Human response to thermal environment in rooms with chilled beams

Similar documents
Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams

To describe human body heat transfer, the concept. Thermal comfort with radiant and convective cooling systems. Articles. REHVA Journal June

The impact of thermal loads on indoor air flow

COMPARISON OF THE THERMAL ENVIRONMENT IN ROOMS WITH CHILLED BEAM AND RADIANT PANEL SYSTEMS

Thermal Comfort with Convective and Radiant Cooling Systems

Use of local convective and radiant cooling at warm environment: effect on thermal comfort and perceived air quality

American Society of Heating, Refrigerating and Air-Conditioning Engineers

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

Comparison of radiant and convective cooling of office room: effect of workstation layout

MODELLING AND SIMULATION OF A ROOM WITH A RADIANT COOLING CEILING. Technicka 4, Prague 6, Czech Republic

Experimental study of space cooling using ceiling panels equipped with capillary mats

Performance of Chilled Beam with Radial Swirl Jet and Diffuse Ceiling Air Supply in Heating Mode

Thermal Environment Evaluation in Commercial Kitchens of United States

Center for the Built Environment October 2013

State of the Art of HVAC Technology in Europe and America

IMPLEMENTATION OF DISPLACEMENT VENTILATION SYSTEM BY USING A WALL-MOUNTED AIR CONDITIONER

Thermal Environment in a Space with Capillary Mats Large-Area Cooling and Heating

Comfort and health-indoor air quality

Improvement of Temperatures Stratification caused by Air-conditioner. by means of Ceiling Fan in Classroom

Aalborg Universitet. Diffuse Ceiling Inlet Systems and the Room Air Distribution Nielsen, Peter Vilhelm; Jensen, Rasmus Lund; Rong, Li

VENTILATIVE COOLING CONTROL STRATEGIES APPLIED TO PASSIVE HOUSE IN ORDER TO AVOID INDOOR OVERHEATING

The Performance of Diffuse Ceiling Inlet and other Room Air Distribution Systems Nielsen, Peter Vilhelm; Jakubowska, Ewa

A CEILING CONDENSING UNIT WITH PELTIER ELEMENTS FOR DRYING AND COOLING

AN ANALYSIS OF THE ACTUAL THERMAL PLUMES OF KITCHEN APPLIANCES DURING COOKING MODE

IEA EBC Annex 59 - Possibilities, limitations and capacities of indoor terminal units

Displacement Ventilation

Healthy Buildings 2017 Europe July 2 5, 2017, Lublin, Poland. Evaluation of task air conditioning system with convection, conduction, and radiation

INFLUENCE OF SOLAR RADIATION AND VENTILATION CONDITIONS ON HEAT BALANCE AND THERMAL COMFORT CONDITIONS IN LIVING-ROOMS

Air and operative temperature measurements in a plus-energy house under different heating strategies

Air Distribution and Ventilation Effectiveness in a room with Floor/Ceiling Heating and Mixing/Displacement Ventilation

ANALYSIS OF RESIDENTIAL ROOM TEMPERATURE AND OCCUPANT S THERMAL COMPLAINT IN WINTER FIELD SURVEY

Ventilation Strategies for Healthy IEQ and Energy Efficiency

Analysis on combinations of indoor thermal microclimate parameters in radiant cooled residential buildings and drawing of new thermal comfort charts

Halton Vario Design Guide

Unit 4: Science and Materials in Construction and the Built Environment. Thermal Comfort

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

EXPERIMENTAL INVESTIGATION OF THE AIR CLEANING EFFECT OF A DESICCANT DEHUMIDIFIER ON PERCEIVED AIR QUALITY

Life cycle cost comparison of TABS vs. other HVAC (UK) TECHNICAL BROCHURE

This is an electronic reprint of the original article. This reprint may differ from the original in pagination and typographic detail.

EFFECT OF SATURATION EFFICIENCY OF DIRECT EVAPORATIVE COOLER ON INDOOR CONDITIONS AND THERMAL COMFORT IN A SMALL OFFICE ROOM OF A BUILDING

Don t Turn Active Beams Into Expensive Diffusers

Typologies of Hybrid Ventilation in Schools

EFFECTS OF EXTREMELY LOW HUMIDITY ON COMFORT AND FATIGUE OF JAPANESE OCCUPANTS

Sprinklers Modeling for Tunnel Road Fire Fighting

COMPARISON OF THE USE TRICKLE VENTILATORS IN EUROPEAN RESIDENTIAL VENTILATION STANDARDS

For Global Application. Active and Passive Beam Application Design Guide. Front Cover. Joint publication of REHVA and ASHRAE

Cooling load calculations of radiant and all-air systems for commercial buildings

AR/IA 241 LN 231 Lecture 6: Passive Cooling

buildingscience.com Windows and Occupant Comfort EEBA Building Solutions 2003 Lincolnshire, IL

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

ω = (1) Kirby S. Chapman Ph.D.

