Research on Fault Detection and Diagnosis of Scrolling Chiller with ANN 1

Similar documents
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING

Experimental Investigate on the Performance of High Temperature Heat Pump Using Scroll Compressor

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

STUDY ON THE CONTROL ALGORITHM OF THE HEAT PUMP SYSTEM FOR LOAD CHANGE

Virtual Refrigerant Pressure Sensors for Use in Monitoring and Fault Diagnosis of Vapor- Compression Equipment

HVAC Water chiller selection and optimisation of operation

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Clemens Felsmann 1, Jean Lebrun 2, Vincent Lemort 2 and Aad Wijsman 3 ABSTRACT INTRODUCTION METHODOLOGY

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Reducing energy consumption of airconditioning systems in moderate climates by applying indirect evaporative cooling

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Workshop on AFDD for RTUs Moving from R&D to Commercialization July 13, Introduction

Application of the VRV Air-Conditioning System Heat Recovery Series in. Interior Zone and Analysis of its Energy Saving

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Experimental Research of Air Source Heat Pump Frosting and Defrosting in a. Double Stage-Coupling Heat Pump

How to Cut Chiller Energy Costs by 30%

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Best Row Number Ratio Study of Surface Air Coolers for Segmented Handling Air-conditioning System

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

PRESSURE-ENTHALPY CHARTS AND THEIR USE By: Dr. Ralph C. Downing E.I. du Pont de Nemours & Co., Inc. Freon Products Division

Shortcut Model for Predicting Refrigeration Cycle Performance

Performance of the Variable Refrigerant Volume Air-Conditioning System. with Heat Recovery

A New Dedicated Outdoor Air System with Exhaust Air heat recovery

Performance Evaluation of Eco- Friendly Alternate Refrigerants for VCRS

Public Services Building 155 N First Avenue Hillsboro, OR March 2012

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Electronic Expansion Valves Vs. Thermal Expansion Valves

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Improving and Comparing the Coefficient of Performance of Domestic Refgirator by using Refrigerants R134a and R600a

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

GSJ: VOLUME 6, ISSUE 6, JUNE GSJ: Volume 6, Issue 6, June 2018, Online: ISSN

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Research Article / Araştırma Makalesi EXPERIMENTAL INVESTIGATION OF R600A REFRIGERANT FLOW INSIDE ADIABATIC CAPILLARY TUBE

Partial Load Performance Of Refrigeration System

Experimental Evaluation of a Gas Engine Driven Heat Pump Incorporated with Heat Recovery Subsystems for Water Heating Applications

Dynamic Models of a Home Refrigerator

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

COMPACT HEAT EXCHANGERS FOR MOBILE CO 2 SYSTEMS

Final Report. Prepared for. Albany, NY. Robert M. Carver, P.E. Senior Project Manager. Prepared by. Ithaca, NY

Techniques of Heat Transfer Enhancement and their Application. Chapter 4. Performance Evaluation Criteria for Two-Phase Heat Exchangers

Feasibility of a Liquid Desiccant Application in an Evaporative. Cooling Assisted 100% Outdoor Air System

Available online at ScienceDirect. Procedia Engineering 121 (2015 )

2. CURRICULUM. Sl. No.

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

Chapter 4 Compressors Overview & System Annual Power Consumption

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

Manual Of York Chiller

Development of Bionic Air Cooler Used in High Temperature Coal Mine

Performance of an Improved Household Refrigerator/Freezer

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Experimental Study on Performance Parameters for Refrigerants R22, R410a and R404a at Various Air Outlet Temperatures

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Measurement and modelling of a multifunctional solar plus heatpump system from Nilan. Experiences from one year of test operation.

