Installation and Operation Manual

Similar documents
Installation & Operations Manual

Installation & Operations Manual

Engineering Data and Installation Manual

Engineering Data and Installation Manual

*20D082-05NN* 20D082-05NN

WARNING THIS SYSTEM UTILIZES A PRESSURIZED LOAD CIRCUIT. PLEASE ENSURE THE FOLLOWING:

Installation & Operations Manual

WARNING THIS SYSTEM UTILIZES A PRESSURIZED LOAD CIRCUIT. PLEASE ENSURE THE FOLLOWING:

Installation & Operations Manual

Installation, Operation & Maintenance: Packaged Horizontal, Vertical & Combination Series Units

INSTALLATION INSTRUCTIONS GEO PRIME TANK. (Patent Pending) GPC

Desuperheater Fitting Kit Installation Guide

DOUBLE O-RING GEO-PRIME TANK Non-Pressurized Flow Center System INSTALLATION INSTRUCTIONS. Model: DORGPT-1 NOTE:

3 TON Heating Performance Data TON Cooling Performance Data TON Heating Performance Data TON Cooling Performance Data...

OWNER S MANUAL. Vintage Signature Series models: AC750, AC1050, AC1100, AC1250, AC1500, AC1750. Proudly Made in the USA.

Installation & Operation Manual Hydronic

Installation, Operation & Maintenance: Field-Installed Electric Heater for RXT Series Units

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

OWNER S MANUAL. Vintage Classic HEAT COOL models. Proudly Made in the USA

AHWG Remote Mount Hot Water Generator Module

AHWG Remote Mount Hot Water Generator Module for TTP Series Outdoor Split Unit

EarthLinked HC Series Compressor Unit R-410A Quik-Start Instructions

OWNER S MANUAL. Models: AC110, AC125, AC150 made from 2003 through Proudly Made in the USA

EarthLinked SW Series Compressor Unit R-410A Quik-Start Instructions

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

EarthLinked SCW Series Compressor Unit R-410A Quik-Start Instructions

SuperStor Ultra Stainless Steel Storage Tank

SuperStor Glass Lined Storage Tank

Installation & Operation Manual Forced Air

Condensing Unit Installation and Operating Instructions

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Installation & Operation Manual Models: TSU

Installation, Operation and Maintenance Manual

Installation, Operating, and Maintenance Manual

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

Reinventing Energy Efficiency

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

INSTALLATION INSTRUCTIONS

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

Tranquility Coaxial Geothermal Open Loop Water-to-Water (TCW) Series

CAH SERIES INSTALLATION & MAINTENANCE MODELS CAH CAH

Installation and Service Manual. Hydronic Geothermal Heat Pumps

CH250 AND CH251 CHILLERS

Installation, Operating, and Maintenance Manual

Installation and Service Manual

EarthLinked CC Series Compressor Unit R-410A Quik-Start Instructions

Tranquility Brazed Plate Geothermal Closed Loop Water-to-Water (TBW) Series

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

WM-450-PT WM-900-PT Commercial Wall Mounted Reverse Osmosis

CHILLER. Operator s & Installation Manual

Installation & Operation Manual Models:

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers

Owner s Manual Therma-Stor II Heat Recovery System

G Series. G Series Air Coils Installation ti Manual ENCASED/UNCASED AIR COILS. Geothermal/Water Source Heat Pumps R-410A Refrigerant 2-5 Ton

EarthLinked SC Series Compressor Unit R-407C Quik-Start Instructions

WMHP Series R410a Heat Pump INSTALLATION INSTRUCTIONS

Water to Water Geothermal Heat Pump

water to water heat pumps

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

EXTREME 1 Reverse Osmosis System

TWINTEMP JR. HYDRONIC SYSTEM 2/2013

GENESIS WATER-TO-WATER (GSW) SERIES. Table of Contents

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762

Daikin Water Cooling, Heating, and High Capacity Booster Coils

Rev B, 9/2/2009. Kodiak Chiller Overview

Water-Cooled Dual Compressor Screw Chiller

PACKAGED AIR COOLED Product Data Catalog

INSTALLATION INSTRUCTIONS GPM SERIES LOOP PUMP MODULES

GOLD Plus 30/40/60/80

EXTREME HP-1 Reverse Osmosis System

Engineering Data and Installation Manual

G Series. G Series 7-25 Tons Installation Manual. Water Source/Geothermal Heat Pump Commercial 7-25 Tons. Installation Information

H 2. Hot Water Storage/ Booster Tanks. For Single Tank Installations INSTALLATION, OPERATION & MAINTENANCE MANUAL

Commercial Water Source Heat Pump Water Heater Operations and Installation Manual

Surna 25-Ton Chiller Operating & Maintenance Manual

Verde GSE PCA Bridge and Ground Mount Units 30/45/60/90/120 Tons. Installation and Maintenance Manual

J120 STEAM BOOSTER INSTALLATION, OPERATION, AND SERVICE MANUAL J120 STEAM BOOSTER. J120 Steam Booster Manual D

Ultra Classic (VT) Series Residential Vertical Two-Stage Geothermal Heat Pumps

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

INTRODUCTION THIS MANUAL INCLUDES IMPORTANT SAFETY INFORMATION

INSTALLATION INSTRUCTIONS & HOME OWNERS MANUAL ECO 18 ECO 24 ECO 27 IMPORTANT SAFETY INFORMATION

MAC-120HE-03 Air-Cooled Chiller

Hoshizaki America, Inc.

CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2)

SuperStor Contender Indirect Fired Water Heater

J-PRO V 230V Dual Voltage Hydrogen Peroxide Pump Installation & Start-Up Guide

Heating and Air Conditioning

CHILLER. Model CH3000. Operator s & Installation Manual

Condensing Unit Installation and Operating Instructions

EXTREME 4 Reverse Osmosis System

INSTALLATION & OPERATION MANUAL

J-PRO V 230V Dual Voltage Chlorinator Installation & Start-Up Guide

CommStat 6. Controller for Redundant HVAC Systems PRODUCT DATA SHEET

User s Information Manual

INSTALLATION MANUAL GEO-BOOST GROUND LOOP HEAT EXCHANGER

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

Owner s Manual PRINTED IN CANADA 05/2009

T-SERIES Air Conditioner. T43 Model INSTRUCTION MANUAL nvent Rev. I P/N

MACH N-407 Heat Pump Air-Cooled Chiller

Versatec Ultra Series Installation Manual

Transcription:

Installation and Operation Manual WT MODELS WATER-TO-WATER HEAT PUMPS REVISION C 20D218-09NN 20D218-09NN

Section 1: WT Water-To-Water Unit Model Nomenclature Unit Model Nomenclature... 3 Section 2: Installation Introduction Introduction. Inspection, Unit Protection, Storage, Pre-Installation and Components... 4-5 Section 3: Installation Considerations/Operations and Buffer Tanks Consumer Instructions, D-I-Y Policy, Equipment Installation... 6 Operation Considerations... 7 Buffer Tanks, Unit Placement and Pre-Installation... 8 Section 4: Unit Dimensional Data Unit Dimensional Data... 9 Section 5: Unit Piping Installation Open Loop Piping... 10 Water Quality... 11 Interior Piping... 12 Typical Pressurized Flow Center Installation... 12 Typical Non-Pressurized Flow Center Installation... 13 APSMA PUMP SHARING MODULE... 14 Section 6: Antifreeze Antifreeze Overview... 15-19 Section 7: Desuperheater Installation Typical Desuperheater Installation and Desuperheater Installation in Preheat Tank... 20 Section 8: Controls Features and Operations... 21-24 Wiring Diagrams... 25-33 Section 9: Equipment Start-Up Equipment Start-Up Form... 34 WPD Tables... 35-36 HE and HR Tables... 37-40 Equipment Start-Up Checklist... 41 Section 10: Troubleshooting Troubleshooting and Forms... 42-48 Section 11: Unit Electrical Data Unit Electrical Data... 49 Section 12: Warranty Forms and Revision Table Warranty Order & Claim Form... 50 Warranty Registration Form... 51 Revision Table... 52

Section 1: WT Water-To-Water Unit Model Nomenclature Unit Model Nomenclature 3

Section 2: Installation Introduction Introduction This geothermal heat pump provides heated water and chilled water as well as optional domestic water heating capability. Engineering and quality control is built into every geothermal unit. Good performance depends on proper application and correct installation. Notices, Cautions, Warnings, & Dangers: NOTICE Notification of installation, operation or maintenance information which is important, but which is NOT hazard-related. CAUTION Indicates a potentially hazardous situation or an unsafe practice which, if not avoided, COULD result in minor or moderate injury or product or property damage. WARNING Indicates potentially hazardous situation which, if not avoided, COULD result in death or serious injury. DANGER Indicates an immediate hazardous situation which, if not avoided, WILL result in death or serious injury. Inspection Upon receipt of any geothermal equipment, carefully check the shipment against the packing slip and the freight company bill of lading. Verify that all units and packages have been received. Inspect the packaging of each package and each unit for damages. Insure that the carrier makes proper notation of all damages or shortage on all bill of lading papers. Concealed damage should be reported to the freight company within 5 days. If not filed within 5 days the freight company can deny all claims. Note: Notify, LLC shipping department of all damages within 5 days. It is the responsibility of the purchaser to file all necessary claims with the freight company. Pre-Installation Special care should be taken in locating the geothermal unit. Installation location chosen should include adequate service clearance around the unit. All units should be placed on a formed plastic air pad, or a high density, closed cell polystyrene pad slightly larger than the base of the unit. If units are being placed on racking, the unit must be placed on a solid foundation. All units should be located in an indoor area where the ambient temperature will remain above 55 F and should be located in a way that piping and ductwork or other permanently installed fixtures do not have to be removed for servicing and filter replacement. CAUTION Do not operate the geothermal heat pump unit during building construction phase. Pre-Installation Steps: 1. Compare the electrical data on the unit nameplate with packing slip and ordering information to verify that the correct unit has been shipped. 2. Inspect all electrical connections and wires. Connections must be clean and tight at the terminals, and wires should not touch any sharp edges or copper pipe. 3. Verify that all refrigerant tubing is free of dents and kinks. Refrigerant tubing should not be touching other unit components. 4. Before unit start-up, read all manuals and become familiar with unit components and operation. Thoroughly check the unit before operating. Unit Protection Protect units from damage and contamination due to plastering (spraying), painting and all other foreign materials that may be used at the job site. Keep all units covered on the job site with either the original packaging or equivalent protective covering. Cap or recap unit connections and all piping until unit is installed. Precautions must be taken to avoid physical damage and contamination which may prevent proper start-up and may result in costly equipment repair. Storage All geothermal units should be stored inside in the original packaging in a clean, dry location. Units should be stored in an upright position at all times. Units should not be stacked unless specially noted on the packaging. 4

Section 2: Installation Introduction CAUTION All GEOTHERMAL equipment is designed for indoor installation only. DO NOT install or store unit in a corrosive environment or in a location where temperature and humidity are subject to extremes. Equipment is not certified for outdoor applications. Such installation will void all warranties. WARNING Failure to follow this caution may result in personal injury. Use care and wear appropriate PROTECTIVE clothing, safety glasses and protective gloves when servicing unit and handling parts. CAUTION Before drilling or driving any screws into cabinet, check to be sure the screw will not hit any internal parts or refrigerant lines. Components Master Contactor: Energizes Compressor and optional Hydronic Pump and/or Desuperheater pump package. Logic Board: Logic Board operates the compressor and protects unit by locking out when safety switches are engaged. It also provides fault indicator(s). Terminal Strip: Provides connection to the thermostat or other accessories to the low voltage circuit. Transformer: Converts incoming (source) voltage to 24V AC. Low Voltage Breaker: Attached directly to transformer, protects the transformer and low voltage circuit. Reversing Valve: Controls the cycle of the refrigerant system (heating or cooling). Energized in cooling mode. High Pressure Switch: Protects the refrigerant system from high refrigerant pressure, by locking unit out if pressure exceeds setting. Low Pressure Switch: Protects the refrigerant system from low suction pressure, if suction pressure falls below setting. Flow Switch (Freeze Protection Device): Protects the water heat exchanger from freezing, by shutting down compressor if water flow decreases. Compressor (Copeland Scroll): Pumps refrigerant through the heat exchangers and pressurizes the refrigerant, which increases the temperature of the refrigerant. Shipping Bolts: This unit is equipped with the new COMPRESSOR ISOLATION feature. Do not loosen or remove the bolts. 5

