Typical Mount Height. Combustion Chamber

Similar documents
Min. Mount Height. Min. Mount Height. Length Weight

Insert Manual. DES Series WARNING. For Your Safety

Insert Manual. DET3 Series WARNING. For Your Safety

Typical Mount Height. Combustion Chamber(s)

Insert Manual. RHT Series WARNING. For Your Safety

Insert Manual. SV Series WARNING. For Your Safety

DX2 Series. Models V.6/03

Insert Manual. DES3 Series WARNING. For Your Safety

Insert Manual. XTS3 Series WARNING. For Your Safety. For complete installation instructions, see the General Manual that accompanies this insert.

For complete installation instructions, reference the Tube Heater General Manual that accompanies this insert manual.

Insert Manual. DX3 Series WARNING. For Your Safety

Insert Manual. RVA2 Series WARNING. For Your Safety

Insert Manual. DX3L Series WARNING. For Your Safety

Insert Manual. DX3 Series WARNING. For Your Safety

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

DX SERIES TUBE HEATER

Line Pressure ( w.c.) Gas Supply Min. Max. Pressure ( w.c.) Natural Gas Propane Gas

Engineering Submittal Data PPRTH Patio Radiant Tube Heaters.

SERIES. 10 year limited warranty on Burner Core 5 year limited warranty on All combustion and. 2 year limited warranty on All Burner Controls

CLEARANCES TO COMBUSTIBLES

TUBE HEATER TROUBLESHOOTING GUIDE

tio-pal PH Series Gas-Fired High Intensity Infra-Red Patio Heater ! WARNING! WARNING! WARNING! WARNING! FOR YOUR SAFETY FOR YOUR SAFETY

INFRARED RADIANT HEATERS

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

Commercial Water Heater Replacement Parts. Price List. For Models: SBS, SBD, SBN, SDV, SUF, PCE and CSB. Prices Effective

CSD-1 COMMERCIAL BOILER CONTROLS

GAS-FIRED PRESSURIZED LOW INTENSITY INFRARED HEATERS SERIES TLP

BEACON/MORRIS RBD SERIES INFRARED RADIANT HEATER

Residential Garage Heater Installation, Operation, & Maintenance Instruction Manual (Mount a copy of these instructions adjacent to the heater)

INFRARED RADIANT HEATER RSCA SERIES CERAMIC HEATERS NATURAL GAS PROPANE GAS DATE: PROJECT: ARCHITECT/ENGINEER: CONTRACTOR: SUBMITTED BY:

GUIDE SPECIFICATION ADVANCED RADIANT SYSTEMS DU/DUH DUAL OUTPUT RANGE INFRARED TUBE HEATERS

INSTALLATION AND OPERATION INSTRUCTIONS. INFRARED RADIANT TUBE HEATER Single Stage Pull Through System (Negative Pressure)

DTHS SERIES TUBE HEATER INSTALLATION, OPERATION MAINTENANCE AND PARTS MANUAL. Detroit Radiant Products Company FOR YOUR SAFETY!

Parts List for Ener-Radiant XL Tube Heaters

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

SUPER HIGH EFFICIENCY WATER HEATERS SUPPLEMENT TO INSTRUCTION MANUAL P/N (Replaces pg. 2 in instruction manual.) CONGRATULATIONS!

100T399-SOLA SUPPLEMENT TO INSTALLATION & OPERATION MANUAL INCLUDED WITH WATER HEATER (SERIAL NUMBERS BEGINNING LK AND LATER)

Residential Garage Heater Installation, Operation, & Maintenance Instruction Manual (Mount a copy of these instructions adjacent to the heater)

WARNING WARNING. 7D837A thru 7D849A, 7D851A, 7AR79 thru 7AR88. Installation, Operation, Maintenance, and Parts Manual

STS-JZ (premierschwank) POSITIVE PRESSURE SERIES GAS FIRED INFRA-RED TUBE HEATERS

