Friendly Power Shutdown for LLO Corner Buildings

Similar documents
Keep the power on and

EVLA Memorandum 107 Failure Pathology of EVLA WIDAR Correlator Support Systems October 18 th, 2006 Bob Broilo, Brent Carlson

WaterFurnace FX10 Application Guide Reversible Chiller

Service Settings. EASY PFA Universal Biomass Heating System Controller. Technical Documentation

Power & HVAC. Keep the power on and the climate under control. We re here to help.

Advantage Services Capabilities

SECTION ROTARY-SCREW WATER CHILLERS

KITCHENAID CONSUMER SERVICES Technical Training Department

Motor Solo Run. Power cable energized (2 hours)

IDAHO PORT-OF-ENTRY RAMP MONITORING. August 29, 2011.

LASER INTERFEROMETER GRAVITATIONAL WAVE OBSERVATORY - LIGO - CALIFORNIA INSTITUTE OF TECHNOLOGY MASSACHUSETTS INSTITUTE OF TECHNOLOGY

T Mirror Cooling Specifications & Design Revision: -

Instructions for the fan motor control system with integrated wiring terminals SILVER C

Stockton Infrared Thermographic Services, Inc. presents. A Qualitative Infrared Thermographic Survey Of Electrical Switchgear at the facilities of

R E C T I F I E R I N V E R T E R C O N V E R T E R SB7

Your Chiller Solution For Efficiency And Reliability. McQuay Dual Compressor Centrifugal Chillers 160 to 2500 Tons

Instructions for the fan motor control system, SILVER C

TECHNICAL, OPERATING & INSTALLATION MANUAL TC 15, 33, 52 AIR COOLED PACKAGED WATER CHILLERS

Specification/ Data Sheet

Planned, Limited Notice and Emergency Outage Guidelines

PCD/PEM Power Conversion Department - Equipment Lockout Procedure

Eco-systèmes contribution scale - Household EEE

General Information. FAST-STAT wiring extenders electronically add more wires to a control cable.

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

AEPT SERIES PRODUCT SPECIFICATIONS. Multi-Position, Variable-Speed High-Efficiency Air Handler. 2 and 5 Ton

ADC150 Automatic Draft Control

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Steam and Power Conversion System

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

TEMPERATURE & PRESSURE CONTROLS

Part 3 Troubleshooting

Ammonia Detection System Codes and Design Specifications

FOREST FIRE CONTINGENCY PLAN

DANFOSS OPTYMA PLUS INVERTER UNITS

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...


NYC Department of Education

FLEXBAKE 5 Proof and Bake Oven. Service Training Introduction

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

Pilz Safety Lockout System (PSLS)

Fundamental Principles of Air Conditioners for Information Technology

EBC 10 Fan Control USA CAN. Product Information. ... Chapter 1+2. Mechanical Installation. ... Chapter 3. Electrical Installation. ...

AEPF. 1½ to 5 Tons. Contents Nomenclature... 2 Product Specifications... 3 Dimensions... 4 Wiring Diagram... 6 Accessories... 7

Power System Reliability

Jacket Heater. Sep Jacket Heater 1

TEMPERATURE CONTROL POWER COMPRESSED AIR EMERGENCY OR PLANNED, SHUT DOWN OR TURN AROUND. 24/7/ / ers-cat.com

La Marche Manufacturing Company Option 16 Series. Digital Combined Accessory Package. Installation and Operation Manual

AEPT SERIES PRODUCT SPECIFICATIONS. Multi-Position Air Handler. 2 to 5 Ton

The TC-4F. Time Control Module C P/N 15972:C ECN For the Sensican 2000 Fire Alarm Control Panel

Concealed Ducted Split Series R-407C MBH

DHL-LP-LED Low Profile LED Linear High/Low Bay

Refrigeration and Air Conditioning

SUH-8 UNIT HEATERS. High Efficiency Heating Equipment

PROVIDING EXTRA-HIGH EFFICIENCY AND WORRY-FREE PERFORMANCE

Operation and Maintenance Manual OM MicroTech III Unit Controller with I/O Expansion Module for Two Compressor Water Source Heat Pumps

T5000 LCD Digital Fan Coil Thermostat

Oakwood. Oakwood Lake Zurich. Oakwood Building Lake Zurich, IL Office, Laboratory, Warehouse and Expansion Space

TYPE APPROVAL CERTIFICATE

STRIKE GUARD DELIVERS:

Water Circulator (Chiller) & Cold Trap

Matt Cooper, PE, BEMP, HBDP, Group 14 Engineering Ken Urbanek, PE, HBDP MKK Consulting Engineers, Inc.