Section 3: Installation Considerations/Operations and Buffer Tanks Consumer Instructions Dealer should instruct the consumer in proper operation, maintenance, filter replacements, thermostat and indicator lights. Also provide the consumer with the manufacturer s Owner's Manual for the equipment being installed. D-I-Y Policy s geothermal heat pumps and system installations may include electrical, refrigerant and/or water connections. Federal, state and local codes and regulations apply to various aspects of the installation. Improperly installed equipment can lead to equipment failure and health/ safety concerns. For these reasons, only qualified technicians should install a built geothermal system. Because of the importance of proper installation, Enertech Global does not sell equipment direct to homeowners. Internet websites and HVAC outlets may allow for purchases directly by homeowners and do-it-yourselfers, but Enertech Global offers no warranty on equipment that is purchased via the internet or installed by persons without proper training. has set forth this policy to ensure installations of geothermal systems are done safely and properly. The use of well-trained, qualified technicians helps ensure that your system provides many years of comfort and savings. Equipment Installation Special care should be taken in locating the unit. All units should be placed on a formed plastic air pad, or a high density, closed cell polystyrene pad slightly larger than the base of the unit. All units should be located in an indoor area were the ambient temperature will remain above 55 F and should be located in a way that piping and ductwork or other permanently installed fixtures do not have to be removed for servicing and filter replacement. Loop Pumping Modules Must be wired to the heat pump s electric control box. A special entrance knockout is provided below the thermostat entrance knockout. A pump module connection block, connected to the master contactor, and circuit breaker is provided to connect the Pump Module wiring. Desuperheater Package Water heating is standard on all residential units (units may be ordered without). It uses excess heat during both heating and cooling cycles, to provide hot water for domestic needs. A double wall desuperheater exchanger (coil) located between the compressor and the reversing valve, extracts superheated vapor to heat domestic water; still satisfying its heating and cooling needs. The water circulation pump comes pre-mounted in all residential units, but must be electrically connected to the master contactor. Leaving it disconnected ensures that the pump will not run without a water supply. The Desuperheater package can make up to 60% (depending on heat pump usage) of most domestic water needs, but a water heater is still recommended. Desuperheater Piping All copper tubes & fittings should be 5/8 O.D (1/2 nom) minimum with a maximum of 50ft separation. Piping should be insulated with 3/8 wall closed cell insulation. Note: Copper is the only approved material for piping the desuperheater. Electrical All wiring, line and low voltage, should comply with the manufacturer's recommendations, The National Electrical Code, and all local codes and ordinances. Thermostat Thermostats should be installed approximately 54 inches off the floor on an inside wall in the return air pattern and where they are not in direct sunlight at anytime. 6

Section 3: Installation Considerations/Operations and Buffer Tanks Operation Considerations Enertech recommends the aquastat setting not be set above 110 F for the storage tank temperature. Excessive vibration and part failure can occur at higher than recommended temperature settings. The higher operating temperatures cause substantial efficiency and capacity reductions. The performance is negatively affected as the unit operates at the higher water temperatures and it benefits the unit and the homeowner to operate at or below the recommended water temperature of 110 F. With the lower efficiency created by higher water temperatures, the output capacity of the unit is decreased along with the efficiency. When operating at the higher entering water temperature the heat of extraction is significantly reduced, as well. In order to maintain the needed capacity, more of the heat is coming from the compressor working harder to compress the refrigerant. The illustration below shows the parameters which are safe for compressor operation. Based on the leaving load water of 120 F, the loop would have to maintain 35 F to operate within the acceptable operating conditions for the compressor. Once your loop temperatures drop below 35 F, the acceptable leaving load temperature drops below 120 F. If you are designing loops for 30 F, the recommended leaving load temperature is 110 F. Because the water-to-water machines have become so popular for providing heated water for a multitude of uses, we ve provided the above chart for reference. The obvious correlation is that the warmer the Source Entering Water Temperature, the hotter the Load Leaving Water Temperature can be, to a point. R410A can only handle up to about 125 F Load Leaving Water Temperature before putting the compressor at risk. Actual usage, and choices of heat distribution devices need to follow the acceptable operating conditions presented in the chart. If a question arises, please consult the Technical Services Department. 130 F SCROLL COMPRESSOR OPERATING CONDITIONS (WATER TO WATER) HEATING MODE OPERATION FAILURE ZONE Outside Safe Operating Range 125 F Load Leaving Water Temperature 120 F 115 F 110 F 100 F FAILURE ZONE Safety Factor Acceptable Operating Conditions Safety Factor Acceptable Operating Conditions Outside Safe Operating Range 10 F 15 F 20 F 25 F 30 F 35 F 40 F 45 F Source Entering Water Temperature 50 F 55 F 60 F 65 F 70 F 75 F 80 F 7

Section 3: Installation Considerations/Operations and Buffer Tanks Buffer Tanks Virtually all water-to-water heat pumps used for hydronic applications require a buffer tank to prevent equipment short cycling, and to allow lower flow rates through the water-towater unit than through the hydronic delivery system. The following are considerations for buffer tank sizing. The size of the buffer tank should be determined based upon the predominant use of the water-to-water equipment (heating or cooling). The size of the buffer tank is based upon the lowest operating stage of the equipment. For example, a waterto-water heat pump with a two-stage compressor or two compressors may be sized for first stage capacity, reducing the size of the tank (two-stage aquastat required). Pressurized buffer tanks are sized differently than nonpressurized tanks (see guidelines listed below). Pressurized buffer tanks for predominately heating applications should be sized at one (1) U.S. gallon per 1,000 Btuh of heating capacity (10 gallons per ton may also be used) at the maximum entering source water temperature (EST) and the minimum entering load water temperature (ELT), the point at which the water-to-water unit has the highest heating capacity, usually 50-70 F EST and 80-90 F ELT. For predominately cooling applications, pressurized buffer tanks should be sized at one (1) U.S. gallon per 1,000 Btuh of cooling capacity (10 U.S. gallons per ton may also be used) at the minimum EST and the maximum ELT, the point at which the water-to-water unit has the highest cooling capacity, usually 50-70 F EST and 50-60 F ELT. Unit Placement When installing a geothermal heating and cooling unit, there are several items the installer should consider before placing the equipment. 1. Service Access. Is there enough space for service access? A general rule of thumb is at least 2 feet in the front and 2 feet on at least one side. 2. Unit Air Pad. All geothermal heating and cooling equipment should be placed on either a formed plastic air pad, or a high density, closed cell polystyrene pad. This helps eliminate vibration noise that could be transmitted through the floor. 3. If units are being placed on racking, the unit must be placed on a solid foundation covering the full base of the unit. Also, utilize a foam pad between the unit and the rack. 4. The installer must verify that all applicable wiring, piping, and accessories are correct and on the job site. Pre-Installation Before you fully install the geothermal equipment, it is recommended you go through this quick checklist before placing the equipment. Fully inspect the unit after unpacking. Locate the Unit Start-Up form from this manual and have it available as the unit installation proceeds. Select the size of the tank based upon the larger of the calculations (heating or cooling). Non-pressurized buffer tanks must also be sized based upon predominate use (heating or cooling) and based upon the lowest capacity stage. Requirements for storage are less according to the manufacturer of the HSS series non-pressurized buffer tank. Using the same conditions for maximum heating and cooling capacity mentioned above, non-pressurized buffer tanks require 6 U.S. gallons per ton. 8

Section 4: Unit Dimensional Data Unit Dimensional Data 7.500 16.000 Out (Source Loop) Out (Load Loop) 2.000 Out (Load Loop) Out (Source Loop) I H G F In (Source Loop) In (Load Loop) HWG Water Out HWG Water In A H & I In (Source Loop) In (Load Loop) A E D FRONT VIEW Single Compressor F & G SIDE VIEW *Water Connection Option (Available on WT060 ONLY) B 2.000 HWG Water Out HWG Water In In (Load Loop #1) In (Load Loop #2) C E D F F2 G G2 In (Source Loop #1) In (Source Loop #2) Out (Source Loop) Out (Load Loop) A H I FRONT VIEW Dual Compressor Dimensions TOP VIEW Single Compressor Units Model Overall Cabinet HWG Water Load Water Source Water Load Loop Source Loop Factory Weight A B C D E F F2 I G G2 H IN OUT IN OUT Charge (oz) 036 24 26 34 2.83 5.83 8.83 N/A 17.83 11.83 N/A 14.83 1" 1" 1" 1" 315 65 048 24 26 34 2.83 5.83 8.83 N/A 17.83 11.83 N/A 14.83 1" 1" 1" 1" 345 73 060 24 26 36 2.83 5.83 8.83 N/A 17.83 11.83 N/A 14.83 1" 1" 1" 1" 390 101 060* See 24revision 32 D IOM 36for WT060. N/A N/A 4.16 N/A 21.10 4.16 N/A 21.10 1" 1" 1" 1" 410 101 Dual Compressor Units Model Overall Cabinet HWG Water Load Water Source Water Load Loop Source Loop Factory Weight A B C D E F F2 I G G2 H IN OUT IN OUT Charge (oz) 092 24 30 48 19.71 21.96 17.83 14.83 2.83 11.83 8.83 5.83 1" 1.25" 1" 1.25" 550 68 EA 120 24 30 48 19.71 21.96 17.83 14.83 2.83 11.83 8.83 5.83 1" 1.5" 1" 1.5" 670 76 EA 144 24 30 48 19.71 21.96 17.83 14.83 2.83 11.83 8.83 5.83 1" 1.5" 1" 1.5" 670 81 EA Notes: - *Side Connection Option available on WT060 ONLY - All models & brands (see exception below) use FPT fittings for all source & load loop connections. - Geocomfort, residential only, models 036-060 use 1" Double O-Ring fittings for source loop connections. - Dual Compressor: There are two "IN" connections, but only one "Out" Connection (Source & Load) - All Desuperheater connections are 3/4" FPT. - Electrical connections are 1" for high voltage, 1/2" for low voltage *All measurements are in inches. 9

Section 5: Unit Piping Installation Open Loop Piping Placement of the components for an open loop system are important when considering water quality and long term maintenance. The water solenoid valve should always be placed on the outlet of the heat pump, which will keep the heat exchanger under pressure when the unit is not operating. If the heat exchanger is under pressure, minerals will stay in suspension. Water solenoid valves are also designed to close against the pressure, not with the pressure. Otherwise, they tend to be noisy when closing. A flow regulator should be placed after the water solenoid valve. Always check the product specification catalog for proper flow rate. A calculation must be made to determine the flow rate, so that the leaving water temperature does not have the possibility of freezing. Other necessary components include a strainer, boiler drains for heat exchanger flushing, P/T ports and ball valves. Ball valves allow the water to be shut off for service, and also help when velocity noise is noticeable through the flow regulator. Spreading some of the pressure drop across the ball valves will lessen the velocity noise. Always double check flow rate at the P/T ports to make sure the ball valve adjustments have not lowered water flow too much, and essentially taken the flow regulator out of the equation. It s a good idea to remove the ball valve handles once the system is completed to avoid nuisance service calls. Hose kits are optional, but make for an easier installation, since the P/T ports and connections are included. The hose also helps to isolate the heat pump from the piping system. Since the heat pump can operate at lower water flow on first stage, two stage units typically include two water solenoid valves to save water. The flow regulators should be sized so that when one valve is open the unit operates at first stage flow rate, and when both valves are open, the unit operates at full load flow rate. For example, a 4 ton unit needs approximately 4 GPM on first stage, and approximately 7 GPM at full load. The flow regulator after the first valve should be 4 GPM, and the flow regulator after the second valve should be 3 GPM. When both valves are open, the unit will operate at 7 GPM. Figure 1: Open Loop Piping Example TYPICAL OPEN LOOP PLUMBING AND VALVE INSTALLATION EXAMPLE HEAT PUMP P/T Port (2 required) WYE Strainer Ball Valve (2 required) Optional Hose Kit* IN OUT S Single Speed Units From Well Flow Regulator** Discharge Line Boiler Drain for Heat Exchanger Maintenance (2 required) Water Solenoid Valve *Hose kit used for unit isolation, includes fittings for P/T ports. **See product specifications for flow rates. S S Two- Stage Units Note: All GWT, HWT, & TWT units are two-stage units. Not recommended for 3 ton and smaller. Use single solenoid and flow regulator. 10