INSTALLATION AND OPERATION INSTRUCTIONS. INFRARED RADIANT TUBE HEATER Two Stage Pull Through System (Negative Pressure)

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-1500T DUAL FUEL CONSTRUCTION HEATER

Multi-Function Cooktop

OWNER S MANUAL Manufactured Home Downflow Gas Furnace: MGD-B Series

USER S INFORMATION MANUAL

Service Manual Model 3163

A. Product Data: Include rated capacities, furnished specialties and accessories.

G71MPP WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

USER S INFORMATION MANUAL

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION

Cumberland Heating Systems

T-CLASS GAS-FIRED UNIT HEATERS Separated Combustion - Direct Vent - Horizontal - 60 HZ. Thermal Efficiency - up to 82% Input - 40,000 to 300,000 Btuh

INSTALLATION GUIDE Dual Fuel Ranges

INSTALLATION AND OPERATION INSTRUCTIONS. INFRARED RADIANT TUBE HEATER Two Stage Pull Through System (Negative Pressure)

National Comfort Products 539 Dunksferry Road Bensalem, PA (215) Fax: (215)

Installation, Operation, Maintenance and Parts Manual

SERIES EvenTube INFRARED HEATER. Installation, Operation and Service Instructions. Model ETS Infrared Patio Heater. Two-Stage

G60UH(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

INSTALLATION AND OPERATION INSTRUCTIONS. INFRARED RADIANT TUBE HEATER Single and Two Stage Push Through System (Positive Pressure)

Synergy WARNING FOR YOUR SAFETY. High Intensity Infrared Heaters. Installation, Service, and Maintenance Manual COMBUSTION RESEARCH CORPORATION

LGB Gas fired boiler

EHL Series Installation, Operation, Maintenance and Parts Manual

Gas-Fired Indoor and Outdoor Duct Furnaces

LD Series Installation Manual

INSTALLATION AND OPERATION INSTRUCTIONS. INFRARED RADIANT TUBE HEATER Single and Two Stage Pull Through System (Negative Pressure)

Power Direct Vent PDV(S&T) Models

SLP98UHV WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

Model VPT 120V 60Hz Gas-Fired, Tubular, Radiant, Low-Intensity Infrared Heater

INSTALLATION AND OPERATION INSTRUCTIONS. COLD BLOCKER INFRARED RADIANT TUBE HEATER Single and Two Stage Pull Through System (Negative Pressure)

Owner: Keep this manual in a safe place in order to provide your service technician with the necessary information.

INSTALLATION AND OPERATION INSTRUCTIONS

ASSEMBLY INSTRUCTIONS - NXS SERIES. INFRARED RADIANT TUBE HEATER Single and Two Stage Pull Through System (Negative Pressure)

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) F-400T DUAL FUEL CONSTRUCTION HEATER

INSTALLATION, OPERATION, & MAINTENANCE INSTRUCTIONS

FINNED WATER-TUBE POOL HEATERS

PH Series Manual WARNING. Detroit Radiant Products Co. Installation, Operation, Maintenance and Parts. For Your Safety

EHL Series Installation, Operation, Maintenance, and Parts Manual

Installation, Operation and Service Instructions RS RANGE RESIDENTIAL INFRARED HEATERS

G60UHV(X) WARNING. WARNING Sharp edges. Be careful when servicing unit to avoid sharp edges which may result in personal injury. Service Literature

LS Series Installation Manual

ZG Shown READ ALL INSTRUCTIONS IN THIS MANUAL AND RETAIN FOR FUTURE REFERENCE WARNING

SECTION 7: OPTIONAL HEATER ACCESSORIES. Step Reflector Joint Installation. Step Reflector Joint Detail. FIGURE 19: Reflector Joint Detail


SUBMITTAL DATA S100 & S100U POSITIVE PRESSURE SERIES GAS FIRED INFRA-RED TUBE HEATERS. Page 1 PROJECT: ENGINEER: CONTRACTOR:

STERLING RSS SERIES INFRARED RADIANT TUBE HEATER

EGH Series 5. Control Supplement. EGH-105 to EGH-125 Natural gas CSD-1 control system

Weil-McLain part numbers are found in Weil-McLain Boilers and Controls Repair Parts Lists.

