SERIES 35-63J APPLICATIONS FEATURES SPECIFICATIONS AGENCY CERTIFICATIONS

Similar documents
SERIES VAC Microprocessor-Based Intermittent Pilot Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Direct Spark Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION. Export Information (USA)

SERIES VAC Microprocessor-Based Direct Spark Ignition Control with Inducer Blower Relay FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION

SERIES VAC Microprocessor-Based Hot Surface Ignition Control FEATURES APPLICATIONS SPECIFICATIONS DESCRIPTION AGENCY CERTIFICATIONS

BGH Series Hot Surface Ignition Control

24 VAC Intermittent Pilot Gas Ignition Control

Hot Surface Ignition (HSI) System Booklet

INSTALLATION INSTRUCTIONS FOR SERIES 9 INTERMITTENT PILOT IGNITION CONTROL

24 VAC Direct Spark Gas Ignition

Quick Reference Guide. Application. Gas Furnaces Boilers Water Heaters Commercial Cooking. Features

50M Integrated Single or Two-Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

21D83M-843 Integrated Single Stage Furnace Control Replacement Kit INSTALLATION INSTRUCTIONS

Operator: Save these instructions for future use!

Operator: Save these instructions for future use!

50M56U-843 INSTALLER MUST READ DESCRIPTION PRECAUTIONS WARNING CAUTION

50A Integrated Furnace Control

50M56U-843 Universal Single Stage HSI Integrated Furnace Control Kit INSTALLATION INSTRUCTIONS

G779 Universal Intermittent Pilot Ignition Control

50A Integrated Furnace Control

CAUTION WARNING. 50T Integrated Furnace Control INSTALLATION INSTRUCTIONS DESCRIPTION PRECAUTIONS

Spark Electrodes/Flame Sensors

No. Of Ignition Trials: No. Of Re-Ignition Attempts. Reset by interrupting power for 5.0 Seconds. Diagnostic Output. Re-Ignition Limit Exceeded

Interrupted Ignition Series Oil Primary Control

Model 60200FR Gas Primary Control Data Sheet

CSD-1 COMMERCIAL BOILER CONTROLS

XIII Troubleshooting

EG & PEG Series 5 EGH Series 5

Model Universal Oil Primary Control

S9360A, S9361A, S9380A, S9381A Integrated Boiler Controllers

Y8610U Intermittent Pilot Retrofit Kit

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-SOLO-9/04

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

MG & SG SERIES BOILERS

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

L62GB BASO Safety Shutoff Device

SERVICE AND INSTALLATION MANUAL MODELS HDO(H) OIL FOR YOUR SAFETY

TECHNICAL SUPPORT: SERVICE BULLETIN #4 (v ) AB2017 HOT SURFACE IGNITION MODULE OVERVIEW

Indirect gas-fired air heater

S9361A, S9381A Integrated Boiler Controllers

Technical

LFL Series Burner Flame Safeguard Control

OWNER S MANUAL Manufactured Home Downflow Gas Furnace: MGD-B Series

R7910A SOLA (Hydronic Control) and R7911 SOLA (Steam Control) Systems

Packaged Gas/Electric Units. Owner s Guide to Operating and Maintaining Your Gas/Electric Unit

USER S INFORMATION MANUAL

USER'S INFORMATION MANUAL

USER'S INFORMATION MANUAL

50M TYPICAL WIRING DIAGRAM 24 VAC CLASS II TRANSFORMER 24 VAC 50M COOL PARK HEAT LO HEAT HI LINE XFMR EAC HUM

S9360, S9361, S9370, S9371 Integrated Boiler Controllers

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

DOMESTIC HOT WATER Follow operational sequence

TECHNICAL SERVICE DEPARTMENT Technical Service Bulletin Ultra Low NOx PowerVent with Honeywell Electronic Control California Only

24 VAC SYSTEM CONTROL KIT

Service Handbook COMMERCIAL GAS WATER HEATERS

GAS UNITS KITS AND ACCESSORIES 505,172M 08/06

2017 OUTDOOR CONTROL SYSTEM WEATHER BEATER ELECTRONIC CONTROL SYSTEM

7800 SERIES Relay Modules

New Power Vented Rheem FVIR Tanks

EGH Series 5. Control Supplement. EGH-105 to EGH-125 Natural gas CSD-1 control system

EUROBOX SERIES TYPES CM... SM... MM...

