Product Data TCC3018A through 4TCC3060A Single Packaged Convertible Cooling 13 SEER 1½ - 5 Ton R-410A 07/08

Similar documents
SEER 1½

Product Data TCC3018A through 4TCC3060A Single Package Convertible Cooling 13 SEER 1½ - 5 Ton R-410A. Mar. 03, 2006

Product Data. 4WCY4024A through 4WCY4060A Single Packaged Convertible Heat Pump 14 SEER 2-5 Ton R-410A Trane Pub. No.

Product Data. 4TCY4024 through 4TCY4060 Single Packaged Convertible Cooling 14 SEER 2-5 Ton R-410A Trane Pub. No.

Product Data WCZ6036B through 4WCZ6060B Single Packaged Convertible Heat Pump 16 SEER 3, 4 & 5 Ton R-410A

PRODUCT SPECIFICATIONS 2YCC3036A1096A /1/ /

Product Data. Single Packaged Heat Pump 14 SEER Convertible, 2 5 Ton B-EN. December 2014

4YCC3048A3096A /3/ /

2YCC3060A1120A /1/ / YCC3060A1096A /1/ /

Product Data /4WCC3018A through 2/4WCC3060A Single Package Convertible Heat Pump 13 SEER 1½ - 5 Ton R-22/R-410A

PRODUCT SPECIFICATIONS 2YCC3048A1120A /1/ /

SPECIFICATIONS 4YCC3060A-SPEC-1A SINGLE PACKAGED GAS HEATING ELECTRIC COOLING 4YCC3060A1096/120B TAG:

4YCC3036A1075B /1/ / YCC3036A1064B /1/ /

Product Data WCC3018 through 4WCC3060 Single Packaged Convertible Heat Pump 13 SEER 1½ - 5 Ton R-410A 02/12

Product Data DCZ6036A through 4DCZ6060A Single Packaged Convertible Dual Fuel 16 SEER 3, 4 & 5 Ton, KBTU R-410A

Submittal. Single Packaged Heat Pump 15 SEER Convertible 4WCY5024A-SUB-1A-EN. March WCY5024A1000A TAG:

Product Data EN. 4DCY4024 through 4DCY4060 Packaged Convertible Dual Fuel 14 SEER 2-5 Ton, MBTU R-410A

Product Data YCZ6036A through 4YCZ6060A Single Packaged Convertible Gas/Electric 16 SEER 3, 4 & 5 Ton, MBTU R-410A

Product Data DCZ6036A through 4DCZ6060A Single Packaged Convertible Dual Fuel 16 SEER 3, 4 & 5 Ton, MBTU R-410A

Submittal. Single Packaged Convertible Gas/Electric 14 SEER 4YCC4024A-SUB-1F-EN. August YCC4024A1060A TAG:

PAJ3. Product Specifications

PAR5. Product Specifications

High Heat COP. High/Low Stage

Split System Cooling Product & Performance Data

UP to 14.5 SEER, PACKAGE AIR CONDITIONER UNIT, 2 to 5 TONS 208/230 Volt, 1 phase, 60 Hz REFRIGERATION CIRCUIT

Rooftop Units 60HZ. PACKAGED HEAT PUMPS 13HPP / rhp13 PRODUCT SPECIFICATIONS 13 HPP 36 A P - 1 A RHP 13 A 36 T - 1 A MODEL NUMBER IDENTIFICATION

Modular Multi-position Air Handler

SPLIT SYSTEM HEAT PUMP 1½ 5 TON HERITAGE 13 MODELS 2A6H A American Standard Heating & Air Conditioning

Multi-position, Upflow, Horizontal Left, or Horizontal Right, Modular Air Handlers

Split System Cooling Product & Performance Data

15 SEER, PACKAGE AIR CONDITIONING UNITS, 2-5 TONS Single Phase, 208/230 V, 60 Hz COOLING

RGE 13 A T - 1 A

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

Split System Cooling Product Data

SPLIT SYSTEM COOLING 1½ 5 TON ALLEGIANCE 14 MODELS 4A7A C/30-060B American Standard Heating & Air Conditioning

FLD = Furnished by Trane U.S. Inc. / Installed by Equipment Submittal Page 3 of 13

Split System Heat Pump Product & Performance Data

50TM TFF COMBINATION HEATING/COOLING UNITS

Cooling/Heat Pump Convertible Air Handlers

Submittal. Split System Cooling 5.0 Ton 4A7A3060D1000P TAG:

Cooling/Heat Pump Convertible Air Handlers

50TM COMBINATION HEATING/COOLING UNITS

Split System Cooling Product Data

Advance Release September 2009

Split System Cooling Product Data

Product Data. Fig. 1 - Unit 50VR -A

15 SEER SINGLE- PACKAGED HEAT PUMP SYSTEM WITH PURON

DSV Model Air Cooled Self Contained Indoor Packaged Units 3-5 Tons Preliminary Application Data

50HS018, 024, 030, 036, 042, 048 & 060 STANDARD-EFFICIENCY COMBINATION HEAT PUMP UNITS W/OPTIONAL ELECTRIC HEAT

Split System Heat Pump Product Data

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

Submittal. Split System Cooling 4A7A6024J-SUB-1B-EN. January A7A6024J1000B TAG:

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

Vertical Upflow Horizontal Left Air Handlers

Split System Cooling Product Data

48GS(N) STANDARD EFFICIENCY 48GX(N) HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING ELECTRIC COOLING UNITS

Split System Cooling Product Data XB 1000

Product Data. 50ZPB Single---Packaged Air Conditioner System With R---410A Refrigerant Single Phase 2 to 5 Nominal Tons (Sizes )

7/8 NO NO NO PROPELLER DIRECT / /230/1/ SPINE FIN /8 8 LBS., 0 OZ. YES 7/8 3/8

WPH4 Product Specifications

Hyperion TM Split Systems

WJH4 Product Specifications

Product Data PA3Z- B SINGLE- PACKAGED AIR CONDITIONER SYSTEM WITH R- 410A REFRIGERANT SINGLE PHASE 2 TO 5 NOMINAL TONS (SIZES )

Submittal. 1 1/2 Ton Convertible Air Handler TEM3A0B18S21SA TEM3A0B18-SUB-1C-EN. July 2014 TAG:

Submittal. 2 Ton Convertible Air Handler TEM3A0B24S21SA TEM3A0B24-SUB-1C-EN. July 2014 TAG:

Submittal Data PERFORMANCE DATA CERTIFIED DIMENSION PRINTS CERTIFIED ROOF CURB DIMENSION PRINTS SERVICE OPTION DIMENSION PRINTS

Split System Cooling Product Data

Product Data. Split System Cooling A. November 2013

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTB6-SF-3. Split System Cooling 4TTB6048A1000A, 4TTB6049A1000A CAUTION

Product catalog. Hyperion TM split systems 60 Hz / R410A / 13 SEER SSA-PRC009-E4

Submittal. 5 Ton Convertible Air Handler TEM3A0C60S51SA TEM3A0C60-SUB-1C-EN. July 2014 TAG:

Commercial High-Efficiency Condensing Units

208/230/1/ CLIMATUFF /230/1/ YES NO NO PROPELLER 23-1 DIRECT / /230/1/ SPINE FIN

Product Data. PA4Z SINGLE -PACKAGED AIR CONDITIONER SYSTEM WITH PURONr (R -410A) REFRIGERANT SINGLE PAHSE 2 TO 5 NOMINAL TONS (SIZES )

Cooling/Heat Pump Convertible Air Handlers

Product Data. 50JS Single-Packaged Heat Pump Units. 1 1/2 to 5 Nominal Tons

P8SE Series. 14 SEER, Single Phase Packaged Air Conditioner TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 3, 4, 5 Ton Units

48GS HIGH-EFFICIENCY SINGLE-PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTR6024-SF-1B. Split System Cooling 4TTR6024A1000B CAUTION CAUTION WARNING

PACKAGE AIR CONDITIONER

13 GEP A L P - 1 A

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: AC036X10(3,4) THRU 060 (3 THRU 5 NOMINAL TONS, 3 PH) DESCRIPTION

