Gas Safety Products. Installation, operating and maintenance 11/18/2015. Merlin 1000S+ Gas Utility & Electrical Isolation Controller

Similar documents
Gas Safety Products. Installation, operating and maintenance. Merlin 1000S+i Gas & Electric Utility Controller. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. American Gas Safety LLC 1 05/10/2016

Gas Safety Products. Installation, operating and maintenance. Merlin 1500S Gas Interlock System. Rev: 03 Date:

Gas Safety Products. Installation, operating and maintenance 23/08/2016. Merlin 1000BH Gas Proving/Gas Detection System

Gas Safety Products. Installation, operating and maintenance. Merlin 1000BH Gas Proving/Gas Detection System

Gas Safety Products. Installation, operating and maintenance. Merlin 1000VW+ Gas Interlock, Gas Proving, Electric & Water Isolation System

Product Data Sheet. Merlin GDP2. Gas Safety Products. Merlin GDP2. Installation, operating and maintenance 23/08/2016. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance 09/05/2016. Merlin CT1650+ Gas Interlock System. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance 28/10/2015. Merlin CT1250 Gas Interlock System. S&S Northern Ltd 1

Gas Safety Products. Installation, operating and maintenance 11/26/2015. Merlin Gas Detectors. Merlin Gas Detectors. American Gas Safety LLC 1

Gas Safety Products. Installation, operating and maintenance 10/12/2017. Merlin Gas Detectors. Merlin Gas Detectors. American Gas Safety LLC 1

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 2800PPM. Merlin CO2 Monitor 2800ppm. American Gas Safety LLC 1

Gas Safety Products. Installation, operating and maintenance. Merlin Gas Detectors. Read these instructions carefully before operating or servicing.

Troubleshooting Guide

Troubleshooting Guide

Gas Safety Products. Installation, operating and maintenance. Merlin Gas Detectors. Merlin Gas Detectors. Rev: 09 Date: Product Data Sheet

Gas Safety Products. Installation, operating and maintenance. Merlin CO2 Monitor 4500PPM. Merlin CO2 Monitor. Rev: 11 Date:

Boiler Room Control THE MERLIN RANGE GAS DETECTION EQUIPMENT ENGINEERED TO DELIVER EXCEPTIONAL LEVELS OF SAFETY

UPON COMMENCMENT OF INSTALLATION IT IS OF PARAMOUNT IMPORTANCE THAT THE STEP BY STEP GUIDE (INCLUDED) IS FOLLOWED COMPLETELY

Please read this sheet as it contains important information

Installation Instructions. The SEC-L is a gas pressure proving system with water and electric isolation, gas detection and ventilation interlock.

Multi Function Control System for Boiler and Plant rooms SEC-B. The Home of Control & Automation in Ireland

VGPS-evo V3.3. Installation Instructions. The VGPS-evo is a gas pressure proving system with ventilation interlock and optional CO2 detection.

GPPS-evo V3.3. Installation Instructions

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Installation Instructions

GS100M Gas Detector. Technical Specification

OPERATION AND INSTALLATION MANUAL

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

BX444-Mc Gas Detector

Four Channel Gas Detection System AGDS 4. The Home of Control & Automation in Ireland

LEAKSTOPPER MULTIZONE WATER LEAK DETECTION ALARM PANEL INSTALLATION AND OPERATION MANUAL

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Door Release Power Supply

Gas interlock system S & 100 CS

GS100M Gas Detection Controller

intelligent solutions

CaterSense 03 & ATSC-02-xx

LC1 & 2. Fire Alarm Panel 6\VWHPLQVWDOODWLRQRSHUDWLQJ PDLQWHQDQFH LQVWUXFWLRQV

Installation, Operating and Maintenance Manual

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

Reflective Optical Beam Smoke Detector User Guide

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

USER MANUAL FOR OPERATING SYSTEM

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

TT /97. Features INSTALLATION INSTRUCTIONS. Horn. Lamps

100 Series Gas Ventilation Interlock System

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

GRUNDFOS INSTRUCTIONS LCD 108. Installation and operating instructions

Gasflag. Single Channel Control Panel Alarm Only Apparatus. Installation, operating and maintenance instructions, M07225.