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Efficiency of Non-Azeotropic Refrigerant Cycle

A WET-VAPOUR INJECTION AND VARIABLE SPEED SCROLL COMPRESSOR AIR TO WATER HEAT PUMP MODEL AND ITS FIELD TEST VALIDATION

INFLUENCE OF DIFFERENT TEMPERING PERIOD AND VACUUM CONDITIONS ON THE RICE GRAIN BREAKAGE IN A THIN LAYER DRYER

Energy Efficiency Through Waste Heat Recovery. Heat Recovery Centrifugal Chillers and Templifier Water Heaters

A Statistical Analysis of a Liquid Desiccant Dehumidifier/Regenerator in an Air Conditioning System

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

solution, due to the partial vapor pressure difference between the air and the desiccant solution. Then, the moisture from the diluted solution is rem

BASE LEVEL AUDIT REQUIREMENTS REFRIGERATION SYSTEMS 1. SITE DATA COLLECTION. Business Name. Site physical address (Street, Suburb, City)

Analysis of the Design of an HVAC System in a Public Building

PRACTICAL EXPERIENCE WITH AN ALTERNATIVE TO R-22 BASED ON R-32lR /R a. R E Low, B E Gilbert, T W Dekleva.

seasons in regions with hot, humid climates. For this reason, a dehumidification system with a radiant panel system needs to be developed. In a former

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

The Refrigeration Cycle. Jerry Cohen President Jacco & Assoc.

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Available online at ScienceDirect. Energy Procedia 52 (2014 ) Vishal Vadabhat, Rangan Banerjee

An Experimental Study on Clothes Drying Using Waste Heat from Split Type Air Conditioner

Dynamic Simulation of Liquid Chillers

(ME-225) HEATING, VENTILATION AND AIR-CONDITIONING SYSTEM

EFFECT OF COMPACTION ON THE UNSATURATED SHEAR STRENGTH OF A COMPACTED TILL

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Open Access Operation Modes and Energy Analysis of a New Ice-Storage Air- Conditioning System

Technical Note. EHPA Quality Label Model Range Definition Version

WASTE HEAT RECOVERY FROM DOMESTIC REFRIGERATOR Soma A. Biswas 1, Sandeep M. Joshi 2 1,2 Pillai College of Engineering

Numerical Simulation of Window Air Conditioner

FABRICATION OF REFRIGERANT FLOW RATE WITH SPIRALLY COILED CAPILLARY TUBE

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

η second law = Second law efficiency

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Heat Transfer Analysis of Vapor Compression System Using Nano Cuo-R134a

Transcription:

Research on Fault Detection and Diagnosis of Scrolling Chiller with ANN 1 Yuli ZHOU Jie ZHENG Zhiju LIU Chaojie YANG Peng PENG Faculty of Urban Construction and Environmental Engineering, Chongqing University Chongqing 45, China E-mail: jiezheng999@yahoo.com.cn Abstract: At first the basic research about FDD is summarized, and a detection model based on ANN is initially set up. The paper presents experiments that simulate seven faults, including change flow rate of chilled water, cooling water and refrigerant, charge non-condense gas, shift cooling water and alter outside cold load. A set of characteristic parameters are defined in order to differentiate these faults and clarify the reasons. Finally, an FDD tool is programmed based on ANN with experimental results which form a training stylebook and test stylebook. Keywords: Water Cooling Chiller of Screw Fault Diagnose Artificial Neural Network 1 INTRODUCTION Artificial neural network based on the knowledge of neural network of human brain is to artificially form neural networks to implement some functions. It has powerful functions to store and process information. It is widely used in the fields of control and mode identifying. This paper is for the purpose of using artificial neural network to diagnose the faults ly happening in the HVAC systems and does some researches on the fault diagnosis of screw chiller. the refrigerant flow. 3 EXPERIMENT PRECEPETS AND DEVICES 3.1 Experiment Disposal Precept According to the theoretic analysis, interior parameters are chosen as the feature parameters [3]. cool i ng water si de refri gerant side chilled water si de q1(t. G) q2(t) condenser j4(t) j3(t) expansi on val ve compressor j5(t) evaporator d2(t) d1(t. G) j2(p) j1(p. T) Fig.1 The measuring position and parameters In the figure:q cooling water side; d chilled water side; j refrigerant; P pressure side; T point for temperature measuring; G point for flux measuring In order to understand the actual operating situation of the units, several necessary physical points are set for measuring. 2 DETECTION MECHANISM The refrigerating cycle of screw chiller is consisted of four thermodynamic cycles which are compression, heat discharging, throttling and heat absorbing. the change of one or some of the parameters will lead to the changes of many other parameters [2] The 8 faults simulated in this paper are that the cooling water flow or, chilled water flow or, non-condensable gas is added in, cooling load, the inlet water the condenser is over high and 3.2 Experiment Devices There are a single-screw chiller and a chilled water pump, a cooling water pump, two electrostatic precipitators, a water separator and a water collector in the refrigeration machinery room. The temperature conditions of chiller rating running situation: chilled water inlet temperature is 12, extracted temperature is 7; cooling water inlet temperature is 32. The performance parameters of two pumps are: Lift: 32m water column; Rated flow: m 3 /h; Power supply: 3Φ-3V-Hz;Input power: 15kW. 1 Issued by Chongqing University primary teachers program

