LIEBERT LIQUI-TECT 460 KIT ZONE LEAK-DETECTION SENSOR WITH CABLE

Similar documents
Liebert. Liqui-tect Leak Detection and Reporting Comprehensive Detection of Water Based Leaks in Critical Spaces

ACHIEVING ENERGY-EFFICIENT DATA CENTER COOLING: DOES REDUCING FAN SPEED ALWAYS RESULT IN ENERGY SAVINGS?

Booster Power Supply Manual

Liebert. CW kW Chilled Water Cooled Precision Air Conditioning For Data Centers

FTA200-A REMOTE ALARM PANEL

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Liebert. Mini-Mate2 1 To 8 Tons Overhead Precision Cooling And Humidity Control

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

D A R A - 4. Data Aire Relay Auto-Changeover

Liebert. Universal Monitor Monitoring, Control And Remote Communications For Critical Applications

SOLID STATE SECURITIES, INC. THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. SS90-WPS MODEL A/B INSTALLATION MANUAL

RS332N BUTTON OPERATION INTRODUCTION. Installation and Operation Instructions for REMOVING THE THERMOSTAT FROM THE BACKPLATE

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

Independent Zone Control (I.Z.C.)

Model 17A00 Expansion Enclosure

Fiber Optic Cable Fence Disturbance Sensor

R Series Remote Annunciators and Expander Installation and Operation Guide

Water Detection Controllers

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

RMS/RPX Reader. User Manual

Installation Instructions

RELEASE DEVICES RELEASE DEVICE-WPS MODELS A/B INSTALLATION MANUAL U.L. LISTED CANADIAN LISTED CSFM: :100 GENERAL DESCRIPTION:

Sentrol. ShatterPoint Glassbreak Sensor. Installation Instructions DESCRIPTION. Models (3 Volt) (6 Volt) STEP 1 MOUNTING

Firefly II Multi Voltage RELEASE DEVICES. Firefly II & IIB-MV INSTALLATION MANUAL

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

v3 360 Dual Technology Low Voltage Occupancy Sensor with Light Level, Isolated Relay and Manual On feature

Liebert CW kW. Chilled Water Cooled Precision Air Conditioning For Data Centers. Precision Cooling For Business-Critical Continuity

MR3CCUHV Temperature/Defrost Control

Passive Infrared (PIR) Wall Switch Occupancy Sensor Dual Circuit

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

SEC 2000 Millenium Infrared Gas Detector

Models NFPA 1221-A, NFPA 1221-B Public Safety DAS Annunciator Panel. Revision E 61117

21D83M-843 Integrated Single Stage Furnace Control Replacement Kit INSTALLATION INSTRUCTIONS

tcm100, tcm101 Series Temperature Control Modules and PTS100, PTS100/3 Pipe Temperature Sensors Operations Manual

Weber igrill App 4 Battery Replacement 5 Powering On & Off 5 Connecting 6 Disconnecting 6 Mounting 7 Probe Use 8 Probe Wrap Use 9

MTRA-FSP Level Control Relay. Installation & Operation Manual

idevices Connected App 4 Battery Replacement 5 Powering On & Off 5 Connecting 6 Mounting 7 Probe Use 7 Probe Wrap Use 9

Towel Warmer. Luxurious warmth for towels, robes and blankets

THE "SS90" SERIES RELEASE DEVICES MADE IN THE U.S.A. MODELS A/B INSTALLATION MANUAL

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description.

Installation Instructions

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

Installation Instructions Azatrax Dual Infrared Model Train Detector MRD2 'Turnout' Edition

RAPID RESPONSE Model RCP-1 Residential Control Panel 1 or 1-1/2 Inch (DN25 or DN40), 175 psi (12,1 bar) General Description

Touchpad Exit Controller Administration Guide

Towel Warmer MAKE EVERYDAY A SPA DAY

INSTALLATION & USER MANUAL

Weber igrill App 4 Battery Replacement 5 Powering On & Off 5 Connecting 6 Disconnecting 7 Mounting 7 Probe Use 8 Probe Wrap Use 9

ACSI MODEL 1410 POWER SUPPLY INSTALLATION INSTRUCTIONS

DPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N

Installation, Operation and Maintenance Manual

ORP (mv) Controller Model: ORP-XP2. UP DOWN ENTER Time & Date Main Menu Alarm Reset

Matrix2000. User Guide - CPD Advanced Analog Fire Alarm Control Panel 4 24 Zones. Version: 2.0 Revision: 1

Net/X US32 Universal Setback Communicating Thermostat

METEOROLOGICAL INSTRUMENTS

KM300 Carbon Monoxide Detection System Installation Manual

PS6 SERIES. Installation PS6 SERIES. Power Supplies c/w Fire Panel Interface, EOL Trigger and Standby Power Option

Ultrasonic Wall Switch Occupancy Sensor Single Circuit

INSTALLATION MANUAL. * If using remote sensors the thermostat must be hardwired. Need Help?