A-1106 ACCESSORY KIT INSTALLATION INSTRUCTIONS IGNITION CONTROL P/N S , S , S

LGA... Gas Burner Controls. Siemens Building Technologies HVAC Products

USER'S INFORMATION MANUAL

Technical

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

40 Residential Gas Furnace Operation

RM7895A,B,C,D/EC7895A,C; RM7896A,B,C,D 7800 SERIES Relay Modules

COMMERCIAL GAS WATER HEATERS

GAS FIRED COMMERCIAL COPPER BOILERS

OBSOLETE. Y8610U Intermittent Pilot Retrofit Kit GENERAL FEATURES PRODUCT DATA. Contents

Y8610U Intermittent Pilot Retrofit Kit

95M-200. Gas-Fired Direct Vent Modulating Hot Water Boiler. Control Manual And Troubleshooting Guide. P/N , Rev.

Q - Series Boiler. Troubleshooting Manual

southbend A MIDDLEBY COMPANY INSTALLATION AND OPERATION MANUAL CG214 (E) CG314 (E) CG414 (E) CG220 (E) CG320 (E) CG325 (E) GAS BOILERS MODELS:

BC-R10 Series. Burner Controllers

prestige Condensing Water Boiler SERVICE TECHNICIAN S TROUBLE SHOOTING GUIDE TSG-PRESTIGE Date revised: 11/10/08

USER'S INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

Technical

EUROFLAT SERIES TYPES C... S... M...

24 VAC SYSTEM CONTROL KIT

SERVICE FACTS WARNING M801-SF-1C. Gas Furnaces Upflow & Downflow Induced Draft 1 Stage Heat Models: DISCONNECT POWER BEFORE SERVICING M801P040AU24AA

Q7800H Integrated Burner Control Subpanel

WARNING WARNING TROUBLESHOOTING GUIDE INTEGRATED FURNACE CONTROL MODULE

EUROBOX SERIES TYPES CM...N SM...N MM...N

Pilot Burner and Direct Spark Ignition (DSI) Applications with Flame Rectification Sensing

SV9520H SmartValve System Control Line Voltage Polarity Sense Models

Figure 10 or Figure 6

DC50X2 Models 50 Pound Stacked Commercial Dryer. Troubleshooting,Fault Codes, and Schematics. Starting serial number Part # /13

CUSTOMER SPECIFICATION

USER S INFORMATION MANUAL (2,4)SG13B

X341119P10 Gas Furnace Var. Speed Blower Var. Speed Inducer Two Stage Heat Direct Vent Models:

R7120M 7800 SERIES Relay Modules

59MN7A Series 100 TROUBLESHOOTING GUIDE

SLANT/FIN AUTOMATIC VENT DAMPER For Galaxy, Sentinel and Sentry Series Boilers INSTALLATION INSTRUCTION MANUAL AND TROUBLESHOOTING GUIDE

Transcription:

SERIES 35-63J INSTALLATION INSTRUCTIONS FOR REPLACING JOHNSON CONTROLS G77X AND OTHER MODELS WITH FENWAL SERIES 35-63J IP IGNITION CONTROL APPLICATIONS The Fenwal 35-63J series Intermittent Pilot Ignition Control (35-63J) is a microprocessor based ignition control suitable for replacing many existing intermittent pilot ignition controls from various manufacturers. The 35-63J is a direct form, fit, and functional replacement for the discontinued Johnson G77x series controls. The 35-63J is available in a number of timing configurations that match popular G77x applications providing a better solution than a universal type aftermarket control. The most common applications are listed in Control Cross Reference on page 2. The 35-63J is suitable for many types of heating applications including commercial cooking, furnaces, boilers, and water heaters that require intermittent pilot ignition, burner supervision through flame rectification, and safety shutoff. It is designed for use with Natural, LP, and mixed gases used in gas-fired appliances. The microprocessor circuit design of the 35-63J provides precise, repeatable timing and operating sequences. High energy spark output and excellent flame sense characteristics provide reliable burner operation. The on-board diagnostics with LED output make troubleshooting easy and ensure safe and efficient operation. FEATURES Safe start and full-time flame sensing Wide variety of prepurge and interpurge timings Single or three trials for ignition Diagnostic LED with Fenwal error codes Three ground terminals for ease of wiring Remote or local flame sense options Automatic 5 min or 1 hour reset after lockout options AGENCY CERTIFICATIONS Input Power Input Current Drain Main Gas Valve Pilot Gas Valve SPECIFICATIONS Control: 18-30 VAC 50/60 Hz (Class 2 Transformer) 200 ma @ 24 VAC with gas and pilot relays energized (Control only) 2.0A max (continuous) 2.0A max (continuous) Operating Temperature -40 F to + 176 F (-40 C to +80 C) Storage Temperature -40 F to + 185 F (-40 C to +85 C) Flame Sensitivity Flame Failure Response or Reignition Time Flame Detector Self-check Rate Flame Failure Lockout Time Types of Gas 0.3 μa minimum 0.8 seconds minimum Once per second minimum Varies by model, 500 seconds maximum Natural, LP, or manufactured CSA Design certified to ANSI Z21.20, CAN/CSA C22.2 No. 199-M99 Spark Rate Size (LxWxH) Moisture Resistance Tries for Ignition Trial for Ignition Periods Pre-purge Timings Inter-purge Timings Remote sense (50/60 Hz) Local sense (25/30 Hz) 4.70 x 3.10 x 2.50 inches (11.94 x 7.87 x 6.35 cm) Conformal coated to operate noncondensing to 95% R.H. One or three try versions available 8, 25, 50, 85, and 120 seconds available None, 4,15, or 30 seconds available None, 15, 30, or 45 seconds available 06-237172-001 Rev AA

CONTROL CROSS REFERENCE Manufacturer/ Model Number Johnson Controls Fenwal Replacement MOUNTING AND WIRING The 35-63J is not position sensitive and can be mounted vertically or horizontally. The case may be mounted on any surface with #6 sheet metal screws. G770KGA-1,3 G770KHA-2 G770LGA-1,2 G770LGC-1,2,3,4,10 G770LHA-1,2 35-63J101-011 35-63J101-011 The control must be mounted and located in a manner which protects components from exposure to water (dripping, condensate, spraying, rain). Any control that has been exposed to water must be replaced. G770LHC-1 G770MGA-1,2,5 G770MHA-2 35-63J101-015 35-63J101-015 All wiring must be done in accordance with both local and national electrical code. Wiring must be at least #18 AWG rated for 105 C or higher. G770MGC-1,3 G770MHC-1 35-63J101-415 35-63J101-415 The 35-63J uses voltages of shock hazard potential. Wiring and initial operation must be done by qualified service technician. G770NGA-1 G770NGC-4,5,6,7 G770NHA-1 G770NHC-1 G770RHA-2 G77RJA-1 G775RGA-1,2,3 G775RHA-1,2 G775RJD-1,2,13,14,15 G776RGD-11,14 G775LHA-1 (remote flame sense) G779LHA-1 Universal (set-up for Remote flame sense) G779LHA-1 Universal (set-up for Local flame sense) 35-63J103-117 35-63J303-117 35-63J102-013 JCI G77x Operation outside specifications could result in failure of the Fenwal product and other equipment with injury to people and property. Wiring Terminal Names Fenwal 35-63J Description 2 THS THS Thermostat Input 1 PV PV Pilot Valve Power 3 MV MV Main Valve Power Ground Plate _GND Valve Ground Ground Plate GND_ Valve Ground Ground Plate GND System Ground BLIND BLIND No Connection INSTALLATION GUIDELINES 4 SENSE SENSE Remote Flame Sensor CAUTION Label all wires prior to disconnection when servicing or replacing controls. Wiring errors can cause improper and dangerous operation. A functional checkout of a replacement control should always be performed. HIGH VOLTAGE TERMINAL CONNECTION The Fenwal 35-63J uses a Rajah (spark plug) type HV connection which is common to most controls. If the control being replaced does not utilize a Rajah connection, the HV spark cable will need to be replaced or re-terminated using a Rajah style female mating connector. 2 06-237172-001 Rev AA

