C let us discover the seven p3ductal gears C
P3ductal: one system, many solutions P3ductal care air ducts solution with antimicrobial treatment to be used in environments which require high levels of hygiene. P3ductal resistant air ducts solution for aggressive environments, with highly resistant polyester film coated panels. P3ductal indoor standard air ducts solution for internal applications. P3ductal smart8 octagonal air ducts solution for low pressure systems with high aesthetical requirements, made up of pre-cut panels. P3ductal outdoor special air ducts solution for external applications. P3ductal careplus new P3ductal smart4 quadrangular air ducts solution for low pressure systems, made up of pre-cut panels. air ducts solution with self-cleaning and antimicrobial coating to be used in environments which require high levels of hygiene.
For every application the right duct indoor applications duct system outdoor applications duct system high hygiene applications antimicrobial duct system careplus new easy cleaning high hygiene duct[al] system self-cleaning and antimicrobial duct system aggressive applications duct system low pressure duct system low pressure high aesthetics duct system
For every duct the right panel Piral HD Hydrotec standard panels: panels to be used indoor for standard applications or for environments which require high levels of hygiene Requirements > safety > eco-sustainability > energy saving Applications > shopping centres and offices > theatres, cinemas and sports centres > airports and train stations 15HP21 Piral HD Hydrotec Panel - thickness 20,5 mm Aluminium: embossed/embossed, 80μm/80μm 15HS21 Piral HD Hydrotec Panel - thickness 20,5 mm Aluminium: embossed/embossed, 200μm/80μm Features: the 200μm thick external aluminium confers particular resistance and protects the exposed ducts (for example, technical compartments) from accidental damage. 15HP31 Piral HD Hydrotec Panel Big Size - thickness 30,5 mm Aluminium: embossed/embossed, 80μm/80μm Features: the foams 30,5 mm confers to the panel further strength and makes the panel suitable for the construction of ducts with big dimensions with less reinforcements. 15HB21 Piral MD Hydrotec Panel - thickness 20,5 mm Aluminium: embossed/embossed, 60μm/60μm Piral HD Hydrotec Smooth Panel Requirements > high air quality and hygiene > easy cleaning > easy maintenance Applications > hospitals > laboratories > food industry 15HL21 15HN21 15OL21 Piral HD Hydrotec smooth Panel - thickness 20,5 mm Aluminium: embossed/smooth, 80μm/80μm Piral HD Hydrotec smooth Panel - thickness 20,5 mm Aluminium: embossed/smooth, 80μm/200μm Features: the 200μm thick internal aluminium guarantees maximum resistance to potential damage during maintenance and internal cleaning Piral HD Hydrotec smooth Panel - thickness 20,5 mm Aluminium: embossed/smooth, 200μm/80μm Features: the 200μm thick external aluminium confers particular resistance and protects the exposed ducts (technical compartments) from accidental damage. 15HR21* 15HL31* Piral HD Hydrotec smooth Panel - thickness 20,5 mm Aluminium: embossed/smooth, 200μm/200μm Features: the 200μm thick internal aluminium guarantees maximum resistance to potential damage during maintenance and internal cleaning. The 200μm thick external aluminium confers particular resistance and protects the exposed ducts (for example, technical compartments) from accidental damage. Piral HD Hydrotec smooth Panel - thickness 30,5 mm Aluminium: embossed/smooth, 80μm/80μm Features: the 30,5 mm foam board confers to the panel further strength and makes the panel suitable for the construction of ducts with big dimensions with less reinforcements.
Piral HD Hydrotec outsider panels: panels to be used outdoors for standard applications or for environments which require high levels of hygiene. Requirements > resistance to atmospheric agents, snow and wind loads > resistance to perforation and accidental damage Applications > shopping centres and offices > theatres, cinemas and sports centres > airports and train stations 15HS31 Piral HD Hydrotec Outsider Panel - thickness 30,5 mm Aluminium: embossed/embossed, 200 μm/80μm Features: the 30,5 mm foam and 200μm external aluminium, confer to the panel resistance to the atmospheric agents and accidental damage. To be used together with the Gum Skin waterproofing. Piral HD Hydrotec Smooth Outsider Panel Requirements > resistance to atmospheric agents > resistance to perforation and accidental damage > high air quality Applications > hospitals > laboratories > food and pharmaceutical industries 15OL31 Piral HD Hydrotec Smooth Outsider Panel - thickness 30,5 mm Aluminium: embossed/smooth, 200μm/80μm Features: the 30,5 mm foam board and 200μm external aluminium, confer to the panel resistance to the atmospheric agents and accidental damage. This together with the smooth internal aluminium makes this panel ideal for the construction of outdoor ducts at the service of environments with high hygienic requirements. To be used together with the Gum Skin waterproofing. 15HR31 Piral HD Hydrotec Smooth Outsider Panel - thickness 30,5 mm Aluminium: embossed/smooth, 200μm/200μm Features: the 30,5 mm foam board and 200μm external aluminium, confer to the panel resistance to the atmospheric agents and accidental damage. This together with the smooth antimicrobial internal aluminium makes this panel ideal for the construction of outdoor ducts at the service of environments with high hygienic requirements. To be used together with the Gum Skin waterproofing.