Split System Cooling Product Data

4TTR6036B1000A 208/230/1/ CLIMATUFF - SCROLL 3/4 3/4 3/4 3/4 3/4 208/230/1/ NO YES NO PROPELLER DIRECT

Model 655A Sizes

Service Facts. WARNING: HAZARDOUS VOLTAGE - DISCONNECT POWER and DISCHARGE 4TTR6048-SF-1A. Split System Cooling 4TTR6048A1000A CAUTION CAUTION WARNING

DCC Series. Submittal Data Form 15- & 20-TON, THREE-PHASE PACKAGED AIR CONDITIONERS UP TO 11 EER

TECHNICAL GUIDE LISTED. SPLIT-SYSTEM AIR CONDITIONERS 10 SEER R22 60Hz MODELS: H*BA-(T,W)036 THRU 076 (3 THRU 6.3 NOMINAL TONS, 3 PH) DESCRIPTION

Ameristar SUBMITTAL M4AH4E26B1A00AA. 2.0 Ton Multi-position Air Handler M4AH4E26B1A00AA TAG:

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

EER PACKAGE AIR CONDITIONER, 6.9 to 14.4 kw, 2 4 TONS 3 Phase, Standard CFM / Ls EER

Product Data. 50EES--ZP (50Hz) Single Package Air Conditioners 3-5 Nominal Tons

Weathermaster Series 48HJ004, 005, 006, 007, 008, 009, 012 & 014 COMBINATION GAS HEATING/ ELECTRIC COOLING UNITS

Product Data. Split System Heat Pump B-EN. February A6H6024H1000A

1-1/2 THRU 2-1/2 TONS SPLIT SYSTEM FWM Series

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

36,000-62,000 BTUH Nominal Capacity

AMERICAN STANDARD 14 MODELS 4A7B E

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

SKYPAK II, 3 Ton Series, gives you a

Transcription:

Product Data 22-1782-05 4TCC3018A through 4TCC3060A Single Packaged Convertible Cooling 13 SEER 1½ - 5 Ton R-410A 2008 Trane Pub. No. 22-1782-05 07/08

Single Packaged Cooling System Trane offers a complete family of cooling systems, designed to give you the unbeatable combination of energy efficiency and lower operating costs. Introducing the new TRANE Single Packaged Cooling System. Single Packaged Cooling Systems are easy and versatile to install. Because cooling and air handling functions are all contained in a single cabinet, a Trane packaged air conditioner is easy to install and service. It can be flush mounted beside your home at ground level or placed on the roof for horizontal or downflow installation. When connected to an optional Trane thermostat control and air distribution ducts, you have a highly efficient, total home comfort system. Single Packaged Cooling Systems provide better performance. All major components on these products, including the compressor, have been designed and manufactured for maximum service. Every Climatuff compressor is designed and manufactured to exacting specifications. Each design is life tested in extreme environments to ensure reliable and long lasting operation in normal applications. Each compressor has internal motor protection for added reliability. 2

Contents Optional Equipment Listing 4 General Data 5 Heater Data 8 SPEK Data 9 Performance Cooling Data 12 Typical Wiring 19 Optional Equipment 22 Dimensional Data 27 Mechanical Specifications 33 3

Optional Equipment Listing OPTIONAL EQUIPMENT FOR PACKAGED UNITS (check mark [ ] indicates accessories included) Hinged Filter Access Door (4TCC3018-36A) 3... BAYACCDOR1A[ ] Hinged Filter Access Door (4TCC3042-60A) 3... BAYACCDOR2A[ ] Roof Curb Full Perimeter (4TCC3018-36A) 3... BAYCURB050A[ ] Roof Curb Full Perimeter (4TCC3042-60A) 3... BAYCURB051A[ ] Roof Curb Utility Extension Kit (BAYCURB050A)... BAYUTIL101A[ ] Roof Curb Utility Extension Kit (BAYCURB051A)... BAYUTIL102A[ ] 0-25% Manual Fresh Air Damper (4TCC3018-36A) 1.... BAYOSAH001A[ ] 0-25% Manual Fresh Air Damper (4TCC3042-60A) 1.... BAYOSAH002A[ ] Motorized Fresh Air Damper (4TCC3018-36A) 1.... BAYDMPR101A[ ] Motorized Fresh Air Damper (4TCC3042-60A) 1.... BAYDMPR102A[ ] 16" Round Duct Adapter (2 per box) (4TCC3018-36A) 6... BAYSQRD001A[ ] 18" Round Duct Adapter (2 per box) (4TCC3018-60A) 6... BAYSQRD002A[ ] 0-100% Mod Economizer w/baro. Relief (4TCC3018-36A) 124... BAYECON101B[ ] 0-100% Mod. Economizer w/baro. Relief (4TCC042-60A) 124.... BAYECON102B[ ] 0-100% Horizontal Economizer (4TCC3018-36A) 12.... BAYECON200A[ ] 0-100% Horizontal Economizer (4TCC3042-60A) 12.... BAYECON201A[ ] Enthalpy Control for Economizer (solid state).... BAYENTH001A[ ] Remote Potentiometer (All-BAYECON***A)... BAYSTAT023[ ] 1"-2" Filter Frame (4TCC3018-36A) (20 x 25 filter not included) 1.... BAYFLTR101B[ ] 1"-2" Filter Frame (4TCC3042-60A) (20 x 20 & 20X18 filter not included) 1.... BAYFLTR201B[ ] Evaporator Defrost Control (Low Ambient Cooling) Kit 5.... BAYLOAM011A[ ] Head Pressure Control (Low Ambient Cool) (208/240v) Kit 5.... BAYLOAM105A[ ] Quick Start Kit (4TCC3-A1)... BAYQSKT301A[ ] Crankcase Heater Recip (4TCC3018A1)(230v) 5.... BAYCCHT101A[ ] Crankcase Heater Scroll(4TCC3030, 36,48,60A1/3)(230v) 5.... BAYCCHT102A[ ] Crankcase Heater (4TCC3036,48,60A4)(460v) 5.... BAYCCHT404B[ ] Adapter Curb 4TCC3018-036A to BAYCURB030,38... BAYADAP050A[ ] Adapter Curb 4TCC3018-036A to BAYCURB033... BAYADAP051A[ ] Adapter Curb 4TCC3042-060A to BAYCURB030,38... BAYADAP052A[ ] Adapter Curb 4TCC3042-060A to BAYCURB033... BAYADAP053A[ ] Adapter Curb 4TCC3042-060A to BAYCURB034... BAYADAP054A[ ] 12" Duct Shroud Covers Horizontal 4TCC3018-060A7.... BAYCOVR112A[ ] 18" Duct Shroud Covers Horizontal 4TCC3018-060A 7.... BAYCOVR118A[ ] Extreme Condition Mounting Kit - All BAYCURB & BAYADAP... BAYEXMK001A[ ] Extreme Condition Mounting Kit - All BAYUTIL... BAYEXMK002B[ ] Extreme Condition Mounting Kit - All Slab Mounts... BAYEXMK003A[ ] Lifting Lug Kit... BAYLlFT002B[ ] SUPPLEMENTARY HEATERS (1 PHASE) 3.76/5.0 KW Heater (208/240V 1PH) (4TCC3018-060A1)... BAYHTRV105E[ ] 6.0/8.0 KW Heater (208/240V 1PH) (4TCC3018-060A1)... BAYHTRV108E[ ] 7.50/10.0 KW Heater (208/240V 1PH) (4TCC3024-060A1)... BAYHTRV110E[ ] 11.27/15.00 KW Heater (208/240V 1PH) (4TCC3030-060A1)... BAYHTRV115E[ ] 15.0/20.0 KW Heater (208/240V 1PH) (4TCC3048-060A1)... BAYHTRV120E[ ] SUPPLEMENTARY HEATERS (3 PHASE) 3.76/5.0 KW Heater (208/240V 3PH) (4TCC3036-060A3)... BAYHTRV305E[ ] 6.0/8.0 KW Heater (208/240V 3PH) (4TCC3036-060A3)... BAYHTRV308E[ ] 7.50/10.0 KW Heater (208/240V 3PH) (4TCC3036-060A3)... BAYHTRV310E[ ] 11.27/15.0 KW Heater (208/240V 3PH) (4TCC3036-060A3)... BAYHTRV315E[ ] 15.0/20.0 KW Heater (208/240V 3PH) (4TCC3048A3)... BAYHTRV320E[ ] 5.0 KW Heater (480V 3PH) (4TCC3036-060A4)... BAYHTRV405E[ ] 8.0 KW Heater (480V 3PH) (4TCC3036-060A4)... BAYHTRV408E[ ] 10.0 KW Heater (480V 3PH) (4TCC3036-060A4)... BAYHTRV410E[ ] 15.0 KW Heater (480V 3PH) (4TCC3036-060A4)... BAYHTRV415E[ ] 20.0 KW Heater (480V 3PH) (4TCC3048-060A4)... BAYHTRV420E[ ] Single Power Entry Kit 8.... BAYSPEK060E[ ] Single Power Entry Kit 8.... BAYSPEK061E[ ] Single Power Entry Kit 8.... BAYSPEK062E[ ] Single Power Entry Kit 8.... BAYSPEK063E[ ] Single Power Entry Kit 8.... BAYSPEK064E[ ] NOTES: 1 Must use internal filter frame when economizer or fresh air kit is used. 2 Dry bulb control standard with economizer. 3 Ships knocked down. 4 Downflow only. 5 Low Ambient cooling requires crankcase heater (BAYCCHT-----). 6 It is the responsibility of the installing dealer to properly size the ductwork for each specific application. 7 BAYCOVR112,118A will not cover BAYSQRD002A applications. 8 See table on page 8 for matching kit with units and heaters. 4

