ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Similar documents
CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

B-40/B-41 Modulating Temperature Controller

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

K-Controller Brochure.qxp_ Controller Brochure 2/27/17 3:03 PM Page 4 Versa IC Platform

Tri-Stack Smart System

Nov 08 PRODUCT SPECIFICATION SHEET

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

SCC Inc. Master Panel. Specifications. Document No. TS 2010 February 11, Product Description. Sample Specification

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

E340 BOILER CONTROL INSTALLATION MANUAL

MYRIAD DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL VERSION 3.7

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

Lift Station Level Controller

Process & TeMPerATUre UniversAl input DigiTAl MeTers

DPR-145 TEMPERATURE PROTECTION RELAY. DPR-145 User Manual V-2.0 ( ) PT100 INPUTS: 4 RELAY OUTPUTS: 4 RS-485 MODBUS PORT VDC SUPPLY -1-

Replaceable LED modules. Sleep or unattended mode. Auto-silence and auto-acknowledge

TMC. Installation and Operation Manual TMC. Temperature and Pressure Monitoring for Heating and Cooling Applications. Temperature Monitoring Control

CM3500 Controller - ClimateMaster DOAS Water-Source Heat Pumps - Rev.: 7 Oct, 2008B

Table of Contents SECTION PAGE

Control manual. Series. Gas-fired direct vent Cast iron boilers. Control adjustment and Operation instructions

Temperature Controllers

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Table of Contents SECTION PAGE SECTION 1 INTRODUCTION Description Features Models... SECTION 2 RS-232 COMMUNICATIONS...

Application Manual Loop Water Controller

READ AND SAVE THESE INSTRUCTIONS

Carbon Monoxide Transmitter

New Versa IC Platform

User Manual. Digi-Sense TC9500 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

Sequence of operation

NGC-UIT2 MODBUS PROTOCOL INTERFACE MAPPING FOR NGC-30 SYSTEMS. Firmware versions up to V2.0.X

Oakton TEMP 9500 Advanced Multiparameter Controller

NURO. Boiler Controller. Advanced User s Guide NURO. Advanced User s Guide. NURO Boiler V Controller. Advanced User s Guide Rev.

Pump-Down Controller MODEL 4052

Metasys Integrator Cleaver-Brooks Application

INSTALLATION INSTRUCTIONS

Dryer Master DM510 Commissioning Guide

Pump-Up Controller MODEL 4062

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

Service Manual Models: 1.0, 1.3, and 1.5

Series Temperature Controller Instruction Sheet

Tempco Part Number PCT30006 Temperature Control Enclosure with Relay Output for Tote Tank Heating Applications

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

SOFTWARE INTERFACE SPECIFICATION - SOLA MODBUS INTERFACE

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

Trinity Tft/Lx Model #s: Tft60-399/Lx Version Date:

Tempco PCT-3000 Series Temperature Control Console with Relay Output for Heating or Cooling Applications

HeatNet Manual Control Adjustment and Operation Instructions for Hydrotherm Firmware Version 2.8

VTI MODEL itc5000 HEAT TRACING CONTROL SYSTEM OPERATIONS MANUAL

MicroTech Series 200 Centrifugal Chiller

La Marche Manufacturing Company Option 46 Series. Digital Combined Accessory Package. Installation and Operation Manual

CTT8 TEMPERATURE MONITOR DEVICE

ITAS / ITAS-EXT / ITLS / ITLS-EXT

User Manual. Digi-Sense TC9600 Advanced Multiparameter Temperature Controller with Thermocouple, Thermistor, and RTD Inputs

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

Multi Boiler Guide. Kit #

Concert TM Boiler Control

QuadraTouch Pro Software Manual Dryer Control System

Important Supplementary Manual to the main Ezeio manual. 5. Section 2a: Introducing the 2400 input and output expansion field stations.

MO n : 12JMC rév A

Chief Dispatcher Model JC-CDST

Laptop / PC Programming Manual

HTLS. Heat Tracing Line Sensing Control Panel

Digi-Sense TC9000 Advanced PID and On/Off Temperature Controller with Thermocouple Input

STEAMPAK Series BurnerPAK BMS Burner Management Systems

P2267 NETWORK INTERFACE

SCC Inc. TS Series. Technical Instructions. Document No. TS 1000 June 25, TS Touchscreen Kits. Description. Touchscreen

F4 Process Controller Installation and Operation Guide

Two-Channel Gas Controller

Refer to Bulletin E-1101 for detailed information on the FLAME-MONITOR System.

Model D12-IR. Digital Gas Transmitter...

Specification , July 2015

Ion Endeavor Pump Controller Digital Level Control with Pump Alternation and High Water Alarm

Control Application. Supplement - ACVMax

PLL Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

Remote Vacuum Sensor and Variable Speed Vacuum Pump Control Manual. Version Date - June Part Number

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Installation and Operations Manual

M2500 Engine Controller Installation Manual

MicroTech Series-200 Flooded Screw Chiller

Flopurge TS. Operation Manual

Added password for IP setup page : Password must be in IP format!

