ACTUAL ENERGY CONSERVATIONS BY USING NH3/CO2 REFRIGERATION SYSTEM

Similar documents
MAYEKAWA. kongres. 45th HVAC&R CONGRES AND EXHIBITION : IMPROVING ENERGY EFFICIENCY IN CLIMATE AND OZONE FRIENDLY LATEST REFRIGERATION TECHNOLOGIES

MAYEKAWA MFG. CO., LTD Botan Koto-ku, Tokyo , JAPAN TEL:(81) FAX:(81)

Industrial Refrigeration System using NH3/CO2 Refrigerant NewTon - For Cold Storage in Japan and Others -

THE BIG FIVE NATURAL REFRIGERANTS IN DIFFERENT INDUSTRIAL APPLICATIONS. MAYEKAWA EUROPE S.A.,Leuvensesteenweg 605, 1930 Zaventem, Belgium

Our natural refrigerant technology and energy-efficiency solutions

Mayekawa Mfg. Co., Ltd. Kuniaki Kawamura

Global Solutions for Ammonia Industrial Refrigeration

Development of high temperature Heat Pumps using a low GWP refrigerant

Mayekawa Mfg. Co., Ltd. Kuniaki Kawamura 1

Natural Refrigerant Market Trends

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Use of transcritical CO 2 in industrial applications

COMPACT CO 2 /NH 3 REFRIGERATION UNIT FOR THE COLD STORAGE

The cold chain in the fishery sector. Refrigeration Technology Review

Ammonia Refrigeration & Scenario in Industrial Refrigeration. By Ramesh Paranjpey ASHRAE Fellow Life member

9. ENERGY PERFORMANCE ASSESSMENT OF HVAC SYSTEMS

High-efficiency Turbo Chiller (NART Series)

Comparison Ammonia / Secondary Refrigerant System against Direct Evaporation of HCFCs /HFCs

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

DEVELOPMENT OF A KILN DRIED WOOD SYSTEM USING HEAT PUMP TECHNOLOGY

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

FS 231: Final Exam (5-6-05) Part A (Closed Book): 60 points

Performance of an Improved Household Refrigerator/Freezer

Parilla Thermal Storage Project Case Study. May Page 1 of 11

DEMONSTRATION OF ADVANCED INTEGRATED HVAC&R SYSTEMS IN A LOBLAWS SUPERMARKET IN CANADA

CO 2 Ice Bank Answer to the next requirements

CO 2. ECO Water Heaters. Energy efficient and environmentally friendly water and space heating. SANYO Air Conditioners. The natural choice.

TECHNOLOGY and MARKET TRENDS

R&D ON HEAT PUMPS WITH NATURAL WORKING FLUIDS IN JAPAN

Chapter 10. Refrigeration and Heat Pump Systems

Introduction of Panasonic CO2 refrigeration system. Panasonic Corporation Refrigeration and Air-Conditioning Devices Business Division

NATURAL REFRIGERANTS FOR HEAT PUMPS AND AIR-CONDITIONING SYSTEMS. Bernard Thonon Greth

Introducing a New Ammonia/CO 2 Cascade Concept for Large Fishing Vessels

ETI-Z Series Centrifugal Chiller Applied Low GWP Refrigerant to Contribute to the Prevention of Global Warming

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

HFCs or the Old Refrigerants - what is the best Choice?

From the Field to the Supermarket

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

New Copper-based Heat Exchangers for R744 Refrigerant: Technologies for Tubes and Coils. Y. Shabtay, J. Black, N. Cotton

Energy consumption storage facilities examined in ICE-E

Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

investment in R&D, the commitment to - name.

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

EN aquatech.piovan.com

July 2012 was a significant date for the HVAC and Refrigeration industry as it saw the introduction of the Carbon Tax and the HFC Levy.