MODEL RATED Volts/PH/Hz Performance Cooling BTUH Indoor Airflow (CFM) Power Input (KW) EER/SEER (BTU/Watt-Hr.) Sound Power Rating [db(a)] POWER CONN. V/Ph/Hz Min. Brch. Cir. Ampacity Fuse Size Max. (amps) Fuse Size Recmd. (amps) COMPRESSOR Volts/Ph/Hz R.L. Amps L.R. Amps OUTDOOR COIL TYPE Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.) INDOOR COIL TYPE Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.) OUTDOOR FAN TYPE Dia. (in.) Drive/No. Speeds CFM @ 0.0 in. w.g. Motor HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps INDOOR FAN TYPE Dia x Width (in.) Drive/No. Speeds CFM @ 0.0 in. w.g. Motor HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps FILTER / FURNISHED Type Recommended Recmd. Face Area (sq. ft.) REFRIGERANT Charge (lbs.) DIMENSIONS Crated (in.) WEIGHT Shipping (lbs.) / Net (lbs.) 4TCC3018A1000A 18000 675 1.64 11.0 / 13.0 74 10.1 15 15 RECIPROCATING 6.4 / 38.6 SPINE-FIN 2 / 24 13.32 PLATE FIN 3 / 15 3.54 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 23 DIRECT / 1 2530 1/12 / 810 230/1/60 0.5 / 0.95 CENTRIFUGAL 11 X 10 DIRECT / 2 SEE FAN PERF TABLE 1/8 / 825 200-230/1/60 1.0 / 1.5 NO THROWAWAY 4.0 R-410 5.94 H X D X W 45.86 / 44.5 / 52.03 444 / 348 General Data 4TCC3024A1000A 23000 725 2.09 11.0 / 13.0 76 13.6 20 20 RECIPROCATING 200-230/1/60 8.3 / 57.8 SPINE-FIN 2 / 24 13.32 PLATE FIN 3 / 15 3.54 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 23 DIRECT / 1 2530 1/12 / 810 230/1/60 0.9 / 0.95 CENTRIFUGAL 11 X 10 DIRECT / 2 SEE FAN PERF TABLE 1/4 / 825 200-230/1/60 1.4 / 2.8 NO THROWAWAY 4.0 R-410 5.8 H X D X W 45.86 / 44.5 / 52.03 444 / 348 4TCC3030A1000A 28000 1000 2.55 11.0 / 13.0 75 21.7 35 35 SCROLL 14.7 / 72.5 SPINE-FIN 2 / 24 13.32 PLATE FIN 3 / 15 3.54 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 23 DIRECT / 1 3230 1/5 / 830 230/1/60 1.1 / 1.9 CENTRIFUGAL 10 X 10 DIRECT / 3 SEE FAN PERF TABLE 1/2 / 1080 200-230/1/60 2.0 / 4.4 NO THROWAWAY 4.0 R-410 6.3 H X D X W 45.86 / 44.5 / 52.03 445 / 349 4TCC3036A1000A 35000 1200 3.18 11.0 / 13.0 76 23.2 35 35 SCROLL 15.4 / 83 SPINE-FIN 2 / 24 13.32 PLATE FIN 4 / 15 3.54 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 23 DIRECT / 1 3230 1/5 / 830 230/1/60 1.1 / 1.9 CENTRIFUGAL 10 X 10 DIRECT / 3 SEE FAN PERF TABLE 1/2 / 1075 200-230/1/60 2.7 / 5.8 NO THROWAWAY 4.0 R-410 7.75 H X D X W 45.86 / 44.5 / 52.03 450 / 354 4TCC3036A3000A 208-230/3/60 35000 1200 3.18 11.0 / 13.0 76 208-230/3/60 18.2 30 30 SCROLL 208-230/3/60 11.5 / 77 SPINE-FIN 2 / 24 13.32 PLATE FIN 4 / 15 3.54 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 23 DIRECT / 1 3230 1/5 / 830 230/1/60 1.1 / 1.9 CENTRIFUGAL 10 X 10 DIRECT / 3 SEE FAN PERF TABLE 1/2 / 1075 200-230/1/60 2.7 / 5.8 NO THROWAWAY 4.0 R-410 7.75 H X D X W 45.86 / 44.5 / 52.03 450 / 354 1 Rated in accordance with A.R.I. Standard 210/240. 2 Sound Power values are not adjusted for ARI 270-95 tonal corrections. 3 Calculated in accordance with currently prevailing Nat'l Electrical Code. 4 Standard Air -- Dry Coil -- Outdoor. 5 Standard Air -- Dry Coil -- Indoor. 6 Rated in accordance with D.O.E. test procedure. 7 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05" W.C. 5

