FIRE SAFETY INSPECTION REPORT

Similar documents
FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT REDPOINT JACKETS LTD, DHAKA, BANGLADESH

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

FIRE SAFETY INSPECTION REPORT

Letter of Recognition

INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE ASSESSMENT REPORT (FAR)

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

INITIAL FIRE SAFETY ASSESSMENT

City of South Salt Lake Fire Code Training Exiting, Egress Systems and Egress Control

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT

ELECTRICAL SAFETY INSPECTION REPORT

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT

2012 B.C. Building Code Compliance Review (Division B Part 3)

TIME KNITWEAR (PVT) LTD.

INITIAL FIRE SAFETY ASSESSMENT

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

Life Safety - Means of Egress/Exits NFPA 101

PROJECT: CIVIC ADDRESS:... PERMIT APPLICATION NO.: DATE:... CRP:. Certified Professional:.

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

ELECTRICAL SAFETY INSPECTION REPORT

Agency for Health Care Administration

CHAPTER 7 ALTERATIONS LEVEL

INITIAL FIRE SAFETY ASSESSMENT

ELECTRICAL SAFETY INSPECTION REPORT

MWL Consulting Company

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

BC Building Code Checklist Part 3 Planning and Development Department

INITIAL FIRE SAFETY ASSESSMENT - EXPANSION

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

ELECTRICAL SAFETY INSPECTION REPORT

Fire and Smoke Door Inspections Qualified Training 02/03/17

EQUIVALENT INITIAL FIRE SAFETY ASSESSMENT

GENERAL AREAS OF INSPECTION

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

January 1, 2014 Mandatory Effective Date

INITIAL FIRE SAFETY ASSESSMENT

Large Family Daycare Guideline

DEPARTMENT OF HEALTH AND HUMAN SERVICES K 011 K 011 NFPA 101 LIFE SAFETY CODE STANDARD

BOABC Level III Exams 7, 8, 9 and 10 Beginning April 1, 2015

9/20/2016 2:53 PM. Second Revision No NFPA [ Section No ] Supplemental Information. Submitter Information Verification

Residential Care Facilities Requirements

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU STANDARD

Agency for Health Care Administration

ELECTRICAL SAFETY INSPECTION REPORT

Agency for Health Care Administration

First Revision No NFPA [ Global Input ] Submitter Information Verification. Committee Statement

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

2009 International Fire Code Errata. SECOND PRINTING (Posted April 6, 2010)

NFPA 101 and NFPA 99, 2012 Editions Code Update. where art meets engineering

Denver Fire Department Fire Prevention Division

Common Fire Code Violation Checklist. Listed are some of the most commonly found fire code violations and should not be considered as all inclusive.

Building & Fire Code Academy. Building Better With Our Greatest Resource Education. Welcome!

Presented by: Bill Lauzon, PE Lauzon Life Safety Consulting, LLC Web: Lauzon-LSC.com

NFPA 101, 2012 EDITION IMPACT ON NEW AND EXISTING HEALTH CARE FACILITIES

Element C3.5 Means of Escape

12/14/2013. Fire alarm and emergency power SPRINKLER HEAD

Transcription:

FIRE SAFETY INSPECTION REPORT COMFORT APPAREL, ( PVT ) LTD. 96, DARUS SALAM, MIRPUR, DHAKA OTHER FACTORIES: SALMA FASHION WEARS LTD, COMFORT KNIT FASHION LTD March 27, 2014

Page 2 SUMMARY was surveyed for fire safety on 3/27/2014 by Hughes Associates, Inc. This summary identifies the major deficiencies that were identified during the inspection. The purpose of this survey was to identify significant fire safety issues and to provide recommendations for remediation based on applicable standards specified by the Accord. The scope of this initial fire safety inspection was limited to the review and identification of major fire safety issues. The inspection did not include identification of minor deficiencies, which will be further addressed as part of follow-up inspections. Table 1 summarizes the major fire safety issues identified during the inspection. Recommendations have been provided to address each issue. An implementation schedule shall be developed by the factory to remediate each of the findings. The specific timing of improvements, including any requested extensions due to design / installation constraints, shall be submitted to the Accord for approval.

