Asset: P.S. 5 - BROOKLYN, 820 HANCOCK STREET, New York, 11233 Inspection Id Inspection Type Time In Last Edited EE : Electrical 2018-05-25 8:54 AM 2018-06-04 10:18 AM Asset Data Type of Service Does Interactive Whiteboard (IWB) Exist? Water Penetration in Electrical Room? Have any Systems/Major Building Components been upgraded? DEDICATED INTERCOMS IN FIRE RESCUE AREAS Are there any Life Rescue Assistance Areas, Fire Rescue Areas, and/or Holding Rooms in your building? Answer Below Ground Yes No Yes Systems: Exit Lights (Battery Pack) Years: 2018 Systems: Telephone System Years: 2017 Systems: Interior (Except Library) Years: 2015 Systems: Security Lights Years: 2012 Systems: LAN, Local Sound System Years: 2009 Systems: Library Years: 2006 Systems: Intrusion Alarm System Years: 2000 Systems: Public Address System (Amplifier, Tuner) Years: 1999 Systems: Emergency Light/Exit Light Panel Years: 1996 Systems: Partial Molded Case Circuit Breaker Panel Board Years: 1985 No Priority Priority Priority Exist Category Last Year? Description Component Affected Location Description Person(s) Notified Person(s) Title Status PhotoImage No Yes Water Leaks onto Electrical Equipment Public Address System - Speakers Not Operational Due to steam condensation All the speakers in Cafeteria & Gymnasium are not operational Fixture Boiler Room Kalieck Minter Fireman Sent to DSF PUBLIC ADDRESS SYSTEM Cafeteria, Gymnasium, Kitchen Kalieck Minter Fireman Sent to DSF Inspection Electrical AUDITORIUM House Does a Chandelier exist? No PB/A&W Page 1 of 14
AUDITORIUM House Local Sound System Installation Year 2009 Custodial Staff Projection System Theater System Dimming System Theater LIGHTING FIXTURE BEYOND USEFUL LIFE Quantity 36 REPLACE-UPGRADE PB/A&W Page 2 of 14
AUDITORIUM Theater System Theater Photo1 CAFETERIA Local Sound System Installation Year 2009 Projection System Theater System CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE Does a Chandelier exist? Custodial Staff No PB/A&W Page 3 of 14
CLASSROOM/CORRIDOR/ADMINISTRATIVE SPACE LIGHTING FIXTURE BALLAST DEFECTIVE Quantity 8 REPLACE BALLAST Urgency of Action PRIORITY 3 Photo1 COMPUTER LAB Power Panel Raceway With Receptacles Yes PB/A&W Page 4 of 14
COMPUTER LAB Raceway With Receptacles GYMNASIUM Local Sound System Installation Year 2009 Custodial Staff Projection System Scoreboard Theater System KITCHEN PB/A&W Page 5 of 14
KITCHEN LIBRARY Raceway With Receptacles Projection System LOCKER ROOM MULTIPURPOSE ROOM SCIENCE DEMO ROOM SCIENCE LAB SCIENCE PREP ROOM PB/A&W Page 6 of 14
SWIMMING POOL TOILET ROOM - STAFF TOILET ROOM - STUDENT AUXILIARY SIGNAL/BELL SYSTEM Replacement Quantity 90,000 Replacement Uom EMERGENCY DC STANDBY BATTERY POWER EMERGENCY GENERATOR SET EMERGENCY LIGHT/EXIT LIGHT PANEL EMERGENCY LIGHTING Battery Pack Location/Instance Quantity 5 BATTERY NOT OPERATIONAL Gymnasium, 4th Floor by Stairway A, Back of Cafeteria, Main Entrance Lobby, Room 100 REPLACE BATTERY Urgency of Action PRIORITY 5 Purpose of Action LEVEL 4 Photo1 Non Battery Pack 35253131N PB/A&W Page 7 of 14
EXIT LIGHT Battery Pack Non Battery Pack FIXTURE LAMP NOT OPERATIONAL Location/Instance By Room 217, Boiler Room Quantity 3 MAINTENANCE Urgency of Action PRIORITY 5 Photo1 EXIT/EMERGENCY LIGHT CITY FIRE ALARM SYSTEM FIRE ALARM SYSTEM Replacement Quantity 90,000 Replacement Uom Bell/Horn Strobe Manual Pull Station Fan Shutdown Control Duct Smoke Detector Area Smoke Detector CO Detector Heat Detector Elevator Recall Magnetic Door Holder/Contactor Fused Cutout Panel Fire Alarm Digital Communicator Main Panel Bell At Panel Fire Alarm Control Panel (Electronic) Fire Alarm Control Panel (Standard) Instance Instance Instance Quantity 1 Boiler Room PB/A&W Page 8 of 14