INFRARED RADIANT TUBE HEATER

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

Tube Heater General Manual

MICRO 60U24 CONTROL Micro-Processor Based Control

USER S INFORMATION MANUAL

LUMINOUS A PATIO HEATER LIKE NO OTHER

LGB. Control Supplement. Gas fired boiler. Universal Control System. Series 2 Propane gas. Contents

INSTALLATION AND OPERATION INSTRUCTIONS. RESIDENTIAL RADIANT GARAGE TUBE HEATER Single and Two Stage Pull Through System (Negative Pressure)

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

Series RE Infrared Heater

INSTALLATION AND OPERATION INSTRUCTIONS. SUNSTAR ECLIPSE INFRARED RADIANT TUBE HEATER Single Stage Pull Through System (Negative Pressure)

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

Ultra Boiler Series 1 & 2 Jacket Parts

Transcription:

! WARNING: This heater must be installed and serviced by trained gas installation and service personnel only! Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death. Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment. Protect yourself and others by observing all safety information. Retain instructions for future reference. For complete installation instructions, see the General Manual that accompanied this piece. Also available at www.reverberray.com. DES Series Project: Date: Location: City: State: Zip: Contractor: Engineer: Local Representative: Customer Name: Address: City: State: Zip: Model #: Phone#: Serial #: Date of Install: Notes: Table of Contents Page Models Warnings Clearances to Combustibles Product Summary Product Instructions Heater Requirements Theory of Operation Wiring Diagrams Flowchart Parts Listing Series Kit Contents 1 2 2 3 3 4 4 5-7 8-9 10-11 12 Models Qty. Model # Gas Type (circle one) BTU/H Straight Length U-Tube Length Weight Typical Mount Height Combustion Chamber Radiant Emitter Tube "Type" Tube "Type" Tube Pkg #1 Pkg. #2 DES 20-50 N or LP 50,000 21'-7' 13'-0" 120 # 10' - 15' Aluminized 4" Hot-rolled 20-4 Alum-HRT N/A 5 DES 20-60 N or LP 60,000 21'-7' 13'-0" 120 # 11' - 18' Aluminized 4" Hot-rolled 20-4 Alum-HRT N/A 5 DES 20-75 N or LP 75,000 21'-7' 13'-0" 120 # 12' - 20' Aluminized 4" Hot-rolled 20-4 Alum-HRT N/A 5 DES 30-50 N or LP 50,000 31'-3' 17'-8" 120 # 10' - 15' Aluminized 4" Hot-rolled 30-4 Alum-HRT N/A 4 DES 30-60 N or LP 60,000 31'-3' 17'-8" 160 # 11' - 18' Aluminized 4" Hot-rolled 30-4 Alum-HRT N/A 4 DES 30-75 N or LP 75,000 31'-3' 17'-8" 160 # 12' - 20' Aluminized 4" Hot-rolled 30-4 Alum-HRT N/A 4 DES 30-100 N or LP 100,000 31'-3' 17'-8" 160 # 13' - 23' Aluminized 4" Hot-rolled 30-4 Alum-HRT N/A 5 DES 40-50 N or LP 50,000 40'-11' 22'-8" 190 # 10' - 15' Aluminized 4" Hot-rolled 40-4 Alum-HRT N/A 2 DES 40-60 N or LP 60,000 40'-11' 22'-8" 190 # 11' - 18' Aluminized 4" Hot-rolled 40-4 Alum-HRT N/A 2 DES 40-75 N or LP 75,000 40'-11' 22'-8" 190 # 12' - 20' Aluminized 4" Hot-rolled 40-4 Alum-HRT N/A 2 DES 40-100 N or LP 100,000 40'-11' 22'-8" 190 # 13' - 23' Aluminized 4" Hot-rolled 40-4 Alum-HRT N/A 4 DES 40-125 N or LP 125,000 40'-11' 22'-8" 190 # 15' - 25' Aluminized 4" Hot-rolled 40-4 Alum-HRT N/A 4 DES 40-150 N or LP 150,000 40'-11' 22'-8" 190 # 16' - 30' Titanium 4" Hot-rolled 40-4 Titan-HRT N/A 4 DES 50-100 N or LP 100,000 50'-7' 27'-4" 235 # 13' - 23' Aluminized 4" Hot-rolled 40-4 Alum-HRT 10-4-HRT 2 DES 50-125 N or LP 125,000 50'-7' 27'-4" 235 # 15' - 25' Aluminized 4" Hot-rolled 40-4 Alum-HRT 10-4-HRT 4 DES 50-150 N or LP 150,000 50'-7' 27'-4" 235 # 16' - 30' Titanium 4" Hot-rolled 40-4 Titan-HRT 10-4-HRT 4 DES 50-175 N or LP 175,000 50'-7' 27'-4" 235 # 17' - 35' Titanium 4" Hot-rolled 40-4 Titan-HRT 10-4-HRT 2 DES 60-125 N or LP 125,000 60'-3' 32'-4" 235 # 15' - 25' Aluminized 4" Hot-rolled 40-4 Alum-HRT 20-4-HRT 2 DES 60-150 N or LP 150,000 60'-3' 32'-4" 235 # 16' - 30' Titanium 4" Hot-rolled 40-4 Titan-HRT 20-4-HRT 2 DES 60-175 N or LP 175,000 60'-3' 32'-4" 235 # 17' - 35' Titanium 4" Hot-rolled 40-4 Titan-HRT 20-4-HRT 2 Model requires 5EA-SUB accessory package. Warranty registration options: 1. Register online at www.reverberray.com/warranty 2. Complete the information above and fax to Detroit Radiant Products Co. 3. Complete the information above and mail to Detroit Radiant Products Co. Baffle Pieces Printed in U.S.A. 2002 Detroit Radiant Products 21400 Hoover Rd., Warren, MI 48089 T. (586) 756-0950 F. (586) 756-2626 Form# LIODES-2M-12/02 (ID) Replaces Form# LIODES-2M-05/01

