MV THOMSON MAJESTY Engine-room fire South of Gorgona Island 21 October 2016

Similar documents
WORLD CALIMA. Summary report on engine room fire

MAIB SAFETY BULLETIN 2/2010. Failure of fixed high expansion foam system to extinguish fire on board the passenger ferry Oscar Wilde

Report from the Division for Investigation of Maritime Accidents

FINAL REPORT AIRBUS A , REGISTRATION 9V-SKD SMOKE IN LAVATORY SINGAPORE CHANGI AIRPORT 31 JANUARY 2011 AIB/AAI/CAS.072

Engine room fire caused by failed fuel pipe

Fixed plant and mobile equipment fires on surface coal mines

Report on the investigation of. The machinery space fire on board. Oscar Wilde. In Falmouth Bay. 2 February 2010

Dealing with. engine room fires

Stena Clyde. Engine Room Fire 20 th October 2007

IMO DEVELOPMENT OF MODEL PROCEDURE FOR EXECUTING SHIPBOARD EMERGENCY MEASURES. Fire-fighting drills. Submitted by the Republic of Korea

South Australian Regulatory Requirements

Attachment 1. to ClassNK Technical Information No.TEC-0764 Malta Maritime Authority Date Revised 28 August 2008 Page 1 of 10 This Administration Requi

2010 FIRE CODE OF NEW YORK STATE

Government of Bermuda Department of Maritime Administration BERMUDA SHIPPING NOTICE

FIRE SAFETY POLICY. Approval Approved by: University Court Date: March 28 th 2017

BMA INFORMATION BULLETIN No. 97 FIRE FIGHTING EQUIPMENT

Interferry Ro Ro Deck Fire Safety Operational Best Practice Guidance

MSC Guidelines for General Emergency Alarm & Public Address Systems

Unit and Assessment Specification

1 Aviation English Vocabulary Level 4 to 5

Incident Summary (Reference # )

MB05. RESPOND TO EMERGENCIES BASIC KNOWLEDGE OF EMERGENCY PROCEDURES, INCLUDING EMERGENCY SHUTDOWN

STOCKTON POLICE DEPARTMENT GENERAL ORDER OPERATION OF EMERGENCY VEHICLE SUBJECT FROM: CHIEF ERIC JONES TO: ALL PERSONNEL

BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS

DISTRICT OF PORT HARDY BYLAW A BYLAW TO ESTABLISH AND REGULATE THE DISTRICT OF PORT HARDY FIRE DEPARTMENT

Hot Work Permit. Can this job be avoided? Is there a safer alternative? Permit No.:

AMADOR FIRE PROTECTION DISTRICT

FIRE SAFETY FOR OFFICE WORKERS

Fire Safety Guidelines

SCALES NW EMERGENCY ACTION PLAN

ClassNK Technical Information No. TEC-0453 Attachment (1) to ClassNK Technical Information No. TEC-0453 Guidance on SOLAS Chapter II-2 as amended in 2

Banff Mineral Springs Hospital EMERGENCY RESPONSE CODE RED Fire

161 Rosebery Avenue, London, EC1 Fire Safety Management Plan & Evacuation Procedures

Notice No. 7. Rules and Regulations for the Classification of Ships, July Issue date: March Working together for a safer world

THE REPUBLIC OF LIBERIA LIBERIA MARITIME AUTHORITY

Emergency procedures flowcharts

FIRE SAFETY MAINTENANCE INFORMATION for Agricultural Livestock Structures

RRC SAMPLE MATERIAL MANAGING FIRE SAFETY LEARNING OUTCOMES

Tampa, FL Fire Cause Classification Task Group Tue, 14 April 2011

Investigation Report

District of Sicamous. Fire Department Bylaw No. 126, Effective Date February 26, 1996

Crosswalk: Weight-Based Rating versus Performance-Based Rating

APPENDIX D Inspection Check List for Chartering Non-UNOLS Vessels

FIRE PREVENTION IN THE USE OF CUTTING OR WELDING PROCESSES

M.v. SEADREAM I. IMO Number Official Number

Human-centered Design of a Mooring Winch Control Panel DNV GL & IST

Ch. 569 FIRE AND SAFETY SERVICES 28 CHAPTER 569. FIRE AND SAFETY SERVICES GENERAL PROVISIONS INTERNAL DISASTER PLAN EVACUATION DRILLS