Page 3 Table 1. Findings And Recommendations No. Category Finding Recommendation Remediation Timeframe F-1 Fire Rated Construction Unsealed penetrations and openings are located in south exit stair enclosures. Seal all penetrations and openings in exit stair enclosure walls to maintain the fire separation. Immediate

Page 4 F-2 Fire Rated Construction Un protected elevator opening in south stairwell. Provide minimum 1.5-hr fire rated seal all unprotected openings to separate the exit stairs from work areas and other building spaces on all floor levels. Within 1 month F-3 Fire Rated Construction The boiler room in 1st floor and generator room ground floor are not separated by firerated construction (openings, non-rated doors). Separate the boiler and generator room by a minimum 2-hr fire-rated construction. Seal and/or protected all openings to maintain the required fire separations. Within 3

Page 5

Page 6 F-4 Fire Rated Construction Areas used for combustible storage are not separated by firerated construction. Locations: 1st, 2nd, 5th and ground floor. Provide dedicated storage rooms separated by minimum 1-hr fire-rated construction. Where separate storage rooms are not feasible, provide defined storage areas and limit the storage arrangement as follows: - Maximum height of 2.4m and maximum area of 23m2 - If sprinkler protected: maximum height of 3.66m and maximum area of 93m2 Within 3 Separate areas of unenclosed combustible storage by a minimum clear distance of 3m.

Page 7 F-5 Fire Rated Construction The exit stairs are not separated from work areas and other spaces on each floor by firerated construction. Provide minimum 1.5-hr fire rated doors and seal all unprotected openings to separate the exit stairs from work areas and other building spaces on all floor levels. Ensure that the fire doors are self-closing and positive latching and that they are provided with fire exit (panic) hardware where serving production floors. Within 3 If fire doors are required to be held open for functional reasons, provide automaticclosing devices tied to the fire alarm system.

Page 8 F-6 Fire Rated Construction Combustible building materials was constructed in 1st floor. (Store room, Maintenance room.) Provided non combustible construction materials inside the factory area. Within 3

Page 9 F-7 Egress Egress doors and gates with locking features are provided at building exits, exit stairs and exit discharge. All gates and doors were open and unlocked during the inspection. Remove locking features from all egress doors / gates. If locks are required for security reasons, utilize special door locking features complying with NFPA 101. Immediate

Page 10 F-8 Egress Several storage was located in south exit stairwell. Remove all storage from exit stairs and egress paths Immediate

Page 11 F-9 Egress Storage was located in the egress path in 1st floor. Keep egress paths and stairs clear of storage. Immediate F-10 Egress Collapsible gates and sliding doors are provided at building exits, exit stairs and exit discharge. Replace all gates and sliding doors along the means of egress with side-hinged, swinging egress doors. If locks are required for security reasons, utilize special door locking features complying with NFPA 101. Within 1 month

Page 12 F-11 Egress Both exit stairs discharge inside the building garage and it is open to storage and generator room. Modify stair to discharge directly outside. or Provide 2-hr fire-rated exit passageway leading direclty outside (vestibules to separate any storage areas). or Within 3 Provide sprinkler protection for discharge floor in accordance with NFPA 13.

Page 13 F-12 Fire Protection The fire alarm system is antiquated, not a listed system, and does not provide alarm and notification features consistent with acceptable standards. Replace the fire alarm system with a new, listed addressable fire alarm system in accordance with NFPA 72. Design within 4, install within 9

Page 14 F-13 Fire Protection Activation of the fire alarm system by a manual fire alarm station provides automatic occupant notification only on the floor of alarm and not throughout the building. Configure the fire alarm system to initiate automatic occupant notification on all floor levels to facilitate wholebuilding evacuation upon any manual fire alarm station activation. Within 1

Page 15 F-14 Fire Protection Inspection, testing, and maintenance records for the fire alarm system were not available. Inspect, test and maintain the fire alarm system, and keep written records on-site, in accordance with NFPA 72. Within 3 F-15 Fire Protection The building is equipped with single-station smoke alarms. Smoke alarm activation sounds only a local alarm and does not provide automatic fire alarm notification of occupants. Replace the single-station smoke alarms with automatic smoke detectors tied into the fire alarm system. Configure the fire alarm system to initiate occupant notification upon activation of any two smoke detectors in addition to the manual fire alarm stations. Within 6 F-16 Egress Lighting Manual on-off switch is provided for emergency lighting and exit signage units. Remove manual on/off switches from emergency lighting and exit signage units to prevent them from being switched off. Within 1 month

Page 16 F-17 Egress Lighting Several emergency lighting did not function in test mode (burned out) Reguarly test the emergency lighting system on each floor and replace/repair lights as needed. Within 3