Section 5: Unit Piping Installation Water Quality The quality of the water used in geothermal systems is very important. In closed loop systems the dilution water (water mixed with antifreeze) must be of high quality to ensure adequate corrosion protection. Water of poor quality contains ions that make the fluid hard and corrosive. Calcium and magnesium hardness ions build up as scale on the walls of the system and reduce heat transfer. These ions may also react with the corrosion inhibitors in glycol based heat transfer fluids, causing them to precipitate out of solution and rendering the inhibitors ineffective in protecting against corrosion. In addition, high concentrations of corrosive ions, such as chloride and sulfate, will eat through any protective layer that the corrosion inhibitors form on the walls of the system. Ideally, de-ionized water should be used for dilution with antifreeze solutions since de-ionizing removes both corrosive and hardness ions. Distilled water and zeolite softened water are also acceptable. Softened water, although free of hardened ions, may actually have increased concentrations of corrosive ions and, therefore, its quality must be monitored. It is recommended that dilution water contain less than 100 PPM calcium carbonate or less than 25 PPM calcium plus magnesium ions; and less than 25 PPM chloride or sulfate ions. In an open loop system the water quality is of no less importance. Due to the inherent variation of the supply water, it should be tested prior to making the decision to use an open loop system. Scaling of the heat exchanger and corrosion of the internal parts are two of the potential problems. The Department of Natural Resources or your local municipality can direct you to the proper testing agency. Please see Table 1 for guidelines. Table 1: Water Quality Potential Problem Scaling Corrosion Biological Growth Erosion Chemical(s) or Condition Calcium & Magnesium Carbonate Range for Copper Heat Exchangers Cupronickel Heat Exchanger Ranges Stainless Steel Heat Exchanger Ranges Less than 350 ppm Less than 350 ppm Less than 0.1 ppm ph Range 7-9 7-9 7-9 Total Dissolved Solids Less than 1000 ppm Less than 1500 ppm No rigid setpoint Ammonia, Ammonium Hydroxide Ammonium Chloride, Ammonium Nitrate Calcium/Sodium Chloride See Note 4 Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 0.5 ppm Less than 2-20 ppm Less than 125 ppm Less than 125 ppm Less then 0.5 ppm Chlorine Less than 0.5 ppm Less than 0.5 ppm Less than 1 ppm* Hydrogen Sulfide None Allowed None Allowed Less than 0.05 ppm Iron Bacteria None Allowed None Allowed None Allowed Iron Oxide Less than 1 ppm Less than 1 ppm Less than 0.2 ppm Suspended Solids - Note 5 Less than 10 ppm Less than 10 ppm Water Velocity Less than 8 ft/s Less than 12 ft/s * Chlorine can not be used with 304 Stainless Steel. 16-20 mesh strainer recommended Less than 5.5 m/s in the port Notes 1. Hardness in ppm is equivalent to hardness in mg/l. 2. Grains/gallon = ppm divided by 17.1. 3. Unit internal heat exchangers are not recommended for pool applications or water outside the range of the table. Secondary heat exchangers are required for pool or other applications not meeting the requirements shown above. 4. Saltwater applications (approx. 25,000 ppm) require secondary heat exchangers due to copper piping between the heat exchanger and the unit fittings. 5. Filter for maximum of 600 micron size. 11

Section 5: Unit Piping Installation Interior Piping All interior piping must be sized for proper flow rates and pressure loss. Insulation should be used on all inside piping when minimum loop temperatures are expected to be less than 50 F. Use the table below for insulation sizes with different pipe sizes. All pipe insulation should be a closed cell and have a minimum wall thickness of 3/8. All piping insulation should be glued and sealed to prevent condensation and dripping. Interior piping may consist of the following materials: HDPE, copper, brass, or rubber hose (hose kit only). PVC is not allowed on pressurized systems. Typical Pressurized Flow Center Installation The flow centers are insulated and contain all flushing and circulation connections for residential and light commercial earth loops that require a flow rate of no more than 20 gpm. 1-1/4 fusion x 1 double O-ring fittings (AGA6PES) are furnished with the double O-ring flow centers for HDPE loop constructions. Various fittings are available for the double O-ring flow centers for different connections. See figure 2 for connection options. A typical installation will require the use of a hose kit. Matching hose kits come with double O-ring adapters to transition to 1 hose connection. Note: Threaded flow centers all have 1 FPT connections. Matching hose kits come with the AGBA55 adapter needed to transition from 1 FPT to 1 hose. Table 2: Pipe Insulation Piping Material Insulation Description 1 IPS Hose 1-3/8 ID - 3/8 Wall 1 IPS PE 1-1/4 ID - 3/8 Wall 1-1/4 IPS PE 1-5/8 ID - 3/8 Wall 2 IPS PD 2-1/8 ID - 3/8 Wall Figure 2: Typical Single Unit Piping Connection (Pressurized Flow Center) To/From Loop Field ~~ Hose Kit Flow Center P/T Ports GSHP Source Water Out Source Water In IMPORTANT: Heat exchanger failures, flow center/pump failures, and other water-side component failures may not be covered under warranty if the failure is water quality-related. Enertech may require a water sample in some cases. Chemical make-up, as well as suspended solids must be considered at time of installation and service. All systems should be filtered when flushing/ purging the system. System fluid must include the proper inhibitors to protect the heat exchanger, pumps, and other water-side components. Enertech has a comprehensive solution for water treatment, as well as water test kits. Contact your Enertech representative for more details. Equipment Pad 2 Polyethylene Foam 12

Section 5: Unit Piping Installation Typical Non-Pressurized Flow Center Installation Standing column flow centers are designed to operate with no static pressure on the earth loop. The design is such that the column of water in the flow center is enough pressure to prime the pumps for proper system operation and pump reliability. The flow center does have a cap/seal, so it is still a closed system, where the fluid will not evaporate. If the earth loop header is external, the loop system will still need to be flushed with a purge cart. The non-pressurized flow center needs to be isolated from the flush cart during flushing because the flow center is not designed to handle pressure. Since this is a non-pressurized system, the interior piping can incorporate all the abovementioned pipe material options (see interior piping), including PVC. The flow center can be mounted to the wall with the included bracket or mounted on the floor as long as it is properly supported. Figure 3: Typical Single Compressor Unit Piping Connection Hydronic Fan Coil Shutoff Valve Make-up Water Line Backflow Preventer Pressure Reducing Valve Air Vent Water Out Water In Expansion Tank Check Valve To / From Earth Loop Radiant Infloor Heating Pressurized Storage Tank Shutoff Valves Out (Desuperheater) In (Desuperheater) Water to Water Heat Pump Out (Load Loop) Out (Ground Loop) In (Ground Loop) In (Load Loop) Figure 4: Typical Dual Compressor Unit Piping Connection Make-up Water Line Hydronic Fan Coil Shutoff Valve Backflow Preventer Pressure Reducing Valve Air Vent Water Out Water In Expansion Tank Check Valve Pressurized Storage Tank In (Load Loop #1) In (Load Loop #2) In (Ground Loop #1) In (Ground Loop #2) From Earth Loop Radiant Infloor Heating Out (Ground Loop) Out (Load Loop) Heat Pump To Earth Loop 13

Section 5: Unit Piping Installation Figure 5: Typical Storage Tank Piping For Radiant Floor Heating Radiant Infloor Zone 1 & 2 Storage Tank Water to Water Heat Pump Out (Load Loop) Shutoff Valves In (Load Loop) Check Valves Installed APSMA PUMP SHARING MODULE The pump sharing module, part number APSMA, is designed to allow two units to share one flow center. With the APSMA module, either unit can energize the pump(s). Connect the units and flow center as shown in Figure 6. Figure 7 includes a schematic of the board. The module must be mounted in a NEMA enclosure or inside the unit control box. Local code supersedes any recommendations in this document. Board Figure Layout 6: APSMA Module Layout 240VAC Power Source 240V IN 240V OUT 240VAC to Pump(s) Relay Relay 24VAC connection to unit #1 (Y1 & C From Thermostat) 24VAC 24VAC 24VAC connection to unit #2 (Y1 & C From Thermostat) Board Figure Schematic 7: APSMA Module Wiring Schematic 24VAC input from unit #1 DC Bridge + - LED Diode RY1 RY1 RY2 240VAC input 24VAC input from unit #2 + - Diode RY2 240VAC to pump(s) 14

Section 6: Antifreeze Antifreeze Overview In areas where minimum entering source temperatures drop below 40 F, or where piping will be routed through areas subject to freezing, antifreeze is required. Alcohols and glycols are commonly used as antifreeze. However, local and state/ provincial codes supersede any instructions in this document. In addition, the system needs antifreeze to protect the braze plate heat exchanger from freezing and rupturing. Freeze protection should be maintained to 15 F below the lowest expected entering loop temperature. For example, if 30 F is the minimum expected entering loop temperature, the leaving source temperature could be 22 to 25 F. Freeze protection should be set at 15 F (30-15 = 15 F). To determine antifreeze requirements, calculate how much volume the system holds. Then, calculate how much antifreeze will be needed by determining the percentage of antifreeze required for proper freeze protection. See Tables 3a and 3b for volumes and percentages. The freeze protection should be checked during installation using the proper hydrometer to measure the specific gravity and freeze protection level of the solution. Antifreeze Characteristics Selection of the antifreeze solution for closed loop systems require the consideration of many important factors, which have long-term implications on the performance and life of the equipment. Each area of concern leads to a different best choice of antifreeze. There is no perfect antifreeze. Some of the factors to consider are as follows (Brine = antifreeze solution including water): Safety: The toxicity and flammability of the brine (especially in a pure form). Cost: Prices vary widely. Thermal Performance: The heat transfer and viscosity effect of the brine. Corrosiveness: The brine must be compatible with the system materials. Stability: Will the brine require periodic change out or maintenance? Convenience: Is the antifreeze available and easy to transport and install? Codes: Will the brine meet local and state/provincial codes? The following are some general observations about the types of brines presently being used: Methanol: Wood grain alcohol that is considered toxic in pure form. It has good heat transfer, low viscosity, is non-corrosive, and is mid to low price. The biggest down side is that it is flammable in concentrations greater than 25%. Ethanol: Grain alcohol, which by the ATF (Alcohol, Tobacco, Firearms) department of the U.S. government, is required to be denatured and rendered unfit to drink. It has good heat transfer, mid to high price, is non-corrosive, non-toxic even in its pure form, and has medium viscosity. It also is flammable with concentrations greater than 25%. Note that the brand of ethanol is very important. Make sure it has been formulated for the geothermal industry. Some of the denaturants are not compatible with HDPE pipe (for example, solutions denatured with gasoline). Propylene Glycol: Non-toxic, non-corrosive, mid to high price, poor heat transfer in high concentrations, and potential for high viscosity when cold (in high concentrations). It has also been known to form a slime-type coating inside the pipe when inhibitors are not used. Do not use food grade glycol, since it does not include inhibitors. A 25% to 30% brine solution is a minimum concentration for required inhibitors, depending upon brand of glycol. If using a lower concentration (e.g. 20% provides 19 F freeze protection), additional inhibitors must be added. Note that some states/provinces have toxicity requirements that must be verified based upon the chemical composition of the inhibitors. IMPORTANT: Heat exchanger failures, flow center/pump failures, and other water-side component failures may not be covered under warranty if the failure is water qualityrelated. Enertech may require a water sample in some cases. Chemical make-up, as well as suspended solids must be considered at time of installation and service. All systems should be filtered when flushing/purging the system. System fluid must include the proper inhibitors to protect the heat exchanger, pumps, and other water-side components. Enertech has a comprehensive solution for water treatment, as well as water test kits. Contact your Enertech representative for more details. 15

