Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

Similar documents
Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

Acoustical Surfaces, Inc.

Report of Surface Burning Characteristics Test on Acoustical Panel

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

We Identify and S.T.O.P. Your Noise Problems

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

SIGMADEK, LTD. FIRE TEST REPORT

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

ASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet

CAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

Public Comment No. 2-NFPA [ Section No ]

FUNDERMAX GMBH FIRE TEST REPORT

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

CAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

CAN/ULC-S102.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate"

CAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum

Report on Public Input June 2014 NFPA 101

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

Materials Testing by Gregory Havel

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

First Revision No. 6-NFPA [ Section No. 2.2 ]

Safety Code Users. Fire Tests for Life SUPPLEMENT 3. Marcelo M. Hirschler FIRE PROPERTIES

UL 94 Flammability Ratings: Introduction

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

Public Comment No. 1-NFPA [ Section No ]

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015

TEST REPORT. Contact No: SAMPLE NOT DRAWN BY OUR LABORATORY. THE RESULTS RELATE ONLY TO THE ITEMS TESTED

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

J-PRO TM Cable Support System

Contents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions...

Heat and Smoke Release of a Ceiling-Installed Speaker

(a) Flame shall not spread to the outer extremities of the sample on the 8 ft 12 ft (2440 mm 3660 mm) wall. Flashover shall not occur.

CERTIFICATION BULLETIN

ISO/TS TECHNICAL SPECIFICATION. Fire detection and alarm systems Part 9: Test fires for fire detectors

File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33

Classification of Fire Performance of Wall and Ceiling Lining Materials

ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198"

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

Standard for tests for flammability of plastic materials for parts in devices and appliances

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

First Revision No. 2-NFPA 90B-2012 [ Section No. 1.3 ] Submitter Information Verification. Committee Statement and Meeting Notes

File E Project 97SC January 21, 1998 REPORT

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

Criteri di Preselezione in Accordo ad UL 94 e Conformità del Prodotto Finito. Matteo Paleari Senior Project Engineer

BCTC CARPET TECHNICAL CENTRE

Report on First Revision June 2014 NFPA 101

Chilled Water DOAS Fan Powered Terminal Units

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda*

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Hugh Hoagland Consulting, Inc. ArcWear.com. Electric Arc Exposure Tests. for Stern & Stern

"Spray area" is the term that is used throughout the document. This change is for consistency.

C-01 FIRE DECKS AND BULKHEADS

F, T, L and W Ratings - What are the Code & Testing Requirements?

BS 476: Part 6: 1989+A1:2009

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

SOUTHWEST RESEARCH INSTITUTE

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

FIF AAA (F2014) Second Draft Meeting Web/Teleconference Meeting Agenda March 18, :00 5:00 p.m. ET

Test Report: ICL/CR15/11/087

Smoke Layer Height and Heat Flow through a Door

Transcription:

May 18, 2015 Mr. Simone Furiato Ebrille SRL S S Canelli 53/A Nizza Monferrato, AT 14049 Our Reference: Subject: SV29774/4786853196 Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL Dear Mr. Furiato: This is a Report summarizing the results of a test conducted under the Commercial Inspection and Testing Services (CITS) program of UL LLC (UL) identified as Assignment No. 4786853196. GENERAL: The results relate only to items tested. METHOD: Each test was conducted in accordance with Standard ANSI/UL723, Tenth Edition, dated September 10, 2008 with revisions through August 12, 2013, "Test for Surface Burning Characteristics of Building Materials", (ASTM E84). The test determines the Surface Burning Characteristics of the material, specifically the flame spread and smoke developed indices when exposed to fire.

The maximum distance the flame travels along the length of the sample from the end of the igniting flame is determined by observation. The Flame Spread Index of the material is derived by plotting the progression of the flame front on a time-distance basis, ignoring any flame front recession, and using the equations described below: A. CFS = 0.515 A T when A T is less than or equal to 97.5 minute-foot. B. CFS = 4900/(195-A T ) when A T is greater than 97.5 minute-foot. Where A T = total area under the time distance curve expressed in minute-foot. The Smoke Developed Index (SDI) is determined by rounding the Calculated Smoke Developed (CSD) as described in UL 723. The CSD is determined by the output of photoelectric equipment operating across the furnace flue pipe. A curve is developed by plotting the values of light absorption (decrease in cell output) against time. The CSD is derived by expressing the net area under the curve for the material tested as a percentage of the area under the curve for untreated red oak. The CSD is expressed as: CSD = (A m /A ro ) x 100 Where: CSD = Calculated Smoke Developed A m = The area under the curve for the test material. A ro = The area under the curve for untreated red oak. SAMPLES: The samples utilized in this investigation were neither prepared nor selected by a Laboratories' representative such that no verification of composition can be provided. Test No. 2 Sample Description System EBRILSPLIT LINESETS/TWINSPLIT LINESETS: white closed cell polyethylene foam based insulator with PE white film Due to the rigidity of the test samples, supplementary means of support was not required. RESULTS: The results are tabulated below are considered applicable only to the specific samples tested.