ROLLOUT SWITCH Some control applications may have a separate rollout switch directly connected to the old ignition control. In this case, the rollout switch (normally closed) should be connected directly to the THS terminal on the 35-63J. Verify the rollout switch is wired in series (downstream) with the thermostat signal. The old THS wire should be left unconnected and insulated to prevent the possibility of a short-circuit. VENT DAMPER CONNECTIONS The 35-63J does not include an integral vent-damper connector. When replacing an older control (in applications using a vent damper) that has a standard 6-pin vent damper plug, the vent damper wires from the plug must be re-terminated and connected as follows: 35-63J THS PV MV _GND GND_ 5 2 Pilot Gas Valve Vent Damper 4 1 Thermostat Main Gas Valve Note: If the old control has a vent damper plug (with a jumper between pins 2 and 3), but the heating appliance has no vent damper, then ignore this section. GND Blind_Term Sense H.V. Pin # on Damper Plug System Connection Pilot 24 VAC 1 Full-time 24VAC Hot 2 Call for Heat signal (from damper) 3 Fused 24 VAC (not used) 4 24VAC Common 5 24 VAC from Thermostat 6 Not Used To connect the Vent Damper, the wire from Pin 1 should be connected to 24VAC Hot from the supply transformer. The wire from pin 2 should be connected to the Thermostat input (THS) on the 35-63J control. This should be the only wire attached to the THS terminal. The wire from Pin 4 connects directly to the 24VAC Common. The wire from pin 5 should be connected directly to the Thermostat (call for heat signal) and not to the 35-63J control. Figure 2. Vent Damper Wiring Diagram VENT DAMPER CHECKOUT During the checkout of the new control, you must confirm the proper operation of the vent damper as follows: With the system in standby (no call for heat) the vent damper should be driven closed by the 24 VAC power. When the Thermostat calls for heat, the vent damper starts to open. After the damper is fully open, the 35-63J then sees the 24 VAC call for heat at the THS input and begins the normal ignition sequence. 24 VAC Common 4 1 5 2 6 3 Full -time 24 VAC Hot Call for Heat signal (from damper) 24 VAC from Thermostat Fused 24 VAC (Not Used) Not Used Figure 1. Wire Sideview of Plug 06-237172-001 Rev AA 3

WIRING DIAGRAMS CHECKOUT Risk of Explosion or Fire Verify there are no gas leaks by using a rich soap and water solution on all joints and pipe connections. Never use a match or lighter to test for the presence of gas. Failure to test properly before operation can lead to explosion or fire and may result in severe injury or death. Test the gas control system after any service or component changes to the appliance using the following method: Figure 3. Local Sense Wiring 1. Perform a visual check of all piping, burners, and venting. Check all wiring for integrity and proper electrical and ground connections. Verify the pilot burner is properly grounded. 2. With the gas supply and thermostat off, turn on power to the appliance. 3. Turn the thermostat to a setting high enough to initiate a call for heat. Verify the ignition control proceeds through the operating sequence to a safety shutoff (lockout) condition. (The burner will not light because the gas is shut off) 4. Turn off the thermostat. 5. Turn on the gas supply, and purge the gas lines of air. Check for gas leaks on all joints upstream of the gas valve with a soap solution. 6. Turn the thermostat to a setting high enough to initiate a call for heat. Verify the ignition control proceeds through the operating sequence to a normal run (burner lit) condition. Confirm there are no gas leaks downstream of the gas valve using a soap solution. 7. Turn the thermostat setting down below the room temperature. Verify the main and pilot burner flames go out. Figure 4. Remote Sense Wiring 4 06-237172-001 Rev AA