Section 6: Antifreeze Figure 8: Antifreeze Specific Gravity 1.0500 1.0400 1.0300 Glycols are heavier than water (>1) Specific Gravity 1.0200 1.0100 1.0000 Pure water has a specific gravity of 1 0.9900 0.9800 Alcohols are lighter than water (<1) 0.9700 0.9600 0 5 10 15 20 25 30 Freeze Protection, deg F Ethanol Methanol Propylene Glycol Notes: 1. Consult with your representative or distributor if you have any questions regarding antifreeze selection or use. 2. Some antifreeze suppliers and manufacturers recommend the use of either de-ionized or distilled water with their products. Some brands are designed to work with tap water. Consult the antifreeze manufacturer s technical data. CAUTION Use extreme care when opening, pouring, and mixing flammable antifreeze solutions. Remote flames or electrical sparks can ignite undiluted antifreezes and vapors. Use only in a well ventilated area. Do not smoke when handling flammable solutions. Failure to observe safety precautions may result in fire, injury, or death. Never work with 100% alcohol solutions. 16

Section 6: Antifreeze Antifreeze Charging Calculate the total amount of pipe in the system and use (Table #3a) to calculate the amount of volume for each specific section of the system. Add the entire volume together, and multiply that volume by the proper antifreeze percentage needed (Table #3b) for the freeze protection required in your area. Then, double check calculations during installation with the proper hydrometer and specific gravity chart (Figure 7) to determine if the correct amount of antifreeze was added. Table #3a: Pipe Fluid Volume Type Size Volume Per 100ft US Gallons Type Size Volume Per 100ft US Gallons Copper 1 CTS 4.1 HDPE.75 SDR11 3.0 Copper 1.25 CTS 6.4 HDPE 1 SDR11 4.7 Copper 1.5 CTS 9.2 HDPE 1.25 SDR11 7.5 Additional component volumes: Unit coaxial heat exchanger = 1 Gallon Flush Cart = 8-10 Gallons 10 of 1 Rubber Hose = 0.4 Gallons HDPE 1.5 SDR11 9.8 HDPE 2 SDR11 15.4 Table #3b: Antifreeze Percentages by Volume Type of Antifreeze Minimum Temperature for Freeze Protection 10 F (-12.2 C) 15 F (-9.4 C) 20 F (-6.7 C) 25 F (-3.9 C) ProCool (Ethanol) 26% 23% 18% 13% Methanol 21% 17% 13% 5% Propylene Glycol* 30% 25% 20% 13% Heat Transfer Fluid (HTF) Mix according to manufacturer s directions on container label Antifreeze solutions are shown in pure form - not premixed HTF is a premixed Methanol solution *Concentrations below 25-30% (consult manufacturer) typically require additional inhibitors. 17

Section 7: Desuperheater Installation Desuperheater Installation Units that ship with the desuperheater function must be connected to the water heater/storage tank with the optionally offered Desuperheater Connection Kit or (as supplied by others) shown on the following sections of this manual. Note: Desuperheater capacity is based on 0.4 GPM Flow per nominal ton at 90 F entering hot water temperature. Note: Units that are shipped with a desuperheater do not have the desuperheater pump wires connected to the electrical circuit, to prevent accidentally running the pump while dry. Pump has to be connected to the electric circuit (master contactor) when the lines from the water heater are installed & air is removed. CONTENTS OF THE DESUPERHEATER FITTING KIT: (1) p/n 20D052-01NN, Installation Instructions (1) p/n 33P211-01BN, 3/4 x 3/4 x 3/4 FPT Brass Tee (1) p/n 33P210-01NN, ¾ Boiler Drain Valve (1) p/n 11080005001, ¾ MPT x 3-1/2 Brass Nipple (3) p/n 11080006001, ½ SWT x ¾ MPT Copper Adaptor (1) p/n 11080007001, ¾ x ¾ x ½ SWT Copper Tee Plumbing Installation Note: All plumbing and piping connections must comply with local plumbing codes. 1. Disconnect electricity to water heater. 2. Turn off water supply to water heater. 3. Drain water heater. Open pressure relief valve. WARNING To avoid serious injury, it is recommended that a anti-scald mixing valve is installed on the hot water supply line into the home. Even though hot water tank temperatures could appear to be set at lower levels, high temperature from the desuperheater could raise tank temperatures to unsafe levels. 4. Remove drain valve and fitting from water heater. 5. Thread the ¾ MPT x 3-1/2 nipple into the water heater drain port. Use Teflon tape, or pipe dope on threads. 6. Thread the center port of the ¾ brass tee to the other end of the nipple. 7. Thread one of the copper adaptors into the end of the tee closest to the heat pump. 8. Thread the drain valve into the other end of the nipple. 9. Above the water heater, cut the incoming cold water line. Remove a section of that line to enable the placement of the copper tee. 10. Insert the copper tee in the cold water line. 11. Thread the remaining two ½ SWT x ¾ MPT copper adaptors into the ¾ FPT fittings on the heat pump, marked HWG IN and HWG OUT. 12. Run interconnecting ½ copper pipe from the HOT WATER OUT on the heat pump, to the copper adaptor located on the tee at the bottom of the water heater. 13. Run interconnecting ½ copper pipe from the HOT WATER IN on the heat pump, to the copper tee in the cold water line. 14. Install an air vent fitting at the highest point of the line from step 13 (assuming it s the higher of the two lines from the heat pump to the water heater). 15. Shut off the valve installed in the desuperheater line close to the tee in the cold water line. Open the air vent and all shut off valves installed in the hot water hot. 16. Turn the water supply to the water heater on. Fill water heater. Open highest hot water faucet to purge air from tank and piping. 17. Flush the interconnecting lines, and check for leaks. Make sure air vent is shutoff when water begins to drip steadily from the vent. 18. Loosen the screw on the end of the desuperheater pump to purge the air from the pump s rotor housing. A steady drip of water will indicate the air is removed. Tighten the screw and the pump can be connected to the contactor or terminal block. 19. Install 3/8 closed cell insulation on the lines connecting the heat pump to the water heater. 20. Reconnect electricity to water heater. TIP: Measure the distance above the floor or shelf that the water heater is setting on, to where the drain valve is located. This distance must be greater than one-half the width of the tee you re about to install, or you won t be able to thread the tee on to the water heater. 18

Section 7: Desuperheater Installation Figure 9: Water Heater Connection Kit Assembly for Bottom of Water Heater NOTE: Drawing shown vertically for detail. Fitting installs horizontally into hot water tank. Connection to Hot Water Tank Copper Tee For Domestic Cold Water In Line Drain Brass Tee Adapter to Unit Water Line 19

Section 7: Desuperheater Installation Figure 10: Typical Desuperheater Installation Cold Water Supply Hot Water Shutoff Valves Air Vent Located at System High Point Water Heater (or Storage Tank) Heat Pump Drain Valve Shutoff Valves Desuperheater Out Desuperheater In 2 Polyethylene Equipment Pad Figure 11: Desuperheater Installation in Preheat Tank Hot Water Cold Water Supply Air Vent Located at System High Point Hot Water Cold Water Supply Shutoff Valves Water Heater No. 2 (or Storage Tank) Water Heater No. 1 (or Storage Tank) Heat Pump Drain Valve Drain Valve Shutoff Valves Desuperheater Out Desuperheater In 2 Polyethylene Equipment Pad 20

Section 8: Controls Microprocessor Features and Operation geothermal heat pump controls provide a unique modular approach for controlling heat pump operation. The control system uses one, two, or three printed circuit boards, depending upon the features of a particular unit. This approach simplifies installation and troubleshooting, and eliminates features that are not applicable for some units. A microprocessor-based printed circuit board controls the inputs to the unit as well as outputs for status mode, faults, and diagnostics. A status LED and an LED for each fault is provided for diagnostics. Removable low voltage terminal strips provide all necessary terminals for field connections. Not only are the thermostat inputs included, but there are also removable terminal strips for all of the accessory wiring for ease of installation and troubleshooting. Startup/Random Start The unit will not operate until all the inputs and safety controls are checked for normal conditions. At first power-up, the compressor is energized after a five minute delay. In addition, a zero to sixty second random start delay is added at first power-up to avoid multiple units from being energized at the same time. Short Cycle Protection A built-in five minute anti-short cycle timer provides short cycle protection of the compressor. Component Sequencing Delays Components are sequenced and delayed for optimum space conditioning performance and to make any startup noise less noticeable. Test Mode The microprocessor control allows the technician to shorten most timing delays for faster diagnostics by changing the position of a jumper located on the lockout board. Water Solenoid Valve Connections Two accessory relay outputs at the terminal strip provide a field connection for two types of water solenoid valves, a standard 24VAC solenoid valve, or a 24VAC solenoid valve with an end switch. Additional field wiring is no longer required for operation of the end switch. Loop Pump Circuit Breakers The loop pump(s) and desuperheater pump on single compressor units are protected by control box mounted circuit breakers for easy wiring of pumps during installation. Dual compressor units only protect the desuperheater pump but do not protect the loop or load side pumps. All loop and load side pumps must be wired externally using relays and circuit breakers supplied by others. Circuit breakers eliminate the need to replace fuses. Safety Controls The control receives separate signals for high pressure, low pressure, and low water flow. Upon a continuous 30-second measurement of the fault (immediate for high pressure), compressor operation is suspended (see Fault Retry below), and the appropriate LED flashes. Once the unit is locked out (see Fault Retry below), an output (terminal L ) is made available to a fault LED at the thermostat (water-to-water unit has fault LED on the corner post). Low Pressure: If the low pressure switch is open for 30 continuous seconds, the compressor operation will be interrupted, and the control will go into fault retry mode. At startup, the low pressure switch is not monitored for 90 seconds to avoid nuisance faults. High Pressure: If the high pressure switch opens, the compressor operation will be interrupted, and the control will go into fault retry mode. There is no delay from the time the switch opens and the board goes into fault retry mode. There is also no delay of switch monitoring at startup. Flow Switch: If the flow switch is open for 30 continuous seconds, the compressor operation will be interrupted, and the control will go into fault retry mode. At startup, the flow switch is not monitored for 30 seconds to avoid nuisance faults. Fault Retry All faults are retried twice before finally locking the unit out. The fault retry feature is designed to prevent nuisance service calls. There is an anti-short cycle period between fault retries. On the third fault, the board will go into lockout mode. 21

Section 8: Controls Over/Under Voltage Shutdown The lockout board protects the compressor from operating when an over/under voltage condition exists. The control monitors secondary voltage (24VAC) to determine if an over/ under voltage condition is occurring on the primary side of the transformer. For example, if the secondary voltage is 18VAC, the primary voltage for a 240V unit would be approximately 180V, which is below the minimum voltage (197V) recommended by the compressor manufacturer. Under voltage (<18VAC) causes the compressor to disengage and restart when the voltage returns to >20VAC. Over voltage (>31VAC) causes the compressor to disengage and restart when the voltage returns to <29VAC. Intelligent Reset If the thermostat is powered off and back on (soft reset), the board will reset, but the last fault will be stored in memory for ease of troubleshooting. If power is interrupted to the board, the fault memory will be cleared. Diagnostics The lockout board includes five LEDs (status, high pressure, low pressure, low water flow, condensate overflow) for fast and simple control board diagnosis. Below is a table showing LED function. When an O/U Voltage condition occurs, the board will initiate a fault, shut down the compressor, and start the five minute ASC period. All four fault LEDs will flash (HP + LP + FS + CO) and the thermostat Call For Service indicator will be illuminated. This feature is self-resetting. If voltage returns to normal range normal operation will resume if/when the ASC period is over (except if in lockout mode). If voltage is still out of range at the end of the ASC period the control will execute a Fault Retry. On the third fault within 30 minutes, the board will go into lockout mode and illuminate the Call For Service indicator. When normal operation is restored the four fault LED s will stop flashing and the Call For Service indicator will turn off. Table 4: LED Identification LED Color Location 1 Function Normal Operation Fault Retry 2 Lockout 2 Green Top High Pressure OFF Flashing 3 ON 3 Orange 2nd Low Pressure OFF Flashing 3 ON 3 Red 3rd Water Flow OFF Flashing 3 ON 3 Yellow Not applicable on water-to-water units Green Bottom Status Flashing 4 Flashing 5 Flashing 4 Notes: 1. Looking at the board when the LEDs are on the right hand side 2. If all five lights are flashing, the fault is over/under voltage 3. Only the light associated with the particular fault/lockout will be on or flashing. For example, if a high pressure lockout has occurred, the top green light will be on. The orange, red, and yellow lights will be off 4. Status lights will be off when in test mode 5. Flashes alternately with the fault LED 22