For every duct the right panel Piral HD Hydrotec with antimicrobial treatment: panels treated with antimicrobial to be used in environments which require high levels of hygiene. Requirements > highest air quality > absolute hygiene Applications > operating rooms > clean rooms 15HL21ABT Piral HD Hydrotec Panel - antimicrobial treatment (side with smooth aluminium) - thickness 20,5 mm Aluminium: embossed/smooth, 80μm/80μm Features: the internal smooth antimicrobial aluminium makes this panel ideal for ducts at the service of environments with the highest hygiene requirements. 15OL31ABT Piral HD Hydrotec Outsider Panel - antimicrobial treatment (side with smooth aluminium) - thickness 30,5 mm Aluminium: embossed/smooth, 200μm/80μm Features: the 30,5 mm foam and 200μm external aluminium, confer to the panel resistance to the atmospheric agents and accidental damage. This together with the internal smooth antimicrobial aluminium makes this panel ideal for the construction of outdoor ducts at the service of environments with the highest hygiene requirements. To be used together with Gum Skin waterproofing. 15HN21ABT Piral HD Hydrotec Panel - antimicrobial treatment (side with smooth aluminium) - thickness 20,5 mm Aluminium: embossed/smooth, 80μm/200μm Features: the 200μm thick internal aluminium guarantees maximum resistance to potential damage during maintenance and internal cleaning. This together with the internal smooth antimicrobial aluminium makes this panel ideal for the construction of outdoor ducts at the service of environments the highest hygiene requirements. 15HR31ABT Piral HD Hydrotec Outsider Panel - antimicrobial treatment (side with smooth aluminium) - thickness 30,5 mm Aluminium: embossed/smooth, 200μm/200μm Features: the 30,5 mm foam and 200μm external aluminium, confer to the panel resistance to the atmospheric agents and accidental damage. This together with the internal smooth antimicrobial aluminium makes this panel ideal for the construction of outdoor ducts at the service of environments with the highest hygiene requirements. To be used together with Gum Skin waterproofing. careplus easy cleaning high hygiene duct[al] system P3ductal careplus - antimicrobial panels with self-cleaning nanostructured coating to be used in environments which require high levels of hygiene. new Requirements > highest air quality > total cleaning > absolute hygiene Applications > operating rooms > clean rooms 15HL21PLUS Piral HD Hydrotec panel with self cleaning and antimicrobial treatment on smooth aluminium side - th. 20,5 mm Aluminium: embossed/smooth, 80μm/80μm Features: the internal smooth self-cleaning and antimicrobial aluminium makes this panel ideal for ducts at the service of environments with the highest hygiene requirements. 15OL31PLUS Piral HD Hydrotec Outsider panel with self cleaning and antimicrobial treatment on smooth aluminium side - th. 30,5 mm Aluminium: embossed/smooth, 200μm/80μm Features: the 30,5 mm foam and 200μm external aluminium, confer to the panel resistance to the atmospheric agents and accidental damage. This together with the internal smooth selfcleaning and antimicrobial aluminium makes this panel ideal for the construction of outdoor ducts at the service of environments with the highest hygiene requirements. To be used together with Gum Skin waterproofing. 15HN21PLUS Piral HD Hydrotec panel with self cleaning and antimicrobial treatment on smooth aluminium side - th. 20,5 mm Aluminium: embossed/smooth, 80μm/200μm Features: the 200μm thick internal aluminium guarantees maximum resistance to potential damage during maintenance and internal cleaning. This together with the internal smooth self-cleaning and antimicrobial aluminium makes this panel ideal for the construction of ducts at the service of environments with the highest hygiene requirements. 15HR31PLUS Piral HD Hydrotec Outsider panel with self cleaning and antimicrobial treatment on smooth aluminium side - th. 30,5 mm Aluminium: embossed/smooth, 200μm/200μm Features: the 30,5 mm foam and 200μm external aluminium, confer to the panel resistance to the atmospheric agents and accidental damage. This together with the internal smooth selfcleaning and antimicrobial aluminium makes this panel ideal for the construction of outdoor ducts at the service of environments with the highest hygiene requirements. To be used together with Gum Skin waterproofing.