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

OPERATION & INSTALLATION MANUAL FOR ALARM PANEL M2AP01

Carbon Monoxide Transmitter

Fire-Cryer. Plus Application Guide APPLICATION GUIDE FIRE EXIT VIMPEX. Shaping Alarm Technology

MERLIN RANGE GAS DETECTION EQUIPMENT

STATUS ALARM ALARM HISTORY POWER HISTORY RESET

Added password for IP setup page : Password must be in IP format!

Hydrosense. Vimpex Limited. Star Lane. Great Wakering. Essex SS3 0PJ. Tel: +44 (0) Fax +44 (0)

WD-CS. Water leak detection cable. Technical Overview. Features. Page 1. Data Sheet Ref: Issue: 5.1.

Multi Channel Gas Detection System AGDS MC. The Home of Control & Automation in Ireland

ESP TECHNOLOGIES LIMITED

FR-4000 & FR-8000 Fire Alarm Monitor Installation Manual

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Beacon 110 Gas Monitor Operator s Manual

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Saffire User & Installation Manual. IMPORTANT This manual should be left with the panel after installation.

TECHNICAL MANUAL EDITION 1.0 VANDAL RESISTANT AUDIO AND VIDEO DOOR ENTRY SYSTEMS

21-light Remote Annunciator. Owner s Manual

GasScanner 1C. Single Channel Monitor. Operator s Manual. MINT-0278-XX Rev A

ANALOX 5001 Carbon Dioxide Monitor. User Manual ANALOX Analox 5001 Carbon Dioxide Monitor User Manual

FIRE ALARM CONTROL EQUIPMENT. Addendum October 2006 Instructions for new style EN54-4 Power supply unit module

PTE0705 Electric Fence Monitor

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

GasScanner 8C. Eight Channel Monitor. Operator s Manual. MINT-0281-XX Rev. A 01/29/08

Beacon 800 Gas Monitor Operator s Manual

Installation and user manual for the BiWire / Conventional Repeater Panel

MERLIN RANGE KITCHEN EQUIPMENT CT1200S CT1250

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

EXAMPLES OF HOW TO ORDER

Power Supply / Battery Charger Units, incorporating load switching relays for Smoke Dispersal, Bell Booster or other uses

Intelligent Security & Fire Ltd

ACCU-TEST SAFETY. Assured Gas Shut Off Protection

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

EXTINGUISHING AGENT RELEASE MODULE

BX444-M Gas Detector. Features. Application. Operation

NZ 400 AUTOMATIC FIRE ALARM SYSTEM OPERATORS MANUAL

FEC400 Series. Installation Manual

EXAMPLES OF HOW TO ORDER

OPERATION & MAINTENANCE MANUAL GUARDIAN SPACE PRESSURE MONITOR WITH REMOTE AUXILLARY ALARM

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

A System That Utilizes the LD-2000 or LD-3000 Mechanical Line Leak Detector to Perform 3 10 PSI (catastrophic) Line Tests

QA16 Addressable System

ELSEMA MD2010. Application Controls automatic doors or gates when a vehicle is present. Description

Water Detection Controllers

Installation Guide. Disabled Persons Emergency Alarm Kit. Single Zone Call Control/Call answered unit c/w Sounder LED indicators and Braille lettering

KM300 Carbon Monoxide Detection System Installation Manual

Installation Instructions 4 Zone Fire Panel

Flopurge TS. Operation Manual

Some alarms can be manually cleared from the current alarms list. This is indicated for the alarms where this is possible.