DES Series! WARNING! T FOR RESIDENTIAL USE! Do not use in the home, sleeping quarters, attached garages, etc.! WARNING! This heater must be installed and serviced by trained gas installation and service personnel only. Read and understand these instructions thoroughly before attempting to install, operate or service this heater. Failure to comply could result in personal injury, asphyxiation, death, fire, and/or property damage. Retain these instructions for future reference.! WARNING! This is not an explosion-proof heater. Where there is the possibility of exposure to flammable vapors, consult the local fire marshal, the fire insurance carrier and other authorities for approval of the proposed installation.! WARNING! Failure to comply with the stated clearances to combustibles could result in personal injury, death and/or property damage.! WARNING! In locations used for the storage of combustible materials, signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles. Signs must either be posted adjacent to the heater thermostats or inthe absence of such thermostats, in a conspicuous location.! WARNING! This heater should be installed so that the minimum clearances to vehicles, as marked on the heater, will be maintained. If vehicle lifts are present, ensure that these clearances will be maintained from the highest raised vehicle. CLEARANCES TO COMBUSTIBLES (IN.) MODEL. MOUNTING SIDE ANGLE FRONT BEHIND TOP BELOW DES(20,30,40)-50 [N,P] 0º 9 9 6 47 45º 39 8 10 47 W/1 side shield 0º 29 8 6 47 W/2 side shields 0º 9 9 6 47 20 ft from burner 0º 7 7 6 30 DES(20,30,40)-60 [N,P] 0º 9 9 6 47 45º 39 8 10 47 W/1 side shield 0º 29 8 6 47 W/2 side shields 0º 9 9 6 47 20 ft from burner 0º 7 7 6 30 DES(20,30,40)-75 [N,P] 0º 9 9 6 60 45º 39 8 10 60 W/1 side shield 0º 29 8 6 60 W/2 side shields 0º 9 9 6 60 20 ft from burner 0º 7 7 6 30 DES(30,40,50)-100 [N,P] 0º 14 14 6 66 45º 39 8 10 66 W/1 side shield 0º 29 8 6 66 W/2 side shields 0º 16 16 6 66 20 ft from burner 0º 7 7 6 30 DES(40,50,60)-125 [N,P] 0º 20 20 6 76 45º 58 8 10 76 W/1 side shield 0º 42 8 6 76 W/2 side shields 0º 20 20 6 76 20 ft from burner 0º 7 7 6 30 DES(40,50,60)-150 [N,P] 0º 24 24 6 81 45º 58 8 10 81 W/1 side shield 0º 42 8 6 81 W/2 side shields 0º 23 23 6 81 20 ft from burner 0º 11 11 6 44 DES(50,60)-175 [N,P] 0º 34 34 6 92 45º 63 8 10 92 W/1 side shield 0º 50 8 6 92 W/2 side shields 0º 30 30 6 92 20 ft from burner 0º 11 11 6 44 SIDE 0 MOUNTING ANGLE FRONT TOP BELOW TOP BELOW SIDE BEHIND 45 MOUNTING ANGLE FRONT 0 W/1 SIDE SHIELD SIDE TOP BELOW TOP BELOW BEHIND SIDE 0 W/2 SIDE SHIELDS 2