SEQUENCE OF OPERATION / FLAME RECOVERY / SAFETY LOCKOUT START UP - HEAT MODE When a call for heat is received from the thermostat supplying 24 volts to THS the following sequence occurs in the order listed: 1. The control resets and then performs a self check routine, flashing the diagnostic LED once in the first two seconds. 2. The control begins a pre-purge delay. 3. Following the pre-purge period, the control energizes the pilot gas valve. The main gas valve remains de-energized until the pilot flame is detected. 4. The control enables the high voltage spark output for the trial for pilot ignition period. 5. When the control detects the presence of pilot flame during the trial for ignition, the control terminates the sparking process and energizes the main gas valve. 6. The thermostat and pilot burner flame are constantly monitored to assure the system continues to operate properly. 7. When the thermostat is satisfied and the demand for heat ends, both the pilot and main gas valves are de-energized immediately. FLAME FAILURE RESPONSE RECYCLE MODE (STANDARD) With "recycle after loss of flame", upon loss of pilot flame, both the pilot and main gas valves are de-energized immediately. After the flame recycle delay, the control attempts to relight the pilot flame. Multi-try models allow three tries for ignition including inter-purges. If the pilot burner relights, normal operation resumes. If the pilot burner does not relight, the control will go into lockout as described in Failure to Light - Lockout on page 5. RE-IGNITION MODE (OPTIONAL) If the established pilot flame signal is lost while the burner is operating, the control will respond within 0.8 seconds by deenergizing the main gas valve. The control then energizes the HV spark for the programmed TFI period in an attempt to relight the pilot burner. If the pilot burner does not light within the TFI, the pilot gas valve is de-energized immediately and on multi-try models a new TFI sequence begins. If the pilot burner does not relight, the control will lockout as previously described in Failure to Light - Lockout on page 5. Multi-try models will make 2 more attempts to light the burner. If the pilot flame is re-established, normal operation resumes. FAILURE TO LIGHT - LOCKOUT SINGLE TRIAL MODEL Should the pilot burner fail to light, or if the pilot flame is not detected during the trial for ignition period, the control performs the following actions: 1. The control enters ignition lockout. 2. Both the pilot and main gas valves are de-energized immediately. 3. The LED indicates the fault code for ignition lockout. MULTI TRIAL MODEL Should the pilot burner fail to light, or if the pilot flame is not detected during the first trial for ignition period, the control performs the following actions: 1. The pilot and main gas valves are de-energized. 2. The control then goes through an interpurge delay before another ignition attempt. 3. The control attempts two additional ignition trials before going into lockout and the pilot and main gas valve relays are de-energized immediately. 4. The LED indicates the fault code for ignition lockout. LOCKOUT RESET Recovery from lockout requires a manual reset by either recycling the thermostat or removing 24 volts for a period of 5 seconds. On models with automatic reset, if the thermostat is still calling for heat after 5 minutes the control will automatically reset and attempt to ignite the burner. 06-237172-001 Rev AA 5

