. INSIDE VIEW FFII-MV FIGURE 2 END LINK TB2 TB3 TB1-1 LOGIC BOARD MV Board 2A

TROUBLE RELAY (TB1-8,9&10) The trouble relay toggles immediately upon a power loss or alarm condition and may be used for turning on signalling appliances (horns,strobes,etc.) or other external signalling functions requiring a dry contact open or closure. Figure 4 illustrates contacts with no power to unit. With power applied TB1-9&10 are closed and toggle in alarm and power loss. Optional wiring - Verify that all operating voltage is off before continuing. 5. Normally open lower limit/proximity switch (closes in down limit). Connect wiring from *Aux. electrical loop to TB1 screws 5 & 6. Leave jumper in TB1-6&7. Remove jumper & use TB1-6&7 for a N/C which opens in down limit. 6. Trouble Relay - Connect wiring to common TB1-9 and either N/O contact TB1-10 or N/C contact TB1-8. * Note: Electrical loop must be provided as dry contacts and may not be used in conjunction with the simultaneous switching of a motor control or any other voltage through the same contacts. Connections of this type will result in immediate damage to the release device. Verify all connections made within unit. Close hinged cover and secure screw on lid after all connections are made. DO NOT LEAVE COVER OPEN AFTER CONNECTIONS ARE MADE! Firefly II-MV SERIES RELEASE DEVICE ELECTRICAL AND MECHANICAL CHARACTERISTICS OPERATING VOLTAGES MODEL FFII-MV... 24VDC +10% /-15% 24VAC +10% /-15% 120VAC +10% /-15% FFIIB-MV... 24VDC +10% /-15% 24VAC +10% /-15% 120VAC +10% /-15% CURRENT REQUIREMENTS -------------------------------- Operating Voltage --------------------------------- 24VDC 24VAC 120VAC Current rating SUPERVISORY/ALARM SUPERVISORY/ALARM SUPERVISORY/ALARM Model FFII-MV.025A/.045A.075A/.130A.300A/.650A FFIIB-MV.025A/.045A.075A/.130A.300A/.650A INITIATING LOOPS - CAUTION: All initiating devices shall be dry contact type only Maximum loop resistance: 100 Ohms Maximum current: Not to exceed.002a Maximum voltage: 15Vdc FORM C OUTPUT (MAXIMUM CONTACT RATING) FUSE RATINGS 2A/15Vdc 30 Watt DC Resistive Load Only Model FFII PC Board - 0.75 AMP @250V 2AG FAST ACTING TYPE 3 MV PC BOARD F1 2A @ 250v, 2AG Fast Acting, high voltage input F2 1A @ 250v, 2AG Fast Acting, low voltage input F3 1A @ 250v, 2AG Fast Acting, low voltage output MECHANICAL- LOAD RATING DIMENSIONS Support and release: 40LB. MAXIMUM 7 1/2" x 8 " x 4" (H x W x D)

ELECTRICAL CONNECTIONS (TYPICAL) - FIGURE 4 FOUR WIRE- INDEPENDENT ALARM & POWER LOSS DELAYS Refer to Section C - Electrical Connections pages 2&3 for complete FFII wiring instructions. Reference all footnotes below for additional installation information. End of line relay (4)(8) Per U.L. 864 FFIIB Only PC MOUNT TB2 Motor sense (2) Initiating Device (Smoke detector, etc.) Model FFII PC MOUNT TB1 (3) Input power (4)(5)(8) Break wire for proper supervision. Do not loop wire around terminals Down Limit Detection Proximity switch option FFII B only (1)(4)(6) } (1)(4)(6) TROUBLE RELAY FFIIB Only (unit de-energized) CHASSIS MOUNT 120VAC only USE TB3 CHASSIS MOUNT 120Vac only OR low voltage to MV PC Board (+) (-) Chassis ground MV PC Board 24VAC/DC ONLY Observe polarity for DC supply (1) Dotted line indicates factory jumper which must be removed when connecting the N/C device. (2) See NFPA 80 and NFPA 92-1993 for proper placement. (3) Verify input voltage to model being used. (4) Maximum loop resistance 100 ohms. Verify contact rating of End of Line Relay. (5) Jumper must remain installed for two wire installation (figure 4A). (6) Jumper must remain installed if not using this option. (7) All fuses 2AG Fast Acting. See page 5, figures 5 &5A for proper ratings (8) End of line relay as per U.L. 864 See smoke detector installation instructions for proper End of Line Relay p/n and contact ratings. Installation of all wiring and related connecting hardware must be performed in accordance with the latest NFPA, U.L., and N.E.C. standards and codes. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material type, wiring gauge related to power capacity requirements and circuit length and wiring methods. 3A

