Project Report 7 REFRIGERATION ENERGY USE IN THE FOOD CHAIN

Similar documents
Energy use in the chilled food sector. Case study Air blast chilling of solid/liquid food mixtures. (pie fillings)

Project Report 6 REFRIGERATION ENERGY USE IN THE FOOD CHAIN PROJECT REFERENCE (TBA) CONTRACT REFERENCE (TBA)

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

Energy consumption storage facilities examined in ICE-E

AIM: TO STUDY THE PERFORMANCE OF THE DOMESTIC REFRIGERATION RIG.

BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City)

Chapter-8 Capacity Control of Refrigeration Systems

MACH N-407 Heat Pump Air-Cooled Chiller

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Refrigeration / Air Conditioning Systems Circuit Drawings. Student Resource Package No: NR 24

The potential of ambient cooling systems for reducing refrigeration loads and saving energy

ICC COOLING STORAGE UNIT ICC/ICU SYSTEM

Parilla Thermal Storage Project Case Study. May Page 1 of 11

R07. Answer any FIVE Questions All Questions carry equal marks *****

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

MAC N-407 Air-Cooled Chiller

Suction Accumulators. Introduction. Suction Accumulators

Institute of Aeronautical Engineering (Autonomous) Dundigal, Hyderabad B.Tech (III II SEM) MECHANICAL ENGINEERING

500 EX Fusion Compressor Series

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

PERFORMANCE EVALUATION OF CO 2 HEAT PUMP HEATING SYSTEM ABSTRACT 1. INTRODUCTION

LOW RECIRCULATION RATE EVAPORATORS

Refrigeration System Report March 2017

AIR CONDITIONER PERFORMANCE RATING

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

Application and Installation Bulletin for Master-Bilt Refrigeration Superheat Controller Kit Assembly(A ), 120/208/240/1/60, R404A, LT/MT APPS

Thomas J Kelly. Fundamentals of Refrigeration. Sr. Engineering Instructor Carrier Corporation. August 20, Page number: 1.

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

commercial refrigeration products

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

Kramersaver Air Cooled Condensing Units

Application Engineering

Water Jet Nozzle to reduce the operation cost in Air Conditioning unit

Optimisation of cooling coil performance during operation stage for improved humidity control

Comparative Performance of HFO Blends in a Condenser

Experiment 2: Test on Domestic Refrigerator for evaluation of EER.

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

SERVICE ASSISTANT OVERVIEW FDSI Online Training

THERMAL ENGINEERING LABORATORY II. To train the students with principles and operation of thermal Engineering equipments.

Commercial Refrigeration

EXPERIMENTAL INVESTIGATION OF WATER COOLER SYSTEM BY USING ECO-FRIENDLY REFRIGERANT (R-134a)

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

Low GWP Refrigerants for Air Conditioning Applications

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

IP TRONIK. Project Scope: Simulation of car refrigerant circuit with the software GT SUITE and its comparison with real test bench measurements

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

cussons Refrigeration Assembly Range TECHNOLOGY REFRIGERATION AND AIR CONDITIONING CUSSONS TECHNOLOGY LABORATORY RECOMMENDATION

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Frequently Asked Questions

DeCA DESIGN CRITERIA HANDBOOK PRODUCT REFRIGERATION SYSTEM

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)


Kawasaki centrifugal chiller using water as a refrigerant. Sep 26 th 2017 Kawasaki Heavy Industries, Ltd. Machinery Division Hayato Sakamoto

Transcritical CO2 Bottle Cooler Development

Technical Information

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

FALCON Rooftop Units ACPSE 50/60Hz Cooling Capacity : 36 to 1388 MBH (11 to 407 kw) Heating Capacity : 40 to 1298 MBH (12 to 380 kw)

Air Conditioning System with Modified Condenser Ducts and Evaporative Cooling

Air Cooled Scroll Chiller / Heat Pump

LAB EQUIPMENT DETAILS

3. (a) Explain the working of a rotary screw compressor. [10] (b) How the capacity control is achieved in refrigerant compressor?

