IRIS IP65 IRIS UNISCAN APPLICATION MANUAL

Similar documents
COMPACT FLAME CONTROLLER CFC 200 (Formerly 8.XX)

COMPACT FLAME CONTROLLER CFC 1000

LFE50. UV Flame Safeguard. Building Technologies Division DETACTOGYR

FIREYE C9707A ALL FUEL SCANNER

CARVER CASCADE 2 & CASCADE 2 GE CARAVAN WATER HEATER INSTALLATION INSTRUCTIONS LEAVE THESE INSTRUCTIONS WITH THE USER

UV Flame Supervision System

LFE50. UV Flame Safeguard. Siemens Building Technologies HVAC Products DETACTOGYR. Series 02

EURO-OIL SERIES TYPES G.. G../. OR.. OR../. F.. FR..

UV Scanner. Model Specification. Introduction. 854 Instruction Manual

Flame Monitor for Multiple Burner Furnaces D-LE 603 D-UG 660

COMPACT FLAME CONTROLLER CFC 100

UV - flame detector dual fuel burners for intermittent burner operations

COMPACT FLAME CONTROLLER CFC 2000

SLATE. UV Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001S1071

UV - flame detector KLC 10 for oil -, gas- and dual fuel burners for intermittent burner operations

EUROFLAT SERIES TYPES C... S... M...

Eclipse 90 UV Scanner Model A Version 1

DATASHEET. Burner control unit FDA 601x

SLATE. Rectification Ampli-Check Flame Amplifier INSTALLATION INSTRUCTIONS R8001V1031

SLATE. Base Module INSTALLATION INSTRUCTIONS R8001A1001

Infrared Flame Detectors

Flame detector. The QRA4.U is for use with the following types of burner control:

Infrared Flame Detectors

Operating Instructions. For. Alarm Control Module. Model SSR 500

Safety. Operating instructions UV sensor UVS 10 DANGER WARNING. Contents CAUTION Edition Please read and keep in a safe place

ABB. Measure IT Uvisor System Dual sensor flame scanner. UR460 Mod. UVIR /ER/EF/DV Flame Scanner Product Data Sheet (rev B)

C Note! LGI16... Burner Controls. Building Technologies

Chemical Processes in the Combustion

SLATE. Sub-Base Module INSTALLATION INSTRUCTIONS R8001S9001

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

Products Catalog. Flame Monitoring & Evaluation Systems

QRA4.U. Flame Detector. Siemens Building Technologies HVAC Products

EUROBOX SERIES TYPES CM... SM... MM...

FIRERAY 2000 EExd Hazardous Area Smoke Detector Installation Guide

MBCE-110/230UV Flame Sensor Module

LC2200 Level Controller Installation and Maintenance Instructions

QRA2... QRA10... QRA53... QRA55... Flame Detectors. Siemens Building Technologies HVAC Products

User's Instructions. Alpha CB50

Eclipse Self-Check UV Scanner

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

QRC1... Blue-flame Detectors. Siemens Building Technologies HVAC Products

Fireray Application and. Installation Guide FEATURES. Range metres. 12V to 24V dc operation. Selectable alarm thresholds

With a power output ranging from 13kW to 24kW, they provide the flexible answer for the majority of traditional installation scenarios.

FLAME AMPLIFIER MODULE 3001D

1500 SERIES SMALL CAPACITY ULTRA 2 LOW NO X TM BURNER

Model DRD-AS Conventional Infrared Flame Detector User Manual Ver. 1.0

INSTRUCTION & SERVICE MANUAL

QRA10... QRA53... QRA55...

Flame detector FD 2011 / FD 2012

Flame detector. The QRA4.U is for use with the following types of burner control:

Format System 25 HE. User instructions. Please read the Important Notice within this guide regarding your boiler warranty

ATMOSPHERIC GAS BOILER INSTALLATION, OPERATING AND MAINTENANCE MANUAL

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

Distributed By: M&M Control Service, INC

INSTRUCTION & SERVICE MANUAL

Bert Uneken, Field Engineering Manager Ruben Kranenburg, Technical Support

INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY

GS100-ATEX. Hazardous Areas Infra-Red Beam PULSE MODULATED ACTIVE INFRA-RED BEAM FOR HAZARDOUS AREAS ZONE 1 OR ZONE 2 GENERAL

User's Instructions. Alpha CD24C/32C. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

SLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001

Indirect gas-fired air heater

MBCE-110/230FR Flame Sensor Module

System s30. User Guide FAN POWERED HIGH EFFICIENCY MODULATING DOMESTIC CONDENSING GAS SYSTEM BOILER

TITLE SLIDE. FIRERAY2000 EExd OPTICAL BEAM SMOKE DETECTOR. Doc. No: Copyright Fire Fighting Enterprises Ltd.