MODEL RATED Volts/PH/Hz Performance Cooling BTUH Indoor Airflow (CFM) Power Input (KW) EER/SEER (BTU/Watt-Hr.) Sound Power Rating [db(a)] POWER CONN. V/Ph/Hz Min. Brch. Cir. Ampacity Fuse Size Max. (amps) Fuse Size Recmd. (amps) COMPRESSOR Volts/Ph/Hz R.L. Amps L.R. Amps OUTDOOR COIL TYPE Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.) INDOOR COIL TYPE Rows/F.P.I. Face Area (sq.ft.) Tube Size (in.) Refrigerant Control Drain Conn. Size (in.) OUTDOOR FAN TYPE Dia. (in.) Drive/No. Speeds CFM @ 0.0 in. w.g. Motor HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps INDOOR FAN TYPE Dia x Width (in.) Drive/No. Speeds CFM @ 0.0 in. w.g. Motor HP/R.P.M. Volts/Ph/Hz F.L. Amps/L.R. Amps FILTER / FURNISHED Type Recommended Recmd. Face Area (sq. ft.) REFRIGERANT Charge (lbs.) DIMENSIONS Crated (in.) WEIGHT Shipping (lbs.) / Net (lbs.) 4TCC3036A4000A 460/3/60 35000 1200 3.18 11.0 / 13.0 76 460/3/60 8.7 15 15 SCROLL 460/3/60 5.1 / 35 SPINE-FIN 2 / 24 13.32 PLATE FIN 4 / 15 3.54 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 23 DIRECT / 1 3230 1/5 / 830 230/1/60 0.6 / 1.3 CENTRIFUGAL 10 X 10 DIRECT / 2 SEE FAN PERF TABLE 1/2 / 1075 460/1/60 1.7 / 3.12 NO THROWAWAY 4.0 R-410 7.75 H X D X W 45.86 / 44.5 / 52.03 450 / 354 General Data 4TCC3042A1000A 40000 1450 3.64 11.0 / 13.0 78 27.9 45 45 SCROLL 19.2 / 104 SPINE-FIN 2 / 24 18.01 PLATE FIN 3 / 15 5 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 27.6 DIRECT / 1 4380 1/4 / 825 230/1/60 1.4 / 3.5 CENTRIFUGAL 10 X 10 DIRECT / 3 SEE FAN PERF TABLE 1/2 / 1075 200-230/1/60 2.5 / 3.2 NO THROWAWAY 5.3 R-410 8.1 H X D X W 47.86 / 47.4 / 61.75 523 / 395 4TCC3048A1000A 46500 1600 4.23 11.0 / 13.0 80 31.1 50 50 SCROLL 20.5 / 109 SPINE-FIN 2 / 24 18.01 PLATE FIN 3 / 15 5 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 27.6 DIRECT / 1 4380 1/4 / 825 230/1/60 1.4 / 3.5 CENTRIFUGAL 10 X 10 DIRECT / 3 SEE FAN PERF TABLE 3/4 / 1080 200-230/1/60 4.0 / 8.4 NO THROWAWAY 5.3 R-410 8.2 H X D X W 47.86 / 47.4 / 61.75 607 / 479 4TCC3048A3000A 208-230/3/60 46500 1600 4.23 11.0 / 13.0 80 208-230/3/60 23.6 35 35 SCROLL 208-230/3/60 14.6 / 91 SPINE-FIN 2 / 24 18.01 PLATE FIN 3 / 15 5 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 27.6 DIRECT / 1 4380 1/4 / 825 230/1/60 1.4 / 3.5 CENTRIFUGAL 10 X 10 DIRECT / 3 SEE FAN PERF TABLE 3/4 / 1080 200-230/1/60 4.0 / 8.4 NO THROWAWAY 5.3 R-410 8.2 H X D X W 47.86 / 47.4 / 61.75 607 / 479 4TCC3048A4000A 460/3/60 46500 1600 4.23 11.0 / 13.0 80 460/3/60 11.7 15 15 SCROLL 460/3/60 7.1 / 46 SPINE-FIN 2 / 24 18.01 PLATE FIN 3 / 15 5 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 27.6 DIRECT / 1 4380 1/4 / 825 460/1/60 0.7 / 1.6 CENTRIFUGAL 10 X 10 DIRECT / 2 SEE FAN PERF TABLE 3/4 / 1080 460/1/60 2.2 / 4.36 NO THROWAWAY 5.3 R-410 8.2 H X D X W 47.86 / 47.4 / 61.75 607 / 479 1 Rated in accordance with A.R.I. Standard 210/240. 2 Sound Power values are not adjusted for ARI 270-95 tonal corrections. 3 Calculated in accordance with currently prevailing Nat'l Electrical Code. 4 Standard Air -- Dry Coil -- Outdoor. 5 Standard Air -- Dry Coil -- Indoor. 6 Rated in accordance with D.O.E. test procedure. 7 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05" W.C. 6

MODEL 4TCC3060A1000A RATED Volts/PH/Hz Performance Cooling BTUH 58000 Indoor Airflow (CFM) 1800 Power Input (KW) 5.27 EER/SEER (BTU/Watt-Hr.) 11.0 / 13.0 Sound Power Rating [db(a)] 79 POWER CONN. V/Ph/Hz Min. Brch. Cir. Ampacity 43.5 Fuse Size Max. (amps) 60 Fuse Size Recmd. (amps) 60 COMPRESSOR SCROLL Volts/Ph/Hz R.L. Amps L.R. Amps 27.5 / 158 OUTDOOR COIL TYPE SPINE-FIN Rows/F.P.I. 2 / 24 Face Area (sq.ft.) 20.54 Tube Size (in.) INDOOR COIL TYPE PLATE FIN Rows/F.P.I. 4 / 15 Face Area (sq.ft.) 5 Tube Size (in.) Refrigerant Control EXPANSION VALVE Drain Conn. Size (in.) 3/4 FEMALE NPT OUTDOOR FAN TYPE PROPELLER Dia. (in.) 27.6 Drive/No. Speeds DIRECT / 1 CFM @ 0.0 in. w.g. 4380 Motor HP/R.P.M. 1/4 / 825 Volts/Ph/Hz 230/1/60 F.L. Amps/L.R. Amps 1.4 / 3.5 INDOOR FAN TYPE CENTRIFUGAL Dia x Width (in.) 11 X 10 Drive/No. Speeds DIRECT / 3 CFM @ 0.0 in. w.g. SEE FAN PERF TABLE Motor HP/R.P.M. 1 / 1075 Volts/Ph/Hz F.L. Amps/L.R. Amps 7.6 / 7.4 FILTER / FURNISHED NO Type Recommended THROWAWAY Recmd. Face Area (sq. ft.) 5.3 REFRIGERANT R-410 Charge (lbs.) 10.0 DIMENSIONS H X D X W Crated (in.) 49.86 / 47.4 / 61.75 WEIGHT Shipping (lbs.) / Net (lbs.) 610 / 482 General Data 4TCC3060A3000A 208-230/3/60 58000 1800 5.27 11.0 / 13.0 79 208-230/3/60 31.7 50 50 SCROLL 208-230/3/60 18.1 / 137 SPINE-FIN 2 / 24 20.54 PLATE FIN 4 / 15 5 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 27.6 DIRECT / 1 4380 1/4 / 825 230/1/60 1.4 / 3.5 CENTRIFUGAL 11 X 10 DIRECT / 3 SEE FAN PERF TABLE 1 / 1075 7.6 / 7.4 NO THROWAWAY 5.3 R-410 10.0 H X D X W 49.86 / 47.4 / 61.75 610 / 482 4TCC3060A4000A 460/3/60 58000 1800 5.27 11.0 / 13.0 79 460/3/60 19.5 25 25 SCROLL 460/3/60 9.0 / 62 SPINE-FIN 2 / 24 20.54 PLATE FIN 4 / 15 5 EXPANSION VALVE 3/4 FEMALE NPT PROPELLER 27.6 DIRECT / 1 4380 1/4 / 825 460/1/60 0.7 / 1.6 CENTRIFUGAL 11 X 10 DIRECT / 3 SEE FAN PERF TABLE 1 / 1075 7.6 / 7.4 NO THROWAWAY 5.3 R-410 10.0 H X D X W 49.86 / 47.4 / 61.75 610 / 482 1 Rated in accordance with A.R.I. Standard 210/240. 2 Sound Power values are not adjusted for ARI 270-95 tonal corrections. 3 Calculated in accordance with currently prevailing Nat'l Electrical Code. 4 Standard Air -- Dry Coil -- Outdoor. 5 Standard Air -- Dry Coil -- Indoor. 6 Rated in accordance with D.O.E. test procedure. 7 Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per manufacturer's recommendation with a clean resistance of 0.05" W.C. 7