Commercial High-Efficiency Condensing Units

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

PERFORMANCE EVALUATION OF GAS COOLER/ CONDENSER FOR CO2 REFRIGERATION SYSTEMS

Air Flow Study inside the Supermarket Refrigeration System

An Experimental Study of a Simple Vapour Compression Refrigeration System with Varying Parameters

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

The Saturation process

Precision air handling cabinets Ciatronic MICRO/EXPAIR

Performance investigation of Air-conditioning system using ejector as expansion device

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

ORTEC HIGH CAPACITY REFRIGERATED AIR/GAS DRYERS

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Mechanical Heat Pump R515

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec REFRIGERATION & AIR-CONDITIONING (Mechanical Engineering)

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

Pressure Enthalpy Charts

Test Report No.: Page 2 of 14

Life-Cycle Energy Costs and Greenhouse Gas Emissions for Gas Turbine Power

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Microchannel REMOTE AIR COOLED CONDENSER WITH ELECTRONICALLY COMMUTATED AXITOP MOTORS. Technical Bulletin. Products that provide lasting solutions.

Today s Value-Added Performers. The DRY-30 Series Dehumidifiers from DryAire Systems.

GLOBAL PROPERTY INSPECTIONS TECHNICAL BULLETIN August 1, 2002

Technical Note. EHPA Quality Label Model Range Definition Version

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

EN aquatech.piovan.com

2. CURRICULUM. Sl. No.

Transcription:

Project Report 7 REFRIGERATION ENERGY USE IN THE FOOD CHAIN by Professor Ian W. Eames Professor John Missenden Professor Graeme Maidment, Department of Engineering Systems London South Bank University Summary This report summarises the research carried out by the LSBU team into the 'Food Chain Refrigeration Energy Use ' between March and October 28. The report describes and evaluates the continued development and validation of the VCR software and provides charts comparing the experimental and model data. The results were found to be very encouraging. Some suggestions are made for the improvement of the system used in the case study. 17 October 28

Contents 1 Introduction 2 Model developments 3 Validation Case Study 4 Software validation results 5 Observations for the Case Study Data 6 Conclusion Appendix A Compressor technical data 1

1. Introduction A project objective for LSBU is to develop integrated transient refrigeration food process system models to test (and optimise) various refrigeration systems used in the industrial production chain for food. This report describes the results of LSBU's progress up to 12 October 28. 2. Model developments The main part of the research during this period has been to increase the number of refrigeration system control options available to the program user. This has included the following: Compressor: The user may now select up to 6 compressors. The control options include stagedrunning, manual and automatic speed control. Thermostat control of the automatic and staged running options is available. Evaporator fan: An automatic speed control function has been added. Control of the fan speed is based on the setting of a thermostat within the Refrigerator Design Screen. Manual control is still available within the Run Screen. Condenser fan: Automatic speed control has been added. As with the evaporator fan, this is activated by a choice of thermostat settings. Manual control is still available. Compressor protection: A compressor start-up timer code has been added to the software. In practice this protects a compressor by preventing it from being started more than a specified number of times per hour. The time delay between consecutive compressor starts can be set by the user within the Refrigerator Design Screen. Stage start-up and shut-down: In practice it is usual to stage the start-up of electric motors in order to reduce the surge current associated with inductive electrical loads. The needed to simulate the effects of staging the start of condenser fan motor, the evaporator fan motor and compressor motors is particularly important when the operation of a refrigeration system is highly transient, as in the Validation Case Study, described in the next section. Thermostat options: The range of options for the control thermostat has been extended to include evaporator saturation temperature, evaporator air-on and air-off. At the request of FRPERC the thermostat function can also be switched of within the Refrigerator Design Screen. Defrost options: This now includes options to choose either a timed defrost or initiated by the temperature difference between evaporator coil air-on temperature and saturation temperature. 3. The Validation Case Study Background: Pieminister is a pie manufacturer based at Brentry, Bristol. The company batch produce pies of various types. This is a labour intensive process. The blast-cooler used to validate 2