Fireye FLAME SCANNERS

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

RIELLO 40 GS/M SERIES

C7007A, C7008A, C7009A Flame Rod Holder & Flame Rod Assemblies

IR4000. Point Infrared Combustible Gas Detection System. The Reliable and Flexible Safety Solution That s Low Maintenance

Wide Band Flame Detector KLC 20 for all kind of oil flames with intermittent burnerr operations

ABB. Measure IT Uvisor System Flame scanner for gas and oil burners. UR450 Mod UV flame scanner Product Data Sheet (Rev. B)

C Installation and Operation Manual

S55XB and S55XBE Series Viewing Heads

Water Leak Detector - Four Zone with open/short-circuit detection. Product overview

IMAX XTRA EL. 715kW FLOOR STANDING CONDENSING FEATURES AND BENEFITS

PAC1500Xi PORTABLE APPLIANCE CHECKER

USER GUIDE LOGIC HEAT H

AUR300C. Advanced Ultraviolet Burner Controller

User's Instructions. Alpha CD25X/28X. Range of Wall Mounted, Fan Assisted, Room Sealed, Gas Fired, High Efficiency Condensing Combination Boilers

INSTRUCTION MANUAL (ATEX / IECEx)

U2 Combination Viewing Head and Signal Processors

Flame Safeguards LFE10. Building Technologies HVAC Products

W-FLAME IR/UV FLAME DETECTOR

SIME FORMAT WALL HUNG BOILERS MODEL 34i AND MODEL 34e. cod A

FLAME AMPLIFIER MODULE 3001

We offer ceramic radiant heaters and infra-red radiant tubes.

HART XL High Sensitivity Smoke Detection

R7824, R7847, R7848, R7849, R7851, R7852, R7861, R7886 Amplifiers for 7800 SERIES and R7140 Relay Modules

PRODUCT: SEL-SV-MCQ-O5- K6 VERSION TECHNICAL SHEET 1/5 SAC

Distributed By: M&M Control Service, INC

INSTRUCTION & SERVICE MANUAL D1xS1 & D1xS2 ALARM HORNS For Use In Hazardous Locations - Gas

ABB. Measure IT Uvisor System Flame scanner for fuel oil and coal flame. UR600 IR Mod flame scanner Product Data Sheet (rev.

PLEASE LEAVE THIS INSTRUCTION WITH THE USER. Ecomfort 30 HE. User instructions

RL/1 SERIES. One Stage Light Oil Burners FIRING RATES LIGHT OIL RL 34/1 MZ kw

INDUSTRIAL FLAME SCANNERS

DSF-2010-SB KEEP THIS MANUAL IN A SAFE PLACE FOR FUTURE REFERENCE!

Advanced Monitoring and Characterisation of Combustion Flames

S55XB and S55XBE Series Viewing Heads

ELECTROPROJECT GTV-A POWER SUPPLY FOR DOOR MAGNETS

QRA10... QRA53... QRA55...

Transcription:

IRIS IP65 IRIS UNISCAN APPLICATION MANUAL 01/08/05

DESCRIPTION TABLE OF CONTENTS PAGE IRIS - UNISCAN... 1 SPECIFICATION... 1 SUPPLY VOLTAGE: -... 1 OUTPUTS: -... 1 TRANSMISSION: -... 1 CABLE: -... 1 FLAME DROP OUT TIME: -... 1 DISCRIMINATION CUT-OFF FREQUENCIES: -... 1 ACCESSORIES: -... 1 DESCRIPTI0N.... 1 IRIS UNISCAN - INSTALLATION & COMMISSIONING INSTRUCTIONS... 1 INSTALLATION... 1 WIRING... 1 IMPORTANT... 1 SETTINGS... 1 SETTING UP PROCEDURE.... 2 SIGHTING (SEE FIG. 4)... 2 LIST OF FIGURES FIGURE 1 IRIS UNISCAN POWER SUPPLY MODULE DIN RAIL MOUNTED 2 FIGURE 2 IRIS UNISCAN PCB BOARD AND DETECTOR HEAD ASSEMBLY 3 FIGURE 3 IRIS UNISCAN WIRING CONNECTION-SYSTEM ASSEMBLY 4 FIGURE 4 IRIS UNISCAN UNISCAN HEAD SIGHTING 5 01/08/05