DES Series Mechanical Instructions This supplement is designed to address the specifics of the DES Series - See page 12 for specific product features. Product Summary DES Series heaters are available from 20 to 60 foot, 50,000 to 175,000 BTU s, natural or LP gas. DES Series are positive pressure, single stage heaters and feature hot-rolled steel for it s radiant pipes. DES Series heaters also feature a direct spark ignition system. Specific Mechanical Instructions Be sure to identify the aluminized (50-125 MBTU/H) or titanium (150-175 MBTU/H) combustion chamber and place as the first tube section. 175,000 BTU/H models must be installed with a stainless steel tube clamp at the second joint of the exchanger between the first and second ten foot radiant tube. Note baffle quantities for your model and place baffles in the last tubes (farthest from the burner) as shown on pages 13-14 of the general manual. Tube Installation Sequence B Aluminized (50-75 MBTU/H) Combustion Tube B = Burner Location Baffle Location B Aluminized (50-100 MBTU/H) Combustion Tube Aluminized or Titanium (50-125 MBTU/H) (150 MBTU/H) B Combustion Tube Aluminized or Titanium B (100-125 MBTU/H) (150-175 MBTU/H) Combustion Tube Aluminized or Titanium (125 MBTU/H) (150-175 MBTU/H) B Combustion Tube 3

DES Series Electrical Requirements 120 Volt - 60 HZ, single phase, 3-wire. 25V thermostat connection. Starting Current 1.7 Amps. Running Current 1.1 Amps. 24V controls. Wiring must not run above or below the heater, nor exposed to the radiant output. Heaters must be grounded in accordance with the National Electrical Code ANSI/NFPA70 (latest edition). Observe proper electrical polarity. It is recommended that the thermostat be installed on the hot side of a fused supply line and have sufficient ampere rating for the heater(s) that it controls. Gas Requirements Manifold Pressure Nat. 3.5 LP. 10.0 Minimum Inlet Pressure Nat. 5.0 LP. 11.0 Maximum Inlet Nat. 14.0 LP. 14.0 Theory of Operation Starting Circuit (see internal wiring diagrams) When voltage is applied to L1 and L2, a circuit is completed from L1 via the blower motor to L2. The blower fan is mounted in the control box and rated to supply sufficient air for combustion. Air pressure generated by the blower will cause the normally open pressure switch to close. Another circuit is completed from L1 to the spark ignition module and back to L2. After a seven (7) second pre-purge, the spark electrode and gas valve are energized simultaneously. The trial for ignition is fifteen seconds. Running Circuit After ignition, the flame rod monitors the flame. As long as a flame is present, the valve is held open. If the flame is lost, the control acts to close the valve within one second, and a new trial sequence identical to that at start-up is initiated. If proof of flame is not established within the 15 second trial for ignition, the unit will retry two additional times before entering lockout mode. If lockout occurs, the control can be reset by briefly interrupting the power source. Ventilation Requirements Consult the general manual for venting instructions. For unvented operation, there must be a positive air displacement of at least 4.0 CFM per 1000 BTU/H for natural gas or 4.5 CFM per 1000 BTU/H for LP gas. WVE-4 termination cap must also be used. 4