Transcription:

Gas Safety Products Installation, operating and maintenance 11/18/2015 American Gas Safety LLC 1

Table of contents 1 General information... 3 2 Installation... 3 2.1 Panel Mounting.... 3 2.2 Power Supply.... 3 2.3 Gas solenoid valve.... 3 2.4 Electric Contactor.... 3 2.5 BMS Connections.... 3 2.6 Gas Pressure Transducer.... 3 2.7 Timeout Facility.... 3 2.8 Remote emergency shut off buttons.... 3 2.9 Gas Detector.... 4 2.10 FS 123... 4 2.11 CO2 Monitor.... 4 2.12 12v DC.... 4 2.13 Internal Buzzer.... 4 3 Operation Instructions... 4 3.1 How to turn the system on and off... 4 3.2 Explanation of LED status... 4 3.2.1 Power LED... 4 3.2.2 Gas on LED... 4 3.2.3 Electric on LED... 4 3.2.4 Testing LED... 5 3.2.5 Test Fail LED... 5 3.2.6 Pressure Low LED... 5 3.2.7 Timeout LED... 5 3.2.8 EM Stop LED... 5 3.2.9 Gas Detected LED... 5 3.2.10 CO2 High... 5 3.3 Using the emergency shut off... 5 3.4 BMS integration... 6 3.5 Fire alarm integration... 6 3.6 Fan switch integration... 6 3.7 Gas fill and prove time... 6 3.8 Auto reset... 6 1000S+ Wiring Diagram... 7 Reminder: Waste electrical products must not be disposed of with general waste. American Gas Safety LLC 2

1 General information The Merlin 1000S+ is a gas shut off, gas detection & electrical isolation utility controller. The system comprises of a control panel and a gas pressure sensor. The Merlin 1000S+ can receive connections from remote emergency shut-off buttons, gas detectors and a CO2 monitor. It can also be integrated with a BMS and fire alarm. It is recommended that the user reads this guide before using the system. Please do NOT attempt to operate the unit until the contents of this document have been read and are thoroughly understood. 2 Installation 2.1 Panel Mounting. The control panel is designed for surface mounting using 4 mounting screws. Removing the cover on the panel gives access to the circuit board. The PCB should be removed before drilling entry holes into the case. 2.2 Power Supply. A 100-240VAC electrical supply should be supplied to the panel. This should be externally fused at 3 Amps using a fused spur and should be connected to the terminals marked LNE Power IN 2.3 Gas solenoid valve. The gas solenoid valve should be powered using the terminals on the Merlin 1000S+ marked LNE to VALVE. 2.4 Electric Contactor. An electrical output will be supplied to an electrical contactor. This will be internally fused at 3 Amps and should be connected to the terminals marked LNE Electric Contactor. 2.5 BMS Connections. Terminal connections are available on the circuit board for connections to Building Management systems etc. Detailed on the circuit board as BMS OUT N/C, COM and N/O these are volt free connections. 2.6 Gas Pressure Transducer. The terminals marked pressure sensor + - IN.These wire to the gas pressure transducer which is screwed into the downstream port on the gas solenoid valve. Red + positive, Black negative and Yellow IN. Please ensure this is wired as instructed. Minimum Operating Pressure = 0.17psi Maximum Operating Pressure = 1.45psi 2.7 Timeout Facility. The Merlin 1000S+ has a built-in Auto-shut down feature and it will turn itself off after predefined time. Auto-shut down timeout is selectable. There are two dip-switches located on the inside facia of the Merlin 1000S+ labelled Time1 and Time2. They are factory set in the off position for a 2 hour timeout. On installation, they can be switched to the on position to select required timeout. Time1 Off, Time2 Off 2 hours Time1 On, Time2 Off 4 hours Time1 Off, Time2 On 8 hours Time1 On, Time2 On no timeout (auto-shut down disabled) On Auto-shut down gas supply will be turned off. 2.8 Remote emergency shut off buttons. The terminal for remote emergency shut-off buttons is detailed on the circuit board as EM Remote. These connections are linked out as a factory setting. Remote emergency shut-off buttons should be volt free and wired to the Merlin 1000S+ using two-core cable. American Gas Safety LLC 3