FIGURE 4A - TWO WIRE/SINGLE DELAY High voltage connections (1) (2) (3) 120VAC Input power Initiating Device (Smoke detector, etc.) Model FFII PC MOUNT (4) Break wire for proper supervision. Do not loop wire around terminals TB3 CHASSIS MOUNT MV PC MOUNT NOT USED Low voltage connections (1) (2) (3) 24VAC or DC Input power Initiating Device (Smoke detector, etc.) Break wire for proper supervision. Do not loop wire around terminals Model FFII PC MOUNT (4) CHASSIS MOUNT NOT USED (+) (-) MV Board PC MOUNT 24VAC/DC ONLY Observe polarity on DC units (1) See NFPA 80 and NFPA 92-1993 for proper placement. (2) Verify input voltage to model being used. (3) See smoke detector installation instructions for contact ratings. Installation of all wiring and related connecting hardware must be performed in accordance with the latest NFPA, U.L., and N.E.C. standards and codes. In addition, all installations subject to Canadian standards shall be performed in accordance with the Canadian Electrical Code, Part I, with respect to wiring material type, wiring gauge related to power capacity requirements and circuit length and wiring methods. (4) Jumper must remain installed for two wire installation. (5) All fuses 2AG Fast Acting. See page 5, figures 5 &5A for proper ratings 3B

SECTION D. TEST PROCEDURES TO BE PERFORMED BY FACTORY AUTHORIZED PERSONNEL ONLY! THE COOKSON COMPANY RECOMMENDS REGULAR TESTING OF ALL RELEASE DEVICE EQUIPMENT. TESTING SHALL BE WITNESSED FOR PROPER OPERATION. Follow step A for electronic testing of Model Firefly II-MV. Step B refers to Model Firefly IIB-MV with Close Limit option. Step C power loss test may be performed on both models II and IIB. Testing does not affect normal operation of alarm system when connected to release device. Testing and normal operation can only be accomplished with power applied to unit. When power is applied to unit under test the Power LED (red) will be lit on the bottom of the release device. CLEAR FIRE DOOR OPENING AND PROHIBIT ALL TRAFFIC THROUGH DOOR OPENING DURING TESTING OF SYSTEM! Door must be in open position with power applied to unit to begin testing. A) 1. Depress and continue to hold test button on side of release device (figure 1). After factory adjusted 10 second alarm verification (10 sec. delay) device will release door. Release test button. 2. Reset and raise door, then reset release device by pushing reset lever in direction of arrow as indicated on device label. Fully insert end link through release device side opening and release reset lever to latch end link. B) 1. Using chain hoist, lower door to fully closed position. 2. Reset door, then release device by pushing reset lever in direction of arrow as indicated on device label. Fully insert end link through release device side opening and release reset lever to latch end link. 3. Verify that Close Limit LED (amber) is lit indicating the door is closed. Depress and continue to hold test button on side of release device for 10 seconds. Active Lower Limit logic will prohibit the release device from energizing. Release test button. 4. Raise door to fully open position. C. Power Loss Test. 1. Make sure door is in the fully open position. Turn off all power to release device (including motor control voltage when used on the model B). After approximately 10 seconds of continuous power loss, a mechanical release will be initiated. 2 Reset and raise door, then reset release device by pushing reset lever in direction of arrow as indicated on device label. Fully insert end link through release device side opening and release reset lever to latch end link. After completing all tests, make sure door is in its normally open position and all power required for normal operation is restored to unit. This unit is designed to operate with power applied. REMINDER: Testing of the Firefly II-MV release device is independent of, and shall in no way be interpreted as an alternative method of, testing of the fire alarm system, motorized operator and/or any other system component employed on the fire door or counter fire door installation. TESTING SHALL BE PERFORMED AND WITNESSED FOR PROPER OPERATION. 4