Investigation of Thermal Environments in Humid Tropical Classroom in Indonesia

Everything you need to know about Radiant Heating but didn t dare ask

This document is a preview generated by EVS

Thermal Comfort Performance Field Investigation of a Residential Forced- - Air Heating and Cooling System with High Sidewall Supply Air Outlets

The cooling capacity of the Thermo Active Building System combined with acoustic ceiling

Literature review: Side Effects of Low Exergy Emission Systems March 2000

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

COOLING ENERGY SAVING SYSTEM USING A WATER MIST DEVICE ON WINDOWS

As mentioned earlier, the fundamental purpose of HVAC systems is to provide human comfort.

Hot-air heating of family houses with accumulation of energy in the floor

DESIGN OF AIR-CONDITIONING SYSTEM FOR SARS WARDS. By Yuguo Li and SARS Busters * Background

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress volume 9 Heiselberg, Per Kvols. Publication date: 2016

Engineering Guide VAV Diffusers. Please refer to the Price Engineer s HVAC Handbook for more information on VAV Diffusers.

DR AS 5389:2016 Space heating and cooling and ventilation systems Calculation of energy consumption. The physical testing

NOVEMBER 2012 THE EUROPEAN EXPERIENCE

System technology. System technology. List of contents

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

,Chaojian He6, f. School of Guangxi University, Nanning , China.

The new ASHRAE-REHVA Active and Passive Beam Application Design Guide

Human preference and acceptance of increased air velocity to offset warm sensation at increased room temperatures

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

A study of radiant cooling for a room with daytime application in tropical climate

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

GUIDANCE AND TOOLS FOR CHILLED CEILINGS COMBINED WITH A WET COOLING TOWER

Investigation of a Novel Ceiling Panel for Heat and Moisture Control in Buildings

Residential ventilation concepts based on the idea of displacement airflow distribution

The thermal performance of green roofs in a hot, humid microclimate

AIRFLOW PATTERN AND PERFORMANCE ANALYSIS OF DIFFUSE CEILING VENTILATION IN AN OFFICE ROOM USING CFD STUDY

EXPERIMENTAL AND CFD STUDIES ON SURFACE CONDENSATION

Use each of the terms in the box to explain how heat is lost from inside a house through the window. conduction convection radiation

Experimental study of fan coil assisting radiant floor heating system

nzeb office building

How to ensure Thermal Comfort in buildings with CFD

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Monetization of Thermal Comfort in Residential Buildings

Improving Single-Sided Room Ventilation by Using a Ceiling Fan

TRNSYS modeling of a novel ceiling panel designed to maintain space humidity in an office building

STATE UNIVERSITY OF NEW YORK COLLEGE OF TECHNOLOGY CANTON, NEW YORK

Field Study of Diffuse Ceiling Ventilation Performance in a Landscape Office

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

DYNAMIC THERMAL MODELING OF A RADIANT PANELS SYSTEM AND ITS ENVIRONMENT FOR COMMISSIONING: APPLICATION TO CASE STUDY

EMBEDDED PIPE SYSTEMS. SURFACE HEATING AND COOLING Heat transfer coefficient COOLING CAPACITY. Max. heating-cooling-capacity

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

BALANCING ENERGY EFFICIENCY & INDOOR THERMAL COMFORT

Technical Report Three

Transcription:

Human response to thermal environment in rooms with chilled beams Arsen Melikov 1, Boryana Yordanova 1, Lyuben Bozkhov 1, Viktor Zboril 1,2, Risto Kosonen 3 1 International Center for Indoor Environment and Energy, Department of mechanical Engineering, Technical University of Denmark 2 Department of Environmental Engineering, Faculty of Mechanical Engineering, CTU in Prague, Prague 166 47 - Czech Republic 3 Halton Oy Corresponding email: melikov@mek.dtu.dk SUMMARY The importance of heat load and airflow pattern control for occupants thermal comfort is studied in a full-scale test room ventilated with chilled beams. The room was furnished with two desks, computers and table lights. Solar irradiation on window and part of the floor was simulated as well. The room temperature was maintained at 24ºC. Thirty subjects (15 female and 15 male subjects) participated in the experiments. The increase of the heat load from 30 /m 2 to 70/m 2 increased substantially non-uniformity of the thermal environment in the room. The percent of subjects dissatisfied due to their thermal comfort conditions and due to draught increased with the increase of the heat load. The provided induction control of the chilled beams changed the air flow distribution in the occupied zone and decreased the reported draught discomfort. The induction control is efficient way for improving occupants thermal comfort but it should be used carefully in practice. INTRODUCTION The air-conditioning of office buildings is maintained mainly with systems based on the mixing ventilation principle. During the recent years the use of active chilled beams for ventilation of buildings has increased due to their ability for removing higher heat loads in more energy efficient way than other systems for office ventilation [1]. Furthermore chilled beams, allow for control of the induced amount of room air and thus for change of airflow pattern in rooms when uncomfortably high velocity is reported by occupants. Air distribution in rooms with active chilled beams is result of complex interaction of ventilation flow from the beams with the convection flow generated by heat sources, occupants, warm/cold window surfaces, office equipment. The airflow distribution depends on several factors, including arrangement of chilled beams, supplied airflow rate and momentum flux, lay out of workplaces, strength and location of heat sources, etc. Only limited studies on the air distribution in rooms with chilled beams is reported in the literature [2, 3, 4]. The impact of the airflow interaction in rooms with active chilled beams on occupants comfort is needed. The efficiency of the airflow pattern control for achieving comfortable thermal conditions for occupants is not documented. This paper presents results on human response to thermal environment generated by active chilled beams. The impact of heat load and airflow pattern control on thermal comfort is

studied with human subjects under realistically simulated laboratory conditions. Only part of the collected and analyzed results are presented and discussed in this paper. EXPERIMENTAL DESIGN Experimental facilities A full-scale test room (L x x H = 5.4m x 4.2m x 2.5m) was used to simulate a real office room. The room was furnished with two desks each with a real computer to simulate the heat loads from office equipment. Artificial windows with surface temperature control were used to simulate the impact of the outdoor environment during summer season. Several heating panels were placed on the floor and used in some of the experiments to generate heat and simulate solar irradiation (it is difficult to simulate properly the solar radiation). The work place near the window is referred as P2 and this on the opposite side as P1 (Figure 1). Three chilled beams were mounted crosswise installation as shown in Figure 1. Previous physical measurements identified this lay out as most critical in regard to occupants thermal comfort [3]. The amount of room air inducted into the beams was regulated by shutters placed in the beams. hen the shutter is closed (right side of the chilled beam shown in Figure 1) maximum cross section area for the flow is ensured and thus maximum amount of room air is induced through the beam). This setting is referred in this paper as Induction 1 (I1). hen the shutter is open (left side of the chilled beam in Figure 1) the cross section area decreases and thus the air supplied to the room decreases (the amount of induced room air also decreases). This setting is referred as Induction 2 (I2). The surface temperature of the artificial windows, the air temperature, etc. were measured and controlled. Experimental conditions Three experiments referred in Table 1 as Case 1, Case 2 and Case 3 were performed. In cases 1 and 2 the heat load was kept constant but the induction of room air was changed, Induction 1 (I1) and induction 2 (I2). The low induction (Case 2) was activated for the side of the chilled beams facing P1. The cooling capacity of the chilled beams was maintained the same by lowering of the temperature of the inlet water for the heat exchanger. In Cases 1 and 3 the induction was kept constant (I1) but the heat load was changed. Table 1. Experimental conditions. Case number Induction control Temperature in the room, ºC Case 1 Case2 Case 3 High induction (induction 1) Low induction (induction 2) High induction (induction 1) Heat loads, /m² Surface temperature of windows, ºC 24.0± 0.2 70 40.4 24.1 ± 0.1 70 41.5 24.0 ± 0.2 30 36.1

Figure 1. Experimental set-up in the room and sketch of cross section of the chilled beam with right shutter closed and the left shutter open is shown as example. During the experiments the flow rate of the primary air was 1.5l/s/m². The experiments represented summer conditions and the room temperature was maintained to be 24ºC. The distribution of the heat loads in the test room for each case is listed in Table 2. The window surface temperature of 40.4 ºC is high but possible in practice. Table 2. Distribution of the heat loads Case number Heat gain from windows, Heat gain from PCs, Heat gain from people, Heat gains from floor panels, Heat gain from lightning, Case1 2x325 2x80 2x75 520 116 Case2 2x325 2x80 2x75 520 116 Case3 2x220-2x75-116 Subjects Thirty subjects, 15 males and 15 females, participated in the experiment. They were at age from 20 to 45 years (average 24.3 ± 5 years). Experimental procedure Each subject participated in three experiments (Cases 1, 2 and 3 in Table 1). At their arrival, before entering the experimental office, the subjects relax for 20 minutes from previous activities. During that time they were explained the experimental procedure and how to fill in

