INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

Similar documents
INSTALLATION INSTRUCTIONS FOR 7370A736 FLUSH MOUNT CEILING PLENUM

INSTALLATION INSTRUCTIONS FOR 6797A737 HEAT PUMP FLUSH MOUNT CEILING PLENUM

INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

INSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

INSTALLATION INSTRUCTIONS FOR 9330F4552 FREE DELIVERY PLENUM KITS

INSTALLATION INSTRUCTIONS FOR 7330*5511 OR 7330*5512 MOUNTING KIT 7330B751 CONTROL BOX KIT (12 VDC COOL ONLY)

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT 7330B751 CONTROL BOX KIT (12 VDC COOL ONLY) CONTROL BOX KIT (12 VDC HEAT/COOL)

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

INSTALLATION INSTRUCTIONS FOR SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMP

INSTALLATION INSTRUCTIONS FOR 6636 SERIES PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTIONS FOR 6536 SERIES TWO TON PACKAGED HEAT PUMP

SERVICE MANUAL FOR 6636A & 6636B SERIES TWO TON HIGH EFFICIENCY PACKAGED AIR CONDITIONERS

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTIONS FOR. 230/240 VAC, 1ø, 50Hz SERIES RV ROOF TOP AIR CONDITIONER/HEAT PUMP

CONTENTS A FEW WORDS ABOUT YOUR NEW AIR CONDITIONING UNIT 2 ELECTRICAL DATA 2 OPERATING INSTRUCTIONS 4

SERVICE MANUAL FOR 6633 SERIES PACKAGE AIR CONDITIONER

INSTALLATION INSTRUCTIONS FOR MODEL 7330D3351 & 7330D3361 WALL THERMOSTAT

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES HEAT PUMP INSTRUCTIONS D INSTALLATION DE LA POMPE À CHALEUR SÉRIE 47000

INSTALLATION INSTRUCTIONS FOR. 230/240 VAC, 1ø, 50Hz 473X3 SERIES RV ROOF TOP AIR CONDITIONER

SERVICE MANUAL FOR 6795B,C,D SERIES PACKAGED AIR CONDITIONERS

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6535D, 6537C, 6538 A&B SERIES TWO TON PACKAGED HIGH EFFICIENCY HEAT PUMPS

QUICK REFERENCE GUIDE P.C. BOARD/WALL THERMOSTAT FOR 6536A891, 6536B891 & 6536C891 TWO TON PACKAGED HEAT PUMPS

SERVICE MANUAL FOR ROOF TOP AIR CONDITIONERS

RV Products Division INSTALLATION INSTRUCTIONS FOR SERIES AIR CONDITIONERS

09/23/2013. RECORD THIS UNIT INFORMATION FOR FUTURE REFERENCE: Model Number: Serial Number: Date Purchased:

OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS

SERVICE MANUAL FOR 6537 & 6538 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

LIFTAIRE I ELEVATOR AIR CONDITIONER

T874 Multistage Thermostat and Q674 Subbase

LIFTAIRE II ELEVATOR AIR CONDITIONER

INSTALLATION INSTRUCTIONS

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

INSTALLATION INSTRUCTION

Installation Instructions

T8190A/191108AJ Heating or Cooling Thermostat/Wallplate; T8190A/Q682B Heating/Cooling Thermostat/Subbase

INSTALLATION INSTRUCTIONS

OPERATION AND MAINTENANCE INSTRUCTIONS FOR ROOF TOP HEAT PUMPS AND CEILING PLENUMS

Installation Instructions

INSTALLATION & OPERATING INSTRUCTIONS. Roof Top Unit. Model. USA SERVICE OFFICE Dometic Corporation 2320 Industrial Parkway Elkhart, IN 46516

INSTALLATION, OPERATING & MAINTENANCE INSTRUCTIONS FOR 350 SERIES CIRCULATION HEATERS

Air Conditioner

Installation Instructions

238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual

VIKING RANGE CORPORATION, P.O. DRAWER 956, GREENWOOD,MS USA

Installation Instructions

Orrin. Instruction Manual. Includes our new CoolTouch TM Control System Looks permanent, but goes wherever you go! U.S.

TraceTek Sensing Module Installation, Operation and Maintenance Instructions DESCRIPTION SPECIFICATIONS APPROVALS TYPE NM

Installation Instructions

FitchTM. Instruction Manual. Includes our Basic Function CoolTouch TM Control System Looks permanent, but goes wherever you go!