the VCR refrigeration system model was manufactured by Fosters (Figure 1). The dimension of the unit, condenser, evaporator and pipe-line information was recorded by the FRPERC team (Table 1). At the time of our visit it was being used to cool cooked pie filling from about 75 o C to about o C. After cooking the pie filling in tureens, these are then covered with cling film, stacked on to trolley racks and pushed into the blast- cooler (Figure 1). The blast-cooler air-on coil temperature is controlled by thermostat. Figure 5 shows a schematic plan view of the blast-cooler, showing the layout of the system and the direction of the air-flow through the evaporator, fans and across the food product. Figure 1: Pie-filling cooling room at Pieminister, (door dimensions width = 71 cm, height = 174 cm ). Manufactured by Fosters 3

Table 1: Dimension of the blast freezer and refrigerator components required as input data for the VCR model Condenser dimensions Width = 66 cm Height = 77 cm Depth = 36 cm Coil pipe = 9.7 mm O/D Coil length = 3 rows by 6 deep Fin spacing = 8 per inch (Aluminium) Mean face velocity (Air on) = 3.4 m.s - Evaporator dimensions Width = 66 cm Height = 162.5 cm Depth = 3 cm Coil pipe = 6.4 mm O/D Coil length = 6 rows by 4 deep Fin spacing = 8 per inch (Aluminium) Mean face velocity (Air on) = 2.1 m.s -1 Pipe lengths Evaporator to compressor = 38.5 m x 28.6 mm O/D (Armaflex insulation = 15 mm thick) Compressor to condenser = 3 m x 28.6 Condenser to receiver = 3 m x 19.1 mm O/D Receiver to evaporator = 38.5 m x 19.1 mm O/D Blast chiller dimensions (Foster) Internal length = 195. cm Internal width (between inner wall and evaporator face) = 86.5 cm Internal height = 195.5 cm External length (excluding doors) = 221. cm External width = 163. cm External height = 226.5 cm 1 Figure 3: Semi-hermetic (air-cooled?) Presscold, (now owned by Copland) compressor unit, Model R15/138 S/D (Presscold model number), Serial No 9483 (38/42VAC, 3-phase, 32 FLA, 4 LRA) Reconditioner s phone number 1491 629671. See Appendix A for technical data Figure 2: Schematic plan view of blast-cooler 4

The refrigeration plant: The refrigeration unit is an air-air DX system powered by a single compressor. The compressor was a reconditioned semi-hermetic Presscold compressor unit, Model R15/138 S/D, Serial No 9483 (38/42VAC, 3-phase, 32 FLA, 4 LRA). Figure 2 shows a photograph of the compressor installation. The technical data for the compressor is provided in Appendix A. The system included a high-pressure liquid receiver (approximately cm x 3cm diameter), filter/drier in the liquid line and a hot-gas line oil separator/muffler. The liquid and suction lines are long as seem in Table 1. The suction line is insulated with a standard type of foam insulation. There were a number of differences between the VCRmodel system and that used for the case study. These are listed in Table 2. Before validation could be carried out the model was further developed to remove these differences. Table 2: Comparison between the validations blast-cooler system at Pieminister and the VCR model. Pieminister system VCR model Comments System charged with R22 At present on R44a is Include R22 properties option available option No suction line heat exchanger Suction line heat exchanger option is available The software can simulate a system without a slhx by setting its effectiveness to zero in the Refrigerator design screen. An hp liquid receiver is Not included This option could be added. included. A hot-gas line oil separator/muffler(?) is included Not included This option could be added The thermal mass of the freezer cabinet is probably significant Evaporator fans are switched off for defrost cycle The blast-freezer model neglects the thermal mass and volume of the blast freezer Evaporator fans are left on The cold-store model could be used instead to simulate the system. (This was used as shown by the results given later) An option to switch the fans off at defrost will need to be included Operating and control strategies: According to the company, the refrigeration plant operates daily between 8 to 9 am and 11 pm, Monday to Friday. The company believed the blast-cooler takes approximately 45 minutes to pull-down from ambient conditions to it normal operating temperature. However, test results indicate the pull down period to be less than minutes. A thermostat controls the air-on temperature to the evaporator coil. According to the company its upper set-point is - o C and its lower set-point is -12 o C. The defrost is by means of electric resistance heater coil embedded within the evaporator tube rows. The defrost cycle is timed to come on every 5 hours and stays on for 3 minutes. The evaporator fans are switched off during defrost. Food product normally enters the blast-cooler at a temperature between 75 o C and 85 o C. The target cooling 5

