SENTINEL D - Fault Passage Monitoring

Similar documents
SENTINEL A - Fault Passage Indicator

REA 105 Arc Protection Module. Operator s Manual

Cat. N. Cat. N (s) 1. DESCRIPTION - USE 3. OVERALL DIMENSIONS. Technology : 4. PREPARATION - CONNECTION 2. PRODUCT RANGE

1S25. Arc Fault Monitor 4 Zones, 8 Sensors. Features. Introduction. ARC Fault Protection

VAMP 120 & 121. Arc flash detection units. Product picture

VAMP 120 & 121. Arc Flash Protection Units. Arc Protection. Customer benefits

VAmP 120. Arc Flash Protection Units. Arc Protection. Customer benefits

7XG3120 ReyArc20 Arc Fault Monitor Relay Energy Management

ISOMETER IRDH375. Insulation monitoring device for unearthed AC, AC/DC and DC systems (IT systems)

Kickspot Self-testing/AutoDiag self-contained emergency lighting unit

Laboratory Honeywell Technology Solutions, Bangalore-EMC Lab, 19/2, Devarabisanahalli Village, K.R. Puram, Varthur Hobli, Bangalore, Karnataka

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Operation and use. Functions and characteristics

EARTH LEAKAGE RELAY. User Manual - Issue 1.0

Silent Alert Fire Safe System

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Early Streamer Emission Lightning Rod REMOTE TESTING

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

Instruction manual. Remote control electric IR HEATER

New Silent Alert Fire Safe System

MODEL: 47LPQ. Digital Panel Meters 47 Series. [3] ALARM OUTPUT 0: None 1: N.O. relay contact, 4 points 2: SPDT relay contact, 2 points

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

DUAL MONITORED INPUT/OUTPUT UNIT BN-305

1.7 A-ISOMETER IRDH575. RoHS. Dipl.-Ing. W. Bender GmbH & Co. KG Londorfer Str Grünberg Tel.: Fax:

BE1-50/51B with S1 Case or FT-11 sized Case and Cover For non-retrofit applications, see Product Bulletin UHD.

Universal fault annunciator for panel mounting

1. General Safety Block diagram Description of operation Connections Commissioning...11

TEMON 4-C. Doc. N MO-0368-ING TEMPERATURE MONITOR DEVICE TYPE TEMON 4-C OPERATION MANUAL. Microener- Copyright 2010 FW 2.1 Date Rev.

HIGH VOLTAGE A.C.(50 or 60Hz) CONTACT CAPACITIVE HIGH VOLTAGE DETECTOR

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

Product Catalogue. Safety Equipment. Capacitive Voltage Detectors and Voltage Detection Systems

setting up your wireless system P300W, C300W, D300W and wireless interface Standards NFS NFS EN 54-11

ISOMETER IR1575. Insulation monitoring device for unearthed AC/3(N)AC systems up to 480 V and DC systems up to 480 V

ISOMETER IRDH275BM-7 with coupling device AGH675-7 and AGH675-7MV15

INSTRUCTION MANUAL A121APPX, AL121APPX & MV121 APPELLO Alarm Tone and Voice Annunciation Sounder

Annunciator Unit SACO 16 D1. Product Guide

User Manual. Dryer Controller M720

INSTRUCTION MANUAL A105NAPPX & AL105NAPPX APPELLO Alarm Tone and Voice Annunciation Sounder

INSTRUCTIONS. Family 4 N 4062 Issue C Date 01/2011. CMV Certification reference NF205.

AQ 100 Series. Arc Flash Protection System

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

DPB52. True RMS 3-Phase, Multifunction monitoring relay. Benefits. Description

Refrigerated air dryers

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Audible warning devices for external alarm

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

Replaced by A5367CA. DISCONTINUED PRODUCT SMOKE DETECTOR WITH INTERCONNECT AND TIMER FEATURES

INSTRUCTION MANUAL T119 1MN0110 REV. 0. operates with ISO9001 certified quality system

EasyTronic III MANUAL SERVICE

Dryer Controller M720

TECHNICAL MANUAL SIRENS RF. Range of wireless sirens 869 MHz. Made in FRANCE. SIRYNX_RF Indoor siren. PILOTE_RF Interface emissor / receptor

Installation, Operating and Maintenance Manual

Secure WANDERING INSTALLATION AND USAGE GUIDE

TYBOX PAC. * _rev1* User guide. Programmable thermostat for heat pumps

DISCONTINUED PRODUCT. For reference only SMOKE DETECTOR WITH INTERCONNECT FEATURES. ABSOLUTE MAXIMUM RATINGS (Voltages are referenced to V SS

Annunciator unit. Application

Panel Mounted Fault Annunciator Series

VAMP 121. Arc protection unit. User manual

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

LAE10 LFE10. Use. Series 02

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

SDG&E Feeder Protection Philosophy:

ANEMOMETER 4403-RF-BAT

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

DEIF A/S. Technical Manual. Type EC-2 Engine Control Unit D. Technical Manual

7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for Infrastructure & Cities.