the questionnaires. They were not informed about the experimental conditions, e.g. the temperature in the room, the ventilation system, the flow rate, etc. After 20 minutes the subjects entered the test room two at a time and sat at the workplaces. They were asked to fill in the questionnaires every 5 minutes staring from the fifth minute. The subjects were allowed to write or read while seated on the desk. The subjects stayed in the office 25 minutes then they went out for 10 minutes break. After the break they returned to the office and stayed there for another 25 min. This time they changed the workplaces. They completed questionnaires as during the first 25 min. During the whole experiment the subjects were encouraged to adjust their clothing according to their preferences. At the end of the experiment for the day they filled in a questionnaire about their clothing. This procedure was identical for the three experiments the subjects participated. Questionnaires The subjective response to the thermal environment was collected by means of questionnaires. They were presented to the subjects on a paper. The questions related to whole body and local thermal sensation - 7-point ASHRAE scale [6], acceptability of the thermal environment (ranging from clearly unacceptable to just unacceptable and then from just acceptable to clearly acceptable, air movement sensation, body part where the movement was felt, whether it was acceptable or not, and the last question was on preference for more, less or unchanged air movement. Data analyses The data obtained from the questionnaires was analyzed statistically using the program Statistica 5. Each of the samples was tested for normality of the distribution using the Shapiro-ilk test. Tests for significant differences of the samples were performed with ilcokson match pair test. RESULTS AND DISCUSSION The individual whole-body thermal sensation votes as reported by the subjects were used to define the average thermal sensation vote. Figure 2 compares the obtained results for each of the three experiments. The average thermal sensation of the occupants in all of the cases was within the comfortable range of ±0.5 (from slightly cool to slightly warm) recommended in the present standards [6, 7]. Only at P2 in Case 2-70/m²- I2 the thermal sensation was above slightly warm, 0.7. In this case the thermal sensation of the occupants was influenced by the thermal radiation from the warm windows which were located 0.9 m from P2. The thermal sensation was just below neutral only at P1 in the experiment with 30/m² (Case 3). The results were statistically checked for significance. Significant differences were found in the average thermal sensation between P1 and P2 in Case 2-70/m²- I2 (p=0.006), at P2 between Case 1-70/m²-I1 and Case 2-70/m²-I2 (p=0.0262) and at P2 between Case1-70/m²-I1 and Case3-30/m² (p=0.039). The subjects felt warmer the whole body with the conditions at P2 in Case 2-70/m²- I2. The local thermal sensation for the different body parts as reported by the subjects was analyzed. The local thermal discomfort due to warmth was defined for the body parts with

local thermal sensation slightly warm, warm or hot which was felt as uncomfortable. Figure 3 shows the results of these analyses. Figure 2. Average thermal sensation of the subjects at workplace 1 (P1) and workplace 2 (P2). Percent dissatisfied due to warmer body parts, % 50 45 40 35 30 25 20 15 10 5 0 P1 P2 70/m2-I1 70/m2-I2 30/m2 Figure 3. Percent dissatisfied due to warmer body parts The highest percent of subjects who felt local warm discomfort for one or more body parts was for Case 2-70/m²- I2. The conditions at P2 in Case 2-70/m²- I2 were identified as the worst; almost half of the assessment panel (43%) felt discomfort at that workplace located close to the heated window. The local warmth discomfort decreased when the heat load in the room decreased (Case 3-30/m²). During the experiments the subjects were asked to assess whether they felt air movement at any of the specified body parts and if so, if the air movement was comfortable or not. The subjects responses were defined as draught discomfort if: 1) the person felt particular body part cooler than neutral and 2) if the person felt the local cooling uncomfortable; and 3) if the