temperature is o C. It normally takes 6 hours to achieve this. However, it can take up to 12 hours, depending on the air gap between layers of tureens. Other issues: The compressor enclosure was insulted to reduce noise emissions. This would have caused the temperature of the air surrounding the compressor to be high, which over time would have caused early failure were it not for the company fitting a ventilation fan to the enclosure. The power of the ventilation fan is unknown at this time. Refrigeration system control settings: In order to model the system it was necessary to determine a number of control settings, such as thermostat upper and lower set points, compressor start-up delay timer setting, timer settings for fan starting and defrost power and timer settings. This was achieved by examining the charts shown in Figures 4 and 5 draw using experimental data supplied by the FRPERC team. Power (kw), Temp (oc) 5 4 3 2 compressor signal to stop here compressor 'OFF' about here 2 to 3 min delay compressor signal to start about here 2 to 3 min delay compressor 'ON' about here thermostat upper set point = oc TcAirOff TcAirOn CompPower TeAirOn - over-shoot -2 under-shoot 2 22 24 26 28 3 32 34 Time (minutes) Thermostat lower set-point = -12oC Figure 4: Experimental data motor control characteristics of the blast-freezer 15 heater 'ON' heater 'OFF' Te(sat)=>oC switches heater 'OFF' Residual heat in heater raises Te(sat) and Tair-off Power ( kw), Temperature (oc) 5 - The available data suggests that the defrost cycle is timed at 4 hours intervals and lasts for approximately 2 minutes. The heater switches 'ON' at the start of the cycle and switches off if the evapoator saturation temperature rises above oc. Cold-store air temperature TotPower -2 CompPower TeAirOn Te(sat) 475 48 485 49 495 5 Time (minutes) Figure 5: Experimental data - defrost control details for the evaporator 6

4 Software validation results Using system data supplied by the FRPERC team and that gathered during our visit to Pieminister Ltd and from data supplied by the compressor manufacturer, the VCR refrigeration system model was set-up and run for the validation experiment. The output results from the VCR model are compared with the experimental data in the following Figures 6 to 12. Figure 6 compares the experimental data for evaporator saturation temperature and evaporator airon temperature with that predicted by the VCR model. There appears to be a close correlation between the data. Figure 7 shows a comparison between the experimental and model data during the first 6 minutes of run-time after the system was started. It is seen that the model predicts accurately the rapid switching ON and OFF of the compressor. This makes the system highly transient, which supports the view that a highly developed transient models of refrigeration systems are required by system designers if energy efficiency are to be made. Figure 8 compares the predicted and actual variation in electrical power used by the system over the first 6 minutes of operation. According to the recorded data Case Study system used 64.2 kwh of electricity during the 57 minutes of the test run. The model predicted a total energy usage of 43. 7 kwh. However, the VCR model did not account for the additional power used by the compressor enclosure cooling fan. If this was taken into account the results would be much closer. Figures 9 and show the results for both the measured data and the VCR model during the time interval when the food product was loaded and the first defrost cycle was initiated. There appears to be some differences in predicted and actual evaporator saturation temperature during this period. This is though to have been caused by thermostatic valve hunting when the condenser temperature increased during this period. Thermostatic valve hunting was not present in the model, although the phenomenon can be simulated. This topic will be discussed in the following section. Figure 11 shows the variation in predicted and measured food-product surface temperature during the chilling process. This predicted results to vary from the measured data as do those for the foodcore temperature shown in Figure 12. Figure 13 shows the predicted and measure results for the ambient air temperature and condenser saturation temperature. The difference between the measured and predicted results may be explained be the error in the predicted ambient air temperature, which controls the temperature of the air-on to the condenser. 5 Observations from the case study data The measured results shown in Figure 9 for the evaporator saturation temperature indicate that the thermostatic expansion valve (TEV) was hunting when the condenser temperature increased during relatively longer periods of compressor operation. Hunting is caused by either or a combination of oversized valve or a poorly located sensing bulb. This results in the evaporator being alternately flooded and starved of refrigerant fluid which causes the otherwise unexplained rise and fall in saturation temperature. The VCR model has a facility to simulate the hunting phenomenon. Figure 14 shows the VCR prediction of how evaporator saturation temperature falls as a TEV is increasing undersized whilst Figure 15 shown the effects of over sizing and poor location of the 7