INSTALLATION, OPERATION AND MAINTENANCE MANUAL FOR COMMERCIAL INDIRECT POWERED WATER HEATER

Summer Breeze Heater Service Manual

User s Manual. For the SHORE POWER CONNECTION MONITOR MODEL 9151

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

BR342 Ducted Installation Instructions Australian Version Electronic Wall Control

Model R11C. Replacement for: Westinghouse "RB" Series Chassis R21C. Replacement for: Climate Master (Friedrich) 701 Series R23C R23H.

L A signature series TA T N E RE O, A L L A T S IN

USER S MANUAL AND INSTALLATION INSTRUCTIONS IMPORTANT

OPERATION AND MAINTENANCE INSTRUCTIONS FOR SERIES ROOF TOP HEAT PUMPS AND CEILING PLENUMS

Sunburst. Instruction Manual. Includes our new Wall Control System. A Kichler Décor ceiling fan

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

60" Lyndon Patio. Instruction Manual Customer Service :30 AM to 5:00 PM EST, Monday - Friday A Kichler Decor ceiling fan

Rotary XL (558 Series) and Classic (548 Series)

ChicagoTM. Instruction Manual. Includes our new CoolTouch TM Control System Looks permanent, but goes wherever you go! U.S.

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

52 DorsetTM. Instruction Manual. Basic Function Wall Control System Included. A Kichler Decor ceiling fan

Installation, Operation, & Maintenance Manual

42 Kevlar. Instruction Manual. Kichler Lighting 7711 East Pleasant Valley Road P.O. Box Cleveland, Ohio

FES - Series Portable Electric Heaters. YES - Series Suspended Electric Heaters CONTENTS

BUILT-IN DISHWASHER INSTALLATION INSTRUCTIONS

SAVE THESE INSTRUCTIONS

ELECTRIC COOKTOP INSTALLATION INSTRUCTIONS

60" Tulle PatioTM. Instruction Manual. A Kichler Select ceiling fan

60" Hatteras BayTM. Patio. Instruction Manual. Includes our new Wall Control System. A Kichler Décor ceiling fan

ValkyrieTM. Instruction Manual. Includes our new CoolTouch TM 6 Speed DC Control System Looks permanent, but goes wherever you go! U.S.

Installation Instructions 30 French Door Built-in Wall Ovens

HotLine Internal Sewer Pipe Heater Installation Manual

INSTALLATION INSTRUCTIONS UNDERCOUNTER DISHWASHERS

TC-5231 Series, TC-5232, & TC-5241 Series

Your safety and the safety of others are very important.

CircoloTM A Kichler Décor ceiling fan Designed to coordinate with a popular Kichler Lighting collection.

USER INSTRUCTIONS FOR FLANGE IMMERSION HEATERS USED IN HAZARDOUS LOCATIONS

54" Skye. Instruction Manual Customer Service :30 AM to 5:00 PM EST, Monday - Friday A Kichler Decor ceiling fan

C-IV 60 CEILING FAN READ AND SAVE THESE INSTRUCTIONS. FAN RATING AC 120V. 60Hz

OPERATING AND MAINTENANCE MANUAL FOR ELECTRIC STAINLESS STEEL HEATER FOR DEIONIZED (DI) WATER ELECTRIC HEATER COMPANY BASE MODEL D

Tommy Bahama INDOOR/OUTDOOR 52 in. / 132 cm. CABRILLO COVE CEILING FAN

Installation Instructions

V Refrigeration Module

Hatteras BayTM. Patio. Instruction Manual. Includes our new CoolTouch TM Control System Looks permanent, but goes wherever you go! U.S.

FOR TM-16 EMERGENCY WARNING SYSTEM

52 StarkkTM. Instruction Manual. A Kichler Select ceiling fan

52 Lacey LED. Instruction Manual. 6 Speed DC Wall Control System

Installation Instructions

Carbon Heating Film. Failure to follow these instructions may result in fire, electrical shock, property damage, personal injury, or death.

Installation in Standard & Variable Speed Indoor Air Handlers IMPORTANT

BRISK AIR 579 Series 590 Series 595 Series

1. SAFETY RULES WARNING WARNING. 8. Avoid placing objects in the path of the blades.

Installation Instructions

Installation Instructions Wall Ovens

Transcription:

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

TABLE OF CONTENTS Warnings...3 Package Contents...3 General Information...3 Supply Ducting And Registers...3 Routing 115 VAC Wiring...5 Routing 24 VAC Thermostat Wiring...5 Ceiling Assembly Installation...6 Connect 115 VAC Wiring...8 Connect 24 VAC Wiring...9 Thermostat Checkout...11 Install Return Air Grille And Filter...11 Thermostat Operation...11