UV Flame Supervision System

EARTH FAULT METER MD-08

Flame Safeguards LFE10. Building Technologies HVAC Products

DGC-1000 DIGITAL GENSET CONTROLLER

Item Number Description Price. Accessories " Diesel/Water/Waste tank sender $ Battery temperature sensor $2.22

VdS SCHADENVERHÜTUNG. VdS-Rules for Intruder Alarm Systems

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

0-2 m/s Lo Alarm 0-6 m/s Hi Alarm Signal Stregth EASZ-12 Doppler Flow Switch Measuring Flow Worldwide

APPLICATION NOTE. Applying pressure sensing in arc flash protection applications with air magnetic circuit breakers

Guide Specification Model CTG Automatic Transfer Switch

Consultant Specification AGILE Wireless Fire Detection System

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on 24 V supply lines for medical locations SELVTESTER-24

Overhead lines detection Reminder on MV & HV lines DETECT LINE NG SKY NG RADIO DETECT LINE POMPIER SKY NACELLE POMPIER

WIRELESS MEASUREMENT SYSTEM OF GAS BOTTLES FILLING LEVEL WITH GAS LEAK DETECTION GMS 300. User Manual

Schedule of Accreditation issued by United Kingdom Accreditation Service 2 Pine Trees, Chertsey Lane, Staines-upon-Thames, TW18 3HR, UK

CTT8 TEMPERATURE MONITOR DEVICE

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

Scope of functions 32 VAR 51/37 64 DC 64 R

Forced draught gas burner

SEL Arc-Flash Solutions

4 & 8-POINT ANNUNCIATORS Instruction Manual

EKL3 short circuit and earth fault indicator

X803 ELECTRONIC CARD Control unit for generating sets OPERATING MANUAL

ZED UV Monitor PRO11DPI-I

DSS SERIES. Single Channel Hall Effect Speed Sensor. Product ID

Safety Standards for Electronic Products

Flame Safeguards LFE10. Building Technologies HVAC Products

Gas ventilation monitoring and control system

Panel Mounted Fault Annunciator Series

LINETRAXX VME420. Multi-functional relay for overvoltage, undervoltage and frequency monitoring in AC/DC systems with external supply voltage

Carbon Monoxide Transmitter

DSF xx15.xx xhv Ex-Atex Ex-Atex Certified Two wire Hall Effect Speed Sensor

Electrical rating 230V AC, 50Hz 100mA max per (maximum 35mA for originating unit with 16 Devices interconnected).

Transcription:

SENTINEL D - Fault Passage Monitoring DIRECTIONAL FAULT PASSAGE INDICATORS FOR OVERHEAD MV NETWORKS Installed on poles of overhead lines, the Overhead-Sentinel-D range allows locating the fault arisen on the MV network, whether they are single phase to earth, multi-phase, transient or permanent. It allows identifying quickly the failing section of network, by suppling : A blinking light for the permanent fault. A counting of all events (transient or permanent). The Sentinel-D is a fault indicator for overhead lines, adapted to all the earthing mode of the MV neutral : Network with arc suppressing coil (Petersen coil). Network with impedance earthing. Network with direct earthing. Network with isolated earthing. FRENCH PRODUCTION Enedis APPROVED > DESCRIPTION Functioning Directional detection The Overhead-Sentinel-D measures the electromagnetic field and the electric field supplied by the overhead line. The sensor integrated in the indicator provides an image of the residual current. Another sensor provides an image of the residual voltage. The detection is based on the analysis of the transient residual current and voltage when fault single phase to the earth occurs. HV - MV Substation The detector indicates in which geographic direction (downstream, upstream) the defect is located on the network. A fault passage indicator will flash if the capacitive current downstream to this detector is significant compared with the total capacitive current of the network. Uo Z Case 2 Case 1 Case 3 Amperemetric detection The Overhead-Sentinel-D includes a sensor that provides an image of the phase current flowing in the network. 1

> FAULT LOCALIZATION Single phase earth faults To HV-MV Substation Downstream fault OVERHEAD-SENTINEL-D The single-phase earth faults are indicated with only one color light. When all detectors are installed on the same face (ie on the same way that high voltage substation or on the opposite), the fault is located on the network section before the first detector : that changes color. or is not flashing because of a too low intake of capacitive current of the downstream section. Upstream fault Green Green Service Red or light off Dual and multi-phase faults They differ from other defects by double colors (alternating Red and Green). Only detectors located between the high voltage station and the defect flash. The fault is located on the network section between the last detector whose flashes and the first whose is not flashing. To HV-MV Substation Red Downstream fault Green Red Upstream fault Green Light off Service 2