sensing bulb. These results demonstrate how a system designer might use the VCR software to explore options in TEV selection. Figure 16 shows a close-up of the variation in evaporator saturation temperature during one ON/OFF compressor cycle, which indicates the measured and predicted effects of TEV hunting. This result indicates the ability of the VCR software to simulate the complex nature of refrigerator. However, as shown in Figure 17, the hunting phenomenon can be complex. A further important application for the VCR software is in the selection of components. Table 2 lists the predicted energy usage for the Pieminister Case Study. Table 2a lists the predicted energy consumption for the Case Study whilst Table 2b lists that predicted if a replacement compressor with a design cooling capacity of 6.5 kwc were to be fitted. The results indicate and overall energy saving of 37% and a similar reduction in CO2 emissions. Figure 18 compares the predicted variation in both food-product surface temperature and evaporator saturation temperature over the whole chilling process. These results suggest that there is little effect on the mean temperature of the food-product surface resulting from the change in the compressor s design-point cooling capacity. However, Figure 19, which shows a close up of the variation in the evaporator saturation temperature for both the 13 kwc and 6.5 kwc compressors, shows clearly a marked reduction in the switching ON/OFF frequency for the small unit. Table2 (a) Design-point cooling capacity of the refrigerator = 13 kwc Total energy = 43.7 kwh Compressor = 17.7 kwh Condenser fan = 8.3 kwh Evaporator fan = 13 kwh Defrost = 4.7 kwh Carbon produced = 17.9 kg (1.88 kg/h) Table 2(b) Design-point cooling capacity of a 6.5 kwc refrigerator Total energy = 27.3 kwh Compressor = 9.28 kwh Condenser fan = 6.94 kwh Evaporator fan = 6.42 kwh Defrost = 4.7 kwh Carbon produced = 11.5 kg (1.21 kg/h) 6. Conclusions At the outset of this project we knew that computer models of refrigeration systems that were available were not capable of modelling complex applications and although new theoretical ideas relating to modelling compressors, expansion valves, heat exchangers, pumps and fans, had been developed by the LSBU team they were untested. During this project the theoretical ideas concerning modelling of refrigeration systems have been validated. The operation and performance of refrigeration systems used in the food processing industry can be extremely transient as evidenced by the frequent on/off switching of the compressor in the validation case. We now know that the energy consumption of whole refrigeration systems can not be estimated with any reasonable accuracy from steady-state modelling alone and that transient modelling of the type provided by the VCR model provides a clear way forward. The research carried out as part of this project clearly shows that whole system efficiency is equally a function of component selection, steady-state design and transient operation. Any weakness in any of these factors will strongly impact on the energy consumption and carbon release of a system 8