Piral HD Hydrotec panel coupled with polyester film: aggressive applications panels Requirements > resistance to aggressive environments > resistance to corrosion Applications > swimming pools > cheese factories > seasoning rooms 15HE21 Piral HD Hydrotec Panel coupled with polyester layer - thickness 20,5 mm Aluminium: embossed/embossed, 80μm/80μm + 13μm polyester film, Panels for the smart4 system: quadrangular air ducts solution for low pressure systems. Requirements > fast and easy to assemble > reduced transport volumes > off-cuts reduction Applications > quadrangular ducts to be installed in civil, commercial and professional systems with pressures up to 250 Pa. Piral HD Hydrotec panel for Smart4 construction system - thickness 12 mm Aluminium: embossed/embossed, 80μm/80μm The panels are provided exclusively pre-cut in kit format in a box, together with the labyrinth bayonet for the fast closing of the ducts. Panels for the smart8 system: octagonal air ducts solution for low pressure systems with high aesthetical requirements. Requirements > fast and easy to assemble > reduced transport volumes > off-cuts reduction > high aesthetics Applications > octagonal ducts to be installed in civil, commercial and professional systems with pressures up to 300 Pa. Piral HD Hydrotec panel for Smart8 construction system - thickness 12 mm Aluminium: embossed/embossed, 80μm/80μm The panels are provided exclusively pre-cut in kit format in a box, together with the labyrinth bayonet for the fast closing of the ducts.
standard indoor applications The pre-insulated aluminium HVAC ducts will be produced using environmentally compatible sandwich panels like the PIRAL HD HYDROTEC PANEL and with the following properties: Panel thickness: 20.5 mm; External aluminium: 0.08mm thick, embossed and protected with polyester lacquer; Internal aluminium: 0.08mm thick, embossed and protected with polyester lacquer; Initial thermal conductivity: 0.022 W/(m C) at 10 C; Insulating material density: 50-54 kg/m 3 ; Insulating material: polyurethane which has been expanded with the use of only water and not with CFC, HCFC, HFC or HC gasses; Insulation expanding agent: ODP (ozone depletion potential) = 0 and GWP (global warming potential) = 0; % closed cells: > 95% according to ISO 4590; Rigidity class: R 200,000 according to UNI EN 13403; Fire reaction class: 0-1 according to Italian ministerial decree (D.M.) 26/06/84; Fire reaction class: B according to European Standard EN 13501-1; Fire reaction class: approved according to the ISO 9705 standard (Room corner test); Smoke toxicity and opacity: class F1 according to NF F 16-101; Smoke toxicity: FED and FEC < 0.3 according to pren 50399-2-1/1; Smoke toxicity: below 6.7 according to the British Naval Engineering Standard NES 713; Ducts will be built to P3ductal standards and in conformity with the UNI EN 13403 standard. REINFORCEMNETS Where necessary, the ducts will be fitted with special reinforcement bars in order to provide further mechanical strength during operation. Said reinforcements will be calculated using the manufacturer s charts. The maximum deflection of the sides of the duct must not exceed 3% or in any case 30 mm, as laid down in standard UNI EN 13403. FLANGING The individual lengths of ducting will be joined together by means of special invisible flanges with hidden bayonet connections, providing a suitable airtight and mechanical seal to meet the requirements of standard UNI EN 13403. The maximum length of each section of duct will be 4 metres. TURNING VANES & SPLITTERS All rectangular elbows must be fitted with special turning vanes; the large circular elbows will be fitted with splitters in order to meet the requirements of standard UNI EN 1505. SUPPORTS Ducts will be supported by special brackets at intervals which should not exceed 4 metres if the widest side of the duct is less than 1 metre, and at intervals which should not exceed 2 metres if the widest side of the duct is more than 1 metre. Accessories, such as: volume dampers, fire dampers, diffusers, in-duct heating coils etc. will be supported independently so that the ducts do not have to support their weight. INSPECTION Ducts will be fitted with special control points for airflow sensors and doors for inspection and cleaning set at intervals along the ducts as laid down by standard EN 12097 and by the Guidelines published in the Italian Official Gazette dated 3/11/2006 relating to ventilation system maintenance. Doors may be made using the same type of sandwich panel used to produce the ducting, in conjunction with the relevant profiles. Doors will be fitted with seals in order to provide the required airtight seal. Alternatively, P3ductal inspection hatches may be used. AHU CONNECTION Connections between air handling units and ducting will be performed by means of special antivibration joints in order to isolate them from vibrations. Ducts will be supported independently in order to pevent that the weight of the ducts be transferred to the flexible fittings. Moreover, connection with the air handling unit will allow the unit to be uncoupled for system maintenance purposes. Should the antivibration joints be fitted outdoor, they will have to be waterproof.