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

Environmentally friendly refrigeration systems for industrial use

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Refrigerants Type Expensive Coefficient of Performance Toxic

Effects of Latent/Sensible Heat Separation Air-Conditioning and Natural Ventilation on Indoor Thermal Environment in Environment-Friendly Office

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Magnetic Refrigeration. Study Case

Commercial CO 2 Refrigeration Systems

A Technical Introduction to Cool Thermal Energy Storage Commercial Applications

ICE THERMAL STORAGE SYSTEM USING DYNAMIC ICE IN HERBIS OSAKA PHASE I AND II PROJECTS

Development of centrifugal chiller and heat pump using low GWP refrigerant

Refrigeration and Air Conditioning

natural refrigerants - global trends & developments

REFRIGERATED AIR DRYERS SCFM. CRPC Energy Saving Series

Experimentation and Fabrication of Iceplant Using Ecofriendly Refrigerant

Exhibition Hall 1. Fachprogramm. Technical Programme

Thermodynamics II Chapter 5 Refrigeration

System Using Exhaust Heat from Residential GHPs

REDUCING AMMONIA REFRIGERANT CHARGE IN SKATING RINK REFRIGERATION SYSTEMS

Open and Closed Door Moisture Transport and Corresponding Energy Consumption in Household Refrigerator

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Comparative assessment for drop in replacement of R134a in domestic refrigerator.

PHASE-IN of natural refrigerants. Prof. Dr. Armin Hafner NTNU Norway

Brazed Plate Heat Exchanger for CO Applications

Improving Cold Chain Competitiveness with Danfoss Energy Efficiency Solutions.

AN EXPERIMENTAL REFRIGERATOR WITH AN INVERSE AIR CYCLE FOR FREEZING IQF FOOD PRODUCTS

PRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR /R a. R E Low, B E Gilbert, T W Dekleva.

Performance of non-cfc refrigerator driven by chilled water from 35 kw LiBr/H2O solar absorption cooling system

PACKAGED REFRIGERATION EQUIPMENT

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

TOP-ECO TECHNOLOGY HISTORY

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

THE INSTITUTE OF REFRIGERATION

Natural Refrigerants: Future-proof Solutions for Today. eurammon End-Users Day 2011

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

Mayekawa Mfg. Co., Ltd. Kuniaki Kawamura 1

Global Warming Impacts of Ozone-Safe Refrigerants and Refrigeration, Heating, and Air-conditioning Technologies. Steve Fischer Jim Sand Van Baxter

Low GWP Refrigerants for Air Conditioning Applications

RESEARCH ON NATURAL REFRIGERANTS IN JAPAN. WASEDA UNIVERSITY Kiyoshi SAITO

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

A new method for preventing air-source heat pumps and refrigerators from frosting

DRYTEC REFRIGERANT DRYERS

Emerging Refrigeration Technologies

Energy Performance of Low Charge NH3 Systems in Practice. Stefan S. Jensen

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Experimental study on automotive cooling and heating air conditioning system using CO 2 as a refrigerant

CHAPTER 1 INTRODUCTION

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

ORTEC INDUSTRIAL FLUID CHILLERS FC SERIES ( TONS) Compressed Air, Gas & Fluid Technologies. i e n d. l y. t a. R e. f r. i g e.

Air to Water Heat Pump Utilising Natural Refrigerant C02

Current use of HFCs and HCFCs. Trends, alternatives and climate impact. YEREVAN, Armenia, May 18-19, International Institute of Refrigeration

Transcription:

Proceedings of the 3 rd International Conference of Saving Energy in Refrigeration and Air-Conditioning ICSERA2013 October 23-25, 2013, Chonnam National University, Yeosu, Jeollanam-Do, KOREA ICSERA2013-3-C-2 ACTUAL ENERGY CONSERVATIONS BY USING NH3/CO2 REFRIGERATION SYSTEM Hideyo Asano 1), Nelson Mugabi 2) 1) NewTon Production Div., Moriya Factory, Mayekawa Mfg.Co.,Ltd., Mycom Tatsusawa 2000, Moriya City, Ibarakji Pref., Japan, 302-0118 2) R&D Div., Moriya Factory, Mayekawa Mfg.Co.,Ltd., Mycom Tatsusawa 2000, Moriya City, Ibarakji Pref., Japan, 302-0118 ABSTRACT: Electrical power supply in Japan continues to be unstable since March 11 th 2011 when the great Tohoku earthquake caused massive tsunamis that crippled the Fukushima nuclear power plant. The industrial world, therefore, is required to save energy. Since the refrigeration and storage industry consumes a lot of energy, power saving is urgently required. MYCOM has verified energy conservation in refrigeration plants using the NewTon series. The NewTon series uses environment friendly natural refrigerants NH 3 and CO 2 as primary and secondary refrigerants respectively to provide highly efficient cooling systems for the refrigeration industry. This paper reports on some examples of energy conservations (25 to 50%) realized in cold storage and freezing plants. 1. INTRODUCTION Power supply in Japan continues to be unstable since March 11 th 2011 when the great Tohoku earthquake caused massive tsunamis that crippled the Fukushima nuclear power plant. Almost all nuclear plants have been shut down because emphasis has shifted from steady power supply to safety. As a result steady power supply has become difficult and energy conservation is being required. Since the refrigeration and storage industry consumes a lot of energy, power saving is urgently required. In 2008 and with funds from the ministry of environment, MYCOM developed the NewTon with the aim of reducing environmental load. The NewTon series uses environment friendly natural refrigerants NH 3 and CO 2 as primary and secondary refrigerants respectively to provide highly efficient cooling systems for the refrigeration industry. This paper reports on some examples of energy conservations (25% to 50%) realized in refrigeration, storage and freezing plants. 2. THE IDEAL REFRIGERATION CYCLE Among the natural refrigerants, ammonia has the best physical and thermal properties with proved application. Figure 1 compares theoretical COPs of single, two stage and the CO 2 cascade systems working with ammonia. The two stage system offers the best COP between evaporating temperatures of -10 degree C and-50 degree C. A two stage system manufactured with high efficiency, therefore, conserves the most energy. Fig.1 Theoretical COP 3. CHARACTERISTICS OF NewTon NewTon was developed in 2008 with funds from the ministry of environment under Power conservation natural refrigerant refrigerators grant for the purpose of reducing CO 2 emissions. In order to reduce the environmental load, a natural refrigerant, ammonia was

Fig.2 NewTon R-3000 used. The aim was to achieve 20% energy conservation compared to the existing HCFC-22 systems. 3-1. NewTon CONCEPT Figure 3 shows the basic concepts of the NewTon. 3-3. IPM MOTOR Fig.4 Screw Compressor The screw compressor is mounted with a semi hermetic IPM motor. As shown in figure 5, an IPM motor has higher efficiency, 10%~15%, compared to the conventional induction motors. The IPM motor is a synchronized motor and uses an inverter as driver. Efficiency during part load operation is, therefore, improved compared to the conventional slide valve type. 1) Water cooled Fig.3 Basics concepts of the NewTon NewTon uses a closed circuit cooling tower to lower the condensing temperature thus reducing power consumption. A water cooled type increases freedom of installation place and is easy to maintain. It also helps reduce the amount of ammonia charged. 2) Ammonia package The ammonia package is factory fabricated and fully automated. The package includes an IPM motor and a screw compressor with a double economizer system and compact heat exchangers all specifically developed for this system. 3) CO 2 secondary refrigerant CO 2 is used as the secondary refrigerant. It is non toxic, requires less transport power because of low viscosity, and requires less refrigerant circulation because latent heat is used. Since CO 2 has no contaminants, air cooler performance does not deteriorate. 3-2. SCREW COMPRESSOR In order to increase the efficiency of the NewTon package, compound two stage screw was used. The compressor rotors have new profiles and are grinded for high precision finishing. Fig.5 Motor efficiency 3-4. DOUBLE ECONOMIZER After sub cooling liquid ammonia to the intermediate temperature, further sub cooling in the low stage economizer is done to improve the efficiency. Flush tanks are used to eliminate losses within heat exchangers. 3-5. SHELL & PLATE HEAT EXCHANGERS In order to minimize approach temperature and refrigerant charge, at the same time realize a compact package shell and plate heat exchangers are used for the condensers and evaporators. For example, approach temperature in evaporator is 1.7 degree and a 45kW motor model R-3000 uses only 25kg of ammonia. Refrigeration capacity per NH 3 charge is 3.9 kw/kg. 4. APPLICATIONS More than 400 packages have been installed and energy conservation has been verified. About 67% of the installed NewTon series are used in cold storages