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

OVEN INDUSTRIES, INC.

Operating Manual. Gasgard 100 Control System. Order No.: /00. MSAsafety.com

NGC-40 Bridge. Modbus Overview. Raychem-AR-H58862-NGC40BridgeModbusOV-EN-1805 nvent.com 1

OnTrac Boiler Management System

Custom Control Systems Inc. Ellis Dryer Control Configuration and Operation Manual

ibox Modbus Server Gateway for the integration of Notifier ID3000 / ID3002 / ID60 / ID50 fire panels in Modbus enabled monitoring and control systems

prestige Control Application Supplement - ACVMax

MANUAL FOR MODEL MP600 HIGH VOLTAGE ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS

Simplex Panel Interface Guide

Series Digital Controller Instruction Sheet

Intelligent 2 & 4 Loop Fire Alarm Control Panels

I/O logger box. User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT!

PLL. Pump-Lead-Lag. Provides Pump Rotation, Auxiliary Pump Activation, and Pump Failure Alarm Control. Installation and Operation Manual

SEQUENCE OF OPERATIONS

Transcription:

ModSync Sequencing System Installation & Operation Manual For use with Fulton Steam Boilers. Revision 3.0 8/21/2008

- 2 -

Table of Contents Introduction Page 4 Features Page 4 Sequence of Operation Page 5 Installation Time/Date Setup Page 7 Page 10 Screen Descriptions Page 11 General - Page 13 Main Menu Screen - Page 14 System Status Screen - Page 15 Boiler Config Screens - Page 16 Process Config Screens - Page 18 Lead/Lag Screens - Page 20 Setback Schedule Screen - Page 24 Boiler Status Screen - Page 26 System Configuration Screens - Page 27 Alarm Screens - Page 32 Troubleshooting - Page 33 Modbus Network Page 35 Specifications Page 41 Warranty Page 42 Parts Information Page 43-3 -

Introduction The ModSync Sequencing System has been designed to provide precise pressure control of multiple Fulton Steam Boilers. The ModSync provides advanced functionality over existing sequencing systems. The enhanced Lead/Lag capabilities are provided through user-friendly displays and an easy to use Touchscreen Interface. This manual details the ModSync s setup screens and configuration for use with Fulton Steam Boilers. Features Lead/Lag Control The Steam boilers are staged on and off to match the existing load. The ModSync will stage additional boilers on automatically to maintain header pressure. Setback Schedule The steam header setpoint can be configured to change based on the Time of Day and Day of the Week. Multiple Setpoint Control Modes The steam header setpoint can be field selected to be controlled by the ModSync, Remote 4-20mA Signal or SCADA Modbus Value. Modbus Communication The ModSync can communicate over the Modbus protocol to SCADA Systems. Steam System Interface Remote Enable/Disable contacts and Alarm monitoring. Auto/Manual Mode Control The ModSync can be configured for automatic or manual control of the Steam boilers. The Manual features help to decrease the boiler commissioning time by assisting with verification of the communication interface. Alarm Status Boiler alarm status is monitored and annunciated via an Alarm Screen, minimizing troubleshooting time requirements. Alarm History Alarm History screen provides Date, Time and Fault information for the last eight alarm occurrences. - 4 -

Sequence of Operation Designed to provide precise pressure control of a multiple steam boiler system, the ModSync stages the boilers based on load demands. A typical sequence of operation is as follows: 1. The ModSync monitors the steam header pressure using a pressure transducer. A PID Control Variable determines when the steam boilers will begin sequencing based on the difference between the actual header pressure and the steam pressure setpoint. 2. When a request for steam is determined by the ModSync, the Lead Steam Boiler is energized. The initial firing rate (if applicable) is determined by the Lead Start Firing Rate variable set in the Lead/Lag configuration section. 3. If the steam pressure continues to decrease, the PID Control Variable will increase. The Lead Steam boiler s firing rate will reach 100% before the Lag Start CV value. The ModSync will enable a Lag Boiler when the Lag Boiler Start control variable value has been reached. 4. If additional steam is required, the ModSync will enable each additional Lag Boiler stage determined by the Lag Stage Start CV value. Each Lag Stage will reach a 100% firing rate before the next stage is enabled. 5. As the steam pressure increases, the ModSync will begin to decrease the firing rate and number of Steam boilers required to maintain the steam header pressure 7. The Lead Boiler is disabled when the steam pressure reaches a selectable value referenced around the steam header setpoint. - 5 -

- 6 -

- 7 -

Installation Enclosure NEMA Classification: NEMA 12, 4, 4X. (IP 65) Figure 1. Enclosure Dimensions - 8 -