Field Application of Advanced Residential Air Conditioning Systems

SOP FOR FEP CENTURA TOOL

HOKKIM INTEGRATED AMF CONTROL BOARD MANUAL FOR MODELS: HAMF-8 AND HAMF-4

wireless. web-based. worthy of the name RACO.

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Air Compressor Electrical Fire

Energy Use Rationalization Act

MAC-120HE-03 Air-Cooled Chiller

Fire Risks of Loviisa NPP During Shutdown States

DIESEL Engine Fire Pump Controllers Features. FD120 Diesel Engine Controllers

GSI Competitor & EMCS Portable Dryer Models

More Precision. indusensor // Linear inductive displacement sensors

Inspection Points Trailers & Fifth Wheels

DATATECH PFW kw. Quick facts

Hoshizaki America, Inc.

Life Cycle Considerations for Microprocessor Relays

A Chiller is equipment to control temperature of customers heating sources. Application Examples

NYC Department of Education

TYPE APPROVAL CERTIFICATE

XRD XRD-1500 High-Temperature Oven. Innovation in Material Science...

TECHNICAL BULLETIN [ 1 / 10 ]

WHY THE REMOVAL OF NONCONDENSABLE GASES AND AIR IS CRITICAL IN A STEAM SYSTEM

Safety Instrumented Fire & Gas Systems

PSM CONTROL & MANAGEMENT PRODUCT CATALOGUE. GAMATRONIC, A SolarEdge Division. 17 Hartom Street, Jerusalem , Israel

G SERIES: Security INTEGRATION as you want it. Greater expansion, communication, video integration, system resilience, and automation.

AND WORRY-FREE PERFORMANCE

Michigan State University Construction Standards COMMISSIONING OF FIRE ALARM SYSTEMS PAGE

TC-150 CONVEYORIZED OVEN. OPERATION AND MAINTAINANCE MANUAL Ovens with Omron PLC and Touchscreen

ICM Simple Systems. CC750 Comfort Control Center CC and CC Application Guide

IFT-RC150 IntelliFire Touch Remote Control Installation Instructions

1.0 Digital Controller

AxxonSoft. Operation Manual TROMBONE. Fire and Security Alarm Integration Module. Version 1.1. Moscow

HOME ENERGY DETECTIVES

B. Configuration of system shall be through Schneider Electric in Homewood, Illinois (Jerry Lanfear ).

CONTROL PANEL INSTRUCTIONS RSQ-4

THE LOGICAL SELECTION FOR YOUR SYSTEM INTEGRATION

An Instrumentation and Control for Loop Test

Power Factor (1) 350 ma 90 ~ 132 Vac 34~68 Vdc 24 W 85% 0.95 LLC-024S035RSP. Max. Output Power. Efficiency (1)

Transcription:

Friendly Power Shutdown for LLO Corner Buildings There are two kinds of power shutdowns: Friendly, meaning we planned it, and Unfriendly, meaning the universe burped. This procedure is intended to identify Friendly power shutdown procedures. Initially, it is incomplete because eventually each subsystem using DC power must provide a procedure for that specific subsystem. 1

Power Shutdown Locations Staging Building Air Conditioners LDAS Air Conditioners SEC MAINS Disconnect Mechanical (Chiller) Building MAINS Disconnect CDS DC Power Supply Transformer Disconnect Control Room Automation Computer Maintenance Room MAINS Disconnect 2