> SIGNALLING FAULTS Flashing information The information of the presence of a fault that led to the definitive trip of feeder is indicated locally by a LED. The signalling is performed at a rate of one flash per second : Red flash in the event of a single-phase fault (or green if the fault is in the opposite direction) Alternately red flash and green flash in the event of a multi-phase fault or double fault to earth Flashing dedicated to remote control Two relay outputs (dry potential free contacts) copy the light signalling. These contacts (NO) allow to bring back fault information to an external application. These contacts are activated for 100 ms to the appearance of transient fault then, if the fault becomes permanent, the contacts are activated for the duration of the light signalling. Flashing of alarm «Equipment fault» A third relay output provides to an external application, information on the correct operation of the fault passage indicator. Two dry contacts («normally open» and «normally closed») are activated from the loss of supply of the fault passage indicator (end of autonomy of the rechargeable element - ultra capacitor - end of battery life) or in the event of processor failure (watchdog). It indicates that the detector is no longer operational : the NO contact opens the NC contact closes > HUMAN MACHINE INTERFACE The Overhead-Sentinel-D, in addition with its functions of detection and signalling, counts and returns the number of transient faults, semi-permanent and permanent of different types (single phase and multi phase). A «human-machine interface» consisting of a display and push buttons allows the user: Consultation of clear messages. Visualization of 3 fault counters. Configuration of different parameters and setting thresholds. METER READING In option, a radio remote control to access and configure the Overhead- Sentinel-D is available. It is fitted with the same keyboard than the local keyboard of the detector. Of a range of about twenty meters, remote control provides access to the same menu as the local display. It facilitates the configuration and consultation counters : Without leaving the vehicle. In inaccessible places. When the detector is installed at more than 2 m high. It uses standard batteries (2 LR06 alkaline AA 1.5V). 3

> INSTALLATION The Overhead-Sentinel-D is designed to be installed on electric poles of overhead lines. The supports can be concrete, wood or metal. The box is fixed to the pole height between 1.5 m and 3.5 m (2 m being the default position). The height between the floor and the lowest of the line wire shall be between 7 m and 14 m. The pole must be free of all vegetation high on a radius of 3 meters around the support. Warning : To maintain its sensitivity, the Overhead- Sentinel-D should not be installed : Less than 50 m from another MV line. Less than 200 m from HV line (<100kV) or railway. Less than 500 m from HV line (>100kV). Less than 50 m from an overheadunderground connection. 7 to 14 m OVERHEAD-SENTINEL-D Attention : The Overhead-Sentinel-D should not be installed in the following cases : On cross supports. On overhead-underground connection. On mix supports (with multiple networks HV, LV). 1.5 to 3.5 m The Overhead-Sentinel-D must be installed at the center of the pole in the center of the overhead line : Special case For the use of Overhead-Sentinel-D on a double support, the detector must be installed on a crossbar between two poles. 4

> OPERATION Display of fault counters The buttons " " and " " allow scrolling the display of 3 fault counters. Once these were read, the user has the ability to perform their reset. In addition to the default counters, the Overhead-Sentinel-D indicates the time since the last increment of each counter. This additional information : allows to know, after the extinction of the signals, if the Overhead-Sentinel-D has seen the fault. provides assistance for preventive maintenance of the HV line. When an unusual increase in the number of transient faults occurs, the Overhead-Sentinel-D provides valuable information on the section of the HV network causing these transient faults. With fault counters and this time information, it is possible to know which fault passage indicators have seen these faults and so, to identify the fault location before it causes a definitive trip. Example of using the fault counters to find the section causing transient faults. With timers, it is easy to identify the faulty section : HV Substation «Poly» (Multi-phase) Meter : 4 0 Day 1h51 min «Poly» (Multi-phase) Meter : 11 1 Year 163 Day «Poly» (Multi-phase) Meter : 15 0 Day 1h51 min «Poly» (Multi-phase) Meter : 8 120 Day 08h15 min METER READING Press on OK MULTIPHASE METER : 4 O J 1 H 51 MIN Press on or RED METER : 12 20 J 12 H 36 MIN Press on or GREEN METER : 8 20 Y 213 D Press on OK Press on OK Press on OK METER READING : 8 RAZ Meters? Press on or Press on OK RAZ meters 5