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation

"VIP 2" ADVANCED LUBRICATION CONTROLLER

GL-CO-RFG Channel Gas Leak Alarm System

SAFESMART Backup Controller SAFE-FSP. Installation & Operation Manual

MADE IN THE U.S.A. ADVANCE FIRE CONTROL MODEL LM21-AFC MANUAL RELEASE DEVICES TEST WEEKLY TO ASSURE PROPER OPERATION OF RELEASE DEVICE/CONTROL PANEL

Installation, Operating and Maintenance Manual

WARNING Important Safety Information

WIRING DIAGRAM AND INSTRUCTIONS

THE "SS90" SERIES RELEASE DEVICES MODEL B2 INSTALLATION MANUAL

M O D E L S F I R E G A R D M C V ADVANCE FIRE CONTROL RELEASE DEVICE

GSM RFID VOICE Alarm System

PSC-ID-x-CM Series Ceiling Mount Occupancy Sensor

SC-3 Controller INSTALLATION AND OPERATING INSTRUCTIONS FOR GAS-FIRED, OIL FIRED AND DUAL FUEL HOT WATER HEATING PLANTS. SC-3 Applications CONTENTS

TOTAL SOLUTIONS. Liquid Level Control Product Guide. MATELEC AUSTRALIA innovative by design

/ XPS Interconnection Diagrams

Premier Hazard STC Instructions

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

KEY POINTS OF DESIGN, INSTALLATION AND MAINTENANCE FOR CONFIGURING LIEBERT XD SYSTEMS. Technical Note

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to range before servicing, unless testing requires power.

TRX MAINS CONNECTION DIAGRAM

Public Safety DAS Annunciator Panel

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

Carbon Monoxide (CO) Detecting Ventilation Fan Controller Model COSTAR 24VC-e Single Relay

4100U City and Relay Cards Installation Instructions

OWNER S MANUAL. High-Wall Fan Coil Unit CONTENTS

English. FCC declaration. Electro Magnetic Compatibility (EMC) Warning. This device complies with part 15 of the FCC rules.

1126 Series Ceiling Mount PIR Motion Detector

SECTION AUTOMATIC TRANSFER SWITCHES

Tilt 'N Plug Jr. Interconnect Box

SPECIFICATIONS Power Requirements: V, 9.5A, 60Hz V, 5.8A, 50Hz Including 2A for internal convenience outlet.

Room Sensor for BACnet VAV Actuator

ACS-30-EU-VIA-DU-20-MOD

Warnings, Safety Information and Guidance

Remote Booster Power Supply Technical Reference Manual

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

SLATE. Burner Control Module INSTALLATION INSTRUCTIONS R8001B2001

MicrOTDR. Optical Fault Locator. User Manual

Transcription:

LIEBERT LIQUI-TECT 460 KIT ZONE LEAK-DETECTION SENSOR WITH CABLE Liebert Liqui-tect Leak Detection Sensors install quickly and work simply for reliable detection of conductive aqueous fluid leaks. The Liqui-tect 460 Sensor provides zone protection using the easyto- install and quick-drying Liebert leak detection cable. LEDs on the top cover provide visual indication. A reset button provides optional manual acknowledgement of alarms. DIMENSIONS - TOP, FRONT AND SIDE The top cover is hinged, for easy access to the electronics inside the steel enclosure. Terminal blocks allow easy interconnection of power and alarm outputs. Dual Form-C relay outputs simultaneously signal the local alarm panel and remote monitoring system. The sensor features supervised operation through alarms for cable faults, circuit failure or loss of power, ensuring a completely self-monitored leak detection system. The is available in packaged kits with 20, 25, 30, 35 or 45 feet of leak detection cable and hold-down clips. Note that additional cable cannot be added to packaged kits. The sensor can also be purchased independently. The sensor can accommodate up to 100 feet of leak detection cable. TOP VIEW FRONT VIEW SIDE VIEW 4.75 (121 mm) 4.25 (108 mm) 2.00 (51 mm) 3.25 (83 mm) Leak detection cable connector Form-C relay outputs and power wiring 1