Internal Wiring Diagrams DES LADDER DIAGRAM L1 120VAC L2 BLOWER PRESSURE SWITCH R IGNITOR/SENSOR W GAS VALVE G W G IGNITION MODULE R Y IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED, IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING OF AT LEAST 105 C. DES BLOCK DIAGRAM TERMINAL BLOCK BURNER IGNITOR/SENSOR A B C D PRESSURE SWITCH L1 120VAC W L2 G M C P 1 2 3 R W G Y W M 1 BLOWER C P 2 3 OFF GAS VALVE IGNITION MODULE R 5

DES Series Field Wiring Diagrams WHITE 24V T-stat 115V TO HEATER BRANCH #1 G W R WHITE Common required for thermostats that require constant power. 24V 24V BY OTHERS 115V TO HEATER BRANCH #2 POLE #2 POLE #1 W R G COIL Y C W B L2 L1 115V A Transformer Relay is used in conjunction with most low voltage T-stats when wiring tube heaters. TE: The Transformer Relay selected must be able to handle the combined start-up amperage per relay branch. 24V T-Stat & Connection(s) T-stat HEATER BURNER BOX TE: Up to 10 line voltage tube heaters can be wired to 22 amp t-stats. Heaters on same vent must share the same t-stat. GRD NC COM HEATER BURNER BOX For multiple heater connection HEATER BURNER BOX L1 L2 120V Connection(s) 6

Alternative Wiring Diagrams THIS PAGE INTENTIONALLY LEFT BLANK. THERE ARE ALTERNATIVE WIRING DIAGRAMS FOR THE DES SERIES 7

DES Troubleshooting Flowchart Turn up Thermostat The fan is faulty and must be replaced. Is there 120V coming to the fan? Is the blower obstructed? Is the power at the heater 120V? Does the fan blower turn on? Correct wiring. Find the source of the electrical problem. Remove obstruction & lubricate fan. WARNING: Bypassing any switch is for testing purposes only. Do not leave switch bypassed during normal operation or heater s built-in safety mechanisms will be compromised. Replace ignitor. Is the ignitor physically damaged? Does the ignitor spark? Check the gap on the ignitor. Is the gap between 3/16 and 1/4? Adjust gap. 8 Repair wiring or hose connections. Check for loose wiring or restrictions in hose connections to the pressure switch. Are they ok? Is the inlet or the outlet of the unit obstructed? I.e. ice, birds nest, dirt, etc. Replace the appropriate switch after verifying the following: The heater is equipped with a safety pressure switch. The switch is a normally open switch and located in the gas valve compartment. Temporarily place a jumper across the terminal of the switch. (Be sure to reinstall the cover.) Does the ignitor spark? Remove obstruction. Baffle(s) is in the tube(s) farthest from the burner. Heater, fan blower, squirrel cage, intake and exhaust are clean and free from dirt and obstructions. The 4 air intake pipe does not exceed 20 feet and/or 2 elbows. There is not a negative pressure experienced at the area of air intake (i.e. attic space, high-winds, very tight building). Temporarily place jumper across the pressure switch and check for 120V going from switch to circuit board. (Be sure to reinstall the cover.) Is there 120V entering the circuit board? Replace circuit board. If any of the previous were occurring, please address the problem. Faulty wiring. Repair or replace wiring.