Data sheets and graphical plots of flame travel versus time and smoke developed versus time are also enclosed. Table 1: Flame Spread Summary Test No. Test Code Sample Description 2 05141509 CFS Calculated Flame Spread (Ceiling) FSI Flame Spread Index (Ceiling)+ CFS Calculated Flame Spread (Floor) FSI Flame Spread Index (Floor)++ EBRILSPLIT LINESETS/TWINSPLIT LINESETS: white closed cell polyethylene foam based insulator with PE white film 0.00 0 1.52 0 + - Flame Spread Index while material remained in the original test position. indicated. ++ - Ignition of molted residue on the furnace floor resulted in flame travel equivalent to calculated Flame Spread Index Table 2: Smoke Developed Summary Test No. Test Code Sample Description 2 05141509 CSD Calculated Smoke Developed (Prior to Floor Ignition) SDI Smoke Developed Index (Prior to Floor Ignition) CSD Calculated Smoke Developed (Entire Test Duration) SDI Smoke Developed Index (Entire Test Duration) EBRILSPLIT LINESETS/TWINSPLIT LINESETS: white closed cell polyethylene foam based insulator with PE white film 0.1 0 50.8 50 The Classification Marking of UL on the product is the only method provided by UL to identify products which have been produced under its Classification and Follow-Up Service. No use of a Classification Marking has been authorized as a result of this investigation. Since the anticipated work has been completed, we have instructed our Accounting Department to terminate the investigation and invoice you for the charges incurred to date. Should you have any questions, please contact the undersigned. Very truly yours Reviewed by: James Smith Staff Engineering Associate Building Materials & Systems Randall Laymon Sr. Staff Engineer Building Materials & Systems

Project: 4786853196 File: SV29774 TestCode: 05141509 Tested by: LUCAS NOLLIN Engineer: JAMES SMITH Date: 2015-05-14 TEST METHOD: The test was conducted in accordance with UL 723, Tenth Edition. Client Name: Ebrille SRL Test Duration 10 minutes Test No.: 2 Hot Test: No Mounting: Self Test Type: CITS Burn-Out Required: Yes Test Sample: EBRILSPLIT LINESETS/TWINSPLIT LINESETS: white closed cell polyethylene foam based insulator with PE white film FLAME SPREAD RESULTS Ceiling Flame Spread Data Distance (Feet) Ignition 18 Floor Flame Spread Data Distance (Feet) Ignition 36 0.5 396 1 480 Time (Sec) Time (Sec) Calculated Flame Spread (CFS): 0.00 Flame Spread Index (FSI): 0 Time to Ignition (sec): 18 Maximum Flame Spread (ft): 0.0 Area Under the Flame Spread Curve (ft.-min): 0.0 Time to Floor Ignition (sec): 36 Maximum Floor Flame Spread (ft): 1.0 Calculated Floor Flame Spread: 1.52 SMOKE RESULTS Calculated Smoke Developed (CSD): 50.8 Smoke Developed Index (SDI): 50 Area Under the Smoke Curve (Obs-min.): 43.72 Area Under Red Oak Curve (Obs-min.): 86.02 Area Under the Smoke Curve Before Floor Ignition (Obs-min.): 0.06 Smoke Developed Prior to Floor Ignition: 0.1 Post-Test Observations Discoloration (Feet From Burner): 24 Melt (Feet From Burner): 24 Char (Feet From Burner): 5 ULS-00723-BIKT-DataSheet-2001 Form Issued: 2004-01-28 Form Page 5 Form Revised: 2007-15-10 Form Copyright 2012 UL LLC Only those products bearing the UL mark should be considered as being covered by UL

Flame Spread / Smoke Results Ebrille SRL EBRILSPLIT LINESETS/TWINSPLIT LINESETS: white closed cell polyethylene foam based insulator with PE white film 100 90 80 70 % Obscuration Flame Spread Floor Flame Spread 20 18 16 14 Obscuration (%) 60 50 40 30 20 10 12 10 8 6 4 2 Flame Spread (feet) 0 0 1 2 3 4 5 6 7 8 9 10 Time (Minutes) 0 Test Num.: 2 Flame Spread Index: 0 SV29774 / 4786853196 Smoke Developed Index: 50 05141509 Max. Flame Spread (ft.): 0.0