As shown in the illustration on the next page, the Liqui-tect 460 () may be placed on a subfloor, where it is connected to the leak detection cable that surrounds the leak detection zone the area directly beneath the unit being protected or other areas such as the perimeter of a room. NOTE: For a downflow unit, the leak detection cable must be located six feet in front of the unit. The requires a 24 VAC power supply from the environmental unit or an external source. There are two sets of Form-C dry contacts for connection to a Liebert environmental unit and an external monitoring panel. Detection-cable Placement Precautions Do not use detection cable that is damaged or dirty (from plaster, spackle or construction debris.) Do not drag detection cable through contaminants (dirty or greasy areas). Floor must be clean for the detection cable to function properly and for the hold-down clips to adhere to the floor surface. Take careful consideration to place detection cable out of the direct discharge airflow path of environmental equipment, which can discharge moisture into the airflow. Place cable 6 ft from discharge to avoid nuisance alarms during humidification. Tools or heavy objects can do permanent damage when dropped, rolled, or set on the detection cable. Avoid foot traffic on the detection cable as well. Do not use any type of adhesive tape to secure the detection cable. Do not allow soldering or welding near the detection cable without providing protection from heat or contaminants. (Also avoid installing the detection cable in or near these type of areas.) Mild dishwashing liquid can be used to clean the detection cable of many contaminants. Installation of Leak Detection System Cable 1. Attach the leak detection cable to the module, activate module and test detection cable. (Touch detection cable with a clean moist cloth or paper towel.) Dry detection cable to remove the alarm condition. (A hair dryer can be used to speed up the drying.) NOTE: Do not try to saturate the detection cable for testing. It only requires a small amount of water to alarm. The detection cable must dry for the alarm condition to clear. 2. Install the hold-down clips in pairs in pairs as shown in the figure below, and one pair as needed to maintain consistent uniform contact between the floor and detection cable. IMPORTANT: Be certain the detection cable is protected from the adhesive installation for the hold-down clips. No adhesive should come in contact with the detection cable. 3. Once adhesive is completely dry, snap the cable into each hold-down clip. 4. Check that there are no gaps between the floor and detection cable. (Add clips as required.) 5. Be certain there are no alarms present on the module, and do final testing as per instruction in Step 1. 3 to 4 ft (0.9 to 1.2 m) 6 to 8 ft (1.8 to 2.4 m) 3 to 4 ft (0.9 to 1.2 m) 2

PLACEMENT ON SUBFLOOR UNDER COOLING SUPPORT EQUIPMENT To a Liebert environmental unit and an optional monitoring To external power supply or directly from unit Leak detection zone (directly beneath unit) Leak detection cable Leak-detection Kit Installation Scenarios Refer to the documentation included with your Liebert Thermal Management system for configuration and dimensions and the table below to calculate the length of the leak-detection cable required for proper placement of the cable. SCENARIO BY UNIT CONFIGURATION Cable clearance (distance from unit) Upflow around unit Upflow sides and front Downflow around unit Downflow sides and front Back 2 ft No cable behind 1 ft No cable behind Sides 2 ft 2 ft 1 ft 1 ft Front 2 ft 2 ft 6 ft 6 ft 3

POWER WIRING The is rated for 24 VAC, 50/60 Hz, and 0.12 A. Liebert DS, DSE, CW, PDX, or Mini-Mate2 (8 ton) T5 (24V) G5 (Ground) Liebert Mini-Mate2 (1 to 5 ton) From 24V Transformer Location of T5 (24V) connection on main controller board of Liebert unit. * Requires external transformer (there are no designated terminal connections on the unit) Liebert CRV Medium Control Board 6 4 WIRING TO AUXILIARY ALARM PANELS The has two Form-C dry-contact alarm-output contacts (TB2 and TB3). Each contact is rated for 24 VAC at 3 amp.. TB2-2 (C) Orange Wires Liebert DS, DSE, CW, PDX or Mini-Mate2 (8 ton) Environmental Unit 24 (24V) TB2-1 (N.O.) 50, 51, 55 or 56 TB2 (C) TB2-1 (N.O.) Note: Terminal 50 not available on Mini-Mate2 (8-ton) Orange Wires Orange Wires Liebert Mini-Mate2, (1 to 5 ton) Environmental Unit Liebert CRV Environmental Unit TB2-2 (C) 60 TB2-1 (N.O.) 61-1 (24V) -2 or -3 NOTE: In icom, use the Service Options menu to add that the Liqui-tect is installed. Transformer From 24V Transformer TB2 TB2-2 (C) TB2-1 (N.O.) Liebert contact monitor panel Alarm Panel Input contact (N.O.) 4