OFFSHORE SUPPORT VESSELS 2014

FIRE SAFETY POLICY LEEDS METHODIST MISSION. Oxford Place Centre

Securities Dealing Policy

FIRE SAFETY POLICY and FIRE SAFETY ARRANGMENTS

BYLAW 5542 *******************************************************************************

Standard Operating Procedure Ottawa Fire Services. Fire Operations- Structural Fire Incidents SUBJECT. Fire Alarm Systems (Silence/Reset) - Revised

Course Outline Cover Page

Fire outbreak inside a warehouse 5 December 2013 Crépy-En-Valois (Oise) France

2. How to trace out fault in an electrical circuit? Step 1 - Power Down

Only the Danish version is authentic Notice D II-2 N(2) 1 October 2002 CHAPTER II-2 N(2)

CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY

Fire Safety Guidelines

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

By: Svein Flogeland, DNV Head of section, classed units in operation. Presentation at NPD / Petrobras seminar, Stavanger

Order on fixed CO 2 fire-extinguishing systems 1

Emergency. Management. Emergency. Readiness Checklist

Fire Safety & Evacuation Procedures

CCTV, HOW DOES IT WORK?

COMMISSION REGULATION (EU)

Rambo CAST IRON RING BURNERS OPERATING INSTRUCTIONS. C40LP 3 Ring Burner C50LP 4 Ring Burner

LESSEE EMERGENCY RESPONSE PLAN AFAS Live

Patrick County Horizons Jeb Stuart Hwy. Stuart, Va

ACCIDENT REPORT. Dieppe Seaways. Report on the investigation of. a fire on board the RoPax ferry. on the approach to, and subsequently alongside,

INFORMATION BULLETIN No. 150

Technical Information

ClassNK Technical Information No. TEC-0838 (iii) The dormant period, visual indication, first stage audible alarm, second stage remote audible alarm a

Electrical Safety Policy and Management System

Technical Data Sheet BNWAS. Bridge Navigational Watch Alarm System. Technical Data Sheet. General Features

Implementing By-law and Decisions Related to Law No. (24) of 2008 Concerning Security Service Providers and Users 1

NOTTINGHAM CITY HOMES

COMDTPUB P NVIC Mar NAVIGATION AND VESSEL INSPECTION CIRCULAR NO Electronic Version for Distribution Via the World Wide Web

BY-LAW NO AND WHEREAS Council has, by By-law Number adopted a Forest Fire Management Plan for the Town of Bracebridge;

CIRCULAR LETTER. SUBJECT: PARIS MoU Harmonized Verification Programme (HAVEP) on passenger vessels.

To: All SAAS Accredited Certification Bodies Subject: Clarification to Emergency and Health & Safety Requirements in the SA8000 Standard

References: Patent Law (Article 2(3), Article 68, and Article 100) Reasons

Charter reference Conflicts between county and municipal ordinances, 2.01, 2.04.

Installation Manual September Opticom Infrared System. Model 798 Emitter Bezel Mount Kit

Sec False alarms.

MGN 453 (M) Maritime and Coastguard Agency Logo MARINE GUIDANCE NOTE

Fire Safety Policy. (The Regulatory Reform (Fire Safety) Order 2005) Last Reviewed: January Next Review: January 2019

Fired Heater Flooding

SERVICE VERSUS REMOVAL OF OBSOLETE COMMERCIAL KITCHEN PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

A) Floor training. Participant Performance Grading Criteria: C Very Poor B Poor A Needs Improvement. Verification of CAP. Overall Participants Grade

IMO. Resolution A.951(23) Adopted on 5 December 2003 (Agenda item 17) IMPROVED GUIDELINES FOR MARINE PORTABLE FIRE EXTINGUISHERS

Part 6 Additional class notations Chapter 6 Additional fire protection for passenger vessels

Health and Safety Documents in connection with offshore oil and gas operations

BYLAW NO Being a Bylaw of the Town of Rainbow Lake to provide for the Establishment and Operation of a Fire Department

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance

Ultrasonics Now & the Future

OXNARD FIRE DEPARTMENT Fire Watch Guidelines

MAINTENANCE AND INPSECTION OF FIRE PROTECTION SYSTEMS AND APPLIANCES

CLYST ST. MARY VILLAGE HALL

BY-LAW NUMBER OF THE CORPORATION OF THE CITY OF STRATFORD

Transcription:

Marine Safety Investigation Unit SIMPLIFIED SAFETY INVESTIGATION REPORT REPORT NO.: 22/2017 October 2017 The Merchant Shipping (Accident and Incident Safety Investigation) Regulations, 2011 prescribe that the sole objective of marine safety investigations carried out in accordance with the regulations, including analysis, conclusions, and recommendations, which either result from them or are part of the process thereof, shall be the prevention of future marine accidents and incidents through the ascertainment of causes, contributing factors and circumstances. Moreover, it is not the purpose of marine safety investigations carried out in accordance with these regulations to apportion blame or determine civil and criminal liabilities. NOTE This report is not written with litigation in mind and pursuant to Regulation 13(7) of the Merchant Shipping (Accident and Incident Safety Investigation) Regulations, 2011, shall be inadmissible in any judicial proceedings whose purpose or one of whose purposes is to attribute or apportion liability or blame, unless, under prescribed conditions, a Court determines otherwise. The report may therefore be misleading if used for purposes other than the promulgation of safety lessons. Copyright TM, 2017. This document/publication (excluding the logos) may be re-used free of charge in any format or medium for education purposes. It may be only reused accurately and not in a misleading context. The material must be acknowledged as TM copyright. The document/publication shall be cited and properly referenced. Where the MSIU would have identified any third party copyright, permission must be obtained from the copyright holders concerned. Course of events Thomson Majesty was enroute to Calvi, France from Livorno, Italy with 1478 passengers and 579 crew members. On the day of the departure, at about 2115, the duty engineer was in the control room. Soon after, the engineering officer of the watch (OOW) returned to the control room and briefed the duty engineer on the status of the main and auxiliary engines. Minutes later, the OOW looked towards the CCTV monitors and observed smoke and flames from auxiliary engine no. 4 (Figure 1). The auxiliary engine was immediately stopped by pressing the emergency stop button, the circuit breakers for the preferential tripping were opened, and the alarm raised. The watertight doors were closed and the oiler, who was in the engine-room at the time, grabbed a fire extinguisher to MV THOMSON MAJESTY Engine-room fire South of Gorgona Island 21 October 2016 Figure 1: The start of the fire captured on CCTV fight the fire. In the meantime, the chief engineer, who was in the officer s messroom, heard a loud noise in the alleyway. Upon enquiring, he walked out of the messroom and noticed smoke in the alleyway. He was also informed of a fire in the engine-room. MV Thomson Majesty 1

The chief engineer rushed to the engineroom, where he observed that auxiliary engine no. 4 had been stopped whereas the three other auxiliary engines were still running. Taking stock of the situation, the chief engineer informed the master of the fire and status of the engine-room. shut down automatically due to the activation of the fresh water high temperature alarm at about 2200. The situation was, however, alleviated with the automatic starting of the emergency generator. The chief engineer requested that the fuel oil feed and booster pumps for auxiliary engine no. 4 1 and the ventilation fans are stopped, and fire flaps closed. In the meantime, within 19 seconds, the fire had become more intense, the smoke was more dense and visibility was significantly reduced (Figure 2). Figure 2: The extent of the fire and smoke density 19 seconds after the fire started The engine-room fire squad had also assembled under the supervision of the chief engineer. Within a few minutes of the assembly of the fire squad, the fire was brought under control and extinguished with the use of portable fire extinguishers. Due to the fire, the rubber bellows fitted on the cooling water line in way of auxiliary engine no. 4 was damaged and leaked heavily (Figure 3). Consequently, before the crew members could identify and rectify the problem, the cooling water expansions tanks leaked dry and the running auxiliary engines 1 Stopping the two pumps for auxiliary engine no. 4 caused a fuel oil starvation on auxiliary engine no. 3 because both engines share the same pumps. Figure 3: Damaged rubber bellows Subsequently, the damaged bellows was replaced, the system replenished, and purged from air. Power was restored at about 0200 on 22 October 2016 and the vessel returned to Livorno with two auxiliary engines and two main engines running. No injuries had been reported. Extent of damage The damages were contained within the proximity of auxiliary engine no. 4. Electrical cables routed above the auxiliary engine and other control cables had to be cleaned and replaced where necessary (Figure 4). MV Thomson Majesty 2