Heater Data UNIT MODEL ELECTRIC HEATER MODEL RATED VOLTAGE PHASE AMPS HEATER CAPACITY KW/STAGE NO. OF KW BTUH STAGES 1 2 MCA MAX FUSE OR HACR CKT BKR SIZE (4) CANADA ONLY MAX. CKT BKR SIZE (5) ^W/TC*3018-060A1 ^W/TCY4024-060A1 ^WCZ6036-060A1 ^W/TC*3018-060A1 ^W/TCY4024-060A1 ^WCZ6036-060A1 ^W/TC*3024-060A1 ^W/TCY4024-060A1 ^WCZ6036-060A1 ^W/TC*3030-060A1 ^W/TCY4030-060A1 ^WCZ6036-060A1 ^W/TC*3048-060A1 ^W/TCY4042-060A1 ^WCZ6048-060A1 ^W/TC*3060A1 ^W/TCY4042-060A1 ^WCZ6048-060A1 ^W/TC*3036-060A3 ^W/TCY4036-060A3 ^WCZ6036-060A3 ^W/TC*3036-060A3 ^W/TCY4036-060A3 ^WCZ6036-060A3 ^W/TC*3036-060A3 ^W/TCY4036-060A3 ^WCZ6036-060A3 ^W/TC*3036-060A3 ^W/TCY4036-060A3 ^WCZ6036-060A3 ^W/TC*3048-060A3 ^W/TCY4048-060A3 ^WCZ6048-060A3 ^W/TC*3060A3 ^W/TCY4048-060A3 ^WCZ6048-060A3 ^W/TC*3036-060A4 ^WCZ6036-060A4 ^W/TC*3036-060A4 ^WCZ6036-060A4 ^W/TC*3036-060A4 ^WCZ6036-060A4 ^W/TC*3036-060A4 ^WCZ6036-060A4 ^W/TC*3048-060A4 ^WCZ6048-060A4 ^W/TC*3060A4 ^WCZ6048-060A4 BAYHTRV105E BAYHTRV108E 208/240 1 29/33 6.0/8.0 20500/27300 1 6.0/8.0 36/41 40/45 40/45 BAYHTRV110E BAYHTRV115E# BAYHTRV120E# BAYHTRV125E# BAYHTRV305E 208/240 1 18/21 208/240 3 10/12 3.76/5.0 12800/17100 1 3.76/5.0 13/15 BAYHTRV308E 208/240 3 17/19 6.0/8.0 20500/27300 1 6.0/8.0 21/24 25/25 25/25 BAYHTRV310E BAYHTRV315E BAYHTRV320E BAYHTRV325E# BAYHTRV405E 38500/51200 17100 BAYHTRV408E 480 3 10 8.0 27300 1 8.0 13 15 15 BAYHTRV410E BAYHTRV415E BAYHTRV420E BAYHTRV425E 208/240 208/240 1 72/83 15.0/20.0 51200/68300 2 7.5/10.0 208/240 208/240 3 208/240 3 480 3 6 5.0 480 1 208/240 3 480 480 1 36/42 3 3 52/60 18.78/25.0 3.76/5.0 12800/17100 1 3.76/5.0 21/24 7.5/10.0 25600/34100 1 12 10.0 34100 18 15.0 480 3 24 20.0 3 1 7.5/10.0 2 7.5/10.0 3.76/5.0 23/26 3.76/5.0 68/78 25/30 45/52 45/60 70/80 25/30 70/80 7.5/10.0 90/104 90/110 90/110 90/104 18.78/25.0 64100/85300 2 11.26/15.0 7.5/10.0 113/130 125/150 31/36 11.27/15.0 30 7.5/10.0 25600/34100 208/240 1 54/63 11.27/15.0 38500/51200 2 7.5/10.0 25.0 7.5/10.0 26/30 30/30 39/45 64100/85300 2 11.26/15.0 7.5/10.0 65/75 70/80 51200 68300 85300 1 5.0 1 10.0 2 2 2 7.5/10.0 208/240 3 42/48 15.0/20.0 51200/68300 2 7.5/10.0 10.0 10.0 15.0 5.0 10.0 10.0 52/60 60/60 8 15 23 30 38 125/150 15/15 15/15 30/30 60/60 70/80 15 15 15 25 30 40 45/60 40/45 40/45 15 25 30 40 NOTES: 1. Any power supply and circuits must be wired and protected in accordance with local electrical codes. (2) The MCA values listed are for electric heater only. 3. Field wire must be rated at least 75 C (4) The HACR circuit breaker is for U.S.A. installations only. (5) For Canada installation reference only. * Heater uses fuses. 8

Single Power Entry Kit Data 9

Single Power Entry Kit Data 10

Single Power Entry Kit Data 11

Performance Data Cooling 4TCC3018A AT 600 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. TOTAL D.B. W.B. CAP. 72 75 78 80 KW 59 17.5 11.6 14.0 16.3 17.5 1.43 85 63 18.2 10.7 12.8 14.9 16.3 1.44 67 19.7 9.2 11.1 12.9 14.1 1.46 71 21.2 7.6 9.2 10.7 11.7 1.47 59 15.9 11.0 13.2 15.4 15.9 1.57 95 63 16.6 10.1 12.1 14.2 15.5 1.58 67 17.8 8.7 10.5 12.2 13.3 1.60 71 19.3 7.2 8.7 10.1 11.1 1.62 59 14.3 10.3 12.4 14.3 14.3 1.71 105 63 14.9 9.4 11.4 13.2 14.5 1.72 67 16.0 8.2 9.8 11.4 12.5 1.75 71 17.3 6.8 8.1 9.5 10.4 1.76 59 12.6 9.5 11.4 12.6 12.6 1.85 115 63 13.2 8.7 10.5 12.2 13.2 1.86 67 14.2 7.5 9.0 10.5 11.5 1.89 71 15.3 6.2 7.5 8.7 9.5 1.91 CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR) AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY LOW 525 0.98 0.97 HIGH 675 1.02 1.03 VALUES AT ARI RATING CONDITIONS TOTAL NET CAPACITY = 18000 BTUH AIRFLOW = 675 CFM COMPRESSOR POWER = 1183 WATTS I.D. FAN POWER = 236 WATTS O.D. FAN POWER = 217 WATTS S.E.E.R. = 13.00 BTUH/WATT E.E.R = 11.00 BTUH/WATT ALL TEMPERATURES IN DEGREES F. 4TCC3024A AT 800 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. TOTAL D.B. W.B. CAP. 72 75 78 80 KW 59 22.5 14.7 17.7 20.6 22.5 1.91 85 63 23.5 13.5 16.2 18.9 20.7 1.92 67 25.3 11.6 14.0 16.3 17.8 1.95 71 27.3 9.7 11.6 13.5 14.8 1.97 59 20.6 13.8 16.6 19.3 20.6 2.07 95 63 21.5 12.6 15.2 17.7 19.4 2.08 67 23.2 10.9 13.1 15.3 16.7 2.12 71 25.0 9.1 10.9 12.7 13.9 2.14 59 18.8 12.8 15.4 17.9 18.8 2.23 105 63 19.6 11.7 14.1 16.4 18.0 2.25 67 21.1 10.1 12.2 14.2 15.5 2.28 71 22.8 8.4 10.1 11.8 12.9 2.31 59 16.9 11.7 14.1 16.5 16.9 2.39 115 63 17.6 10.8 13.0 15.1 16.5 2.41 67 19.0 9.3 11.2 13.0 14.2 2.45 71 20.5 7.7 9.3 10.8 11.8 2.47 CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR) AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY LOW 700 0.98 0.97 HIGH 900 1.02 1.03 VALUES AT ARI RATING CONDITIONS TOTAL NET CAPACITY = 23000 BTUH AIRFLOW = 725 CFM COMPRESSOR POWER = 1698 WATTS I.D. FAN POWER = 191 WATTS O.D. FAN POWER = 202 WATTS S.E.E.R. = 13.00 BTUH/WATT E.E.R = 11.00 BTUH/WATT ALL TEMPERATURES IN DEGREES F. 4TCC3030A AT 1000 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. TOTAL D.B. W.B. CAP. 72 75 78 80 KW 59 26.8 18.3 22.0 25.6 26.8 2.24 85 63 28.0 16.8 20.1 23.5 25.7 2.26 67 30.2 14.5 17.4 20.3 22.1 2.29 71 32.6 12.0 14.4 16.8 18.4 2.32 59 24.9 17.3 20.8 24.3 24.9 2.49 95 63 26.0 15.9 19.1 22.3 24.3 2.50 67 28.0 13.7 16.5 19.2 21.0 2.55 71 30.2 11.4 13.7 15.9 17.4 2.57 59 23.0 16.3 19.6 22.9 23.0 2.73 105 63 24.0 15.0 18.0 21.0 22.9 2.75 67 25.9 12.9 15.5 18.1 19.8 2.80 71 27.9 10.7 12.9 15.0 16.4 2.82 59 21.1 15.3 18.3 21.1 21.1 2.98 115 63 22.0 14.0 16.8 19.6 21.4 3.00 67 23.7 12.1 14.5 16.9 18.5 3.05 71 25.6 10.0 12.1 14.0 15.4 3.08 CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR) AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY LOW 875 0.98 0.97 HIGH 1125 1.02 1.03 VALUES AT ARI RATING CONDITIONS TOTAL NET CAPACITY = 28000 BTUH AIRFLOW = 1000 CFM COMPRESSOR POWER = 1922 WATTS I.D. FAN POWER = 315 WATTS O.D. FAN POWER = 308 WATTS S.E.E.R. = 13.00 BTUH/WATT E.E.R = 11.00 BTUH/WATT ALL TEMPERATURES IN DEGREES F. 12