WARNINGS IMPORTANT NOTICE These instructions are for the use of qualified individuals specially trained and experienced in installation of this type equipment and related system components. Installation and service personnel are required by some states to be licensed. PERSONS NOT QUALIFIED SHALL NOT SERVICE THIS EQUIPMENT. WARNING Improper installation may damage equipment, can create a hazard and will void the warranty. The use of components not tested in combination with these units will void the warranty, may make the equipment in violation of state codes, may create a hazard and may ruin the equipment. WARNING - SHOCK HAZARD To prevent the possibility of severe personal injury or equipment damage due to electrical shock, always be sure the electrical power to the appliance is disconnected. CAREFULLY FOLLOW ALL INSTRUCTIONS AND WARNINGS IN THIS BOOKLET TO AVOID DAMAGE TO THE EQUIPMENT, PERSONAL INJURY OR FIRE. PACKAGE CONTENTS 1) Ceiling Assembly 1) Return Air Grille 1) Return Air Filter 1) Small Parts Package 4) #10 x 1" Return Air Grille Mounting Screws 1) Basepan Foam Gasket GENERAL INFORMATION The flush mount ceiling assembly is designed for application in systems that utilize field fabricated (OEM supplied) cold air supply ducting and registers. The ceiling assembly mounts through a 14" x 14" opening through the ceiling and roof to the bottom of the roof top unit. The supply duct connection and the return air path are located in this ceiling cavity opening. All air conditioning functions are controlled by a low voltage wall mounted thermostat. The thermostat controls a 24 VAC electrical circuit which is used to energize control relays in the ceiling assembly. The thermostat is supplied with 24 VAC by a 115/24 VAC transformer mounted above the electrical box in the ceiling assembly. The thermostats most commonly used are combination (Heat/Cool) thermostats. These thermostats are capable of operating both the roof top air conditioner and any furnace with a 24 VAC control circuit with or without its own transformer. A low temperature sensor also connects to the ceiling assembly compressor control circuit. The sensor inserts into the evaporator coil of the roof top unit and shuts the compressor off in the event of a freeze-up condition. This flush mount ceiling assembly will mount to and operate all current production roof top air conditioners. Regardless which roof top unit is used, this system will operate with only one fan speed. This system is not designed for and will not accept electric strip heating. A divider for separating the supply and return air areas in the ceiling cavity, and the hardware for mounting the ceiling assembly, is to be supplied by the OEM (See Ceiling Assembly Installation Section). SUPPLY DUCTING AND REGISTERS A. Ducting 1. The supply ducting routed in the cavity between the interior ceiling and roof must attach to both sides of the ceiling assembly. A minimum of two ducts are required, with one duct attached to each side of the assembly. See Figures 1 and 2 for both an overhead view of the system with ducts and a ceiling assembly installation. 3

2. Each duct must have a minimum height of 1 1/2". Total free area inside each duct must be no less than 10 square inches. To decrease restriction and increase air flow, the ducting should make as few bends and turns as possible. When corners or turns are required, we recommend that you radius the corners to keep air flow at a maximum. 3. Where ducting secures to the ceiling assembly, maximum width is 8 inches. 4. All field fabricated cold air supply ducting must be insulated and must have a vapor barrier. Ten (10) square inches of free area per duct is the minimum requirement. Larger ducting will improve air flow and system performance. 2" x 6" has proven to be highly effective. FIGURE 1 FIGURE 2 4

IMPORTANT Insulating reduces cooling loss and helps prevent water staining of the vehicle ceiling due to moisture condensation. B. Registers 1. Supply (cold air) registers should have a minimum discharge area of 48 square inches per system, or 24 square inches per duct. Figure 3 shows how to determine the discharge area for a given register, and how to determine the number of registers required. The register in Figure 3 provides 6 square inches of discharge area. Each duct would require 4 registers of this size to satisfy the 24" requirement. FIGURE 3 ROUTING 115 VAC WIRING 1. Following RV Products high voltage wiring specifications and all local and national electrical codes, route the roof top unit 115 VAC supply wiring from its power source and into the front of the roof top opening. To allow attachment to ceiling assembly high voltage connections, extend approximately 12" of the wiring into the opening. High Voltage Wiring Specifications 2. To prevent voltage drops of greater than 10% during starting loads, adhere to the following guideline: For lengths greater than 50', use #10 AWG. Circuit Protection - Refer to upper unit nameplate. 3. Allowances must be made to prevent wire pinching and to promote ease of installation. 1. U.L. approval requires the power supply to be copper conductors only with minimum sizing utilizing #12 AWG. ROUTING 24 VAC THERMOSTAT WIRING 1. Following the instructions packed with the thermostat, determine a location for thermostat mounting. 2. Following RV Products low voltage wiring specifications and all local and national electrical codes: A. Route the thermostat 24 VAC supply and control wiring from the front of the ceiling cavity opening to the thermostat mounting location. Three wires are required: (1) Red wire for +24 VAC (1) Yellow wire for compressor circuit (1) Green wire for fan circuit B. To protect the wall mount thermostat from overcurrent damage, it is necessary to provide a 2 amp circuit protection device in the 24 VAC supply wire to the thermostat. Using a circuit protection device in this manner will prevent thermostat circuitry burnouts. 3. RV Products low voltage wiring specifications: A. All OEM supplied low voltage wiring should be minimum 18 gauge. B. All low voltage wires should be solid conductors. 5