high hygene indoor applications The pre-insulated aluminium HVAC ducts will be produced using environmentally compatible sandwich panels like the PIRAL HD HYDROTEC SMOOTH PANEL with the following properties: Panel thickness: 20.5 mm; External aluminium: 0.08 mm thick, embossed and protected with polyester lacquer; Internal aluminium: 0.08 mm thick, smooth and protected with polyester lacquer; Initial thermal conductivity: 0.022 W/(m C) at 10 C; Insulating material density: 50-54 kg/m 3 ; Insulating material: polyurethane which has been expanded with the use of only water and not with CFC, HCFC, HFC or HC gasses; Insulation expanding agent: ODP (ozone depletion potential) = 0 and GWP (global warming potential) = 0; % closed cells: > 95% according to ISO 4590; Rigidity class: R 200,000 according to UNI EN 13403; Fire reaction class: 0-1 according to Italian ministerial decree (D.M.) 26/06/84; Fire reaction class: B according to European Standard EN 13501-1; Fire reaction class: approved according to the ISO 9705 standard (Room corner test); Smoke toxicity and opacity: class F1 according to NF F 16-101; Smoke toxicity: FED and FEC < 0.3 according to pren 50399-2-1/1; Smoke toxicity: below 6.7 according to the British Naval Engineering Standard NES 713; Ducting will be built to P3ductal standards and in conformity with the UNI EN 13403 standard. REINFORCEMNETS Where necessary, the ducts will be fitted with special reinforcement bars in order to provide further mechanical strength during operation. Said reinforcements will be calculated using the manufacturer s charts. The maximum deflection of the sides of the duct must not exceed 3% or in any case 30 mm, as laid down in standard UNI EN 13403. FLANGING The individual lengths of ducting will be joined together by means of special invisible flanges with hidden bayonet connections, providing a suitable airtight and mechanical seal to meet the requirements of standard UNI EN 13403. The maximum length of each section of duct will be 4 metres. TURNING VANES & SPLITTERS All rectangular elbows must be fitted with special turning vanes; the large circular elbows will be fitted with splitters in order to meet the requirements of standard UNI EN 1505. SUPPORTS Ducts will be supported by special brackets at intervals which should not exceed 4 metres if the widest side of the duct is less than 1 metre, and at intervals which should not exceed 2 metres if the widest side of the duct is more than 1 metre. Accessories, such as: volume dampers, fire dampers, diffusers, in-duct heating coils etc. will be supported independently so that the ducts do not have to support their weight. INSPECTION Ducts will be fitted with special control points for airflow sensors and doors for inspection and cleaning set at intervals along the ducts as laid down by standard EN 12097 and by the Guidelines published in the Italian Official Gazette dated 3/11/2006 relating to ventilation system maintenance. Doors may be made using the same type of sandwich panel used to produce the ducting, in conjunction with the relevant profiles. Doors will be fitted with seals in order to provide the required airtight seal. Alternatively, P3ductal inspection hatches may be used. AHU CONNECTION Connections between air handling units and ducting will be performed by means of special antivibration joints in order to isolate them from vibrations. Ducts will be supported independently in order to pevent that the weight of the ducts be transferred to the flexible fittings. Moreover, connection with the air handling unit will allow the unit to be uncoupled for system maintenance purposes. Should the antivibration joints be fitted outdoor, they will have to be waterproof.
outdoor applications The pre-insulated aluminium HVAC ducts will be produced using environmentally compatible sandwich panels like the PIRAL HD HYDROTEC OUTSIDER PANEL and with the following properties: Panel thickness: 30.5 mm; External aluminium: 0.2mm thick, embossed and protected with polyester lacquer; Internal aluminium: 0.08mm thick, embossed and protected with polyester lacquer; Initial thermal conductivity: 0.022 W/(m C) at 10 C; Insulating material density: 46-50 kg/m 3 ; Insulating material: polyurethane which has been expanded with the use of only water and not with CFC, HCFC, HFC or HC gasses; Insulation expanding agent: ODP (ozone depletion potential) = 0 and GWP (global warming potential) = 0; % closed cells: > 95% according to ISO 4590; Rigidity class: R 900,000 according to UNI EN 13403; Fire reaction class: 0-1 according to Italian ministerial decree (D.M.) 26/06/84; Fire reaction class: B according to European Standard EN 13501-1. Ducts will be protected once installed with a waterproofing Gum Skin resin. Bitumen-based compounds must not be used. It is advisable to apply strengthening gauze around flanging points. Ducts will be built to P3ductal standards and in conformity with standard UNI EN 13403. REINFORCEMNETS Where necessary, the ducts will be fitted with special reinforcement bars in order to provide further mechanical strength during operation. Said reinforcements will be calculated using the manufacturer s charts. The maximum deflection of the sides of the duct must not exceed 3% or in any case 30 mm, as laid down in standard UNI EN 13403. FLANGING The individual lengths of ducting will be joined together by means of special invisible flanges with hidden bayonet connections, providing a suitable airtight and mechanical seal to meet the requirements of standard UNI EN 13403. The maximum length of each section of duct will be 4 metres. TURNING VANES & SPLITTERS All rectangular elbows must be fitted with special turning vanes; the large circular elbows will be fitted with splitters in order to meet the requirements of standard UNI EN 1505. SNOW/WIND LOADS Ducts must be also sized in order to bare the snow/wind loads as stated in the manufacturer s tables. CONSTRUCTION SOLUTIONS Should the ducts pass through the roof, they should be fitted at the end with gooseneck shaped bends in order to prevent water and/or snow from getting in. All external duct openings, like the exhaust outlets, external air intakes etc. will be fitted with special bird grids.