Mechanical (Chiller) Building Power Shutdown 1. Shut down the bake ovens in the VPW. 2. Shut down the LDAS computers. 3. Shut down the three air conditioners for the Staging Building. 4. Shut down the three air conditioners for the LDAS room. 5. Turn off the Chillers using the Automation Computer in the Control Room. 6. De-energize the MAINS in the Mechanical Building. These MAINS in the Mechanical Building control power to: 1. The Mechanical Building 2. The Vacuum Processing Warehouse (VPW) 3. The Staging Building including: a) The High Bay b) The Offices c) The LDAS Room d) HPLF e) The Banquet Room 4. The House Trailer 3

Mechanical (Chiller) Building Power Startup 1. Energize the MAINS in the Mechanical (Chiller) Building. 2. Turn on the Chillers using the Automation Computer in the Control Room. 3. Start up the air conditioners for the LDAS room. 4. Start up the air conditioners for the Staging Building. 5. Start up the LDAS computers. 6. Start up the bake ovens in the VPW. 4

Mechanical (Chiller) Building MAINS Disconnect 5

Staging Building Air Conditioners << Shutdown Instructions << Startup Instructions Air Conditioner #1 is inside, in Panel PNL MDP, Circuit ACU #1 Air Conditioners #2 and #3 is outside, near the air conditioners. 6

Staging Building Air Conditioner 1 Disconnect << Staging Building Locations << Shutdown Instructions << Startup Instructions AC #1 Use BREAKER to shut off. 7

Staging Building Air Conditioners 2 and 3 Disconnects << Staging Building Locations << Shutdown Instructions << Startup Instructions AC #2 Use DISCONNECT to shut off. AC #3 Use DISCONNECT to shut off. 8

LDAS Air Conditioners << Shutdown Instructions << Startup Instructions 9

LDAS Air Conditioning Shutdown << LDAS Air Conditioners LDAS Air Conditioners AC #1 Use CONTROLS to shut down. AC #2 De-energize with disconnect switch. AC #3 Use CONTROLS to shut down. 10

LDAS Air Conditioning Startup << LDAS Air Conditioners LDAS Air Conditioners AC #1 Use CONTROLS to start up. AC #2 Energize with disconnect switch. AC #3 Use CONTROLS to start up. 11

SEC MAINS Location << Shutdown Instructions << Startup Instructions SEC MAINS Disconnects 12

SEC MAINS Disconnects << SEC MAINS Location << Shutdown Instructions << Startup Instructions 13

SEC MAINS Power Shutdown << SEC MAINS Disconnects 1. Turn off power to the LP Panel. 2. Turn off power to the RP Panel. 3. Turn off power to the MP Panel. 14

SEC MAINS Power Startup << SEC MAINS Disconnects 1. Turn on power to the LP Panel. 2. Turn on power to the RP Panel. 3. Turn on power to the MP Panel. 15

Automation System Computer in the Control Room 16

Maintenance Room Power Shutdown 1. Ramp down and turn off the LVEA fans using the Automation Computer in the Control Room. 2. Turn off air handler 4 using the Automation Computer in the Control Room. 3. De-energize the DC Transformer breaker switch. 4. De-energize the MAINS in the Maintenance Room. 5. Turn off all subsystem DC supplies. (Optional) These MAINS in the Maintenance Room control power to: 1. The Office Support Building (OSB) 2. The Laser and Vacuum Equipment Area (LVEA) 3. All computers that are NOT on their own UPS systems, but note that the times for power backup vary considerably. 4. The Guard Shack The DC Supplies fall into roughly three categories: 1. The +12VDC Supplies used for Timing Chassis 2. The +24VDC Supplies that power IO Extender Chassis 3. All the rest, which are subsystem dependent 17

Maintenance Room Power Startup 1. Energize the MAINS in the Maintenance Room. 2. Energize the DC Transformer breaker switch. 3. Turn on air handler 4 using the Automation Computer in the Control Room. 4. Turn on and ramp up the LVEA fans using the Automation Computer in the Control Room. 5. Turn on DC Power Supplies for each subsystem according to specific procedures for that subsystem. (Optional) 18

Maintenance Room MAINS Disconnect 19

CDS DC Transformer Breaker Switch 20

CPR - DC Power Supplies ISC PSL SEI SUS TCS DAC 21