TROUBLESHOOTING Risk of Explosion or Fire The 35-63J ignition control cannot be serviced by the user. If any control faults are detected, the 35-63J control module must be replaced by qualified service personnel. Risk of explosion or fire can result if the control module has been opened or with any attempts to repair it, and the warranty is void. Before troubleshooting the system, check the following items: Verify all mechanical and electrical connections are secure and tight. Verify all system wiring is correct. Verify there is a proper system ground. The igniter, flame sensor, and ignition module must share a common ground with the burner. Nuisance shutdowns are often caused by a poor or erratic ground. Perform the instructions in Checkout on page 4, as the first step in any troubleshooting. Verify that the system is powered and that the thermostat is calling for heat. If the control proceeds to an error code on the red diagnostic LED, troubleshoot per the Fault Conditions table below: Symptom 1. Control does not start 2. Thermostat on - no spark 3. Valve on - no spark during TFI 4. Spark on - valve off 5. Flame okay during TFI - no flame sense after TFI Troubleshooting Guide Probable Cause A. Mis-wired B. 24 VAC Transformer bad C. Fuse/Circuit breaker bad (no power) D. Bad control, check LED for steady on or flashing codes. A. Mis-wired B. Bad thermostat, no voltage at thermostat terminal THS C. Bad control, check LED for steady on or flashing codes. A. Shorted electrode B. Verify 1/8th inch spark gap. C. Check high voltage cable. A. Gas Valve coil open B. Valve wire disconnected C. Bad control, check voltage between gas valve terminals PV or MV and GND. A. Check electrode position B. Check high voltage wire C. Poor ground at burner D. Poor flame, check flame current Off LED Indication Fault Conditions Normal Operation Fault Mode 2 Flashes Pilot flame without call for heat PROPER ELECTRODE LOCATION Proper location of the electrode assembly is important for optimal system performance. The electrode assembly should be located so that the tips are inside the flame envelope and about 1/2 inch (1.2 cm) above the base of the flame. 3 Flashes Ignition Lockout Steady On Internal Control Failure The LED will flash on for 1/4 second, then off for 1/4 second during a fault condition. The pause between fault codes is 3 seconds. INTERNAL CONTROL FAILURE If the control detects an error in its software or hardware, all outputs are turned off and the LED displays a steady ON condition. If this condition persists after an attempt to restart then the control must be replaced. Ceramic insulators should not be in or close to the flame. Electrode assemblies should not be adjusted or disassembled. Electrodes should have a gap spacing of 0.125± 0.031 inch (3.12± 0.81 mm), unless otherwise specified by the appliance manufacturer. If this spacing is not correct, the assembly must be replaced. Electrodes are NOT fieldadjustable. Exceeding the temperature limits can cause nuisance lockouts and premature electrode failure. Electrodes must be placed where they are not exposed to the appliance user in normal operation. 6 06-237172-001 Rev AA

STANDARD PART NUMBER CONTROL CONFIGURATION 35 63 J XX X X X X Description TRIAL FOR PILOT IGNITION 1 = 8 Seconds 3 = 25 Seconds 5 = 50 Seconds 7 = 85 Seconds 8 = 120 Seconds INTER-PURGE (RECYCLE DELAY) 0 = None (Single try models only) 1 = 15 Seconds 2 = 30 Seconds 3 = 45 Seconds PRE-PURGE 0 = None 1 = 15 Seconds 2 = 30 Seconds 4 = 4 Seconds TRIES FOR IGNITION & METHOD OF FLAME SENSE 0 = Single Try - Local Sense 1 = Single Try - Remote Sense 2 = Single Try - Local Sense with 5 Minute Automatic Reset 3 = Single Try - Remote Sense with 5 Minute Automatic Reset 5 = Three Tries - Local Sense 6 = Three Tries - Remote Sense 7 = Three Tries - Local Sense with 5 Minute Automatic Reset 8 = Three Tries - Remote Sense with 5 Minute Automatic Reset ENCLOSURE 0 = Noryl Gray Enclosure 1 = Integral Stand-Offs 2 = Board Only OPTIONS 1 = Recycle After Loss of Flame (Standard) 3 = 1 Hour Auto Reset (in place of 5 minutes) 5 = Re-Ignition After Flame Loss 9 = Special OEM Configuration 06-237172-001 Rev AA 7

DIMENSIONS Figure 5. Control Dimensions with Cover 06-237172-001 Rev AA 2011 Kidde-Fenwal, Inc. 8 Fenwal Controls, Kidde-Fenwal Inc. A UTC Fire & Security Company 400 Main Street Ashland, MA 01721 Tel: 800-FENWAL-1 Fax: 508-881-7619 www.fenwalcontrols.com