Performance Data Cooling 4TCC3036A AT 1200 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. TOTAL D.B. W.B. CAP. 72 75 78 80 KW 59 33.6 22.6 27.2 31.7 33.6 2.80 85 63 35.0 20.8 25.0 29.1 31.8 2.82 67 37.8 17.9 21.5 25.1 27.5 2.86 71 40.8 14.9 17.9 20.8 22.8 2.89 59 31.2 21.6 26.0 30.3 31.2 3.11 95 63 32.5 19.9 23.9 27.8 30.4 3.13 67 35.0 17.1 20.6 24.0 26.3 3.18 71 37.8 14.2 17.1 19.9 21.8 3.21 59 28.7 20.5 24.7 28.7 28.7 3.42 105 63 29.9 18.9 22.7 26.4 28.9 3.44 67 32.2 16.3 19.6 22.8 24.9 3.50 71 34.8 13.5 16.2 18.9 20.7 3.53 59 26.2 19.3 23.3 26.2 26.2 3.74 115 63 27.3 17.8 21.3 24.9 27.2 3.76 67 29.5 15.3 18.4 21.5 23.5 3.82 71 31.8 12.7 15.3 17.8 19.5 3.86 CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR) AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY LOW 1050 0.98 0.97 HIGH 1350 1.02 1.03 VALUES AT ARI RATING CONDITIONS TOTAL NET CAPACITY = 35000 BTUH AIRFLOW = 1200 CFM COMPRESSOR POWER = 2556 WATTS I.D. FAN POWER = 420 WATTS O.D. FAN POWER = 206 WATTS S.E.E.R. = 13.00 BTUH/WATT E.E.R = 11.00 BTUH/WATT ALL TEMPERATURES IN DEGREES F. 4TCC3042A AT 1400 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. TOTAL D.B. W.B. CAP. 72 75 78 80 KW 59 38.1 25.6 30.7 35.8 38.1 3.17 85 63 39.8 23.5 28.2 32.9 35.9 3.19 67 42.9 20.2 24.3 28.4 31.0 3.24 71 46.3 16.8 20.2 23.5 25.7 3.27 59 35.5 24.6 29.5 34.4 35.5 3.53 95 63 37.0 22.5 27.1 31.6 34.5 3.55 67 39.9 19.4 23.4 27.2 29.8 3.61 71 43.1 16.1 19.4 22.6 24.7 3.65 59 32.9 23.4 28.2 32.8 32.9 3.89 105 63 34.3 21.5 25.8 30.1 32.9 3.92 67 36.9 18.6 22.3 26 28.4 3.98 71 39.9 15.4 18.5 21.6 23.6 4.02 59 30.2 22.2 26.7 30.2 30.2 4.26 115 63 31.5 20.4 24.5 28.5 31.2 4.28 67 33.9 17.6 21.1 24.6 26.9 4.35 71 36.6 14.6 17.5 20.4 22.3 4.40 CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR) AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY LOW 1225 0.98 0.97 HIGH 1575 1.02 1.03 VALUES AT ARI RATING CONDITIONS TOTAL NET CAPACITY = 40000 BTUH AIRFLOW = 1450 CFM COMPRESSOR POWER = 3009 WATTS I.D. FAN POWER = 518 WATTS O.D. FAN POWER = 109 WATTS S.E.E.R. = 13.00 BTUH/WATT E.E.R = 11.00 BTUH/WATT ALL TEMPERATURES IN DEGREES F. 4TCC3048A AT 1600 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. TOTAL D.B. W.B. CAP. 72 75 78 80 KW 59 43.8 29.8 35.8 41.7 43.8 3.74 85 63 45.6 27.3 32.9 38.3 41.9 3.76 67 49.2 23.6 28.3 33 36.1 3.82 71 53.1 19.6 23.5 27.4 30.0 3.86 59 41.4 28.8 34.6 40.3 41.4 4.13 95 63 43.2 26.4 31.7 37.0 40.4 4.16 67 46.5 22.8 27.4 31.9 34.9 4.23 71 50.2 18.9 22.7 26.5 28.9 4.27 59 39.0 27.7 33.3 38.8 39.0 4.53 105 63 40.7 25.4 30.5 35.6 38.9 4.55 67 43.8 21.9 26.3 30.7 33.6 4.63 71 47.3 18.2 21.9 25.5 27.8 4.67 59 36.6 26.5 31.9 36.6 36.6 4.92 115 63 38.2 24.3 29.2 34.1 37.3 4.95 67 41.2 21.0 25.2 29.4 32.1 5.03 71 44.5 17.4 20.9 24.4 26.7 5.08 CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR) AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY LOW 1400 0.98 0.97 HIGH 1800 1.02 1.03 VALUES AT ARI RATING CONDITIONS TOTAL NET CAPACITY = 46500 BTUH AIRFLOW = 1600 CFM COMPRESSOR POWER = 3330 WATTS I.D. FAN POWER = 583 WATTS O.D. FAN POWER = 314 WATTS S.E.E.R. = 13.00 BTUH/WATT E.E.R = 11.00 BTUH/WATT ALL TEMPERATURES IN DEGREES F. 13

Performance Data Cooling 4TCC3060A AT 2000 CFM (CAPACITIES ARE NET IN BTUH/1000-INDOOR FAN HEAT DEDUCTED) O.D. I.D. TOTAL SENS. CAP. AT ENTERING D.B. TEMP. TOTAL D.B. W.B. CAP. 72 75 78 80 KW 59 56.0 35.7 42.9 50.0 54.6 4.72 85 63 58.4 32.7 39.4 45.9 50.1 4.75 67 62.9 28.3 34.0 39.6 43.3 4.82 71 67.9 23.4 28.2 32.8 35.9 4.87 59 52.1 34.3 41.2 48.1 52.1 5.24 95 63 54.3 31.5 37.8 44.1 48.2 5.27 67 58.5 27.2 32.7 38.1 41.6 5.36 71 63.2 22.5 27.1 31.6 34.5 5.41 59 48.2 32.8 39.4 45.9 48.2 5.77 105 63 50.2 30.1 36.1 42.1 46.0 5.80 67 54.1 25.9 31.2 36.3 39.7 5.90 71 58.4 21.5 25.9 30.2 33.0 5.95 59 44.3 31.0 37.3 43.5 44.3 6.29 115 63 46.2 28.5 34.2 39.9 43.6 6.33 67 49.7 24.6 29.6 34.4 37.7 6.44 71 53.7 20.4 24.5 28.6 31.2 6.50 CORRECTION FACTORS FOR OTHER AIRFLOWS (MULTIPLY DATA BY FACTOR) AIRFLOW TOTAL CAPACITY SENSIBLE CAPACITY LOW 1750 0.98 0.97 HIGH 2250 1.02 1.03 VALUES AT ARI RATING CONDITIONS TOTAL NET CAPACITY = 58000 BTUH AIRFLOW = 1800 CFM COMPRESSOR POWER = 4391 WATTS I.D. FAN POWER = 595 WATTS O.D. FAN POWER = 287 WATTS S.E.E.R. = 13.00 BTUH/WATT E.E.R = 11.00 BTUH/WATT ALL TEMPERATURES IN DEGREES F. 14