very high hygene applications The pre-insulated aluminium HVAC ducts will be produced using environmentally compatible sandwich panels like the PIRAL HD HYDROTEC Antimicrobial PANEL with the following properties: Panel thickness: 20.5 mm; External aluminium: 0.08mm thick, embossed and protected with polyester lacquer; Internal aluminium: 0.2mm thick, smooth and with antimicrobial treatment; Initial thermal conductivity: 0.022 W/(m C) at 10 C; Insulating material density: 50-54 kg/m 3 ; Insulating material: polyurethane which has been expanded with the use of only water and not with CFC, HCFC, HFC or HC gasses; Insulation expanding agent: ODP (ozone depletion potential) = 0 and GWP (global warming potential) = 0; % closed cells: > 95% according to ISO 4590; Rigidity class: R 200,000 according to UNI EN 13403; Fire reaction class: 0-1 according to Italian ministerial decree (D.M.) 26/06/84; Fire reaction class: B according to European Standard EN 13501-1; Fire reaction class: approved according to the ISO 9705 standard (Room corner test); Smoke toxicity and opacity: class F1 according to NF F 16-101; Smoke toxicity: FED and FEC < 0.3 according to pren 50399-2-1/1; Smoke toxicity: below 6.7 according to the British Naval Engineering Standard NES 713; Efficacy of antimicrobial active principle: verified in conformity with standard ISO 22196 by an Italian Ministry of Health accredited laboratory; Antimicrobial active principle: notified in conformity with European biocidal products directive BPD; Antimicrobial active principle approvals: EFSA (food contact evaluated), EPA (non food contact approved) and FIFRA (food contact approved). Ducts will be built to P3ductal standards and in conformity with the UNI EN 13403 standard. The ducts will have to be manufactured using accessories with antimicrobial treatment. REINFORCEMNETS Where necessary, the ducts will be fitted with special reinforcement bars in order to provide further mechanical strength during operation. Said reinforcements will be calculated using the manufacturer s charts. The maximum deflection of the sides of the duct must not exceed 3% or in any case 30 mm, as laid down in standard UNI EN 13403. FLANGING The individual lengths of ducting will be joined together by means of special invisible flanges with hidden bayonet connections, providing a suitable airtight and mechanical seal to meet the requirements of standard UNI EN 13403. The maximum length of each section of duct will be 4 metres. TURNING VANES & SPLITTERS All rectangular elbows must be fitted with special turning vanes; the large circular elbows will be fitted with splitters in order to meet the requirements of standard UNI EN 1505. SUPPORTS Ducts will be supported by special brackets at intervals which should not exceed 4 metres if the widest side of the duct is less than 1 metre, and at intervals which should not exceed 2 metres if the widest side of the duct is more than 1 metre. Accessories, such as: volume dampers, fire dampers, diffusers, in-duct heating coils etc. will be supported independently so that the ducts do not have to support their weight. INSPECTION Ducts will be fitted with special control points for airflow sensors and doors for inspection and cleaning set at intervals along the ducts as laid down by standard EN 12097 and by the Guidelines published in the Italian Official Gazette dated 3/11/2006 relating to ventilation system maintenance. Doors may be made using the same type of sandwich panel used to produce the ducting, in conjunction with the relevant profiles. Doors will be fitted with seals in order to provide the required airtight seal. Alternatively, P3ductal inspection hatches may be used. AHU CONNECTION Connections between air handling units and ducting will be performed by means of special antivibration joints in order to isolate them from vibrations. Ducts will be supported independently in order to pevent that the weight of the ducts be transferred to the flexible fittings. Moreover, connection with the air handling unit will allow the unit to be uncoupled for system maintenance purposes. Should the antivibration joints be fitted outdoor, they will have to be waterproof.
outdoor applications with high hygiene requirement The pre-insulated aluminium HVAC ducts will be produced using environmentally compatible sandwich panels like the PIRAL HD HYDROTEC OUTSIDER Antimicrobial PANEL with the following properties: Panel thickness: 30.5 mm; External aluminium: 0.2mm thick, embossed and protected with polyester lacquer; Internal aluminium: 0.2mm thick, smooth and with antimicrobial treatment; Initial thermal conductivity: 0.022 W/(m C) at 10 C; Insulating material density: 46-50 kg/m 3 ; Insulating material: polyurethane which has been expanded only with the use of only water and not with CFC, HCFC, HFC or HC gasses; Insulation expanding agent: zero ODP (ozone depletion potential) and zero GWP (global warming potential); % closed cells: > 95% according to ISO 4590; Rigidity class: R 900,000 according to UNI EN 13403; Fire reaction class: 0-1 according to Italian ministerial decree (D.M.) 26/06/84; Fire reaction class: B according to European Standard EN 13501-1; Efficacy of antimicrobial active principle: verified in conformity with standard ISO 22196 by an Italian Ministry of Health accredited laboratory; Antimicrobial active principle: notified in conformity with European biocidal products directive BPD; Antimicrobial active principle approvals: EFSA (food contact evaluated), EPA (non food contact approved) and FIFRA (food contact approved). Ducts will be protected once installed with a waterproofing Gum Skin resin. Bitumen-based compounds must not be used. It is advisable to apply strengthening gauze around flanging points. Ducts will be built to P3ductal standards and in conformity with standard UNI EN 13403. The ducts will have to be manufactured using accessories with antimicrobial treatment. REINFORCEMNETS Where necessary, the ducts will be fitted with special reinforcement bars in order to provide further mechanical strength during operation. Said reinforcements will be calculated using the manufacturer s charts. The maximum deflection of the sides of the duct must not exceed 3% or in any case 30 mm, as laid down in standard UNI EN 13403. FLANGING The individual lengths of ducting will be joined together by means of special invisible flanges with hidden bayonet connections, providing a suitable airtight and mechanical seal to meet the requirements of standard UNI EN 13403. The maximum length of each section of duct will be 4 metres. TURNING VANES & SPLITTERS All rectangular elbows must be fitted with special turning vanes; the large circular elbows will be fitted with splitters in order to meet the requirements of standard UNI EN 1505. SNOW/WIND LOADS Ducts must be also sized in order to bare the snow/wind loads as stated in the manufacturer s tables. CONSTRUCTION SOLUTIONS Should the ducts pass through the roof, they should be fitted at the end with gooseneck shaped bends in order to prevent water and/or snow from getting in. All external duct openings, like the exhaust outlets, external air intakes etc. will be fitted with special bird grids.