Fault display While fault searching,, the alphanumeric display can provide the operator, additional assistance by indicating clearly the type of fault, "multiphase", "double", "red phase" or " green phase ". The fault is stored as long as the MV voltage is absent. In the absence of fault, the Overhead-Sentinel-D indicates the presence or absence of MV voltage. Press on OK AUSCULTATION AUSCULTATION Present voltage Charge level of the ultra-capacitor (depending on model) OVERHEAD-SENTINEL-D Use this menu to check the charge level of the ultra-capacitor associated with photovoltaic panels. CHARGE CAPACITOR Press on OK CHARGE CAPACITOR Charge = 85 % Status of the fault passage indicator The «fault passage indicator status» menu allows for a diagnosis in an event of equipment failure of Overhead-Sentinel-D. INDICATOR STATUS Press on OK INDICATOR STATUS Indicator OK 6

> ELECTRICAL CHARACTERISTICS MV NETWORK Rated voltage U N Rated frequency Detection of single- phase earth faults Detection principle Sensitivity (Amplitude of the transient) SENTINEL - D Until 36 kv 50 Hz Directional (Transitory phenomenon analysis) Two threshold choices Residual current transient detection threshold (peak) : «Jeu1 : 30A», «Jeu2 : 60A»* Residual voltage transient detection threshold (peak) : «Jeu1 : 0.25Un», «Jeu2 : 0.55Un»* Validation voltage threshold (rms) : «Jeu1 : 0.1Un», «Jeu2 : 0.2Un»* Signalling Detection of dual single phase faults Detection principle Phase current detection threshold Handling time Signalling Detection of multi-phase faults Detection principle Phase current detection threshold Handling time Signalling Time delays Before a fault is counted (T delay) Before the indication of a permanent fault (T permanent) Voltage MV presence for «setting» the directional detection MV voltage return for clearing the current fault Indication External indicator light External contact Indication stopped Clearing the fault Through MV voltage return Voltage level Delay Stop of signalling with fault ever stored Through a front panel pushbutton Automatically after a time delay RED or GREEN depending on the direction Amperemetric (Max of current within a specified deadline) 250 A 100 ms RED or GREEN Amperemetric (Max of current within a specified deadline) 450 A 100 ms RED or GREEN 0.34 sec, 0.8 sec, 3 sec 1 sec, 10 sec, 20 sec ou 70 sec 5 sec 5 sec High brightness flashing LEDs Closing dry contact 0.5 Un 5 s 2h, 4h, 12h, 24h * «Jeu 1» and «Jeu 2» correspond to the threshold values that specify the single phase earth fault. For a 15 kv network, the current threshold decrease for one fourth. : «Jeu 1 : 22.5A», «Jeu2 : 45A». 7

> ENVIRONMENTAL CONDITIONS NORMS SENTINEL - D Mechanical Dimensions (W x H x D) Protection rating NF EN 60529 NF EN 62262 Vibrations NF EN 68068-2-6 320 x 260 x 140 mm IP 54 IK 09 Acceleration : 2g/ displacement : 0,15 mm (peak value) - 10 Hz to 500 Hz Climatical Operating temperature NF EN 60068-2-1 NF EN 60068-2-2-25 C to + 55 C Storage temperature NF EN 60068-2-14-40 C to + 70 C Relative humidity NF EN 60068-2-3 Tests Ca - 93% à 40 C 96h closed box, 4h opened box Salt mist NF EN 60068-2-11 178 h Dielectric strength Input voltage 12 V and dry contact ouputs compared to the box CEI 60255-5 2 kv - 50 Hz (1 mn) 5 kv shock (1,2/50 µs) OVERHEAD-SENTINEL-D Electromagnetic Dampened oscillating waves NF EN 61000-4-12 Fast transients NF EN 61000-4-4 Shock waves NF EN 61000-4-5 Electrostatic discharges NF EN 61000-4-2 Electromagnetic field-amplitude NF EN 61000-4-3 2.5 kv un common mode (100 khz et 1 MHz) 1 kv in differencial mode (100 khz et 1 MHz) 4 kv on power circuits 2 kv on other circuits 1 kv coupling between wires 2 kv coupling wire /ground Harshness 4 (8 kv contact discharge, 15 kv air discharge) 10 V / m 27 MHz to 6 GHz Power supply Battery self-sufficiency 3 lithium batteries 13Ah format D (not included) External supply 12V DC 12 V + 30% - 10% Solar panels save by ultra-capacitor 2.5 V maintenance free (15 years) MEDIUM VOLTAGE DIVISION CRDE, a society of Groupe CAHORS ZI des Grands Camps - BP 9 46090 Mercuès - FRANCE Tél. +33 (0)5 65 30 38 10 Fax +33 (0)5 65 20 09 17 8