Indoor Fan Performance 4TCC3018A1 Horizontal Airflow 4TC*3018A1 -HOR Indoor Blower Performance EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW HIGH WATTS 157 155 152 148 - - - - - - - CFM 715 652 578 507 - - - - - - - WATTS - 276 267 254 239 224 210 - - - - CFM - 1103 1043 967 864 737 600 - - - - Down Airflow 4TC*3018A1-DOWN EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW HIGH WATTS 158 156 152 147 - - - - - - - CFM 690 641 565 479 - - - - - - - WATTS - 269 260 251 238 224 211 206 - - - CFM - 1038 990 929 829 696 561 485 - - - Indoor Fan Performance 4TCC3024A1 Horizontal Airflow 4TC*3024A1-HOR EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW WATTS 210 206 199 190 180 170 - - - - - CFM 865 797 748 683 593 492 - - - - - HIGH WATTS - - 366 350 331 307 285 273 - - - CFM - - 1273 1179 1055 896 722 575 - - - Down Airflow 4TC*3024A1-DOWN EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW WATTS 210 205 197 187 177 167 - - - - - CFM 825 780 730 659 563 453 - - - - - HIGH WATTS - - 357 341 326 310 294 276 - - - CFM - - 1181 1098 1002 881 729 550 - - - 15

Indoor Fan Performance 4TCC3030A1 Horizontal Airflow Indoor Blower Performance 4TC*3030A1-HOR EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW WATTS 275 267 263 258 248 - - - - - - CFM 992 930 881 823 746 - - - - - - MEDIUM WATTS 350 342 334 324 311 296 280 - - - - CFM 1164 1120 1067 1002 921 826 720 - - - - HIGH WATTS - - 572 558 542 523 501 473 - - - CFM - - 1463 1390 1306 1210 1088 912 - - - Down Airflow 4TC*3030A1-HOR EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW WATTS 275 267 263 258 248 - - - - - - CFM 992 930 881 823 746 - - - - - - MEDIUM WATTS 350 342 334 324 311 296 280 - - - - CFM 1164 1120 1067 1002 921 826 720 - - - - HIGH WATTS - - 572 558 542 523 501 473 - - - CFM - - 1463 1390 1306 1210 1088 912 - - - Indoor Fan Performance 4TCC3036A1 Horizontal Airflow 4TC*3036A-HOR EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW WATTS 351 342 335 327 314 - - - - - - CFM 1154 1111 1067 1008 930 - - - - - - MEDIUM WATTS 447 434 424 412 397 378 - - - - - CFM 1348 1301 1251 1189 1110 1012 - - - - - HIGH WATTS - - 675 658 640 619 594 563 - - - CFM - - 1545 1490 1418 1311 1169 1012 - - - Down Airflow 4TC*3036A-DOWN EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW WATTS 349 341 331 319 305 - - - - - - CFM 1138 1083 1017 948 878 - - - - - - MEDIUM WATTS 450 433 420 407 392 374 - - - - - CFM 1325 1263 1200 1133 1058 970 - - - - - HIGH WATTS - - 669 652 631 605 579 562 - - - CFM - - 1517 1436 1336 1219 1095 980 - - - 16

Indoor Fan Performance 4TCC3042A1 Horizontal Airflow 4TC*3042A1-HOR EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW MEDIUM HIGH Down Airflow Indoor Blower Performance WATTS 458 450 447 443 436 424 409 395 - - - CFM 1320 1290 1278 1266 1243 1205 1156 1104 - - - WATTS 544 542 535 526 515 503 487 463 426 - - CFM 1501 1506 1490 1466 1440 1408 1362 1282 1143 - - WATTS - 633 621 610 595 574 548 519 492 - - CFM - 1705 1686 1663 1628 1578 1508 1416 1300 - - 4TC*3042A1-DWN EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 WATTS 455 447 443 438 430 417 402 388 - - - LOW CFM 1328 1311 1290 1266 1239 1204 1151 1064 - - - WATTS 540 526 520 513 502 485 464 442 428 - - MEDIUM CFM 1533 1506 1483 1457 1424 1379 1319 1240 1138 - - WATTS - 606 596 588 575 556 529 503 486 493 - HIGH CFM - 1681 1654 1631 1594 1535 1455 1365 1284 1240 - Indoor Fan Performance 4TCC3048A1 Horizontal Airflow 4TC*3048A1 -HOR EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW MED HIGH Down Airflow 4TC*3048A1 -DOWN WATTS 585 575 563 546 526 502 476 - - - - CFM 1530 1520 1494 1455 1405 1343 1270 - - - - WATTS 699 689 671 647 619 587 550 510 - - - CFM 1810 1783 1743 1691 1627 1548 1450 1325 - - - WATTS - 966 944 914 878 837 794 753 721 - - CFM - 2217 2157 2086 1993 1874 1740 1611 1519 - - EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW MED HIGH WATTS 573 565 547 524 503 483 462 - - - - CFM 1533 1519 1478 1426 1372 1315 1248 - - - - WATTS 677 659 639 615 589 561 531 498 - - - CFM 1771 1734 1688 1632 1567 1490 1398 1290 - - - WATTS - 909 882 859 832 797 759 726 712 - - CFM - 2095 2024 1956 1873 1769 1651 1537 1456 - - 17

Indoor Blower Performance Indoor Fan Performance 4TCC3060A1 Horizontal Airflow 4TC*3060A1-HOR EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW MEDIUM HIGH WATTS 475 482 497 513 527 540 551 566 - - - CFM 1935 1888 1855 1826 1796 1762 1728 1698 - - - WATTS 602 639 656 665 675 689 706 722 729 - - CFM 2081 2076 2051 2018 1987 1959 1934 1905 1860 - - WATTS - - 775 789 802 816 831 844 854 856 - CFM - - 2173 2144 2114 2083 2050 2018 1990 1973 - Down Airflow 4TC*3060A1-DOWN EXTERNAL STATIC PRESSURE (IN. WG) MOTOR SPEED 0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 LOW WATTS 498 510 523 536 548 560 573 589 - - - CFM 1902 1854 1827 1805 1777 1740 1697 1659 - - - MEDIUM WATTS 649 668 683 695 707 720 734 747 756 - - CFM 2099 2063 2024 1989 1959 1934 1908 1874 1820 - - HIGH WATTS - 798 813 824 834 843 853 865 879 897 - CFM - 2176 2150 2112 2076 2046 2021 1992 1943 1851-18

Typical Field Wiring UNIT CONTROL BOX UNIT HEATER AREA POLARIZED PLUG ELECTRIC HEATER CONTROL BOX B G Y W1 W2 R COMMON FAN (GR) COMPRESSOR HEAT FIRST STAGE HEAT SECOND STAGE 24V (WH) (WH) GROUND WIRE 1 PH 1 PH POWER POWER 3 PH 3 PH POWER POWER UNIT HEATER NOTE 1,8 TYPICAL THERMOSTAT FIELD PROVIDED JUMPER NOTE 6 UNIT CONTROL BOX TO COMPR. CONTACTOR UNIT HEATER AREA FIELD PROVIDED FIELD CONNECTED WIRED ELECTRIC HEATER CONTROL BOX TO ECONOMIZER FACTORY PROVIDED FIELD INSTALLED WIRES B G 1 PH POWER 3 PH POWER UNIT LOW VOLTAGE AREA GROUND WIRE SINGLE POWER ENTRY SPE ACCESSORY KIT UNIT FUSES HEATER FUSES SEE SPEK INSTALLER'S GUIDE FOR ALL OTHER EXAMPLES UNIT LOW VOLTAGE AREA TYPICAL 2-STAGE THERMOSTAT FIELD INSTALLED JUMPERS Y W1 W2 R UNIT LOW VOLTAGE AREA B G Y W1 W2 R UNIT LOW VOLTAGE AREA NOTE 10 (WH) W1 (WH)W2 BAY24X042 TYPICAL THERMOSTAT FIELD INSTALLED JUMPERS FIELD INSTALLED JUMPERS TYPICAL THERMOSTAT 756977i2 19

Typical Wiring 20

Typical Wiring 21

Optional Equipment BAYCURB050A Full Perimeter Roof Mounting Curb for *****018-036A 17 7/8 46 3 3 5/8 19 1/2 2 3/16 15 19 1/2 38 7/8 14 1 1/2 The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 35 7/8 43 22

Optional Equipment BAYCURB051A Full Perimeter Roof Mounting Curb for *****042-060A 15 7/8 56 1/8 3 1 1/2 20 19 1/2 4 3/4 10 7/8 41 7/8 19 1/2 14 The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 38 7/8 53 1/8 23