IRIS - UNISCAN The Uniscan is a fail safe - self check flame monitor and amplifier mounted in one enclosure, suitable for gas or oil, pilot or main flame monitoring. The techniques used for discrimination and fail safety are unique and are covered by UK patent No. 2131585 and US patent No. 4540886. SPECIFICATION SUPPLY VOLTAGE:- 24V DC + 10% - 25% (separate module available with 110V AC primary and 20V DC secondary - see accessories). OUTPUTS:- One normally open volt powered 20V DC contact for flame on (SPST). One 4-20mA output for flame strength indication. TRANSMISSION:- No limit providing supply cable is sized correctly. CABLE:- 4 core 1.0mm 2 Controlflex SY with outer braid. FLAME DROP OUT TIME:- Selectable to 1, 2 or 3 seconds (factory set at 2 seconds) DISCRIMINATION CUT-OFF FREQUENCIES:- Selectable POS 1 = 36 Hz POS 2 = 71 Hz POS 3 = 105 Hz POS 4 = 186 Hz (factory set at POS 1) SPECTRAL RESPONSE OF CELL:- For Oil Only 200-1080nm S1411 For Gas and Oil 750-1900nm B 1818 DIMENSIONS:- WEIGHT:- 175 x 52 x 80mm 825 grams PROTECTION CLASS:- IP 65 MAXIMUM OPERATING TEMPERATURE:- 70 C MOUNTING:- ACCESSORIES:- 1/2" BSP Din rail mounting power supply module (Fig.1). - Output - 20V DC - LED Indications of DC power on and flame on DESCRIPTI0N. The IRIS Uniscan flame monitor has been developed to satisfy the process heater and smaller utilities market, where the sophisticated discrimination techniques are not required. The Uniscan however, offers certain adjustments, for discrimination purposes and flame drop out time. The unique feature of the system is that all the electronics are situated in the viewing head - thus saving valuable panel space and expensive special cabling. As the power regulation within the system is capable of a wide operating voltage range, 18V to 27V; losses due to long cable runs to the boiler front have little effect on the performance of the system. The flame on signal is 20V DC (nominal) at a high milliampere level - and is therefore unaffected by site electrical noise and transients. The electronics are housed in a cast aluminium case giving protection to IP65 (Fig. 2). The unit should be mounted as near parallel to the axis of the burner as is practical, looking into the primary combustion zone of the flame (see Fig. 4). IRIS UNISCAN - INSTALLATION & COMMISSIONING INSTRUCTIONS INSTALLATION The sighting position should be such that the viewing head is looking into the root of the flame - as near parallel to the axis of the burner as possible (see Fig. 4). Cooling air at a minimum rate of 1 CFM (1.7m 3 /h) should be provided by tee-ing into the sight tube. WIRING There is a 5-pin Amphenol plug (Fig. 3) which must be removed to facilitate wiring. Wire should be Controlflex 4 core with outer braid. The braid is used as the 5 th core. Providing the wire is sized correctly, there is no upper limit to transmission distance. The nominal supply voltage to the head is 20V DC. This can vary between 16V and 27V without detriment to the performance. IMPORTANT The housing must be earthed according to local regulations. SETTINGS Flame drop out: - - Input 110-120/220-240V AC ±10% 1, 2 or 3 seconds factory supplied at 2 seconds 1 01/08/05

Discrimination Selector: - 1, 2, 3 or 4 positions factory supplied at 1 Flame sensitivity: - 25 turns - clockwise to increase - factory set at 12. Should be set to flame on signal strength on meter between 15-20mA. To vary these settings it is necessary to remove the cover from the housing (see Fig. 2). SETTING UP PROCEDURE. 1. With the subject flame off, turn the 25 turn potentiometer (Fig. 2) clockwise to increase the gain, but not so far that the unit indicates flame on. Place the discrimination switch in POS.1 (Fig. 2). 2. Ignite the burner and bring up to normal firing. Adjust the gain so that the meter reading is approx. 15mA. 3. Extinguish the flame and note the meter reading. If it is greater than 3mA with flame off, place the discrimination switch into POS.2. 4. Repeat paragraph's 2 & 3, placing the discrimination switch into positions 3 & 4 if necessary until the best differential between flame on and flame off is achieved. 5. On difficult applications it may be necessary to re-sight the viewing head slightly so that the flame on reading is slightly lower, but a greater differential between flame on and flame off is achieved. SIGHTING (See Fig. 4) The first 30% of the flame, the root, radiates the most intense ultraviolet and high frequency infra-red emissions. Sighting along the flame rather than across it permits the Uniscan to view a greater depth of the flame root, obtain a higher signal and help eliminate nuisance trips due to flame movement or adjacent flame activity. Fig. 1 POWER SUPPLY MODULE DIN RAIL MOUNTED 2 01/08/05

Fig. 2 PCB BOARD AND DETECTOR HEAD 3 01/08/05

Fig. 3 SYSTEM ASSEMBLY 4 01/08/05

DETECTOR IN GOOD SIGHTING POSITION (PARALLEL SIGHTING) BURNER NOZZLE CENTER LINE DETECTOR IN POOR SIGHTING POSITION DETECTOR IN POOR SIGHTING POSITION FIG 4: UNISCAN HEAD SIGHTING 5 01/08/05