careplus easy cleaning high hygiene duct[al] system applications with antimicrobial self-cleaning nanostructured coating to be used in environments which require high levels of hygiene Pre-insulated aluminium ducts for the air thermo-ventilation and air conditioning will have to be manufactured using eco-compatible sandwich panels of the P3ductal careplus line like the PIRAL HD HYDROTEC PANEL WITH SELF-CLEANING AND ANTIMICROBIAL TREATMENT. This panel with the lotus effect, is capable of reducing the possible formation of dust or solid particles and to simplify, consequently, the normal maintenance and cleaning operations of the ducts as foreseen by the guidelines draft in air conditioning systems predictive maintenance technical protocols published by the Italian Health ministry in the Official Gazette on the 3rd of November 2006 and foreseen by the UNI EN 15780 Standard Ventilation for buildings Ductwork Cleanliness of Ventilation System. The panel has the following properties: Panel thickness: 20.5 mm; External aluminium: 0.08 mm thick, embossed and protected with polyester lacquer; Internal aluminium: 0.2 mm thick, smooth and with self-cleaning and antimicrobial treatment; Self-cleaning treatment: nanostructured coating based on liquid glass; Efficacy of the self cleaning effect: verified thanks to large scale testing in collaboration with a University Department; Efficacy of antimicrobial active principle: verified in conformity with standard ISO 22196 by an Italian Ministry of Health accredited laboratory. Initial thermal conductivity: 0.022 W/(m C) at 10 C; Insulating material density: 50-54 kg/m 3 ; Insulating material: polyurethane which has been expanded with the use of only water and not with CFC, HCFC, HFC or HC gasses; Insulation expanding agent: ODP (ozone depletion potential) = 0 and GWP (global warming potential) = 0; % closed cells: > 95% according to ISO 4590; Rigidity class: R 200,000 according to UNI EN 13403; Fire reaction class: 0-1 according to Italian ministerial decree (D.M.) 26/06/84; Fire reaction class: B according to European Standard EN 13501-1; Fire reaction class: approved according to the ISO 9705 standard (Room corner test); Smoke toxicity and opacity: class F1 according to NF F 16-101; Smoke toxicity: FED and FEC < 0.3 according to pren 50399-2-1/1; Smoke toxicity: below 6.7 according to the British Naval Engineering Standard NES 713; Ducts will have to be manufactured to P3ductal standards and in conformity with the UNI EN 13403 standard. The ducts will have to be manufactured using accessories with antimicrobial treatment. FLANGING The individual lengths of ducting will be joined together by means of special invisible flanges with hidden bayonet connections, providing a suitable airtight and mechanical seal to meet the requirements of standard UNI EN 13403. The maximum length of each section of duct will be 4 metres. REINFORCEMENTS Where necessary, the ducts will be fitted with special reinforcement bars in order to provide further mechanical strength during operation. Said reinforcements will be calculated using the manufacturer s charts. The maximum deflection of the sides of the duct must not exceed 3% or in any case 30 mm, as laid down in standard UNI EN 13403. TURNING VANES & SPLITTERS All rectangular elbows must be fitted with special turning vanes; the large circular elbows will be fitted with splitters in order to meet the requirements of standard UNI EN 1505. SUPPORTS Ducts will be supported by special brackets at intervals which should not exceed 4 metres if the widest side of the duct is less than 1 metre, and at intervals which should not exceed 2 metres if the widest side of the duct is more than 1 metre. Accessories, such as: volume dampers, fire dampers, diffusers, in-duct heating coils etc. will be supported independently so that the ducts do not have to support their weight. INSPECTION Ducts will be fitted with special control points for airflow sensors and doors for inspection and cleaning set at intervals along the ducts as laid down by standard EN 12097 and by the Guidelines published in the Italian Official Gazette dated 3/11/2006 relating to ventilation system maintenance. Doors may be made using the same type of sandwich panel used to produce the ducting, in conjunction with the relevant profiles. Doors will be fitted with seals in order to provide the required airtight seal. Alternatively, P3ductal inspection hatches may be used.