person felt air movement and voted that the feeling is uncomfortable and 4) the subject requested for less air movement. Figure 4 represents percentage dissatisfied due to draught at any body part. Percent dissatisfied due to draught, % 25 P1 P2 20 15 10 5 0 70/m2-I1 70/m2-I2 30/m2 Figure 4. Percent dissatisfied due to draught based on all four criteria The highest percent of subjects who felt draught was reported in Case 1-70/m²- I1 at P1. hen the induction control was used, Case 2-70/m²-I2, the percent dissatisfied due to draught subjects at P1 was lowered substantially; in this case only one person reported on draught. The results show that with the lowering of the strength of the heat sources (Case 3-30/m²) the total percent of draught complaints decreased. DISCUSSION Acceptable thermal environment for the whole body was achieved under all the tested conditions. The average thermal sensation of the subjects achieved with the chilled beams at the two workplaces was between neutral and slightly warm. As expected due to the radiant temperature asymmetry generated by the warm window the subjects felt warmer at the P2 than at P1. The flow interaction as discussed in the following left the subjects at P2 with less air movement for cooling their body. However this did not affect subjects general thermal sensation. The general thermal sensation, the local thermal sensation and the draught discomfort reported by the subjects was result of the interaction of the thermal flows generated by heat sources and the ventilation flow supplied from the chilled beams. The convection flows from the window, the solar irradiation simulated on the floor, the person and the PC concentrated on one side of the window (P2) in Case 1 (70/m²- I1) were powerful enough to deflect the ventilation flow toward the opposite side of the room as shown schematically on Figure 5. This resulted in large number of draught complains at P1 (Figure 4). The use the induction control of the chilled beams on the side of the P1 (Case 2-70/m²-I2), decreased the velocity which resulted in decreased draught complaints at P1 as well as at P2. The local thermal discomfort decreased as well (Figure 3). Thus the efficient use of the induction control for decrease of draught discomfort in rooms with chilled beams was validated.

The activated induction control decreased the draught complaints but the number of subjects reporting warmth discomfort at P2 increased from 10 to 13, i.e. near the window. Due to the airflow interaction less cooling air reached the subjects at P2 and this resulted in warmer thermal sensation. Thus the warmth discomfort should be carefully considered together with draught discomfort in practice in rooms with chilled beams when induction control is provided. Figure 5. Air distribution in Case 1 (70/m²- I2) The importance of the airflow interaction was demonstrated in the experiments with different heat load as well. Non-uniformity of the thermal environment decreased when the heat load was decreased from 70/m² (Case 1) to 30/m² (Case 3) and this affected occupants thermal comfort. Draught discomfort decreased (Figure 4), the whole body thermal sensation improved (Figure 2) and the reports on uncomfortable local warmth discomfort decreased (Figure 3). The results reported in this paper were supported by results from comprehensive physical measurements on air distribution and thermal environment in rooms with chilled beams [3, 4]. They confirm the importance of careful consideration of flow interaction in rooms in general. In future buildings occupants and solar irradiation will remain the major heat sources. The increase of the outdoor temperature due to global warming and the use of glass facades will affect the airflow interaction in spaces resulting in increased non-uniformity of the thermal environment. At the same time the recognized impact of the indoor environment on occupants performance [9] will lead to requirements for higher quality of indoor environment in the future standards than the requirements specified in the present indoor climate standards. Therefore the need for of individually controlled environment in buildings which will be able to compensate for the non-uniformity of the indoor environment and for the large individual differences existing between people in regard to the preferred environment will increase. CONCLUSIONS For the conditions provided by the chilled beams the average thermal sensation of the subjects was within the requirements of the existing standards and guidelines (ISO 7730, CEN 1752, REHVA Guidebook).

The flow interaction in the room under the studied conditions had major impact of occupants draught sensation. Higher draught discomfort was discovered for the conditions with higher heat load in the room. The induction control proved to be efficient way for diminishing draught discomfort. ACKNOLEDGEMENT This research was supported by the Danish Technical Research Council (STVF) and the Finnish Technology Agency (TEKES). REFERENCES 1. REHVA. 2006. Guidebook No. 5. Chilled Beam Cooling. Federation of European Heating and Air Conditioning Assiciations. 2. Kosonen, R., Virta, M., Melikov, A. 2007. The impact of thermal loads on indoor air flow. Proceedings of CLIMA 2007, Helsinki. 3. Zbořil, V., Melikov, A., Yordanova, B., Bozkhov, L., Kosonen, R. 2007. Airflow distribution in rooms with active chilled beams. Proceedings of Roomvent 2007, Helsinki. 4. Kosonen, R., Melikov, A., Bozkhov, L., Yordanova, B. 2007. Impact of heat load distribution and strength on airflow pattern in rooms with exposed chilled beams. Proceedings of Roomvent 2007. Helsinki, Finland. 5. ASHRAE HANDBOOK - Fundamentals. 2005. American Society of Heating, Refrigerating and Air Conditioning Engineers. Atlanta. 6. ISO 7730, Moderate thermal environments- Determination of the PMV and PPD indices and specification of the conditions for thermal comfort, 1994. 7. ASHRAE Standard 55-2004: Thermal Environmental Conditions for Human Occupancy, American Society of Heating, Refrigerating and Air Conditioning Engineers, Atlanta, GA. 8. Seppänen, O. and Fisk,.J., 2005, A model to estimate the cost-effectiveness of improving office work through indoor environmental control, ASHRAE Transactions, Part 2.