Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Similar documents
Acoustical Surfaces, Inc.

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.

Report of Surface Burning Characteristics Test on Acoustical Panel

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

July 22, Stewart Audio Inc. Brian Mccormick Po Box 4058 Mountain View, CA File SV17764 / Project 09CA34798

Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

We Identify and S.T.O.P. Your Noise Problems

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

SIGMADEK, LTD. FIRE TEST REPORT

CAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

ASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

Public Comment No. 2-NFPA [ Section No ]

CAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"

CAN/ULC-S102.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate"

CAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

FUNDERMAX GMBH FIRE TEST REPORT

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

Report on Public Input June 2014 NFPA 101

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

REPORT NUMBER: MID-003r1 ORIGINAL ISSUE DATE: March 11, 2015 Revised Date: March 20, 2015

Public Comment No. 1-NFPA [ Section No ]

Contents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions...

TEST REPORT. Contact No: SAMPLE NOT DRAWN BY OUR LABORATORY. THE RESULTS RELATE ONLY TO THE ITEMS TESTED

Second Revision No. 1-NFPA 90A-2016 [ Section No ] Submitter Information Verification. Committee Statement

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

1/8/ :02 AM. Public Input No. 2-NFPA [ Section No ] Statement of Problem and Substantiation for Public Input

SOUTHWEST RESEARCH INSTITUTE

Materials Testing by Gregory Havel

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

File E Project 97SC January 21, 1998 REPORT

Safety Code Users. Fire Tests for Life SUPPLEMENT 3. Marcelo M. Hirschler FIRE PROPERTIES

File E Project 05ME Issued: November 1, 2005 Revised: February 27, 2009 REPORT

6/9/ :58 PM. First Revision No. 1-NFPA [ Section No ] Submitter Information Verification. Committee Statement

First Revision No. 6-NFPA [ Section No. 2.2 ]

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

J-PRO TM Cable Support System

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

Research-Scale Fire Performance Evaluation of a Wood Floor Joist/Tin Ceiling Panel Assembly

ASTM E 662 Rate of Smoke Generation of "Moniflex as manufactured by Isoflex AB"

F, T, L and W Ratings - What are the Code & Testing Requirements?

CANADIAN FIRE ALARM ASSOCIATION An Update on Standards, Technologies and Solutions. Smoke Characterization Study

Standards Update Notice (SUN) Issued: February 2, 2017

File Ex643 Project 95NK34821 Project 96NK19119 Project 97NK2995 Project 98NK20794 Project 99NK21353 *Project 03NK33

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

UL 94 Flammability Ratings: Introduction

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

SECTION (13900) - FIRE SUPPRESSION SYSTEMS

ISO/TS TECHNICAL SPECIFICATION. Fire detection and alarm systems Part 9: Test fires for fire detectors

ASTM E 662 Rate of Smoke Generation of OXIFREE TM198"

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

NF X : Parts 1, 2, 3, 4 & 5

PERFORMANCE TEST REPORT. Rendered to: Metal Building Manufacturers Association Cleveland, Ohio

SECTION ELEVATOR FIRE RATED SMOKE CONTAINMENT SYSTEM

File Ex643 Project 03NK31930 Project 04NK24425 Project 05NK25712 Project 06NK15719 Project 06NK06003 Project 06NK24531

BCTC CARPET TECHNICAL CENTRE

FIRE AND LIFE SAFETY REQUIREMENTS FOR SPECIAL EVENTS STANDARD

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa

Intertek. REPORT NUMBER: SAT-005 ORIGINAL ISSUE DATE: October 29,2008 REVISED DATE: November 19, 2008

STANDARDS UPDATE NOTICE (SUN) ISSUED: August 23, 2017

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

Classification of Fire Performance of Wall and Ceiling Lining Materials

Heat and Smoke Release of a Ceiling-Installed Speaker

Hugh Hoagland Consulting, Inc. ArcWear.com. Electric Arc Exposure Tests. for Stern & Stern

ASTM E 84 Surface Burning Characteristics of "12 mm Stratificato Panel"

BS EN : 2001 & IEC :2000

First Revision No. 6-NFPA 90A-2012 [ Chapter NFPA ] Submitter Information Verification. Committee Statement and Meeting Notes

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

ASTM E662 TESTING FOR COLE MOTORSPORTS/CM RACING PRODUCTS ON WINDSHIELD TEAROFFS ON ¼ GLASS VTEC # TESTED: MARCH 27, 2009

NFPA Technical Meeting (Tech Session) June 24-25, 2015 Agenda*

GUARDIAN FIRE TESTING LABORATORIES, INC.