Section 8: Controls Hot Water Pump Control Controls for high water temperature and low compressor discharge line temperature prevent the hot water (desuperheater) pump from operating when the leaving water temperature is above 130 F, or when the compressor discharge line is too cool to provide adequate water heating. Lockout Board Jumper Selection The lockout board includes three jumpers for field selection of various board features. Water Solenoid Valve Delay (WSD) When the WSD jumper is installed, the A terminal is energized when the compressor is energized. When the jumper is removed, the A terminal is energized 10 seconds after the compressor. If using the Taco water solenoid valve (or a valve with an end switch), the unit terminal strip includes a means for connecting a valve of this type. The WSD jumper should be installed. If using a fast opening valve without an end switch, the jumper should be removed. Test Mode (TEST) When the TEST jumper is installed, the board operates in the normal mode. When the jumper is removed, the board operates in test mode, which speeds up all delays for easier troubleshooting. When service is complete, the jumper must be re-installed in order to make sure that the unit operates with normal sequencing delays. While test jumper is removed, the status (bottom green light) will remain off. Over/Under Voltage Disable (O/V) When the O/V jumper is installed, the over/under voltage feature is active. When the jumper is removed, the over/ under voltage feature is disabled. On rare occasions, variations in voltage will be outside the range of the over/ under voltage feature, which may require removal of the jumper. However, removal of the jumper could cause the unit to run under adverse conditions, and therefore should not be removed without contacting technical services. An over/under voltage condition could cause premature component failure or damage to the unit controls. Any condition that would cause this fault must be thoroughly investigated before taking any action regarding the jumper removal. Likely causes of an over/ under voltage condition include power company transformer selection, insufficient entrance wire sizing, defective breaker panel, incorrect transformer tap (unit control box), or other power-related issues. Figure 12: Lockout Board Layout CCG CC A C R Y L O WSD TEST O/V Lockout Board Sequence of Operation Water-to-Water Units, Single Compressor Heating (Y1) Water-to-Water Units, Single Compressor R2 R1 C2 C1 HP HP LP LP FS FS CO CO Status Heating first stage (Y1) The compressor (first stage) and loop/desuperheater pump(s) are energized 10 seconds after the Y1 input is received. Heating second stage (Y1, Y2) The compressor solenoid is energized immediately upon receiving a Y2 input, switching the compressor to full load. Cooling Operation The reversing valve is energized for cooling operation. Terminal O is connected to the reversing valve solenoid. Cooling first stage (Y1, O) The compressor (first stage) and loop/desuperheater pump(s) are energized 10 seconds after the Y1 input is received. Cooling second stage (Y1, Y2, O) The compressor solenoid is energized immediately upon receiving a Y2 input, switching the compressor to full load. 23

Section 8: Controls Sequence of Operation Water-to-Water Units, Dual Two-Stage Compressors (WT092 Only) Heating first stage (Y1) Compressor A is energized in first stage 10 seconds after the Y1 input is received. Compressor B is energized in first stage 10 seconds after Compressor A. Heating second stage (Y1, Y2) Both compressor solenoids are energized immediately upon receiving a Y2 input, switching the compressors to full load. Cooling Operation The reversing valve is energized for cooling operation. Terminal O is connected to the reversing valve solenoid. Cooling first stage (Y1, O) Compressor A is energized in first stage 10 seconds after the Y1 input is received. Compressor B is energized in first stage 10 seconds after Compressor A. Sequence of Operation Water-to-Water Units, Dual Single Stage Compressors (WT120 & WT144 Only) Heating first stage (Y1) Compressor A is energized 10 seconds after the Y1 input is received. Heating second stage (Y1, Y2) Compressor B is energized 10 seconds after the Y2 input is received. Compressor A remains energized. Cooling Operation The reversing valve is energized for cooling operation. Terminal O is connected to the reversing valve solenoid. Cooling first stage (Y1, O) Compressor A is energized 10 seconds after the Y1 input is received. Cooling second stage (Y1, Y2, O) Compressor B is energized 10 seconds after the Y2 input is received. Compressor A remains energized. Cooling second stage (Y1, Y2, O) Both compressor solenoids are energized immediately upon receiving a Y2 input, switching the compressors to full load. 24

Section 8: Controls Water-to-Water Unit, Two-Stage, Single Compressor Wiring Diagram 2 STAGE AQUASTAT R1 Y1 Y2 Note: On units lower than 8 tons, load side pumping is handled via connection to the loop pump terminals (i.e. the loop and load pumps can be powered from the unit as long as no more than three UP26-116 pumps are connected total (loop and load side). 25

Section 8: Controls Water-to-Water Unit, Two-Stage, Dual Two-Stage Compressor Wiring Diagram Note: Units 8 tons and larger are considered commercial size units and all pumping is handled from a separate electrical circuit outside of the unit 26

Section 8: Controls Water-to-Water Unit, Two-Stage, Dual Single Stage Compressor Wiring Diagram Note: Units 8 tons and larger are considered commercial size units and all pumping is handled from a separate electrical circuit outside of the unit 27

Section 8: Controls Water-to-Water Unit, Single, Two Stage Compressor, Three Phase, 460V, 60 HZ Wiring Diagram 2 STAGE AQUASTAT R1 Y1 Y2 28

Section 8: Controls Water-to-Water Unit, Two-Stage or Single Stage Compressor, Three Phase, 60HZ Wiring Diagram 29

Section 8: Controls Water-to-Water Unit, Dual Two Stage Compressors, Three Phase, 60 HZ Wiring Diagram Note: Units 8 tons and larger are considered commercial size units and all pumping is handled from a separate electrical circuit outside of the unit 30

Section 8: Controls Water-to-Water Unit, Dual Single Stage Compressors, Three Phase, 60HZ Wiring Diagram Note: Units 8 tons and larger are considered commercial size units and all pumping is handled from a separate electrical circuit outside of the unit 31

Section 8: Controls Water-to-Water Unit, Dual Two-Stage Compressors, Three Phase, 460V, 60HZ Wiring Diagram Note: Units 8 tons and larger are considered commercial size units and all pumping is handled from a separate electrical circuit outside of the unit 32

Section 8: Controls Water-to-Water Unit, Dual Single Stage Compressors, Three Phase, 460V, 60 HZ Wiring Diagram Note: Units 8 tons and larger are considered commercial size units and all pumping is handled from a separate electrical circuit outside of the unit 33

Section 9: Equipment Start-Up Equipment Start-Up Form EQUIPMENT START-UP FORM Customer Name: Customer Address: Model #: Serial #: Dealer Name: Distributor Name: Start-up Date: Loop Type: Open Closed (Circle One) Flow Rate Cooling Heating Unit Electrical Data Cooling Heating Source Water Pressure In PSI PSI Line Voltage V Source Water Pressure Out PSI PSI Total Unit Amps A A Source Water Pressure Drop PSI PSI Compressor Amps A A Flow Rate GPM GPM Wire Size GA *Check pressure drop chart for GPM Circuit Breaker Size A Source Water Temp. Difference Cooling Heating Source Water Temperature In ºF ºF Source Water Temperature Out ºF ºF Source Water Temperature Difference ºF ºF Heat of Rejection/Extraction Heat of Rejection Heat Of Extraction Cooling BTU/HR BTU/HR Load Water Temp. Difference Cooling Heating Load Water Temperature In ºF ºF Load Water Temperature Out ºF ºF Load Water Temperature Difference ºF ºF Cooling Heating ºF ºF ºF ºF ºF ºF Heating Heating Heating Heat of Extraction/Rejection = GPM X Water Temp. Difference X 500 (Water - Open Loop) Heat of Extraction/Rejection = GPM X Water Temp. Difference X 485 (Water & Antifreeze - Closed Loop) Air Temperature Difference Supply Air Temperature Return Air Temperature Air Temp. Difference *Confirm auxiliary heaters are de-energized for the above readings. Auxiliary Heat Operation Only Supply Air Temperature Return Air Temperature Air Temp. Difference Auxiliary Heat Electrical Data Line Voltage Total Amperage (Full kw - All Stages) Wire Size Breaker Size CFM = (Watts X 3.413) (Air Temp. Difference X 1.08) Watts = Volts X Auxiliary Heater Amps ºF ºF ºF V A GA A Installer/Technician: Date: 34

Section 9: Equipment Start-Up Water Pressure Drop Tables - Source Heat Exchanger Model WT036 Model WT048 Model WT060 Model WT092 Model WT120 Model WT144 Source Source Pressure Drop at Various Entering Source Temperatures (PSI) GPM 30 F 50 F 70 F 90 F 110 F 5.0 1.5 1.2 1.0 0.9 0.9 7.0 2.6 2.1 1.8 1.6 1.5 9.0 3.8 3.1 2.6 2.4 2.2 Source Source Pressure Drop at Various Entering Source Temperatures (PSI) GPM 30 F 50 F 70 F 90 F 110 F 6.0 0.7 0.6 0.5 0.6 0.6 9.0 2.2 1.8 1.6 1.8 1.9 12.0 4.0 3.2 2.9 3.2 3.4 Source Source Pressure Drop at Various Entering Source Temperatures (PSI) GPM 30 F 50 F 70 F 90 F 110 F 10.0 3.3 3.1 2.9 2.7 2.6 13.0 5.1 4.7 4.4 4.2 4.0 15.0 6.4 5.9 5.5 5.2 5.0 Source Source Pressure Drop at Various Entering Source Temperatures (PSI) GPM 30 F 50 F 70 F 90 F 110 F 12.0 1.4 1.3 1.2 1.1 1.2 18.0 2.9 2.6 2.4 2.3 2.4 24.0 4.8 4.3 4.0 3.8 3.9 Source Source Pressure Drop at Various Entering Source Temperatures (PSI) GPM 30 F 50 F 70 F 90 F 110 F 15.0 2.2 2.0 1.9 1.8 1.8 22.5 4.4 4.0 3.7 3.6 3.6 30.0 7.3 6.7 6.2 5.9 6.0 Source Source Pressure Drop at Various Entering Source Temperatures (PSI) GPM 30 F 50 F 70 F 90 F 110 F 17.8 2.3 2.2 2.2 2.0 2.0 24.9 4.4 4.1 3.9 3.6 3.6 32.0 7.0 6.6 6.2 5.8 5.7 35

Section 9: Equipment Start-Up Water Pressure Drop Tables - Load Source Heat Exchanger Load Pressure Drop at Various Entering Source Temperatures (PSI) Model Load GPM 40 F 45 F 50 F 85 F 95 F 110 F WT036 9.0 N/A N/A N/A 2.6 2.5 2.2 Load Pressure Drop at Various Entering Source Temperatures (PSI) Model Load GPM 40 F 45 F 50 F 85 F 95 F 110 F WT048 12.0 4.0 4.0 4.0 3.6 3.4 3.4 Load Pressure Drop at Various Entering Source Temperatures (PSI) Model Load GPM 40 F 45 F 50 F 85 F 95 F 110 F WT060 15.0 4.6 4.6 4.6 5.2 5.1 4.6 Load Pressure Drop at Various Entering Source Temperatures (PSI) Model Load GPM 40 F 45 F 50 F 85 F 95 F 110 F WT092 24.0 4.0 3.9 3.8 3.2 3.1 3.0 Load Pressure Drop at Various Entering Source Temperatures (PSI) Model Load GPM 40 F 45 F 50 F 85 F 95 F 110 F WT120 30.0 6.1 6.0 5.9 5.0 4.9 4.7 Load Pressure Drop at Various Entering Source Temperatures (PSI) Model Load GPM 40 F 45 F 50 F 85 F 95 F 110 F WT144 32.0 6.8 6.7 6.6 5.9 5.8 5.7 36