2.9 Gas Detector. The terminals detailed on the circuit board as Gas Detector. These connections are +,- and these can be wired to a Merlin Natural gas, Carbon monoxide or LPG detector. If no detector is being used leave the link in between the. Other detector types are available. 2.10 FS 123. This terminal switches when the key is turned on and off. This can be linked to a fan switch (panel supplied separately) which can provide power to the fans when the control panel is switched on. 2.11 CO2 Monitor. This terminal can be wired to CO2 monitor to shut off the system in the event of High CO2 levels. If no CO2 monitor is supplied leave the terminal link in. 2.12 12v DC. This is a permanent 12v DC output when there is power at the panel. 2.13 Internal Buzzer. Operates at 65dB measured 30cm from closed panel. Note: all low voltage connections should be made using a screened cable. To avoid electrical interference this should not be in the same conduit as mains cable as per the low voltage directive. 3 Operation Instructions 3.1 How to turn the system on and off 1. Turn the key switch to on position. 2. Gas and electric will flash for 10 seconds. 3. Press relevant service button to turn required utility on. 4. Turn the key switch to the off position to turn the panel off. Please Note: All services can be turned on or off only within 10 secs of the key switch being turned on. After 10 secs, all utility buttons will be disabled. The user must turn the key off and back on to adjust any services. 3.2 Explanation of LED status 3.2.1 Power LED When the system is connected to the mains supply, the Red LED of the AGS Logo located in the bottom right corner of the panel will illuminate. When no power is present, this LED will not light up. RED = OK OFF = No power to 1000S+, a loose ribbon connection or the fuse may not be intact. 3.2.2 Gas on LED When the key switch is turned on, the Merlin 1000S+ will check the installation for gas leaks. If gas proving is successful, the gas valve will open and the green Gas On LED will illuminate. GREEN = Gas On OFF = Gas Off 3.2.3 Electric on LED When Electric service is turned on, the Electric LED will illuminate BLUE. BLUE = Electric On FLASHING = Electric Off, Electric button enabled OFF = Electric Off, Electric button disabled American Gas Safety LLC 4

3.2.4 Testing LED This LED will illuminate GREEN for approximately 30 seconds when the panel is checking the integrity of the gas installation upon start up. GREEN = proving the gas line, do NOT operate any appliances 3.2.5 Test Fail LED Under normal working conditions this LED is off. When the panel detects a gas leak on startup, the LED will illuminate AMBER. Gas valve will remain closed. AMBER = gas proving failed 3.2.6 Pressure Low LED Under normal working conditions the LED is off. The LED will illuminate AMBER when pressure of the gas supply drops below 0.17psi for 10 seconds. The gas valve will close. AMBER = gas supply pressure low. 3.2.7 Timeout LED Under normal working conditions this LED is off. This LED will illuminate AMBER when auto-shut down has occurred. AMBER = auto-shut down 3.2.8 EM Stop LED If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate AMBER and the gas will be turned off. The EM Stop button must be re-set before restarting the system. AMBER = EM Stop button pressed 3.2.9 Gas Detected LED Under normal working conditions this LED is off. If the external Merlin detector connected detects gas this will show RED and the Gas valve will turn off. RED = Gas detected. 3.2.10 CO2 High Under normal working conditions this LED is off. If the concentration of CO2 in the air is at alarm level (relevant detector required), the LED will show RED and the Gas valve will turn off. RED = the concentration of CO2 is at alarm level. 3.3 Using the emergency shut off The Emergency shut off button is located on the front of the panel. There is also a facility for remote shut off buttons to be wired in series. The Emergency shut off button(s) will cut off the gas supply when activated. To reinstate the system, the Emergency shut off button(s) will need to be reset and the panel restarted. American Gas Safety LLC 5