Test Report: ICL/CR15/11/087

Transcription:

November 10, 2014 Mr. Carlos Khantzis Textures 3D 31280 Oak Crest Dr. #4 Westlake Village, CA 91361 Our Reference: Subject: SV19490/4786557998 Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D Dear Mr. Khantzis: This is a Report summarizing the results of a test conducted under the Commercial Inspection and Testing Services (CITS) program of UL LLC (UL) identified as Assignment No. 4786557998. GENERAL: The results relate only to items tested. METHOD: Each test was conducted in accordance with Standard ANSI/UL723, Tenth Edition, dated September 10, 2008 with revisions through August 12, 2013, "Test for Surface Burning Characteristics of Building Materials", (ASTM E84). The test determines the Surface Burning Characteristics of the material, specifically the flame spread and smoke developed indices when exposed to fire.

The maximum distance the flame travels along the length of the sample from the end of the igniting flame is determined by observation. The Flame Spread Index of the material is derived by plotting the progression of the flame front on a time-distance basis, ignoring any flame front recession, and using the equations described below: A. CFS = 0.515 A T when A T is less than or equal to 97.5 minute-foot. B. CFS = 4900/(195-A T ) when A T is greater than 97.5 minute-foot. Where A T = total area under the time distance curve expressed in minute-foot. The Smoke Developed Index (SDI) is determined by rounding the Calculated Smoke Developed (CSD) as described in UL 723. The CSD is determined by the output of photoelectric equipment operating across the furnace flue pipe. A curve is developed by plotting the values of light absorption (decrease in cell output) against time. The CSD is derived by expressing the net area under the curve for the material tested as a percentage of the area under the curve for untreated red oak. The CSD is expressed as: CSD = (A m /A ro ) x 100 Where: CSD = Calculated Smoke Developed A m = The area under the curve for the test material. A ro = The area under the curve for untreated red oak. SAMPLES: The samples utilized in this investigation were neither prepared nor selected by a Laboratories' representative such that no verification of composition can be provided. Sample Description Test No. System 1 Textures 3D faux leather tiles Each test sample was supported by 2 in. hexagonal poultry netting supported by 1/4 in. diameter steel rods spaced 2 ft. apart. RESULTS: The results are tabulated below are considered applicable only to the specific samples tested. Data sheets and graphical plots of flame travel versus time and smoke developed versus time are also enclosed.

Table 1: Test Summary Test No. Test Code Sample Description CFS Calculated Flame Spread FSI Flame Spread Index CSD Calculated Smoke Developed SDI Smoke Developed Index 1 10301412 Textures 3D faux leather tiles 19.02 20 324.4 300 The Classification Marking of UL on the product is the only method provided by UL to identify products which have been produced under its Classification and Follow-Up Service. No use of a Classification Marking has been authorized as a result of this investigation. Since the anticipated work has been completed, we have instructed our Accounting Department to terminate the investigation and invoice you for the charges incurred to date. Should you have any questions, please contact the undersigned. Very truly yours Reviewed by: James Smith (ext. 42666) Randall Laymon (ext. 42687) Staff Engineering Associate Sr. Staff Engineer Building Materials & Systems Building Materials & Systems

Project: 4786557998 File: SV19490 TestCode: 10301412 Tested by: TIMOTHY WAGNER Engineer: JAMES SMITH Date: 2014-10-30 TEST METHOD: The test was conducted in accordance with UL 723, Tenth Edition. Client Name: Textures 3D Test Duration 10 minutes Test No.: 1 Hot Test: No Mounting: Rods & Wire Test Type: CITS Burn-Out Required: No Test Sample: Textures 3D faux leather tiles FLAME SPREAD RESULTS Flame Spread Data Distance (Feet) Time (Sec) Distance (Feet) Time (Sec) Ignition 22 2.5 48 0.5 32 3 60 1 34 3.5 72 1.5 36 4 76 2 38 Calculated Flame Spread (CFS): 19.02 Flame Spread Index (FSI): 20 Time to Ignition (sec): 22 Maximum Flame Spread (ft): 4.0 Area Under the Flame Spread Curve (ft.-min): 36.9 SMOKE RESULTS Calculated Smoke Developed (CSD): 324.4 Smoke Developed Index (SDI): 300 Area Under the Smoke Curve (Obs-min.): 260.32 Area Under Red Oak Curve (Obs-min.): 80.25 Post-Test Observations Discoloration (Feet From Burner): 24 Char (Feet From Burner): 15 ULS-00723-BIKT-DataSheet-2001 Form Issued: 2004-01-28 Form Page 4 Form Revised: 2007-15-10 Form Copyright 2012 UL LLC Only those products bearing the UL mark should be considered as being covered by UL

Flame Spread / Smoke Results Textures 3D Textures 3D faux leather tiles 100 90 80 70 % Obscuration Flame Spread 20 18 16 14 Obscuration (%) 60 50 40 30 20 10 12 10 8 6 4 2 Flame Spread (feet) 0 0 1 2 3 4 5 6 7 8 9 10 Time (Minutes) 0 Test Num.: 1 Flame Spread Index: 20 SV19490 / 4786557998 Smoke Developed Index: 300 10301412 Max. Flame Spread (ft.): 4.0