Section 9: Equipment Start-Up Heat of Extraction Tables - Heating Mode Analysis Model WT036 Model WT048 Model WT060 EST (deg F) 30 50 70 90 EST (deg F) 30 50 70 90 EST (deg F) 30 50 70 90 Heat of Extraction (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 85 F 95 F 110 F 5.0 25.4 23.5 19.8 7.0 26.4 24.6 20.8 9.0 26.6 24.7 20.9 5.0 35.6 33.6 29.4 7.0 36.9 34.9 30.7 9.0 37.1 35.1 30.9 5.0 47.9 45.8 40.9 7.0 49.4 47.2 42.4 9.0 49.8 47.6 42.8 5.0 55.2 52.9 47.7 7.0 56.9 54.5 49.4 9.0 57.2 54.9 49.6 Heat of Extraction (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 85 F 95 F 110 F 6.0 28.4 26.0 22.2 9.0 31.7 29.2 25.4 12.0 32.8 30.3 26.6 6.0 40.5 37.7 33.4 9.0 44.6 41.8 37.5 12.0 45.8 43.0 38.8 6.0 53.3 50.1 45.3 9.0 58.3 55.1 50.2 12.0 59.8 56.5 51.9 6.0 67.5 64.0 58.6 9.0 73.6 69.9 64.5 12.0 75.3 71.7 66.3 Heat of Extraction (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 85 F 95 F 110 F 10.0 35.8 32.5 27.5 13.0 37.8 34.5 29.6 15.0 38.7 35.5 30.6 10.0 51.2 47.6 42.2 13.0 53.7 50.0 44.6 15.0 55.0 51.3 45.9 10.0 66.2 62.0 55.8 13.0 69.2 65.0 58.9 15.0 70.8 66.6 60.4 10.0 83.8 79.0 72.2 13.0 87.4 82.7 75.7 15.0 89.3 84.5 77.6 37

Section 9: Equipment Start-Up Heat of Extraction Tables - Heating Mode Analysis Model WT092 Model WT120 Model WT144 EST (deg F) 30 50 70 90 EST (deg F) 30 50 70 90 EST (deg F) 30 50 70 90 Heat of Extraction (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 85 F 95 F 110 F 12.0 53.8 49.7 42.3 18.0 70.3 66.2 58.7 24.0 71.6 67.7 60.3 12.0 75.0 70.7 62.5 18.0 95.8 91.5 83.2 24.0 97.3 93.1 84.9 12.0 100.1 95.4 86.5 18.0 126.1 121.3 112.1 24.0 127.6 123.2 114.1 12.0 124.6 119.6 109.9 18.0 155.7 150.6 140.5 24.0 157.5 152.6 142.6 Heat of Extraction (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 85 F 95 F 110 F 15.0 69.1 63.8 54.7 22.5 74.2 69.1 60.2 30.0 76.7 71.7 62.8 15.0 98.1 92.2 82.1 22.5 104.3 98.7 88.7 30.0 107.5 101.9 92.0 15.0 128.1 121.7 110.4 22.5 135.5 129.3 118.1 30.0 139.4 133.2 122.0 15.0 158.3 151.3 138.8 22.5 166.9 160.1 147.8 30.0 171.6 164.7 152.4 Heat of Extraction (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 85 F 95 F 110 F 17.8 84.3 79.4 74.8 24.9 87.9 82.7 77.8 32.0 89.6 84.7 79.4 17.8 117.8 110.9 104.3 24.9 123.4 116.5 109.3 32.0 126.6 119.4 112.2 17.8 148.6 140.1 131.6 24.9 156.5 147.6 138.7 32.0 161.4 152.2 143.1 17.8 175.2 165.0 155.2 24.9 185.7 175.2 164.7 32.0 192.3 181.4 170.6 38

Section 9: Equipment Start-Up Heat of Rejection Tables - Cooling Mode Analysis Model WT036 Model WT048 Model WT060 EST (deg F) 50 70 90 110 EST (deg F) 50 70 90 110 EST (deg F) 50 70 90 110 Heat of Rejection (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 40 F 45 F 50 F 5.0 45.1 48.9 51.7 7.0 46.1 50.0 52.9 9.0 46.1 50.1 52.9 5.0 45.3 49.0 51.7 7.0 46.2 50.1 52.8 9.0 46.3 50.1 52.9 5.0 45.8 49.4 52.0 7.0 46.7 50.4 53.0 9.0 46.7 50.4 53.0 5.0 46.1 49.4 51.8 7.0 46.8 50.2 52.7 9.0 46.8 50.1 52.7 Heat of Rejection (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 40 F 45 F 50 F 6.0 51.7 55.2 58.7 9.0 54.0 57.8 61.5 12.0 57.3 61.4 65.4 6.0 49.8 53.1 56.3 9.0 51.9 55.3 58.7 12.0 54.9 58.6 62.3 6.0 48.0 50.9 53.8 9.0 49.7 52.7 55.9 12.0 52.2 55.5 58.8 6.0 47.9 50.6 53.3 9.0 49.2 52.0 54.8 12.0 51.3 54.4 57.4 Heat of Rejection (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 40 F 45 F 50 F 10.0 70.6 73.0 77.8 13.0 72.5 74.9 79.9 15.0 73.5 76.0 81.0 10.0 69.8 72.0 76.6 13.0 71.4 73.9 78.6 15.0 72.4 74.8 79.6 10.0 69.1 71.2 75.6 13.0 70.6 72.8 77.4 15.0 71.4 73.8 78.3 10.0 69.7 71.8 75.9 13.0 71.0 73.2 77.4 15.0 71.7 74.0 78.2 39

Section 9: Equipment Start-Up Heat of Rejection Tables - Cooling Mode Analysis Model WT092 Model WT120 Model WT144 EST (deg F) 50 70 90 110 EST (deg F) 50 70 90 110 EST (deg F) 50 70 90 110 Heat of Rejection (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 40 F 45 F 50 F 12.0 100.2 106.8 113.8 18.0 107.7 115.0 122.6 24.0 108.8 116.2 123.9 12.0 99.2 105.5 112.0 18.0 106.1 113.0 120.2 24.0 106.9 113.9 121.2 12.0 97.6 103.4 109.4 18.0 103.5 109.8 116.4 24.0 104.0 110.4 117.1 12.0 97.6 102.9 108.3 18.0 102.5 108.3 114.2 24.0 102.6 108.4 114.4 Heat of Rejection (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 40 F 45 F 50 F 15.0 107.3 114.8 122.5 22.5 111.6 119.5 127.7 30.0 114.9 123.1 131.5 15.0 107.8 115.0 122.3 22.5 111.6 119.1 126.9 30.0 114.5 122.4 130.4 15.0 107.6 114.1 121.0 22.5 110.6 117.5 124.7 30.0 113.1 120.3 127.7 15.0 106.5 112.3 118.4 22.5 108.5 114.7 121.1 30.0 110.5 116.9 123.5 Heat of Rejection (MBtuh) at Various Entering Load Source Temperatures (Load Flow Rate at 3 gpm/ton) GPM 40 F 45 F 50 F 17.8 145.7 155.1 164.3 24.9 146.2 155.4 164.8 32.0 146.9 156.4 165.6 17.8 141.8 150.8 159.9 24.9 142.3 151.5 160.7 32.0 143.1 152.3 161.2 17.8 136.5 145.1 154.1 24.9 137.2 145.9 154.6 32.0 137.5 146.2 155.1 17.8 129.8 138.3 146.4 24.9 130.4 138.5 146.9 32.0 130.4 1338.5 146.9 40

Section 9: Equipment Start-Up Equipment Start-Up Checklist Equipment Start-Up Process Check the following before power is applied to the equipment Caution: Do not start-up the unit until the new structure is ready to be occupied Electrical: Geothermal unit high voltage wiring is installed correctly Geothermal unit high voltage wiring and breaker are the correct size Auxiliary electric heaters are wired and installed correctly Circulating pumps are wired and fused (if necessary) correctly Desuperheater pump is NOT wired, unless piping is complete and all air is purged Low voltage wiring is correct and completely installed Plumbing: Pipe and pump sizes are correct Air is purged from all lines Antifreeze is installed All valves are open, including those on the flow center Condensate is trapped and piped to the drain Ductwork: Filter is installed and clean Packaging is removed from the blower assembly Blower turns freely Canvas connections installed on supply plenum & return drop Equipment Start-Up 1. Energize geothermal unit with high voltage. 2. Set the thermostat to Heat or Cool. Adjust set point to energize the unit. System will energize after delays expire (typically a five minute delay). 3. Check water flow with a flow meter (non-pressurized) or pressure drop conversion (pressurized). Pressure drop tables must be used to convert the pressure drop to GPM. The pressure drop can be obtained by checking water pressure in and water pressure out at the P/T ports. 4. Check the geothermal unit s electrical readings listed in the Unit Electrical Data table. 5. Check the source water temperature in and out at the P/T ports (use insertion probe). Allow 10 minutes of operation before recording temperature drop. 6. Calculate the heat of extraction or heat of rejection. 41 7. Check the temperature difference of the load coax (water-to-water) or air coil (water-to-air). P/T ports are recommended for use on the load side, but the line temperatures can be used to check the temperature difference. 8. Change the mode of the thermostat and adjust the set point to energize the unit. Check the data in opposite mode as the previous tests. Amp draws as well as temperature differences and flow rate should be recorded. 9. Check auxiliary heat operation by adjusting the thermostat set point 5 F above the room temperature in Heat mode or set thermostat to Emergency." Record voltage, amperage, and air temperature difference.

Section 10: Troubleshooting Performance Check Heat of Extraction(HE)/Rejection(HR) Record information on the Unit Start-up Form Equipment should be in operation for a minimum of 10 minutes in either mode WITH THE HOT WATER GENERATOR TURNED OFF. 1. Determine flow rate in gallons per minute a. Check entering water temperature b. Check entering water pressure c. Check leaving water pressure Once this information is recorded, find corresponding entering water temperature column in Specification Manual for unit. Find pressure differential in PSI column in Spec Manual. Then read the GPM column in Spec Manual to determine flow in GPM. 2. Check leaving water temperature of unit. FORMULA: GPM x water temp diff, x 485 (antifreeze) or 500 (fresh water) = HE or HR in BTU/HR A 10% variance from data tables in this manual is allowed. Always use the same pressure gauge & temperature measuring device. Water flow must be in range of data tables in this manual. If system has low or high water flow, performance problems should be expected 42

Section 10: Troubleshooting A: UNIT WILL NOT START IN EITHER CYCLE Thermostat Loose or broken wires Blown Fuse/ Tripped Circuit Breakers Low Voltage Circuit Water Flow (runs for 30 sec) Set thermostat on heating and highest temperature setting. Unit should run. Set thermostat on cooling and lowest temperature setting. Unit should run. Set fan to On position. Fan should run. If unit does not run in any position, disconnect wires at heat pump terminal block and jump R, G, Y. Unit should run in heating. If unit runs, replace thermostat with correct thermostat only. Tighten or replace wires. Check fuse size, replace fuse or reset circuit breaker. Check low voltage circuit breaker. Check 24 volt transformer. If burned out or less than 24 volt, replace. Before replacing, verify tap setting and correct if necessary. If water flow is low (less than 3.5 GPM), unit will not start. Make sure Pump Module or solenoid valve is connected (see wiring diagram). Water has to flow through the heat exchanger in the right direction (see labels at water fitting connections) before the compressor can start. If water flow is at normal flow, use an ohmmeter to check if you get continuity at the flow switch. If no switch is open and flow is a normal flow, remove switch and check for stuck particles or bad switch. B: UNIT RUNNING NORMAL, BUT SPACE TEMPERATURE IS UNSTABLE Thermostat Thermostat is getting a draft of cold or warm air. Make sure that the wall or hole used to run thermostat wire from the ceiling or basement is sealed, so no draft can come to the thermostat. Faulty Thermostat (Replace). C: NO WATER FLOW Pump Module Solenoid valve Make sure Pump Module is connected to the control box relay (check all electrical connections). For nonpressurized systems, check water level in Pump Module. If full of water, check pump. Close valve on the pump flanges and loosen pump. Take off pump and see if there is an obstruction in the pump. If pump is defective, replace. For pressurized systems, check loop pressure. Repressurize if necessary. May require re-flushing if there is air in the loop. Make sure solenoid valve is connected. Check solenoid. If defective, replace. D: IN HEATING OR COOLING MODE, UNIT OUTPUT IS LOW Water Load Side Flow Refrigerant charge Reversing valve Water flow & temperature insufficient. E: IN HEATING OR COOLING MODE, UNIT OUTPUT IS LOW Heat pump will not cool but will heat. Heat pump will not heat but will cool. Water heat exchanger System undersized Check speed setting, check nameplate or data manual for proper speed, and correct speed setting. Check for dirty air filter Clean or replace. Restricted or leaky ductwork. Repair. Refrigerant charge low, causing inefficient operation. Make adjustments only after airflow and water flow are checked. Defective reversing valve can create bypass of refrigerant to suction side of compressor. Switch reversing valve to heating and cooling mode rapidly. If problem is not resolved, replace valve. Wrap the valve with a wet cloth and direct the heat away from the valve. Excessive heat can damage the valve. Always use dry nitrogen when brazing. Replace filter/drier any time the circuit is opened. Reversing valve does not shift. Check reversing valve wiring. If wired wrong, correct wiring. If reversing valve is stuck, replace valve. Wrap the valve with a wet cloth and direct the heat away from the valve. Excessive heat can damage the valve. Always use dry nitrogen when brazing. Replace filter/drier any time the circuit is opened. Check for high-pressure drop, or low temperature drop across the coil. It could be scaled. If scaled, clean with condenser coil cleaner. Recalculate conditioning load. F: WATER HEAT EXCHANGER FREEZES IN HEATING MODE Water flow Flow Switch Low water flow. Increase flow. See F. No water flow. Check switch. If defective, replace. G: EXCESSIVE HEAD PRESSURE IN COOLING MODE Inadequate water flow Low water flow, increase flow. 43