4 RESULTS ANALYSIS 4.1 The cooling water flux. As figure 2 shown: considering the errors, the evaporating temperature and the compressor suction temperature do not change as the cooling water flux changes; the condensing temperature, the compressor discharge temperature and the sub-cooling degree of refrigerant increase as the cooling water flux. The principle for predicting this fault is 9 cooling water flux decrease.2 47.2 45 35.1 29.9 25.4 22.1 19.7 cooling water flux(m 3 /h) inlet temperature of condenser outlet condenser evaporate temperature Fig.2 The curve of the system parameter with decreasing flux of cooling water T1-4.2.3 Evaporating temperature keeps T 2-42.>.3 Condensing temperature TJ1-9..3 Compressor suction temperature keeps T J2-78>.3 Compressor discharge temperature Δ T J -5.>.3 Sub-cooling Degree of refrigerant Attention: all of the units in the 3.1 to 3.9 are 4.2 The cooling water flux The experiment results are shown as figure 3. It can be considered as the evaporating temperature does not change when the cooling water flux changes. The principle for predicting this fault is T 1-4.2.3 Evaporating temperature keeps T 2-42. < -.3 Condensing temperature T J1-9..3 compressor suction temperature keep T J2-78 < -.3 Compressor discharge temperature ΔT J -5.< -.3 Sub-cooling degree refrigerant. 55 65 71 75 85 95 flux(m 3 /h) condenser inlet condenser outlet inlet chilled outlet chilled Fig 3 The curve of the system parameter with increasing flux of cooling water 4.3 Chilled water flux As we can see from figure 4, when the chilled water flux, the power of compressor, the parameters of cooling water almost keep, evaporating temperature, condensing temperature almost keeps, compressor suction temperature. The principles for predicting this fault are T1-4.2 >.3 evaporating temperature T2-42..3 condensing temperature keep TJ1-9.>.3 compressor suction temperature TJ2-78.3 compressor discharge temperature keeps ΔT J -5.>.3 sub-cooling degree of refrigerant

9 45 55 68 flux(m 3 /h) condenser inlet condenser outlet inlet chilled outlet chilled Fig 4 The curve of the system parameter with increasing flux of chilled water 4.4 chilled water flux According to the changes of perimeters the principles for predicting this fault are shown as following: T1-4.2 < -.3 evaporating temperature T2-42..3 condensing temperature keeps TJ1-9. <-.3 compressor suction temperature TJ2-78.3 compressor discharge temperature keeps ΔTJ-5.< -.3 sub-cooling degree of refrigerant 4.5 Adding in non-condensable gas The principle for predicting this fault is shown as follows: T 1-4.2>.3 evaporating temperature T 2-42.>.3 condensing temperature T J1-9.>.3 compressor suction temperature T J2-78>.3 compressor discharge temperature ΔT J -5.>.3 sub-cooling degree of refrigerant 4.6 Exterior cooling load According to the changes of perimeters, the principles for predicting this fault are shown as following: T1-4.2 < -.3 evaporating temperature T2-42.< -.3 condensing temperature TJ1-9.< -.3 compressor suction temperature TJ2-78.3 compressor discharge temperature keeps ΔTJ-5..3 sub-cooling degree of refrigerant keeps. 4.7 The inlet water temperature is over high According to the changes the principles for predicting this fault are shown as following: T1-4.2 >.3 evaporating temperature T2-42. >.3 condensing temperature TJ1-9. < -.3 compressor suction temperature TJ2-78>.3 compressor discharge temperature Δ TJ-5.>.3 sub-cooling degree of refrigerant 4.8 Refrigerant flux The principles for predicting this fault are shown as following: T 1-4.2 < -.3 evaporating temperature T 2-42.<-.3 condensing temperature T J1-9.>.3 compressor suction temperature T J2-78>.3compressor discharge temperature ΔT J -5.>.3 sub-cooling degree of refrigerant 5 THE APPLICATION OF ARTIFICIAL OF ARTIFICAL NEURAL NETWORK ON THE FAULT DIAGNOSIS OF SCRWE CHILLER 5.1 Artificial neural network has integrated many advantages of the biology neural network and has some inherent characteristics: Able to work on two or more tasks at one time;highly nonlinear overall function;able to memorize and correct error and associate thoughts;be able to adapt and learn by self 5.2 The model of artificial neural network on the fault diagnosis of screw chiller, see figure 5.