WARNING: Bypassing any switch is for testing purposes only. Do not leave switch bypassed during normal operation or heater s built-in safety mechanisms will be compromised. Possibly, the circuit board and/or wiring harness is faulty. These should be replaced. Test for 120V at valve during valve opening period (usually 10 seconds after power to the heater). Is there 120V to the valve? During the ignition trial, does gas valve open? Correct problem. Replace gas valve. Check to make sure gas pressure is within minimum and maximum inputs, as indicated on CSA burner rating label. Is gas pressure OK? Check the gap on the ignitor. Is the gap between 3/16 and 1/4? Adjust gap. Check to make sure gas pressure is within minimum and maximum inputs, as indicated on CSA burner rating label. Is gas pressure OK? Is the gas cock in an ON position? Make sure gas lines were purged of air and/or correct pressure problems. Does the burner light? Check to make sure flame sensor wire is OK and then replace circuit board. With microammeter, check amperage at flame rod. Is it greater than 0.7 microamps? Is the heater properly grounded? Is the heater s polarity correct? Does the burner stay on for approx. 8 seconds and then shut off? Does the burner stay on? 9 Sensing rod is faulty or flame is weak. Check to make sure heater is operating at proper gas pressure as indicated on CSA burner rating label and then clean or replace sensing rod if needed. Correct problem. Does the burner come on and then turn off immediately (1 or 2 seconds). Does heater stay on until call for heat ends? Check the gap on the ignitor. Is the gap between 3/16 and 1/4? Adjust gap. Correct problem. The following can cause the heater to shut down: Improper grounding High winds Taking combustion air from the attic Dirty environment Baffle not located properly Fluctuating gas pressure Exhaust pressure switch may be faulty or there is a restriction in the exhaust. Check to make sure that the pressure is within minimum and maximum inputs as indicated on the CSA burner rating label. Is gas pressure OK? Troubleshooting ends.

DES Series Parts Breakdown 502 552 579 1 331 501 PS 55A 70 563 97 5 570 551 504 550 17 68A 31B 217 122 554 555 44 9 13 31B 13 503 204 200A 201 223 209 208 212 20C 10 82 12 21B 11 553 26A 26B 21B 220 26C 65I Emitter Tube(s) Combustion Chamber 10

Basic Parts List DES SERIES PARTS LISTING TP# ITEM TP# ITEM TP-1 CONTROL BOX COVER TP-208 "Z" MOUNTING BRACKET TP-5 FLANGE GASKET TP-209 36E36A-246 GAS VALVE - NAT GAS ASSY TP-9 CONDUIT COUPLING TP-209P 36E36A-240 GAS VALVE - LP GAS ASSY TP-10 CONDUIT 4" X 1/2" TP-212 1/2" X 3" PIPE NIPPLE TP-11 IGNITOR BOX TP-217 PRESSURE BARB FITTING TP-12 IGNITOR BOX COVER TP-222 FLAME ROD TP-17 SIGHT GLASS KIT TP-222A FLAME ROD WIRE TP-20C 120" ALUMINUM REFLECTOR TP-223 GAS MANIFOLD TP-20D 120" STAINLESS STEEL REFLECTOR TP-330 DIVIDER GROMMET TP-21B 4" TUBE CLAMP TP-331 GREEN SELF TAP GROUND SCREW TP-26A 10 FT. ALUMINIZED COMBUSTION TUBE TP-501 DIVIDER PANEL TP-26B 10 FT. TITANIUM COMBUSTION TUBE TP-502 LEFT END PANEL TP-26C 10FT. UNCOATED HOT ROLLED RADIANT TUBE TP-503 RIGHT END PANELS TP-31B CONTROL BOX MOUNTING BRACKET TP-504 CONTROL BOX TP-44 AIR ORIFICE W/SCREEN - CONSULT FACTORY TP-550 SPARK TRANSFER WIRE - ORANGE TP-55A FAN BLOWER TP-551 MARK 10DX-117-10 CIRCUIT BOARD W/ PRE-PURGE TP-65I INTERLOCKING 33" BAFFLE SECTION TP-552 WIRING HARNESS TP-68A STRAIN RELIEF BUSHING TP-553 IGNITOR MOUNTING BRACKET TP-70 CONTROL BOX COVER GASKET (PER FOOT) TP-554 SPARK IGNITOR GASKET TP-82 REFLECTOR CENTER SUPPORT TP-555 SPARK IGNITOR ELECTRODE TP-97 1/4" x 1/4" BRASS INT./EXT. ATMOS. BARB FITTING TP-562 1/4" ATMOSPHERIC TUBE (VINYL) TP-108 5' AL-TI TUBE, PAINTED WITH ONE CLAMP TP-563 1/4" PRESSURE TUBE TP-111 5' ALUM. TUBE, PAINTED WITH ONE CLAMP TP-570 16'' DES BURNER TUBE WITH FLANGE TP-112 5' REFLECTOR TP-579 WIRE HANGER W/OUT SPRING CLIP TP-122 GASKET FOR AIR ORIFICE & AIR COLLAR TP-PS N.O. Pressure Switch (Select Switch Below, BTU Dependent) TP-200A BURNER (50 TO 100 MBTU/H) (TP-61B) DIFFERENTIAL PRESSURE SWITCH - 50 TO 100 MBTU/H TP-201 BURNER (125 TO 150 MBTU/H) (TP-61E) DIFFERENTIAL PRESSURE SWITCH - 125 & 150 MBTU/H TP-204 GAS ORIFICE - CONSULT FACTORY (TP-61D) DIFFERENTIAL PRESSURE SWITCH - 175 MBTU/H 6 TOTAL NEEDED TO COVER OUTER EDGES OF A BURNER BOX 11