Section 10: Troubleshooting H: EXCESSIVE HEAD PRESSURE IN HEATING MODE Load Side Flow I: WATER DRIPPING FROM UNIT Unit not level Condensation drain line plugged Water sucking off the air coil in cooling mode Water sucking out of the drain pan J: COMPRESSOR WON T START See E: Noisy blower and low air flow. Level unit. Unplug condensation line. Too much airflow. Duct work not completely installed. If duct work is not completely installed, finish duct work. Check static pressure and compare with air flow chart in spec manual under specific models section. If ductwork is completely installed it may be necessary to reduce CFM. Install an EZ-Trap or P-Trap on the drain outlet so blower cannot suck air back through the drain outlet. Check for proper compressor nameplate voltage. Attempt to restart the compressor OK OK Does Compressor draw current when voltage is applied. Check voltage supply & contactor operation. Yes OK Are the suction & discharge pressures balanced. No Check motor resistance. (See Note B) Yes No Check the wiring, capacitor & contactor operation. (See Note A) Allow time for compressor to balance. OK Allow to start the compressor while measuring voltage on the load side of the contactor. OK No Is the compressor hot? Yes Allow time for the protector to reset. Yes Recheck Resistance Not OK Replace Compressor OK Not Compressor Connection Block C R Voltage supply is too low. S Single Phase 208-230 C = Line Winding R = Run Winding S = Start Winding No OK Is the voltage 197 or higher when the compressor is trying to start. Yes If the compressor fails to start after 3 attempts, replace the compressor. A: Check all terminals, wires & connections for loose or burned wires and connections. Check contactor and 24 Volt coil. Check capacitor connections & check capacitor with capacitor tester. B: If ohm meter reads 0 (short) resistance from C to S, S to R, R to C or from anyone of one of these terminals to ground (shorted to ground), compressor is bad. K: COMPRESSOR WON T PUMP CHART Is th e c o m p re sso r run ning? Y es M easure & record th e am p s, volts, su ction & d isch arg e p ress u re. O K D o e s th e u n it h av e a refrig era n t c h arg e? Y es S hut th e unit d o w n & reverse the ph asing (3 -Phase O nly ) N o N o O K R efer to th e co m p resso r w o n 't start flo w ch art. A dd re frig eran t to th e sy stem. C h eck & v erify th e run ca p acito r O K If th e co m p resso r s till w o n 't pum p rep lace co m p re sso r. O K C h eck th e opera tio n o f th e rev ersing v a lv e. 44

Section 10: Troubleshooting Table 5: Refrigeration Troubleshooting System Faults Mode Discharge Pressure Suction Pressure Superheat Subcooling Air TD Water TD Compressor Amps Under Charge Over Charge Low Air Flow Low Source Water Flow Low Load Water Flow Restricted TXV TXV Stuck Open Inadequate Compression Heat Low Low High Low Low Low Low Cool Low Low High Low Low Low Low Heat High High/Normal Normal High High Normal High Cool High High/Normal Normal High Normal High High Heat High High/Normal Normal High/Normal High Low High Cool Low Low/Normal Low Normal High Low High/Normal Heat Low Low/Normal Low Normal High Low High/Normal Cool High High/Normal Normal High/Normal High Low High Heat High High/Normal Normal High/Normal High Low High Cool Low Low/Normal Low Normal High Low High/Normal Heat High Low High High Low Low Low Cool High Low High High Low Low Low Heat Low High/Normal Low Low Low Low High Cool Low High/Normal Low Low Low Low High Heat Low High High/Normal Low/Normal Low Low Low Cool Low High High/Normal Low/Normal Low Low Low Superheat/Subcooling Conditions Superheat Subcooling Condition Normal Normal Normal operation Normal High Overcharged High Low Undercharged High High Restriction or TXV is stuck almost closed Low Low TXV is stuck open 45

Section 10: Troubleshooting Table 6: Typical R-410A Unit Superheat/Subcooling Values EST Source Flow ELT @ 1.5 3 Load GPM/Ton Full Load Heating No Desuperheater Operation Discharge Suction Subcooling Superheat Source Brine Temp Drop Load Water Temp Rise F GPM/Ton F PSIG PSIG F F F F 50 158 217 52 72 8 23 17 26 4 8 4 16 70 222 288 60 80 5 21 14 23 4 8 4 17 30 3 80 257 326 62 83 4 19 13 22 4 8 4 17 90 295 368 64 84 3 19 12 22 4 8 4 17 100 337 415 65 86 3 19 12 21 3 7 4 16 50 165 224 76 98 10 25 13 23 6 10 6 20 70 231 298 87 110 7 23 11 21 6 10 6 21 50 3 80 267 338 91 114 6 22 10 20 6 10 6 21 90 307 381 93 116 5 21 10 19 6 10 6 21 100 350 429 95 117 5 21 9 19 5 9 6 21 50 171 232 103 124 11 27 12 23 8 12 8 24 70 240 308 118 139 9 24 10 21 8 12 8 26 70 3 80 278 349 123 144 8 23 10 20 8 12 8 26 90 318 394 126 147 7 23 9 20 8 12 8 26 100 363 444 128 149 7 23 9 20 7 12 8 25 50 176 237 128 149 13 28 16 27 10 14 9 28 70 246 315 146 167 10 26 15 25 11 15 10 30 90 3 80 285 357 151 173 9 25 14 25 11 15 10 30 90 327 404 155 176 9 24 14 25 10 14 10 30 100 373 454 157 179 8 24 14 25 10 14 10 29 EST Source Flow ELT @ 1.5 3 Load GPM/Ton Part Load Heating No Desuperheater Operation Discharge Suction Subcooling Superheat Source Brine Temp Drop Load Water Temp Rise F GPM/Ton F PSIG PSIG F F F F 50 156 213 55 76 9 22 14 25 4 8 4 17 70 216 279 61 82 6 19 12 23 4 8 4 17 30 3 80 251 318 64 84 5 19 12 22 4 8 4 17 90 290 360 66 87 4 18 11 21 3 8 4 17 100 332 406 68 89 4 18 10 21 3 7 4 17 50 163 221 81 102 9 24 11 21 7 11 6 22 70 226 290 90 111 6 22 9 19 7 11 7 22 50 3 80 262 330 94 115 5 21 8 18 7 11 7 23 90 302 373 97 118 4 21 7 18 6 10 7 23 100 346 421 100 121 4 21 7 17 5 10 6 22 50 170 229 110 131 11 26 9 19 9 14 8 27 70 235 300 122 143 8 23 7 18 10 14 9 28 70 3 80 273 341 126 148 7 23 7 17 9 14 9 28 90 314 387 131 152 6 22 6 17 9 13 9 28 100 359 436 134 156 6 22 6 17 8 13 9 27 50 177 236 141 163 12 27 10 20 12 16 11 32 70 244 309 156 177 9 25 8 19 13 17 11 34 90 3 80 283 352 162 184 8 24 8 18 12 17 11 34 90 326 400 167 189 7 24 8 18 12 16 11 34 100 373 451 172 194 7 23 8 18 11 15 11 33 46

Section 10: Troubleshooting Table 6: Typical R-410A Unit Superheat/Subcooling Values EST Source Flow ELT @ 1.5 3 Load GPM/Ton Full Load Cooling No Desuperheater Operation Discharge Suction Subcooling Superheat Source Brine Temp Rise Load Water Temp Drop F GPM/Ton F PSIG PSIG F F F F 45 161 205 65 96 7 18 12 25 6 11 5 15 50 163 207 71 103 7 18 12 25 7 12 5 17 50 3 60 167 211 87 120 8 19 11 23 8 13 7 20 70 171 215 102 138 8 19 11 23 10 15 8 22 90 176 220 116 154 9 21 22 34 11 17 9 25 45 225 271 69 100 7 18 11 24 6 11 4 15 50 228 273 75 107 7 18 11 24 7 12 5 16 70 3 60 233 278 91 125 7 19 10 22 8 13 6 19 70 238 284 108 144 8 19 10 22 9 15 7 21 90 246 292 122 161 9 20 22 33 11 16 9 24 45 303 350 72 102 6 18 11 24 6 11 4 13 50 306 353 78 109 6 18 11 23 7 11 4 15 90 3 60 313 360 95 128 7 18 10 22 8 13 6 17 70 320 367 112 147 7 18 11 22 9 14 7 19 90 330 377 127 164 8 19 22 35 10 16 8 22 45 393 442 74 104 5 17 12 24 6 10 3 12 50 397 446 81 112 5 17 12 24 6 11 4 13 110 3 60 406 455 98 131 5 17 11 23 7 12 5 15 70 415 464 115 151 6 17 12 23 8 13 5 17 90 428 477 131 168 6 18 24 37 10 15 7 19 EST Source Flow ELT @ 1.5 3 Load GPM/Ton Part Load Cooling No Desuperheater Operation Discharge Suction Subcooling Superheat Source Brine Temp Rise Load Water Temp Drop F GPM/Ton F PSIG PSIG F F F F 45 160 204 69 100 6 17 12 24 7 12 5 17 50 161 206 77 109 7 17 11 23 8 13 6 18 50 3 60 165 209 92 127 7 17 10 21 8 13 6 18 70 168 213 107 144 8 18 10 21 8 13 6 18 90 177 222 137 178 8 19 13 24 8 13 6 18 45 224 270 73 105 5 16 11 23 7 12 5 16 50 226 272 81 114 5 17 10 22 8 13 5 17 70 3 60 230 276 97 133 6 17 9 20 9 14 7 20 70 235 282 113 151 6 17 10 20 11 16 8 23 90 247 294 144 186 6 18 13 24 13 19 11 28 45 301 348 76 109 4 16 11 23 7 12 4 14 50 303 351 85 119 4 16 10 21 7 12 5 16 90 3 60 309 357 102 138 5 16 9 20 7 12 5 16 70 316 364 118 157 5 16 10 20 7 12 5 16 90 331 380 151 194 5 16 13 24 7 12 5 16 45 390 440 79 112 3 14 12 23 7 11 3 12 50 394 444 88 122 3 15 11 22 7 12 4 14 110 3 60 401 452 105 142 3 15 11 21 7 12 4 14 70 410 460 122 161 3 15 12 22 7 12 4 14 90 430 481 155 199 3 14 15 27 7 12 4 14 47

Section 10: Forms - Troubleshooting Customer/Job Name: Date: Model #: Serial #: Antifreeze Type: HE or HR = GPM x TD x Fluid Factor (Use 500 for water; 485 for antifreeze) GPM Load IN F psi F Liquid line (heating) To suction line bulb F Liquid line (cooling) SH = Suction Temp. - Suction Sat. SC = Disch. Sat. - Liq. Line Temp. To suction line Filter Drier Load Coax TXV For water-to-water units substitute a second coaxial heat exchanger for the air coil. F Load OUT psi Air Coil Reversing Valve psi Suction Line F (saturation) F Suction temp psi F Discharge Line (saturation) F Heating Mode Condenser Suction Evaporator Evaporator Suction Condenser Cooling Mode Optional desuperheater installed in discharge line (always disconnect during troubleshooting) psi Source (loop) IN Cut along this line Discharge Discharge Diagram A: Water-to-Water Unit (Cooling Mode) GPM F psi Source (loop) OUT Source Coax F GPM Load IN psi F Liquid line (heating) To suction line bulb F Liquid line (cooling) To suction line Filter Drier Load Coax TXV For water-to-water units substitute a second coaxial heat exchanger for the air coil. F Load OUT psi Air Coil Reversing Valve psi Suction Line F (saturation) F Suction temp psi F Discharge Line (saturation) F Heating Mode Condenser Suction Evaporator Evaporator Suction Condenser Cooling Mode Optional desuperheater installed in discharge line (always disconnect during troubleshooting) psi Source (loop) IN GPM Source Coax Discharge Discharge F Diagram B: Water-to-Water Unit (Heating Mode) psi Source (loop) OUT 48