Arithmetic and aim of learning Model for Selection Latent fault of training layer Diagnosis samples Training times Fig. 5 Establishment of faults diagnosis model 5.3 Prediction example According to the network trained previously, the program of faults diagnosis can be obtained. Inputting the data collected from the chiller when it is operating, see table 1 and table 2. Tab.1 experimental validation 输入 Fault Type 13.1,8.2,34.1,39.2,16.44, 5.38,78.8,36.6,8.8, 78.1, 4.7 12.7,7.7,.8,36.2,5.3, 14.6, 75.7, 33.9, 8.5,4.6, 4.4 12.4,7.5,33.4,38.3,15.66, 5.66,78.1,36.,8.4,77.6,4.4.8,6.3, 33.6,38.4, non-condensable 16.15,5.,78.5,36.,6.4,77.9, gas 4.3 12.3,7.6,33.9,38.8,16.35, non-condensable 5.,78.7,36.3,8.3,78.1,4.5 gas 12.7,7.9,32.8,37.6,17.71, Cooling water 5.34,81.7,35.3,7.6,79.9,4.7 flux over small 12.9,8.3,32.7,37.6,.55, Cooling water 5.53,95.3,37.,.3,93.5, 4. flux over small Tab.2 comparison between output of network and experiment results Experiment Output of network results.81,.1,.6,.2256,.1,.358,.492,.447,.492,-.447.41,.36,.36,.645,.1314,.592,.645,.394,.645,.394.197,.1527,.497,.1946,.581,.18,.661,.88,.661,.88.7,.999,.31,.248,.348,.124,.1, 1.265,.1,.265.1,.9966,.372,.481,.1,.939,.8, 1.97,.8,.97.485,.1916,.9179,.159,.629,.231,.721, 1.1625,.721,.1625.2,.243,.9966,.4,.121,.67.1134,.221, 1.1134,.221 If the output is bigger than.9, the type of fault can be predicted. The performance of network needs to be tested by large amount of samples. In this paper, the network has been tested by the data obtained from faults experiments and it is proved that the performance of the network is good. When it is operating, the parameters of chiller are listed as follow: According to the table, the output of the network is close to the experiments. The conditions for predicting the fault have been met. 6 CONCLUSIONS This paper specifically analyzed the factors which can influence the performance of chiller, at the same time, attained how various faults influence the characteristic parameters and the performance of chiller via experiment method. This paper researched the faults diagnosis of screw chiller through the method of artificial neural works, and exactly predicts the happening of chiller faults. REFERENCES [1] Henk C.Peitsman.Vincent E.Bakker. Application of Black-Box Model to HVAC Systems for Fault Detection. ASHARE Transactions 2.1996().628-6

[2] Meli Stylianou.Darius Nikanpour. Performance monitoring. Fault detection. and diagnosis of Reciprocating Chillers. ASHARE Transactions.2.1996(). 615-627 [3] Tuo LIU, Jie ZHENG, Yuli ZHOU.HVAC The Analysis Of Fault Characteristics And The Establishment Of Diagnosis System Journal of Guizhou Industry University 3.Vol.32.add.175-178 [4] Srinivas Katipamula, PhD Michael R. Brambley, PhD Methods for Fault Detection, Diagnostics, and Prognostics for Building Systems HVAC&R RESEARCH VOLUME 11, NUMBER 1 JANUARY 5 [5] Andersen, K.K., and T.A. Reddy, 2. The error in variables (EIV) regression approach as a means ofidentifying unbiased physical parameter estimates: Application to chiller performance data. International Journal of Heating, Ventilating, Air Conditioning and Refrigerating Research 8(3):295-9.