FACILITIES PLANNING STUDY RIVER VALLEY SOOL DISTRICT Spring Green Elementary School 830 Daley St. Spring Green, WI 388 7 South Dewey Street Eau Claire, Wisconsin 4701 71.832.160 sdsarch.com
SPRING General Overview Note: Property lines have been approximated Site Acreage: Approx. 0 Acres Parking Stalls: Approx. 46 Building Area: 42,28 GSF Construc on: Masonry/CMU ES Director: Mr. Jaime Hegland Students: 248 GSF/Student: 171 Grades: K through th Paved Area P.1 Descrip on: Visitor Parking Type: Asphalt Net Area: Approx. 2,160 SF Ra ng: Paved Area P.2 Descrip on: General Parking Type: Asphalt Net Area: Approx. 19,60 SF Ra ng: Paved Area P.3 Descrip on: Play Ground Type: Asphalt Net Area: Approx. 20,400 SF Ra ng: P.2 P.1 P.3 * See the final page of Chapter 1 for ra ng system of paved surfaces. Chapter Page 2 Project No. 121 December 201
Site Analysis 1 2 3 4 6 7 8 1 2 4 1 Code/Safety Issue Site photos Chapter Page 3 Project No. 121 December 201
SPRING Building Construction, Remodels and Additions * Fire ra ngs as indica ed by original construc on may currently be compromised by subsequent modifica ons. Year 1988? Project Scope Original Building Construc on Addi on Area 40,8 SF 1,700 SF Legend 1 Founda on: CMU Block Exterior Shell: Brick Cavity Wall R-VALUE: 14.7 Interior: CMU Block 1 Chapter Page 4 Project No. 121 December 201
Roof Analysis R.3 Legend BSPM (Ballasted Single Ply EPDM) ASPM (Adhered Single Ply EPDM) R.1 R.2 Roof Area R.1 Roof Type: ASPM Net Area: 31,07 SF Year Installed: 2011 Condi on: Very Good Roof Area R.2 Roof Type: ASPM Net Area: 7,340 SF Year Installed: 1988 Condi on: Poor Roof Area R.3 Roof Type: ASPM Net Area: 1,700 SF Year Installed: Unknown Condi on: Average R.2R.1 Chapter Page Project No. 121 December 201 Roof photos
SPRING Room Assignments and Building Use Legend Classroom/Instruc on Athle cs Administra on/conference Food Service STORAGE Music/Arts General/Support Circula on ME. STORAGE KITEN MULTI-PURPOSE 4TH GRADE 4TH GRADE 4TH GRADE SPECIAL EDUCATION S LOCKER ROOMS PHY. ED. OFFICE TH GRADE TH GRADE MUSIC 3RD GRADE ART 2ND GRADE 1ST GRADE IMC TOILETS TOILETS KINDERGARTEN KINDERGARTEN ADMIN/ OFFICES K 4K 4K 1ST GRADE Chapter Page 6 Project No. 121 December 201
Floor Plan Analysis 1 2 3 4 6 7 Damaged/worn flooring Restroom is not ADA compliant Damaged/worn cabinets/casework Damaged/worn ceiling Damaged/worn plumbing fixtures Door should swing out to meet exi ng/occupancy requirements Locker Room used as an Office 7 6 6 Interior Photos Code/Safety Issue Safety/Health Issue ADA/Accessibility Issue Program Related Problem Area Chapter Page 7 Project No. 121 December 201
SPRING AC AH Control Air Compressor Air Handling Unit Mechanical Analysis EH Electric Heater Fin Tube Heat EH P P B B 8 B CR CU Boiler Cabinet Unit Heater Condensate Return Sta on Condensing Unit KH Kitchen Hood GS Gas Service MS Mini-Split P Pump CU UH AC AH UH Convector UH Unit Heater AH ED Exhaust Duct UV Unit Ven lator AH Exhaust Fan UH KH 1) Corridors are u lized as return air plenums. 2) The building is served by hea ng only air handling units with constant volume reheat booster coils. Exterior spaces are provided with baseboard radia on to provide addi onal heat. One air handling unit is provided with a remote condensing unit for cooling. The air handling units and reheat coils are in good working condi on, but nearing the end of their useful lives. The condensing unit is past its useful life. Hea ng is provided by two Burnham boilers. The boilers, pumps, valves and accessories are in decent working condi on, but nearing the end of their useful life. Pneuma c controls are used throughout the building. Code/Safety Issue Photos Chapter Page 8 Project No. 121 December 201
G TS Electrical Analysis 10 D Data Center EM Electric Meter FA Fire Alarm Control Panel G Generator P C P E MC Master Clock MS Main Service P Panel UT *pad mounted FA P A P MD MS TP 9 PS Paging System SS Security System UT U lity Transformer TP Phone/Data Termina on Port TS Transfer Switch PS TP P D P B1 P B TV Junc on Box 1) Automa c ligh ng control is not present in all required areas of the building. 2) Code required electrical clearances are not met in front of the main electrical equipment. Refer to picture 9. 3) Code required selec ve coordina on and separa on for NEC 700 emergency loads does not appear to be met. LIGHTING 4) Ligh ng generally consists of fluorescent recessed fixtures that are in good working condi on. ) Some recent ligh ng upgrades appear to have taken place and include high bay fluorescent ligh ng in the gym. POWER 6) All electrical equipment appears to be original to the building and is in working condi on. However, this equipment is nearing 30 years old and will be nearing the end of its expected useful life within the next 10 years. Code/Safety Issue Photos Chapter Page 9 Project No. 121 December 201
SPRING Plumbing Analysis AB Acid Neutralizing Basin CP Circula on Pump GS Gas Service GI Grease Interceptor LS Li Sta on S Water So ener SE Sewage Ejector SP Sump Pump WH Water Heater WS Water Service WH WH CP GS SE WS 11 S GI WH PLUMBING 1) The domes c water is so ened by a Hellenbrand water so ener and heated by a single A.O. Smith gas fired water heater. The plumbing equipment appears to be in good working condi on. FIRE PROTECTION 2) The building is not provided with fire protec on. Code/Safety Issue Photos Chapter Page 10 Project No. 121 December 201
Photographs 1 09-29-201 2 09-29-201 3 09-29-201 4 09-29-201 09-29-201 6 09-29-201 7 09-29-201 8 11-02-201 9 11-02-201 10 11-02-201 11 11-02-201 Chapter Page 11 Project No. 121 December 201