C. Low voltage wiring must be routed into the front side of the ceiling assembly opening. Allowances must be made to prevent wire pinching and promote ease of installation. CEILING ASSEMBLY INSTALLATION A. Preparation and Positioning the Roof Top Unit 1. Consult Sections I through IV of the roof top unit installation instructions for the installation and mounting requirements of the roof top unit. 2. Prepare the roof top unit for installation with the ceiling assembly. The freeze circuit thermistor probe (See Figure 4) installs by inserting it straight in between the two lower evaporator tubes until contacting a tube, then raising the back of the probe and continuing at a 45 degree angle until the probe is fully inserted. Position the roof top unit over the roof opening, lowering the low temperature sensor leads down through the opening. 3. Attach the basepan foam gasket to the bottom of the basepan in the area shown in Figure 5. FIGURE 5 B. Preparation Of The Ceiling Assembly 1. Remove ceiling assembly electrical box cover. Retain screws for reattachment. See Figure 6. Familiarize yourself with the high voltage wiring box, strain relief and wiring. The 115V supply wiring must be routed through the strain relief in the electrical box and secured to the high voltage terminals inside. C. Mounting The Ceiling Assembly 1. Install a divider to separate the supply and return air areas in the ceiling cavity. Duct board or equivalent is the suggested material. If metal is used, the return (warm) air side should be insulated and a vapor barrier provided to prevent condensation build-up. FIGURE 4 The low temperature sensor leads should remain on the return air side of the divider to allow connection to the ceiling assembly low voltage terminal board. The divider must be sealed into the foam at the bottom of the roof top unit and the sides of the roof opening. 6

2. Position ceiling assembly into the ceiling opening. For proper orientation of the ceiling assembly, reference Figure 2. When inserting the ceiling assembly into the roof opening, be careful not to pull the foam insulation away from the sides of the ceiling assembly. The insulation is required to create a positive air seal within the ceiling cavity. 3. Four bolts are needed for fastening the ceiling assembly and roof top unit together. The bolts may be made from 5/16-18 all thread rod. The required length = ceiling cavity depth (from ceiling to roof) plus 2 inches. Nuts and washers are also required. It is suggested to put washers and double nuts on one end of the all thread. The four all thread bolts are to be installed through the ceiling assembly and into the bottom of the roof top unit. The double nutted end of the all thread must not extend far enough to cause interference when the return air grille is installed. Mounting bolts should be tightened evenly. A rotating tightening procedure (similar to car tire rim mounting) is essential for proper gasket compression. The bolt tightening procedure is complete when the gasket under the roof top unit has been evenly compressed 1/4". 4. Cut the plastic wire tie securing the roof top unit 115V electrical harness. The ceiling assembly has a 9 pin socket end harness extending from the front of the electrical box. This mates with the roof top unit 115V electrical harness. IMPORTANT When connecting the 115V electrical harness: 1. Make any adjustments required to relieve pinched or stressed wiring. 2. Verify that the ridged side of both plugs are properly aligned. Verify that the connectors have snapped together on both sides. Do not use excessive force when joining the connectors. FIGURE 6 7