Research is now needed to provide the following: (1) Further validation case studies. (2) Extend the range of component and system options is needed to reflect those currently being used by industry to provide comparisons between various components types and system types. (3)Extension of refrigerant property library If the software is to be made generally available then further work is require to make the software more robust and useful by (1) improving the error trapping function and (2) data output function requires upgrading. In summary, The VCR software has been validated using data from the Pieminister case study Results are extremely encouraging Using the model it can be shown what energy savings are possible Transient modelling is an essential design tool if significant energy savings are to be made Comparison between experimental and model data: evaporator temperatures 2 temperature (oc) 15 5 - TeSatModel TstoreModel TeAirOffModel TeAirOFFexp TeAirOnexp TeSatexp -2-3 2 3 4 5 Figure 6 9

Comparison between experimental and model data: evaporator temperatures for the first 6 minutes run-time temperat ure (oc) - -2 TeSatexp -3 2 3 4 5 6 Figure 7 TeSatModel TstoreModel TeAirOnexp 18 16 14 Comparison between model and experimenatl data: Electrical power input during the first 6 minutes after starting the compressor Comp+CondFanPower (model) Tot-PowerModel CompPwrModel KWTotal,exp kwcomp,exp electrical power (kw ) 12 8 6 4 2 2 3 4 5 6 Figure 8

Comparison between experimental and model data: evaporator temperatures during product loading and first defrost 2 15 TeSatModel TstoreModel TeAirOnexp TeSatexp 5 temperat ure (oc) - -2-3 2 2 22 23 24 25 26 27 28 Figure 9 Comparison between model and experimenatl data: Electrical power input during the first 6 minutes after starting the compressor 18 16 14 product loaded here defrost here Comp+CondFanPower (model) Tot-PowerModel CompPwrModel KWTotal,exp kwcomp,exp 12 electrical power (kw) 8 6 4 2 2 2 22 23 24 25 26 27 28 29 3 Figure 11

Comparitive variation in food product surface temperature between model and experimental data 7 temperature (oc) 6 5 4 3 2 DEFROST TprodSurface(model) Tray1 Surface ( C) Tray2 Surface (oc) Tray3 Surface (oc) Tray6 Surface (oc) Tsurface average(exp) - 215 265 315 365 415 465 515 Figure 11 Comparison between measured and predicted food product core temperature during chilling process 9 temperature (oc) 8 7 6 5 4 3 TprodMean(model) Tray 1 ( C) Tray 2 (oc) Tray 3 ( C) Tray 4(oC) Tray 5 (oc) Tray 6 (C) Measured average(exp) 2 215 265 315 365 415 465 515 565 Figure 12 Variation in condenser air-on and saturation temperature with time - comparing model and experimental data 6 5 TcSatexp TcAirOnexp TcSatmodel OATdbmod temperatur e (oc) 4 3 2 2 3 4 5 6 Figure 13 12

Predicted variation in evaporator temperature with time: Effects of an undersized TEV starving an evaporator evaporatorsaturation temperature - -2 Reducing TEV capacity -3 Reducing TEV capacity causes reduction in saturation temperature. 15. 2. 25. 3. 35. 4. time (seconds) Figure 14 Predicted variation in evaporator temperature with time: Effects of oversized TEV and reduced response time evaporator sat uration temperature (oc) - -2 Oversized TEV causing alternate flooding and starving of refrigerant in evaporator Oversized TEV with reduction in response time (increased time constant) -3 44 46 48 5 52 54 56 58 6 62 64 time (seconds) Figure 15 13

Comparison between experimental and model data: TEV hunting effects on evaporator temperature saturation temperature (oc) - Te(exp) Te(model) TEV capacity = 2 x design capacity -2 2 3 4 5 6 7 8 9 time (seconds) Figure 16 Variation in measured evaporator temperature with time: Effects of TEV hunting saturation temperature ( oc) - -2 Te(exp) 26 265 27 275 28 285 29 Figure 17 14