careplus easy cleaning high hygiene duct[al] system applications with antimicrobial self-cleaning nanostructured coating to be used in environments which require high levels of hygiene AHU CONNECTION Connections between air handling units and ducting will be performed by means of special antivibration joints in order to isolate them from vibrations. Ducts will be supported independently in order to prevent that the weight of the ducts be transferred to the flexible fittings. Moreover, connection with the air handling unit will allow the unit to be uncoupled for system maintenance purposes. Should the antivibration joints be fitted outdoor, they will have to be waterproof. Ducts installed outdoor will have to be manufactured using sandwich panels like the PIRAL HD HYDROTEC PANEL WITH SELF- CLEANING AND ANTIMICROBIAL TREATMENT with the following properties: Panel thickness: 30.5 mm; External aluminium: 0.2 mm thick, embossed and protected with polyester lacquer; Internal aluminium: 0.2 mm thick, smooth and with self-cleaning and antimicrobial treatment; Self-cleaning treatment: nanostructured coating based on liquid glass; Efficacy of the self cleaning effect: verified thanks to large scale testing in collaboration with a University Department; Efficacy of antimicrobial active principle: verified in conformity with standard ISO 22196 by an Italian Ministry of Health accredited laboratory. Initial thermal conductivity: 0.022 W/(m C) at 10 C; Insulating material density: 46-50 kg/m 3 ; Insulating material: polyurethane which has been expanded with the use of only water and not with CFC, HCFC, HFC or HC gasses; Insulation expanding agent: ODP (ozone depletion potential) = 0 and GWP (global warming potential) = 0; % closed cells: > 95% according to ISO 4590; Rigidity class: R 900,000 according to UNI EN 13403; Fire reaction class: 0-1 according to Italian ministerial decree (D.M.) 26/06/84; Fire reaction class: B according to European Standard EN 13501-1; Ducts will be protected once installed with a waterproofing Gum Skin resin. Bitumen-based compounds must not be used. It is advisable to apply strengthening gauze around flanging points. Ducts will be built to P3ductal standards and in conformity with standard UNI EN 13403. The ducts will have to be manufactured using accessories with antimicrobial treatment. FLANGING The individual lengths of ducting will be joined together by means of special invisible flanges with hidden bayonet connections, providing a suitable airtight and mechanical seal to meet the requirements of standard UNI EN 13403. The maximum length of each section of duct will be 4 metres. REINFORCEMENTS Where necessary, the ducts will be fitted with special reinforcement bars in order to provide further mechanical strength during operation. Said reinforcements will be calculated using the manufacturer s charts. The maximum deflection of the sides of the duct must not exceed 3% or in any case 30 mm, as laid down in standard UNI EN 13403. SUPPORTS The ducts will have to be supported every 2 meters, lifted from the ground with appropriate fasteners and will have to have a suitable slope in the horizontal portions in order to drain any water. SNOW/WIND LOADS Ducts must be also sized in order to bare the snow/wind loads as stated in the manufacturer s tables. CONSTRUCTION SOLUTIONS Should the ducts pass through the roof, they should be fitted at the end with gooseneck shaped bends in order to prevent water and/or snow from getting in. All external duct openings, like the exhaust outlets, external air intakes etc. will be fitted with special bird grids.
applications in aggressive environments The pre-insulated aluminium HVAC ducts will be produced using environmentally compatible sandwich panels like the PIRAL HD HYDROTEC PANEL COUPLED W/POLYESTER FILM with the following properties: Panel thickness: 20.5 mm; External aluminium: 0.08mm thick, embossed and coupled with corrosion resistant polyester film 13 μm; Internal aluminium: 0.08mm thick, embossed and coupled with corrosion resistant polyester film 13 μm; Initial thermal conductivity: 0.022 W/(m C) at 10 C; Insulating material density: 50-54 kg/m 3 ; Insulating material: polyurethane which has been expanded with the use of only water and not with CFC, HCFC, HFC or HC gasses; Insulation expanding agent: ODP (ozone depletion potential) = 0 and GWP (global warming potential) = 0; % closed cells: > 95% according to ISO 4590; Rigidity class: R 200,000 according to UNI EN 13403; Fire reaction class: 0-1 according to Italian ministerial decree (D.M.) 26/06/84; Fire reaction class: B according to European Standard EN 13501-1; Fire reaction class: approved according to the ISO 9705 standard (Room corner test); Smoke toxicity and opacity: class F1 according to NF F 16-101; Smoke toxicity: FED and FEC < 0.3 according to pren 50399-2-1/1; Smoke toxicity: below 6.7 according to the British Naval Engineering Standard NES 713; Ducts will be built to P3ductal standards and in conformity with the UNI EN 13403 standard. REINFORCEMNETS Where necessary, the ducts will be fitted with special reinforcement bars in order to provide further mechanical strength during operation. Said reinforcements will be calculated using the manufacturer s charts. The maximum deflection of the sides of the duct must not exceed 3% or in any case 30 mm, as laid down in standard UNI EN 13403. FLANGING The individual lengths of ducting will be joined together by means of special invisible flanges with hidden