CONNECT 115 VAC WIRING 1. WARNING - SHOCK HAZARD To prevent the possibility of severe personal injury or equipment damage due to electrical shock, always be sure the electrical power is disconnected or off before beginning installation. 2. Complying with the Danger notice below, bring the 115 VAC supply wiring previously routed into the frame of the roof opening, through the strain relief in the electrical box and into the high voltage wiring area. DANGER WHEN USING NON-METALLIC SHEATH SUPPLY CABLES (ROMEX, ETC.), STRIP SHEATH BACK TO EXPOSE 4-6 INCHES OF THE SUPPLY LEADS. STRIP THE INDIVIDUAL WIRE LEAD ENDS FOR WIRE CONNECTION (ABOUT 3/4" BARE WIRE). REMOVE NYLON STRAIN RELIEF FROM ELECTRICAL BOX. INSERT THE SUPPLY WIRES INTO THE STRAIN RELIEF. WIRE SHEATH MUST PROTRUDE PAST STRAIN RELIEF. MAKE SURE SHEATH CABLE IS CENTERED IN STRAIN RELIEF BEFORE SNAPPING IT BACK INTO BOX. IF OTHER THAN NON-METALLIC CABLES ARE USED FOR SUPPLY CONDUCTORS, APPROPRIATE STRAIN RELIEF CONNECTORS OR CLAMPS SHOULD BE USED. 3. Secure the 115V supply wiring to the respective high voltage terminals on the p.c. board inside the electrical box. DANGER TO PREVENT ELECTRICAL SHOCK DUE TO MIS-WIRING, CONNECT BLACK WIRE TO TERMINAL MARKED BLACK, WHITE WIRE TO TERMINAL MARKED WHITE AND GROUND WIRE TO TERMINAL MARKED GROUND. 4. Gently fold all wiring into the electrical box while verifying that it is not either pinched or cut. 5. Complying with the warnings listed, connect the 115 VAC supply wiring to its power source. Be sure all power remains off until beginning checkout procedure. DANGER TO PREVENT THE POSSIBILITY OF SHOCK INJURY FROM APPLIANCE OPERATION - THE WHITE WIRE MUST BE CONNECTED TO NEUTRAL IN THE SERVICE BOX ENTRANCE, AND THE MECHANICAL GROUND MUST BE CONNECTED TO A GROUNDING LUG EITHER IN THE SERVICE BOX OR THE MOTOR GENERATOR COMPARTMENT. IN NO CASE SHOULD CLAMPING OR PINCHING ACTION BE APPLIED TO THE INDIVIDUAL SUPPLY LEADS (NEUTRAL AND HOT WIRES). 8

CONNECT 24 VAC CONTROL WIRING A. Ceiling Assembly Connections 1. Bring the thermostat wiring previously routed into the roof opening over to the low voltage terminal board extending from the front of the ceiling assembly electrical box. Also locate the wiring from the low temperature switch installed in the upper unit. These low voltage ceiling assembly wires complete the following circuits: Connect the red, yellow and green thermostat wires to terminals R, Y and G respectively. The wires connect by 1/4"quick connects. Connect the white low temperature switch leads with 1/4" quick connects to terminals marked F. There is no polarity with the low temperature leads. Connect either white wire to F and the remaining wire to the remaining F. B. Wall Thermostat 7330-324 1. Extend both the thermostat control and supply wiring through the thermostat wall opening. 2. Cut the wiring to length (approximately 4 to 5 inches of wiring should be left extended from the opening). Strip the wires removing 5/8" of insulation from each wires end. 3. Obtain the wall mount thermostat. These thermostats separate into 3 pieces. See Figure 7. 4. Separate thermostat into the three separate components. 5. Obtain thermostat sub-base. Pull all the thermostat wiring through the center of the subbase and place it against the wall opening. Level the sub-base and secure it to the vehicle wall with the screws provided in the thermostat package. See Figure 7. 6. Secure thermostat wiring to the sub-base. If a single transformer is used to supply both the air conditioner and furnace, install a jumper wire from terminals RC to 4 (or RC to RH). IMPORTANT The three captive screws that secure the base to the sub-base must be present in order for the thermostat to operate. Do not misplace these screws. Retain for thermostat reassembly. 9

FIGURE 7 10

THERMOSTAT CHECKOUT The following checkout procedure will eliminate burned-out thermostats and provide a quick and accurate evaluation of the system wiring. Checkout will be performed at the thermostat sub-base with a standard volt-ohm meter. Note: Do not complete thermostat assembly until checkout is complete. 1. Energize both the 24V power source for the thermostat and the 115V power source for the air conditioner. 3. Disconnect the 115 VAC which will disable the 24 VAC circuit. 4. Reassemble thermostat. This thermostat is equipped with automatic heat anticipation and requires no adjustment. 2. Using one of the test leads from the volt meter, jumper between terminals: RC and Y for compressor operation RC and G for fan operation RC and W for furnace operation INSTALL RETURN AIR GRILLE AND FILTER Four plated wood screws are provided specifically for the return air grille mounting. Obtain screws from small parts package. Place filter on backside of return air grille. Lift grille into position, centered over the roof opening. Insert one screw into each corner of the grille and secure to ceiling. THERMOSTAT OPERATION Adjusting Setpoint: To adjust the temperature control setpoint, move the temperature select lever located on the side of the thermostat to the temperature desired. 11

1976K156 (6-02) PP RV Products A Division of Airxcel, Inc. P.O. Box 4020 Wichita, KS 67204