3.4 BMS integration The Merlin 1000S+ can be integrated with a BMS to make or break a circuit on gas on/gas off, (valve open or valve closed). This will tell the BMS whether or not power is being sent to the solenoid. There is a dip-switch located on the inside facia of the Merlin 1000S+ labelled BMS Selection. This is factory set in the off position which signals the BMS on gas on/gas off. When switched to the on position, the 1000S+ will only signal the BMS on a fault, i.e. CO2 high level detected, gas detected, EM Stop pressed, etc. 3.5 Fire alarm integration The Merlin 1000S+ can be integrated with a fire alarm to close the gas supply automatically in the event of a fire. The volt free fire alarm signal can be wired in series with any remote emergency shut off buttons. If there is no remote emergency stop buttons installed wire this directly to the terminal marked EM REMOTE. 3.6 Fan switch integration There is the facility to connect a Fan Switch (FS1 or FS2 sold separately). The Fan Switch provides the facility to turn on the fan(s) when the key switch on the Merlin 1000S+ is in the on position and turn the power off to the fan(s) when the key switch on the Merlin 1000S+ is in the off position. There is a dip-switch located inside the facia of the Merlin 1000S+ labelled EM Selection. This is factory set in the off position which instructs the system to shut down the fan(s) and gas supply on activation of the Emergency shut off button(s). On installation, this can be switched to the on position if required. This will instruct the system to leave the fans on and only shut off the gas supply on activation of the Emergency shut off button(s). Note: This option is not available if Fan Switch is not installed. 3.7 Gas fill and prove time Gas fill and prove times are adjustable. There are two dip-switches located on the inside facia of the Merlin 1000S+ labelled Fill Time and Prove Time. They are factory set in the off position. Fill and prove time can be changed by turning the relevant dip switch to on position. Fill time: Off 5 secs, On 10 secs Prove time: Off 30 secs, On 50 secs Once the settings has been changed please remove power from the fuse spur for 10 seconds. 3.8 Auto reset The Merlin 1000S+ has a built-in auto reset feature. There is a dip-switch located on the inside facia of the Merlin 1000S+ labelled Auto Reset. This is factory set in the off position. When the power is restored after the power cut, the panel has to be restarted manually. On installation, this can be switched to the on position if required. This will instruct the system to restart automatically when power is restored after the power cut. American Gas Safety LLC 6

1000S+ Wiring Diagram 1 2 3 4 5 6 7 8 9 10 11 12 13 L N E Pressure Transducer Gas Detector CO2 Monitor Gas Valve L N E EM Stop 1. Mains Input 100-240VAC Single Phase. 2. Gas Solenoid Valve Power Output, 100-240VAC, Max 3A. 3. Electric Contactor Power Output, 100-240VAC, Max 3A. 4. Water Valve, this is disabled on this system. 5. Supply Fan PD Switches terminal, this is disabled on this system. 6. Extract Fan PD Switches terminal, this is disabled on this system. 7. BMS output contacts. Normally Closed, Common and Normally Open. Max.3A @ 100-240VAC. 8. Gas pressure transducer, power supply and returned signal (supplied). 9. Remote EM Stop buttons and Fire Alarm input wired in series (purchased separately). VOLT FREE INPUT 10. Methane, CO or LPG Detector, power supply and volt free input (purchased separately). 11. Fan Switch output (purchased separately). For wiring instruction see Fan Switch user manual. 12. CO2 Monitor (purchased separately). VOLT FREE INPUT 13. Permanent 12VDC output when there is power at the panel. 50mA max Please note, Mains wires and low voltage wires should not be run in the same conduit as per the LOW VOLTAGE DIRECTIVE American Gas Safety LLC 7

CONTACT US: AGS Head Office Tel: (727) 608-4375 Fax: (727) 538-4237 info@americangassafety.com Rev Date Author Description 03 11.18.15 American Gas Safety CD + BT + CM Merlin 1000S+ Third issue American Gas Safety is the owner of this document and reserves all rights of modification without prior notice. American Gas Safety LLC 8