Figure 5: Damaged O-ring Figure 4: Damaged control cables The engine-room in general had visible soot damage and a number of light fixtures had evident heat damage. Cause of the fire 2 The engineers had carried out maintenance on the auxiliary engine on the day of the fire. Maintenance records indicated that the main fuel oil supply and return lines had been dismantled and replaced with new pipes. The fuel lines were fitted in close proximity of the fire seat and therefore the initial inspection of the crew members was directed towards that area. When the fuel oil return pipe was disconnected from the high pressure pump on unit no. 6, it was observed that the O-ring was damaged (Figure 5). The pipe was located very close to the turbocharger and the aft exhaust gas manifold. It was therefore confirmed that the fuel oil leak had originated from the fuel oil return pipe because of the damaged O-ring. 2 The purpose of a marine safety investigation is to determine the circumstances and safety factors of the accident as a basis for making recommendations, and to prevent further marine casualties and incidents from occurring in the future. It was also noticed that there were no records to confirm whether the O-Ring had been renewed before the system was boxed up again earlier during the day of the fire. Whereas it was not excluded that the (old) O-ring s physical and chemical characteristics had changed, it was also very possible that the O-ring got displaced before it was fitted and was permanently damaged when the flange was tightened. Consequently, there was no tight seal and eventually, fuel oil under pressure leaked from between the flanges and the spray. It was therefore evident that the system was either not tested after the repair job was completed or else, if tested, no leaks were detected. Fuel oil alarms Although the entire arrangement was fitted inside a hot box which is designed to contain fuel oil leakages, the hot box did not seal tight, with a side opening on the turbocharger side. The alarm fitted inside the hot box, which should have triggered because of the fuel oil leak did not activate. However, a few minutes before the fire started, there was a low pressure alarm recorded (followed by an exhaust gas temperature alarm) which, however, either did not raise any particular concerns or went unnoticed. MV Thomson Majesty 3

SAFETY ACTIONS TAKEN DURING THE COURSE OF THE SAFETY INVESTIGATION 3 During the course of the safety investigation, the Company issued a Fleet Circular, outlining the following: 1. Crew members assigned to the engine-room must be alert on and prepared for risks associated with hot spots. This is in light of statistical studies released by DNV GL, whereby it is indicated that more than 60% of all engine-room fires have been initiated by a hot spot, and oil coming in contact with hot spots will generally result in one of the fiercest fires; 2. Crew members shall ensure that exhaust lagging or heat shields are properly replaced / renewed after completion of any work on the main or auxiliary engines; 3. The importance of identifying fire hazards and taking measures to eliminate fuel leaks. Regular inspection of oil fuel and lubricating oil pipes and associated fitting should be carried out and fuel leak sources rectified immediately; 4. Fuel oil leak / drain lines from the hot box to the leakage tanks are properly maintained to avoid blockages. Leakage alarm systems should be tested regularly; 5. Routine maintenance, inspections and testing of fire-fighting equipment, including drills and exercises for enhancing crew training in their use, should be carried out effectively; 6. The importance to spend some time to critically review procedures and practices to determine what can go wrong (risk assessment); 7. The importance for crew members to be aware of the location of the ventilation system fire dampers and shutdown devices/remote stops; 8. The importance for the ship s engineer to be aware of the location of the water-mist system and its operation; 9. The importance of not ignoring the alarm system, which may otherwise prevent timely actions; 10. The critical importance of following up an updated PMS/AMOS system; 11. The chief staff engineer shall supervise the repair and maintenance of critical systems and ensure that checks are carried out following routine maintenance or repair works; 12. Reference is to be made to the results of the thermographic inspection, which has been carried out on all the main and auxiliary engines on board Thomson Majesty and another ship under the Company s management. Moreover, the Company has: 13. contacted the maker (Wärtsilä) to assist with technical issues and to provide a technical advice on hot box design and possible upgrades; and 14. organised courses for fire fighting and fire safety/risk assessment during winter layup for all crew members. 3 Safety actions should not create a presumption of blame and / or liability. MV Thomson Majesty 4

` SHIP PARTICULARS Vessel Name: Thomson Majesty Flag: Malta Classification Society: DNV GL IMO Number: 8814744 Type: Passenger Registered Owner: Majesty Trading OPCO LLC Managers: Optimum Shipmanagement Service S. A. Construction: Steel Length Overall: 207.1 m Registered Length: 191.4 m Gross Tonnage: 41662 Minimum Safe Manning: 20 Authorised Cargo: Not Applicable VOYAGE PARTICULARS Port of Departure: Livorno, Italy Port of Arrival: Calvi, France Type of Voyage: Short International Cargo Information: Not Applicable Manning: 1478 MARINE OCCURRENCE INFORMATION Date and Time: 21 October 2016 at 21:28 Classification of Occurrence: Location of Occurrence: Place on Board Injuries / Fatalities: Damage / Environmental Impact: Ship Operation: Voyage Segment: External & Internal Environment: Less Serious Marine Casualty 43 17.04 N 009 54.18 E Engine-room None reported Localised damages to electrical and control cables, soot damage, and damages to various light fixtures. In passage Transit Persons on board: 2057 Clear weather and good visibility. The sea was calm with a variable light breeze. Air temperature was 18 C. MV Thomson Majesty 5