while 26% are used in freezers and the rest in ice skate rinks. The NewTons used in cold storage in Japan currently accounts for 8% of the Japanese cold storage volume (2,500,000m 3 ). 5. VERIFICATION OF ENERGY CONSERVATION Examples of energy conservation in cold storage ware houses and freezer are given here. collected from more than 100 ware houses. Data collected shows that specific power consumption decreases as the size of storage volume increases. The graph also shows that NewTon offers the lowest specific power consumption when compared to HCFC-22 and NH 3 /Brine systems. Compared to HCFC-22 systems, specific power consumption is lower by 25% with NewTon. 5-1. COLD STORAGE The amount of electric power used for refrigeration in clod ware houses accounts for 60 ~70% of the total electric power. Figure 6 shows a breakdown electric power used in large cold storage around Tokyo. Fig.7 Cold storage specific power consumption Fig.6 Electric power usage in ware houses The graph shows that power is least consumed in February (winter) and most consumed in August (summer). The power used in February is nearly 60% of the power used in August. The graph also shows that refrigeration accounts for about 65% of the total power throughout the year. The rest of the power is used in lighting and conveying systems (30%) and office appliances (5%). 1) Specific power consumption Electric consumption in cold storage ware houses is estimated by specific power consumption as shown in the equation below. SPC = PCy/Vc (1) SPC : Specific Power Consumption (kwh/year/m 3 ) PCy : Annual Power Consumption (kwh/year) Vc : Cold Storage Volume (m 3 ) Annual power consumption is the total power consumption of the ware house which includes office appliances, lighting, conveying systems as well as refrigeration systems. Specific power consumption is affected by the type of ware house (storage or distribution), its structure, insulation, storage volume, and type of refrigeration system used. 2) Comparison of refrigeration systems Figure 7 shows a comparison of specific power consumption for various refrigeration systems. Data was 3) Renewal More than half of the cold ware houses in Japan are more than 20 years old and almost all use HCFC-22 as the working fluid. There is a need for renewal of these systems. Table 1 shows electric consumption in some of the ware houses replaced with NewTon. Table 1. Power reduction through renewal with NewTon Case Volume Age Refrigerant formerly used Power reduction (m 3 ) (year) Refrig. Comp. (%) A 45,000 29 HCFC-22 Screw 31.1 B 10,000 33 HCFC-22 Recip 41.2 C 16,250 27 HCFC-22 Recip 24.9 D 6,125 38 HCFC-22 Screw 29.3 E 7,500 25 HCFC-22 Recip 28.0 F 30,000 30 HCFC-22 Screw 19.8 G 32,500 22 HCFC-22 Recip 28.0 H 30,000 25 NH 3/Brine Recip 34.0 Power consumption shown in table 1 is for the whole ware house. Replacement with NewTon reduced power consumption by about 30%. Figure 8 shows power consumption for Case A before and after replacement of the refrigeration system. For Case A, average annual power consumption is reduced by 31.1%, while energy conservation for refriger ation is about 50%, because refrigeration system accou nts for about 65% of total power consumption.