Kit Contents & Product Features Kit contents for the DES Series are shown below. Reference the proper column for your particular models length. FILLED BY: DES SERIES KIT CONTENTS TP# DESCRIPTION 20 FOOT 30 FOOT 40 FOOT 50 FOOT 60 FOOT TP-19B 4" Hangers 3 4 5 6 7 TP-21B 4" Tube Clamps 2 3 4 5 6 TP-82 4" Refl. Cntr. Sprt. 1 1 1 1 1 TP-105 Reflector End Caps 2 2 2 2 2 IOM Install / Op Manual 1 1 1 1 1 4" Hanger TP-19B Generic IOM LIOM-GT AND Series Insert LIOM-DES Notes: 4 Reflector Center Support - TP-82 One 4 stainless steel butt clamp is provided for each 175,000 BTU model. Place as shown in IOM. 4" Butt Clamp TP-21B Product Features APPROVALS CSA/AGA. Commercial approval. BURNER SIGHT GLASS For burner inspection. COMBUSTION AIR INLET & VENT 4 Duct. CONTROLS 100% Safety shut off. Differential pressure switch. Direct spark ignition. Flame rod sensing. Pre-purge controls. Potted circuit board. ENAMELED CONTROL BOX Outside air collar (4 ) attached. Totally enclosed components. EMITTER & COMBUSTION TUBES Aluminized combustion chamber (50-125 MBTU/H models). Titanium combustion chamber (150-175 MBTU/H models). 16ga. 4 O.D. hot-rolled steel radiant tubes. Combustion chamber coated with high temperature, corrosion resistant black coating.95 emissivity. Slip fit connection. GAS CONNECTION 1/2 Male pipe nipple. MOUNTING ANGLE 0 to 45 degrees from horizontal. MOUNTING HEIGHTS MIN. MAX. 50,000 BTU 10 15 60,000 BTU 11 18 75,000 BTU 12 20 100,000 BTU 13 23 125,000 BTU 15 25 150,000 BTU 16 30 175,000 BTU 17 35 WARRANTY 1 year-burner box components. 2 years-combustion and radiant tubes. 3 years-burner. OTHER One reflector center support per heater. Turbulator baffle provided. Made in USA. Visit www.reverberray.com 12