MAINTENANCE REQUIREMENTS The Firefly II-MV model release devices have no scheduled maintenance requirements. The unit has been designed and tested for use in indoor locations. The Cookson Company recommends weekly testing of the unit, but test intervals shall ultimately be subject to criteria established by the Final Authority Having Jurisdiction (AHJ). To increase power loss release time turn VR1 CCW and to increase alarm release time turn VR2 CCW. Serviceable fuses are provided for the following: See Figure 5 for fuse locations on release control board. Figure 5A illustrates fuses on Multi Voltage board. Figure 5 fuses F1 3/4A @ 250v, 2AG Fast Acting, Logic Board Power Supply F2 3/4A @ 250v, 2AG Fast Acting, MODEL B ONLY F3 3/4A @ 250v, 2AG Fast Acting, Power Input Replacement fuses may be ordered directly from the factory thru the technical support number provided below. Should servicing of fuses be required, personnel authorized to perform such maintenance shall ensure that; a) all traffic is prohibited thru door opening, b) door is mechanically released and fully closed, c) all power is disconnected from unit. After servicing equipment as required, unit shall be tested and witnessed for proper operation as described in SECTION D- TEST PROCEDURES, contained herein. FIGURE 5 Fuses Firefly II circuit board 1 2 K1 TB2 F2 3/4A @ 250V F3 3/4A @ 250V TB1 1 2 5 6 7 8 9 10 VR2 - ALARM VR1 - POWER LOSS F1 3/4A @ 250V FIGURE 5A - Fuses MV circuit board F1 2A @ 250v, 2AG Fast Acting, high voltage input F2 1A @ 250v, 2AG Fast Acting, low voltage input F3 1A @ 250v, 2AG Fast Acting, low voltage output F3 1A @ 250V F2 1A @ 250V F1 2A @ 250V Technical Support (602) 272-4244 5

Firefly II / IIB -MV TROUBLESHOOTING GUIDE Verify that desired options are available on unit before troubleshooting. Refer to electrical connection information and the maintenance and service page of this manual for fuse locations. Troubleshooting shall be performed by factory authorized personnel only. Service and/or installation by unauthorized personnel shall void warranty. Review the following guide prior to requesting technical support. If technical support is required, unit serial number (found on front of manual and inside unit), as well as distributor who supplied unit must be supplied. SYMPTOM 1. Red Power LED does not light. POSSIBLE TROUBLE A) Primary power source turned off. B) Loose connection on TB3 or MV board C) Incorrect polarity on D.C. unit D) Incorrect power source applied. Verify voltage and check fuses F1 & F2 of both circuit boards. 2. Red LED is on, but unit does not release door after alarm or power loss delay. 3. Amber Disable LED does not light (Model B) 4. Red LED is on, unit does not respond to manual test button, but works in alarm. 5) Unit blows fuse when power is applied A) N/C Alarm loop is not connected properly to TB1. Remove wires from TB1, 1 & 2. Continuity test on wires should be zero ohms (short) back to initiating device. Place smoke detector in alarm and verify that dry contacts open on alarm. B) Unit is detecting down limit (FFII B only). If Down Limit feature is not being used, jumper must remain in TB1, 6 & 7. C) Load on release mechanism exceeds 40lbs. Remove sash chain and test with manual test button for proper release. D) Damaged unit. Call tech support. A) Motor control voltage not connected to TB2 B) Motor control is D.C.. Check polarity. C) Control voltage is above 30V. Check FFII B circuit board fuse F2. A) Test button is not being depressed long enough. Depress button continuously for the 10 second delay. Unit must be powered up for a minimum of 15 seconds before testing. B) Unit is detecting down limit (FFII B only) Make sure Aux. down limit is connected properly. If N/O down limit is used, N/C loop (TB1-6&7) must have jumper installed. C) Possible defective switch. Call tech support. A) Incorrect power applied. Check unit label. Measure supply voltage. B) Unit has sustained damage from transient voltage. Call tech support. UNIT SERIAL NUMBER DISTRIBUTOR TECHNICAL SUPPORT (602) 272-4244 9AM - 5PM MST MON-FRI 6

NOTES/TEST RECORDS Copy this sheet and attach to manual for additional test data as required. Maintain test records in a secure location for future reference. UNIT SERIAL NUMBER: TEST DATE PERFORMED BY WITNESSED BY COMMENTS 7

OPERATOR NOTES 8

01-30588A