LC1: Cooling down load before freezing LC2: Freezing load LC3: Cooling down load after freezing Equation 2 used to evaluate freezer efficiency takes into account the various frozen materials, various inlet and outlet temperatures of the frozen materials as well as power consumption which varies according ambient temperatures of the seasons. 3) Freezer Energy efficiency factor ( Potatoes) Fig.8 Energy conservation effect Case A 5-2. FREEZER Power consumption data of freezer systems were measured at some customer sites to evaluate energy efficiency of them. 1) Application in Freezers Table 2 shows a comparison of power consumption in a freezer with a newly installed NewTon and an IQF Freezer (FLoFREEZE) with an existing system using HCFC-22 liquid pump and a two stage screw compressor (F2016LSC) to freeze sweet potatoes cut into different sizes. Table2. Comparison of power consumption in a Freezer Potato cut HCFC-22 Power NewTon size (F2016C) reduction (mm) (kwh/ton) ( - ) 4.8/4.8/4.8 133.5 200.0 0.668 10/10/10 109.0 146.2 0.746 15/15/15 122.1 174.9 0.689 The table shows that use of NewTon reduces power consumption by about 30% when freezing one ton of sweet potatoes. 2) Definition of energy efficiency factor for freezers A freezer system is evaluated by quality of frozen material, freezing time (speed) and energy efficiency. The energy efficiency factor for evaluating the freezer is defined in the equation below. ECF = (LCt/Wa)Kca (2) ECF: Energy Efficiency Factor for Freezer system LCt: Required Total Cooling Load Wa: Actual Power consumption Kta: Calibration of ambient temperature The required Total Cooling Load is calculated as shown below. LCt = LC1 + LC2 + LC3 (3) Table 3 shows energy efficiencies calculated using data when freezing potatoes in various potato cut sizes shown in table 2. Conditions used in the calculations are set as follows, freezer inlet and outlet temperatures are 25 degree C and -18 degree C, specific heat of potatoes before and after freezing is 0.813kcal/kgK and 0.407kcal/kgK respectively while the latent heat is 54.9kcal/kg and ambient temperature is 25degree C. The table shows that using NewTon increases the energy efficiency from 34% to 50% compared to HCFC- 22 liquid circulation system. Table3. Freezer energy efficiency factor (Potatoes) Size HCFC-22 Ratio NewTon (mm) (F2016LSC) 4.8 x 4.8 x 4.8 0.622 0.415 1.50 10 x 10 x 10 0.761 0.568 1.34 15 x 15 x 15 0.680 0.475 1.43 4) Freezer energy efficiency factor (Salmon) Table 4 compares energy efficiency when using NewTon and existing HCFC-22 dry expansion system in freezing salmon fillet. Table4. Freezer energy efficiency factor (salmon) Ref. system Inlet temp. Outlet temp. Amb temp. Power consump ECF NewTon 10.0-8.5 18.5 77.5 0.773 HCFC-22 9.0-10.0 10.0 85.7 0.577 Unit (C) (C) (C) (kwh/ton) ( - ) The table shows that compared with the existing system which uses HCFC-22, NewTon reduces power consumption by more than 10% and the energy efficiency factor is about 34% better. 6. CONCLUSIONS The NewTon using natural refrigerants ammonia and carbon dioxide was initially developed to reduce the environmental load. However, since the Tohoku earthquake that disrupted electricity supply, NewTon has also been installed by many customers seeking to reduce power consumption. A survey of NewTon systems in operation shows that compared to HCFC-22 systems, NewTon reduces power consumption by 25%~30% in cold ware houses and 10%~30% in freezers. By using the specific power consumption for ware houses and energy efficiency factor for freezers, ware

houses of different sizes and cooling systems can be compared and also freezers operating in various conditions can be compared. 7. REFERENCES [1] HideyoAsano,2011, Safety and energy saving results of NewTon 3000 with NH 3 /CO 2 refrigerant, ICACR2011, Yong Pyong, Korea [2] Hideyo Asano, 2011, Energy conservation of Refrigerated warehouse using NH 3 /CO 2, Refrigeration, Vol.86 No.1008