Section 11: Unit Electrical Data Unit Electrical Data Model WT036 WT048 WT060 WT092 WT120 Voltage Code/ HWG Option 00 208/230 1 104.0 21.2 0.0 0.0 21.2 26.5 45 01 208/230 1 104.0 21.2 0.5 0.0 21.7 27.0 45 10 208/230 1 104.0 21.2 0.0 4.0 25.2 30.5 50 11 208/230 1 104.0 21.2 0.5 4.0 25.7 31.0 50 20 208/230 3 83.1 14.0 0.0 0.0 14.0 17.5 30 21 208/230 3 83.1 14.0 0.5 0.0 14.5 18.0 30 30/35 460 3 41.0 6.4 0.0 0.0 6.4 8.0 10 00 208/230 1 152.9 27.1 0.0 0.0 27.1 33.9 60 01 208/230 1 152.9 27.1 0.5 0.0 27.6 34.4 60 10 208/230 1 152.9 27.1 0.0 5.5 32.6 39.4 60 11 208/230 1 152.9 27.1 0.5 5.5 33.1 39.9 60 20 208/230 3 110.0 16.5 0.0 0.0 16.5 20.6 35 21 208/230 3 110.0 16.5 0.5 0.0 17.0 21.1 35 30/35 460 3 52.0 7.2 0.0 0.0 7.2 9.0 15 00 208/230 1 179.2 29.7 0.0 0.0 29.7 37.1 60 01 208/230 1 179.2 29.7 0.5 0.0 30.2 37.6 60 10 208/230 1 179.2 29.7 0.0 5.5 35.2 42.6 70 11 208/230 1 179.2 29.7 0.5 5.5 35.7 43.1 70 20 208/230 3 136.0 17.6 0.0 0.0 17.6 22.0 40 21 208/230 3 136.0 17.6 0.5 0.0 18.1 22.5 40 30/35 460 3 66.1 8.5 0.0 0.0 8.5 10.6 15 See Rev D. IOM for WT060 60 Hz Power Compressor HWG Pump Volts Phase LRA RLA FLA 00 208/230 1 152.9 ea. 27.1 ea. 0.0 0.0 54.2 61.0 80 01 208/230 1 152.9 ea. 27.1 ea. 0.5 0.0 54.7 61.5 80 10 208/230 1 152.9 ea. 27.1 ea. 0.0 0.0 54.2 61.0 80 11 208/230 1 152.9 ea. 27.1 ea. 0.5 0.0 54.7 61.5 80 20 208/230 3 110.0 ea. 16.5 ea. 0.0 0.0 33.0 37.1 50 21 208/230 3 110.0 ea. 16.5 ea. 0.5 0.0 33.5 37.6 50 30/35 460 3 52.0 ea. 7.2 ea. 0.0 0.0 14.4 16.2 20 00 208/230 1 178.0 ea. 28.3 ea. 0.0 0.0 56.6 63.7 90 01 208/230 1 178.0 ea. 28.3 ea. 0.5 0.0 57.1 64.2 90 10 208/230 1 178.0 ea. 28.3 ea. 0.0 0.0 56.6 63.7 90 11 208/230 1 178.0 ea. 28.3 ea. 0.5 0.0 57.1 64.2 90 20 208/230 3 136.0 ea. 19.2 ea. 0.0 0.0 38.4 43.2 60 21 208/230 3 136.0 ea. 19.2 ea. 0.5 0.0 38.9 43.7 60 30/35 460 3 66.1 ea. 8.7 ea. 0.0 0.0 17.4 19.6 25 20 208/230 3 149.0 ea. 22.4 ea. 0.0 0.0 44.8 50.4 70 WT144 21 208/230 3 149.0 ea. 22.4 ea. 0.5 0.0 45.3 50.9 70 30/35 460 3 75.0 ea. 10.6 ea. 0.0 0.0 21.2 23.9 30 Notes: 1. All line and low voltage wiring must adhere to the National Electrical Code and local codes, whichever is the most stringent. 2. In determining the correct supply wire size and maximum length, reference NFPA 70, Section 310. If the calculation is close to the maximum allowable ampacity of a particular wire size, use the next size up. This will ensure that no adverse effects occur, such as light dimming and/or shortened compressor life. 3. All fuses class RK-5. 4. Min/Max Voltage: 208/230/60 = 187-252, 460/60 = 432-504 5. See Wiring Diagrams for proper 460V power. *The external loop pump FLA is based on a maximum of three UP26-116F-230V pumps (1/2hp) for 048-144 and two pumps for 024-036. Proper Power Supply Evaluation: When any compressor bearing unit is connected to a weak power supply, starting current will generate a significant sag in the voltage reducing the starting torque of the compressor motor increasing the start time. This will influence the rest of the electrical system in the building by lowering the voltage to the lights. This momentary low voltage causes light dimming. The total electrical system should be evaluated by an electrician and HVAC technician. The evaluation should include connections, sizes of wires, and size of the distribution panel between the unit and the utility s connection. The transformer connection and sizing should be evaluated by the electric utility provider. CAUTION Check compressor Amp draw to verify compressor rotation on three phase units. Compare against Unit electrical tables Reverse rotation results in higher sound levels, lower amp draw, and increased compressor wear. The compressor internal overload will trip after a short period of operation. Ext. Loop Pump FLA Total Unit FLA Min Circuit AMPS Max Fuse HACR 49

Section 12: Warranty Forms Warranty Order & Claim Form WARRANTY ORDER & CLAIM PHONE : 618.664.9010 FAX : 618.664.4597 EMAIL : WARRANTY@ENERTECHGEO.COM ALL WARRANTY REGISTRATIONS SHOULD BE SUBMITTED WITHIN 10 DAYS OF INSTALLATION COMPANY NAME (Form submitter) DATE PHONE FAX EMAIL ORDERED BY JOB NAME/PO # UNIT Model # Serial # FAILURE DATE SHIP TO (If different than company) HOMEOWNER ADDRESS Required if claim is for defective flow center FLOW CENTER MODEL # FLOW CENTER SERIAL # FAILURE CODES, DESCRIPTION AND LABOR REIMBURSEMENT MUST BE FOUND IN WARRANTY MANUAL FAILURE CODE DESCRIPTION PART NUMBER LABOR REIMBURSEMENT REQUESTED NO YES DO YOU NEED PARTS ORDERED? NO (If no, and replacement was purchased from another vendor, attach copy of bill if reimbursement is needed 3.) YES OTHER NOTES FOR ENERTECH COMPANIES USE ONLY SRO# CREDIT MEMO# 1) See warranty coverage summary sheet for labor allowances, conditions and exclusions, etc. 2) Warranty start date is ship date from Enertech facility unless proof of startup is presented. 3) Outsourced warranty replacement parts will be reimbursed in the form of credit for the part only. Credit will be no more than the standard equivalent part cost through Enertech. 4) Factory pre-approval is required for anything outside the scope of this document. 5) Fuses, hose kits and items not mentioned on Warranty Coverage Summary are not covered under this program. 50

Section 12: Warranty Forms Warranty Registration Form WARRANTY REGISTRATION NOW REGISTER ONLINE AT WARRANTY-REGISTRATION.ENERTECHGEO.COM WARRANTY REGISTRATIONS SHOULD BE SUBMITTED WITHIN 60 DAYS OF INSTALLATION Model Number Serial Number Install Date This unit is performing Satisfactorily Not Satisfactorily (please explain) Purchaser/User Name Phone Address City State/Prov Postal Code Email Installer Company Name City State/Prov Email Application Residential New Construction Residential Geo Replacement Residential Replacement of Electric, Gas or Other Multi-Family (Condo/Townhome/Multiplex) Commercial Other Use (check all that apply) Space Conditioning Domestic Water Heating Radiant Heat Swimming Pool Snow/Ice Melt Other Loop Type Horizontal Loop Vertical Loop Pond Loop Open Loop Demographics Household Income Under $30,000 $30,000 $45,000 $45,000 $60,000 $60,000 $75,000 $75,000 $100,000 Over $100,000 Home Size Up to 1500 sq. ft. 1501 to 2500 sq. ft. 2501 to 4000 sq. ft. Over 4000 sq. ft. Home Location Rural Urban Suburban Value of Home Less than $100,000 $100,000 $250,000 $250,000 $500,000 $500,000 $1 mil Over $1 mil Customer Satisfaction How would you rate your overall satisfaction with your new geothermal system? 1 (Very Dissatisfied) 2 3 4 5 6 7 8 9 10 (Very Satisfied) How would you rate your overall satisfaction with your installing geothermal contractor? 1 (Very Dissatisfied) 2 3 4 5 6 7 8 9 10 (Very Satisfied) MAIL THIS FORM TO: EMAIL THIS FORM TO: FAX THIS FORM TO: ENERTECH GLOBAL LLC WARRANTY@ENERTECHGEO.COM ENERTECH GLOBAL LLC 2506 SOUTH ELM STREET 618.664.4597 GREENVILLE, IL 62246 REGISTER ONLINE AT: warranty-registration.enertechgeo.com Rev 30 DEC 2013B 51

Revision Table Date Description of Revision Page 06MAR2019 05MAR2019 Important note on heat exchangers added 12, 15 Layout changes made Layout changes made Revised WPD, HR and HE tables added 34-39 Updated antifreeze information to the latest data available 15-17 Updated inspection information 4 27DEC18 Operating Parameter Tables updated. 40, 41 02FEB18 Electrical Data Table updated 43 17JAN18 Air Handler info removed ALL 06SEPT2017 MPH Fan Chart updated 30 15FEB2017 Revised Electrical Data Table 49 20JUN16 Corrected drawing number reference, 4b 30 13JAN2016 Revised nomenclature and dimensional info 4, 14 03NOV2015 Added air coil installation info and sent VAF to purchasing for Mortex 11 24SEPT2015 Updated water quality table and notes for stainless steel and pool applications 16 18AUG2015 Revised fan speed table to include MPH024 (actually MPD 024 data) 30 14JUL2015 Updated Typical SH/SC table 47 10JUL2015 Inserted corrected electrical data table Updated dimensional drawings, fitting description 15JUN2015 Updated corrected dimensional drawings and tables 14 10JUN2015 Updated dimensional drawings and tables and Rev. B 14 12MAY2015 Adjusted table position for reveal 13 01FEB2015 Updated O/U control info 26 25FEB2015 Updated nomenclature 4 17DEC2014 Corrected DSH info 23-24 30APR2014 Corrected Air Handler Table 30 24FEB2014 Applied new format, revised table of contents, updated WT120 & WT144 AHRI extended data - full load only, wiring diagrams and on-line warranty registration form 31JUL2013 Added cased coils, superheat/subcooling conditions All 05JUN2013 Added 3Ph Wiring Diagrams 54-59 23MAY2013 Updated AHRI Data Tables 6-7 06MAR2013 Updated Loop Pump CB 46 15FEB2013 Updated Wiring Diagrams 52-53 28JAN2013 Updated Description 16 02NOV2012 Updated 144 AHRI Note 6-7 22MAY2012 Added Voltage Code 3 All 02MAR2012 Added Voltage Code 2 All 15FEB2012 Discontinued WT144 Single Phase Model All 20DEC2011 Discontinued WT026 All 11NOV2011 Updated 092-144 AHRI 6-7 28SEPT2011 Discontinued Models 034A - 070A All 28SEPT2011 Added Models 036B - 060B All 22AUG2011 First Published All Various Various 49 All 52

This Page Intentionally Left Blank 53

Greenville, IL - Mitchell, SD info@enertechgeo.com MEMBER is continually working to improve its products. As a result, the pricing, design and specifications of each product may change without notice and may not be as described herein. For the most up-to-date information, please visit our website, or contact our Customer Service department at info@enertechgeo.com. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties, but are merely s opinion or commendation of its products. 20D218-09NN ENERTECH GLOBAL, LLC 190306B