Comparitive variation in evaporator and food product surface temperature for a 13kW and 6.5kW rated cooling capacity condition (VCR model predictions) 7 6 5 TeSat(13 kw) TprodSurface(13 kw) TeSat(6.5 kw) TprodSurface(6.5 kw) 4 temperature (oc) 3 2 - -2-3 2 3 4 5 Figure 18 Comparitive variation in evaporatortemperature for a 13kW and 6.5kW rated cooling capacity condition (VCR model predictions) 5 TeSat(13 kw) TeSat(6.5 kw) temperature (oc) - Note the reduction in the cycling frequency: -2-3 2 3 4 5 6 7 8 9 Figure 19 15

Appendix A Compressor installation technical data and analysis The following provides some technical details and analysis for the PR15/138 compressor. Original data provided by Dr Guy Hundy and Copeland Compressors Ltd Compressor manufacturers data, courtesy of Copeland Ltd Compressor model: PR15/138 Copeland compressor model input data: Motor speed: 5Hz Required refrigeration capacity: 12kW Refrigerant: R22 Suction return temperature: 2. o C Liquid sub-cooling:.k Condenser temperature: 3. o Csat Evaporator temperature: o Csat Predicted performance at the above conditions: Refrigeration capacity: 13.19 kw Electrical power consumption: 5.83 kw Current at 4VAC: 13.32A Mechanical data: Displacement at 5Hz: 49.9 m 3 /h (3.19m3/h based on 3 cylinders with bore and stroke given below Optional capacity steps: 33.3% Number of cylinders: 3 Bore: 61.9(125)mm Stroke: 63.5mm Gross weight: 176kg Max high pressure: 25bar Suction inlet diameter: 1 5/8 inch Discharge diameter: 1 1/8 inch Max standstill pressure: 2.5bar Optional accessories: Crankcase heater Additional fans Oil pressure switch Discharge temperature protection Start un-loader The following performance curves, shown in Figures A1 and A2, were drawn using tabulated data provided by Copeland Compressors Ltd. 16

PR15/138 compressor cooling capacity 7 6 Evaporator temperature (ocsat) Based on compressor operating with R22 with a suctioninlet temperature of 2oC and no liquid sub-cooling at the condenser discharge Cooling capacity (kw) 5 4 3 2 5 - -2-3 25 3 35 4 45 5 55 6 65 Figure A1 Condenser temperature (ocsat) PR15/138: Power input to the compressor Drawn by Ian W. Eames 21 May 28 from data courtacy of Copeland Ltd 18 Electrical power absorbed (kw) 16 14 12 8 6 4 Based on compressor operating with R22 with a suctioninlet temperature of 2oC and no liquid sub-cooling at the condenser discharge -3 Evaporator temperature (ocsat) 5 - -2 2 Figure A2 25 3 35 4 45 5 55 6 65 Condenser temperature (ocsat) Drawn by Ian W. Eames 21 May 28 from data courtacy of Copeland Ltd 17

PR15/138: Predicted variation in COP COP (-) 7 6 5 4 3 2 1 5 - -2-3 Evaporator temperature (ocsat) Based on compressor operating with R22 with a suctioninlet temperature of 2oC and no liquid sub-cooling at the condenser discharge Drawn by Ian W. Eames 21 May 28 from data courtacy of Copeland Ltd 25 3 35 4 45 5 55 6 65 Condenser temperature (ocsat) Figure A3 PR15/138: Variation in overall compressor efficiency with temperature lift.68 Overall efficiency/ (-).66.64.62.6.58.56.54 Based on compressor operating with R22 with a suctioninlet temperature of 2oC and no liquid sub-cooling at the condenser discharge 4 5 6.52 3 Condenser temperature (ocsat) Drawn by Ian W. Eames 21 May 28 from data courtacy of Copeland Ltd.5 1 1.5 1.1 1.15 1.2 1.25 1.3 1.35 Temperature lift (Tc/Te) Figure A4 18