bayonet connections, providing a suitable airtight and mechanical seal to meet the requirements of standard UNI EN 13403. The maximum length of each section of duct will be 4 metres. TURNING VANES & SPLITTERS All rectangular elbows must be fitted with special turning vanes; the large circular elbows will be fitted with splitters in order to meet the requirements of standard UNI EN 1505. SUPPORTS Ducts will be supported by special brackets at intervals which should not exceed 4 metres if the widest side of the duct is less than 1 metre, and at intervals which should not exceed 2 metres if the widest side of the duct is more than 1 metre. Accessories, such as: volume dampers, fire dampers, diffusers, in-duct heating coils etc. will be supported independently so that the ducts do not have to support their weight. INSPECTION Ducts will be fitted with special control points for airflow sensors and doors for inspection and cleaning set at intervals along the ducts as laid down by standard EN 12097 and by the Guidelines published in the Italian Official Gazette dated 3/11/2006 relating to ventilation system maintenance. Doors may be made using the same type of sandwich panel used to produce the ducting, in conjunction with the relevant profiles. Doors will be fitted with seals in order to provide the required airtight seal. Alternatively, P3ductal inspection hatches may be used. AHU CONNECTION Connections between air handling units and ducting will be performed by means of special antivibration joints in order to isolate them from vibrations. Ducts will be supported independently in order to pevent that the weight of the ducts be transferred to the flexible fittings. Moreover, connection with the air handling unit will allow the unit to be uncoupled for system maintenance purposes. Should the antivibration joints be fitted outdoor, they will have to be waterproof.
applications with low pressure systems The pre-insulated aluminium HVAC ducts, with a quadrangular cross section, will be produced using environmentally compatible sandwich panels of the P3ductal smart4 solution with the following properties: Panel thickness: 12 mm; External aluminium: 0.08mm thick, embossed and protected with a light blue colour (RAL 5024) polyester lacquer; Internal aluminium: 0.08mm thick, embossed and protected with polyester lacquer; Initial thermal conductivity: 0.022 W/(m C) at 10 C; Insulating material density: 58-62 kg/m 3 ; Insulating material: polyurethane which has been expanded with the use of only water and not with CFC, HCFC, HFC or HC gasses; Insulation expanding agent: ODP (ozone depletion potential) = 0 and GWP (global warming potential) = 0; Fire reaction class: 0-1 according to Italian ministerial decree (D.M.) 26/06/84; Fire reaction class: B according to European Standard EN 13501-1; The ducts will have to be manufactured according to P3ductal standards and in conformity with the UNI EN 13403 standard. The various pieces of duct will have to be assembled using the labyrinth bayonet and joined together using the appropriate frames. The ducts will maintain an air seal and mechanical strength according to the prescriptions of the UNI EN 13403 standard. The maximum length of each single piece of duct will be of 1.2 metres. The ducts will have to be fixed using appropriate supports which may be placed up to a maximum distance, between them, of 4 metres. The accessories like the fire dampers, diffusers, etc. will have to be held up autonomously in order for them not to weigh on the ducts.
applications with low pressure systems and high aesthetical requirements The pre-insulated aluminium HVAC ducts, with an octagonal cross section, will be produced using environmentally compatible sandwich panels of the P3ductal smart8 solution with the following properties: Panel thickness: 12 mm; External aluminium: 0.08mm thick, embossed and protected with a light blue colour (RAL 5024) polyester lacquer; Internal aluminium: 0.08mm thick, embossed and protected with polyester lacquer; Initial thermal conductivity: 0.022 W/(m C) at 10 C; Insulating material density: 58-62 kg/m 3 ; Insulating material: polyurethane which has been expanded with the use of only water and not with CFC, HCFC, HFC or HC gasses; Insulation expanding agent: ODP (ozone depletion potential) = 0 and GWP (global warming potential) = 0; Fire reaction class: 0-1 according to Italian ministerial decree (D.M.) 26/06/84; Fire reaction class: B according to European Standard EN 13501-1; The ducts will have to be manufactured according to P3ductal standards and in conformity with the UNI EN 13403 standard. The various pieces of duct will have to be assembled using the labyrinth bayonet and joined together using the appropriate frames. The ducts will maintain an air seal and mechanical strength according to the prescriptions of the UNI EN 13403 standard. The maximum length of each single piece of duct will be of 1.2 metres. The ducts will have to be fixed using appropriate supports which may be placed up to a maximum distance, between them, of 4 metres. The accessories like the fire dampers, diffusers, etc. will have to be held up autonomously in order for them not to weigh on the ducts.
07/2012-1000C - Cod. CS05802G - Copyright P3 srl. All rights reserved. No reproductions of any kind are allowed without the authorization of P3. P3 srl Via Don G. Cortese, 3 35010 Villafranca Padovana Loc. Ronchi (Padova - Italy) Tel. + 39 049 90 70 301 - Fax + 39 049 90 70 302 p3italy@p3italy.it - www.p3italy.it