CONFIGURATION-SWITCH SETTINGS A 4 position DIP switch selects two alarm (filter) delays and three mutually-exclusive alarm modes. The switches are located next to the wiring termination blocks. SWITCH SETTINGS 0FF ON ALL CIRCUITS: CLASS 2 Contacts shown in POWERED, NON-ALARM state 1. Leak Detect Filter 2. Alarm Latch 3. Alarm Retest Delay 4. Not Used 10 sec 2 min No Yes No 1 hr Contacts Rating: 24V, 3A TB3-3 TB3-2 TB3-1 N.C. C N.O. Contacts Rating: 24V, 3A TB2-3 TB2-2 TB2-1 N.C. C N.O. CONNECT ENCLOSURE TO EARTH GROUND 24V~ 50/60Hz 0.12A -2-1 SWITCH-SETTINGS SUMMARY SS2 SS2 SS3 SS4 MODE OFF OFF OFF not used Non-latching, 10-second filter delay (factory default) ON OFF OFF not used Non-latching, 2-minute filter delay OFF ON not used Latching, 10-second filter delay ON ON not used Latching, 2-minute filter delay OFF OFF ON not used 1-hour latch/retest, 10-second filter delay ON OFF ON not used 1-hour latch/retest, 2-minute filter delay Leak Detect Filter Delay(SS1) SS1 selects the leak detect filter delay, the interval for which a leak condition must be continuously detected before an alarm is triggered: OFF = 10 seconds (default) ON = 2 minutes This feature is useful for eliminating nuisance alarms. SS1 works independently of the settings of SS2 and SS3. While the alarm delay is selectable (factory default is OFF=10 seconds), the cable fault delay is preset at approximately 2 seconds. Latching or Non Latching Alarms (SS2) SS2 selects latching or non-latching alarms, the setting in which an alarm will latch ON until manually reset: OFF=Non-latching (default) ON=Latching 5

The factory default is OFF=Nonlatching. If the sensor is in latching mode (ON=Latching) and the leak condition clears itself in the interim, a manual reset is required. While the alarm is latched, the sensor goes into a sleep mode and power to the leak detection cable is discontinued. Depowering the cable prevents damage to the cable should it be in contact with the conductive liquid for an extended duration. After a manual reset, the sensor resumes its normal operation, continuously checking for leaks. If the leak condition has not yet cleared but the sensor is manually reset, the sensor will re-alarm after the appropriate leak detect filter delay. SS2 in the ON position will disable the operation of SS3. Alarm Retest Delay (SS3) SS3 selects the alarm retest delay, the setting in which an alarm is latched and retested every hour. OFF=Non-latching (default) ON=Latching-retest each hour The factory default is OFF=Nonlatching. If SS3=ON and a leak is detected, the alarm condition is latched, the sensor goes into a sleep mode and power to the leak detection cable is discontinued. After one hour, the sensor will automatically retest if the leak is still present. If the leak has cleared itself, the sensor deactivates the alarm, resets itself and resumes normal operation; if the leak is still present, the alarm condition remains activated and the sensor goes to sleep and retests in another hour. This procedure will repeat indefinitely until the leak is cleared or until the alarm is manually reset. A manual reset can be initiated at any time. If the leak condition has not yet cleared, the sensor re-alarms after the selected leak detect filter delay; if the leak has cleared, the sensor deactivates the alarm and resets itself. SS3 is disabled if SS2=ON. The factory default settings of SS2=OFF and SS3=OFF place the sensor in a nonlatching, continuous retest mode. The sensor does not go to sleep after detecting a leak instead, it continually checks to determine whether the leak condition has cleared itself. Alarms automatically reset when the leak condition clears. Initiating a manual reset will cause the sensor to trigger the alarm again after the selected leak detect filter delay. The leak detect cable remains powered at all times. SS4 is not used. LED OPERATION System Normal (Green): ON continuously when power is applied to sensor. Alarm Pending (Yellow): ON continuously during leak detect filter delay and cable fault delay. FLASHING (with Leak Detected LED) to indicate cable fault condition. Leak Detected (): FLASHING to indicate leak detected alarm. FLASHING (with Alarm Pending LED) to indicate cable fault condition. NOTES This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of FCC rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. In the event of a severe leak causing submersion or partial-submersion of the enclosure and/or the electronic circuitry inside the enclosure, the entire module should be returned to the factory for inspection. VertivCo.com Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA 2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice. 6