Optional Equipment BAYFLTR101, 201B, 1" - 2" Filter Rack (Mounts in Filter/Coil Section) Filter BAYACCDOR1A & BAYACCDOR2A Hinged Filter Access Door Replaces Filter/Coil Access Panel The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. 24

Optional Equipment BAYECON101,102A Down Discharge Economizer and Rain Hood (Mounts Over Horizontal Return Air Opening) A HVAC Unit Economizer rain hood Economizer Unit ApplicationM odels A Mist eliminator Outside air dampers Return air dampers Required filter kit, order separately BAYECON101A BAYECON102A 2/4YC,WC3018-036A 4TC*3018-036A 4W/T/Y/DCY4024-060 2/4YC,WC3042-060A 4TC*3042-060A 4W/T/Y/DCY4024-060 20.125" 24.375" Relief damper Roofcurb Return Duct BAYECON200,201A Horizontal Economizer and Rain Hood The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. Economizer C A B D Gaskets (2) Duct E Rain Hood Mixed Air Sensor Economizer A B C D E BAYECON200AA 22" 20" 16 7/8" 15 11/16 11 11/16 BAYECON201AA 24" 22 21/32" 19" 17 11/16 14 11/16 25

Optional Equipment BAYOSAH001,002A, 25% Outside Air Damper (Replaces Filter/Coil Access Panel) The drawings on this page are prepared by the manufacturer in order to provide detail regarding job layout only. These drawings are not intended to be used as a basis to construct, build or modify the items depicted in the drawings. The manufacturer is not responsible for the unauthorized use of these drawings and expressly disclaims any liability for damages resulting from such unauthorized use. D C A FULLY OPEN 2/3 1/3 B FULLY CLOSED Manual Fresh Air Model BAYOSAH001 BAYOSAH002 Unit Application Models 2/4YC,WC3018-036A 4TC*3018-036A 4W/T/Y/DCY4024-036A 4W/Y/DCZ6036A 2/4YC,WC3042-060A 4TC*3042-060A 4W/T/Y/DCY4042-060 4W/Y/DCZ6048-060A A B C D 22 7/16" 20 11/16" 12 " 9 3/16" 25 3/16" 20 11/16" 12 " 9 3/16" BAYDMPR101,102A, 25% Motorized Outside Air Damper (Mounts Over Horizontal Return AIr Opening) A C B E BAYDMPR101A BAYDMPR102A Unit Application Models 2/4YC,WC3018-036A 4TC3018-036A 4W/T/Y/DCY4024-036A 4W/Y/DCZ6036A 2/4YC,WC3042-060A 4TC3042-060A 4W/T/Y/DCY4042-060A 4W/Y/DCZ6048-060A A B C D E 15 13/16" 11 13/16" 10 1/4" 11 1/2" 12 1/4" 18 3/16" 15 1/8" 10 1/4" 11 1/2" 12 1/4" D 26

Dimensional Data and Weights NOTE: The view labed "Bottom Side" represents the base as viewed looking up from underneath the unit. 4TCC3018A through 4TCC3036A (1 of 3) 27

Dimensional Data and Weights 4TCC3018A through 4TCC3036A (2 of 3) 28

Dimensional Data and Weights 4TCC3018A through 4TCC3036A (3 of 3) 29

Dimensional Data and Weights NOTE: The view labed "Bottom Side" represents the base as viewed looking up from underneath the unit. 4TCC3042A through 4TCC3060A (1 of 3) 30

Dimensional Data and Weights 4TCC3042A through 4TCC3060A (2 of 3) 31

Dimensional Data and Weights 4TCC3042A through 4TCC3060A (3 of 3) 32

Mechanical Specifications General The units shall be horizontal airflow as shipped and convertible to downflow. All units shall be factory assembled, piped, internally wired and fully charged with refrigerant. Units shall be UL listed and carry a UL label. All units shall be factory run tested to check cooling operation, fan and blower rotation and control sequence. Units shall be designed to operate at ambient temperatures between 115 F and 55 F in cooling as manufactured. Cooling performance shall be rated in accordance with ARI standards. Unit Casing All panels shall be heavy gauge steel, gasketed and insulated. Foil-faced fiber insulation shall be in the heater section. Foil-faced fiber insulation shall be in the evaporator section. Base pan shall be heavy gauge steel. WEATHERGUARD exterior corrosion resistant screws shall be used for added resistance to rust and corrosion. Compressor The compressor shall be a hermetically sealed, high efficiency Climatuff compressor. Internal overcurrent and over temperature protection, internal pressure relief shall be standard. Other features include, roto lock suction and discharge refrigerant connections, centrifugal oil pump and low vibration and noise. Refrigeration System All units shall have refrigerant control. Service pressure tap ports, and a refrigerant line filter shall be standard. Evaporator Coil Internally enhanced -inch OD seamless copper tubing mechanically bonded to aluminum fins, factory pressure and leak tested at 250 to 300 psig. All units have TXV to control refrigerant flow. Condenser Coil The Spine Fin condenser coil shall be continuously wrapped, corrosion resistant all aluminum with minimum brazed joints. This coil is inch O.D. seamless aluminum tubing glued to a continuous aluminum fin. Coils are lab tested to withstand 2,000 pounds of pressure per square inch. The outdoor coil provides low airflow resistance and efficient heat transfer. The coil is protected on all four sides by louvered panels. Indoor Air Fan Direct-drive, forward-curved, centrifugal wheel in a Composite Vortica Blower housing. Motor shall have thermal overload protection. Permanently lubricated motor bearings. Motor/blower assembly isolated from unit with rubber mounts. Outdoor Fan One, direct-drive, statically and dynamically balanced propeller fan shall be used in a drawthrough vertical discharge configuration. Permanently lubricated weather proof motor shall have built-in thermal overload protection. System Controls System controls include condenser fan, evaporator fan and compressor contactors. Accessories Roof Curb The roof curb shall be designed to mate with the unit and provide support and complete weathertight installation when properly installed. Adhesive back polyurethane sealing strips shall be provided to ensure an airtight seal between supply and return openings of the curb and unit. The roof curb design allows field fabricated ductwork to be connected directly to the curb. Curb ships knocked down for field assembly, and includes factory-installed wood nailer strips. Electric Heaters Each heater assembly shall include power supply fusing if over 48 amps, automatic resetting limit switches and heat limiters for thermal protection. Heaters shall be provided with polarized plugs for quick connection to unit low voltage wiring. Electric heat modules shall be UL listed. Single Source Power Entry This accessory when used with electric heat accessory shall allow single source power connection to unit and heater combination. Single source power entry kits shall have specific matching heater(s). Kit shall include high voltage terminal blocks, fuse blocks and fuses, cut-to-length interconnecting wiring, and junction box (if required) to provide power sources with fuse protection as required for both the unit and accessory heater. Kit components shall install within the heater cabinet in the heater access section. Single source branch power circuit shall be protected and wired in accordance with local codes. Fully Modulating Economizer This accessory shall be field installed and be composed of the following items: 0-100% fresh air damper, damper drive motor, fixed dry bulb enthalpy control, and low voltage pigtails for electrical connections. Solid state enthalpy or differential enthalpy control is optional. Economizer operations shall be controlled by the preset position of the enthalpy control. A barometic relief damper shall be standard with the downflow economizer and provide a pressure operated damper that shall be gravity closing and prohibit entrance of outside air on equipment off cycle. Manual Outside Air Dampers Rain hood and screen shall be field installed. Suitable for up to 25% outside air. Start Kit - Extra compressor starting capacity for single phase equipment. Control Options Standard Indoor Thermostats - Two stage heating/cooling or one stage heating/cooling thermostats shall be available in either manual or automatic changeover. Programmable Electronic Night Setback Thermostat - Programmable electronic thermostat shall provide heating setback and cooling setup with 7-day, programming capability. 1 H/1 C or 2H/2C models available. 6200 Troup Highway Tyler, TX 75707-9010 American Standard has a policy of continuous product and product data improvement and it reserves the right to change design and specifications without notice. 33