FIRE ALARM SYSTEM Main Panel Fire Alarm Control Panel (Standard) Instance Instance Manufacturer ACME Equipment Fire Alarm Board Capacity/Size Quantity 6 Capacity/Size UOM Circuits Source of Capacity/Size Diagram Installation Year 1966 Documented BEYOND USEFUL LIFE Location/Instance Boiler Room Quantity 90,000 REPLACE Photo1 Sub-Panel Bell At Panel Fire Alarm Control Panel (Electronic) Fire Alarm Control Panel (Standard) Instance Boiler Room Instance Instance Quantity 1 Instance Instance Manufacturer ACME Equipment Sprinkler Alarm Board Capacity/Size Quantity 2 Capacity/Size UOM Circuits Source of Capacity/Size Inspector Estimate Installation Year 1966 Documented BEYOND USEFUL LIFE Location/Instance Boiler Room Quantity 90,000 REPLACE Photo1 Remote Annunciator Sprinkler Flow/Air Pressure Switch PB/A&W Page 9 of 14
FIRE ALARM SYSTEM Sprinkler Flow/Air Pressure Switch Tamper Flow Switch/Chain GROUNDING SYSTEM INTERCOM SYSTEM LAN Local Distribution Frame (I/LDF) Main Equipment Rack (MDF) LIGHTNING PROTECTION MOTOR CONTROL CENTER MOTOR STARTER/CONTACTOR PANEL BOARD Fused Disconnect Switch Type PANEL BOARD BEYOND USEFUL LIFE Location/Instance Fan Room above Cafeteria, Boiler Room Quantity 3 REPLACE-UPGRADE Photo1 Fused Knife Switch Type Fused Toggle Switch Type PANEL BOARD BEYOND USEFUL LIFE Location/Instance Electrical Room Quantity 1 REPLACE-UPGRADE Photo1 Molded Case Circuit Breaker Type PANEL BOARD BEYOND USEFUL LIFE PB/A&W Page 10 of 14
PANEL BOARD Molded Case Circuit Breaker Type Location/Instance Corridors (1st, 2nd & 4th Floor), Kitchen Quantity 7 REPLACE-UPGRADE Photo1 NO SPARE Location/Instance By Rooms 305, 322, Auditorium, Cafeteria, Boiler Room Quantity 6 REPLACE PANEL BOARD Urgency of Action PRIORITY 3 Photo1 PUBLIC ADDRESS SYSTEM Replacement Quantity 90,000 Replacement Uom Instance General Office Instance Instance Quantity 1 Instance Model N/A Installation Year 1983 Inspector Estimate MASTER CLOCK NOT OPERATIONAL Location/Instance General Office Quantity 90,000 REPLACE Urgency of Action PRIORITY 3 Photo1 SPEAKER NOT OPERATIONAL Location/Instance Cafeteria, Gymnasium, Kitchen Quantity 90,000 REPLACE Urgency of Action PRIORITY 5 Purpose of Action LEVEL 6 Photo1 Location/Instance BEYOND USEFUL LIFE Boiler Room PB/A&W Page 11 of 14
PUBLIC ADDRESS SYSTEM Quantity 90,000 REPLACE Photo1 SECURITY IPDVS/CCTV System Intrusion Alarm System Replacement Quantity 90,000 Replacement Uom Central Control Panel Instance Custodian's Office Instance Instance Quantity 1 Instance Model Vista - 50P Installation Year 2000 Inspector Estimate Infrared Sensor Panic Switch Remote Annunciator Siren/Strobe Ultrasonic Sensor - Security Replacement Quantity 42 Replacement Uom LIGHTING FIXTURE BALLAST DEFECTIVE Location/Instance Building Perimeters Quantity 7 REPLACE BALLAST Urgency of Action PRIORITY 2 Purpose of Action LEVEL 3 Photo1 SERVICE SWITCH PB/A&W Page 12 of 14
SERVICE SWITCH Instance Electrical Room Instance Instance Quantity 1 Instance Instance Manufacturer Royal Switchboard Co. Equipment N/A Capacity/Size Quantity 1,600 Capacity/Size UOM Amps Source of Capacity/Size Nameplate Installation Year 1966 Documented BEYOND USEFUL LIFE Location/Instance Boiler Room Quantity 90,000 REPLACE Photo1 SWITCHBOARD Number of Spares 0 Air Circuit Breaker Type Fused Disconnect Switch Type Instance Instance Instance Quantity 1 Instance Instance Manufacturer Equipment Electrical Room Capacity/Size Quantity 1,600 Capacity/Size UOM Capacity/Size2 Quantity 3 Capacity/Size2 UOM Source of Capacity/Size Installation Year 1966 Location/Instance Royal Switchboard Co. N/A Amps Total Section(S) Service Switch Size Documented BEYOND USEFUL LIFE Boiler Room Quantity 90,000 REPLACE Photo1 Fused Knife Switch Type Molded Case Circuit Breaker Type PB/A&W Page 13 of 14
TELEPHONE SYSTEM PBX/Intercom Standard TRANSFORMER TV SYSTEM Cable System Exist? Operational? Main Equipment Rack Yes No PB/A&W Page 14 of 14