Installation Location The ModSync enclosure (Figure 1) should be located in a clean, dry environment within visual range of the steam boilers. Four (4) mounting supports are provided loose in the enclosure. Secure the supports to the enclosure and mount the ModSync in an easily accessible area of the boiler room. Power Supply A 120/230VAC-50/60HZ-1PH electrical supply is required by the ModSync. The supply should be connected to a 10A circuit breaker for short circuit protection. The incoming AC power should be connected to the corresponding L, N and Earth terminal blocks provided in the ModSync enclosure. Pressure Sensor A Steam Header Pressure Sensor is provided with the ModSync. The pressure sensor range is based on the steam system design. The pressure sensor should be mounted in the common steam piping with a siphon loop isolating it from the header. Steam Boiler Interface The Steam Boilers provide status feedback using contact closures and analog (4-20mA) signals. Please reference the associated electrical diagram provided with the ModSync to determine the communication runs required between the ModSync and the Steam boilers. - 9 -

Installation ModSync Program Download Instructions 1. Locate and extract the ModSync_Downloader.zip file. Locate the folder you extracted the contents to and double-click the ModSync_Downloader_165.exe file to install the ModSync Downloader software program. Restart your computer. 2. Double-click on the provided.udc file to open it in the ModSync Downloader. If the Downloader does not open automatically, Click Start > All Programs > Unitronics > UniDownloader. Click the Open icon (first from left) and navigate to where the.udc file is saved and open it. 3. Connect the serial communication cable from the communication port on the computer to Port 1 on the ModSync. 4. Click on the Connection Settings icon (second from left). Select the appropriate Communication Settings and then click on the Get OPLC Information button to verify communication. V280 should be displayed in the Model: text box if communication is active. Click the Exit button when communication is active. 5. Click the Run icon (third from left) to start the download. Click Close after successfully downloading the program. *Step 1 is only needed if the ModSync Downloader Software does not exist on your computer. Time/Date Update Instructions The following procedure describes the required steps to update the internal time and date of the ModSync control: 1. Press and hold the [?] key on the keypad for approximately 5 seconds. A password screen will appear. Enter 1111. 2. A screen labeled Data Types is displayed. Press the down arrow key once to display the System screen. Press Enter. 3. Press the down arrow key two times so that the Time and Date block is highlighted. Press Enter. 4. To set the time - New time is highlighted on the screen. Press Enter and input the new time (24hr format) and press Enter. 5. To set the date, press the right arrow key when the New Time is highlighted and it will move you to the New Date area. Press Enter and the date field will be highlighted. Keep in mind that the Date field is Day/Month/Year format. Use the keypad to enter the new date and press Enter. 6. Press the Esc key until the ModSync Help Screen is displayed. The changes are now complete. - 10 -

- 11 -

- 12 -

Screen Descriptions ModSync Screens The ModSync Sequencing System provides multiple screen interfaces for easy access and configuration of the Steam Loop control parameters. Parameter values are selected through the touch screen interface and entered using the ModSync keypad. The following section provides a description of each screen and the associated parameters. The FMS-8 screen configurations for a Steam Boiler installation has been used in the following examples. The same screens and common parameter settings will be used when additional boilers are controlled by the ModSync. The ModSync interface includes Soft Keys that surround the operator interface on the left and bottom. The soft keys can be used to navigate to the appropriately labeled screen from anywhere in the ModSync menu levels. The ModSync touch screen allows for screen navigation and parameter input by simply touching inside of the rectangle that outlines the associated variable. The screens will also include Status Indicators that reflect the current operating mode selection. See Figure 3 below: Figure 3. Parameter Input Status Indicator Screen Navigation Soft Keys Touch Screen Keypad Enter Key - 13 -

Main Menu Screen Main Menu Screen The Main Menu Screen is the first screen displayed when power is applied to the ModSync Sequencing System. This screen displays the current System Operating Mode, the Date/Time and current program revision. The Main Menu also provides a touch screen interface to select other screens. - 14 -

System Status Screen System Status Screen The System Status screen is the main ModSync screen. This screen displays the current pressure status of the Steam loop, the header setpoint and the Control Variable value. The current Steam boiler status is also displayed. - 15 -

Boiler Configuration Screens Steam Boiler Configuration Screens The Boiler Configuration Screens are used to independently setup each Steam boiler in the loop. The Steam Boiler Select Screen allows the user to enter the boiler number to select a Boiler Configuration screen. The Steam Boiler Configuration screens allow the user to adjust the mode of each Steam boiler in the loop, along with providing a manual control option. Control Mode/Status: Provide feedback on current mode selection and boiler status. Steam used in Lead/Lag Sequence: Defines whether the Steam boiler will be included in the Lead/Lag process. Auto/Man Select: Used to select Auto or Manual control over the Steam boiler. - 16 -

Boiler Configuration Screens Steam Boiler Configuration Screen Fulton Setting Parameter Range Description Enabled Auto Enabled /Disabled Auto/Manual Start / Stop Steam used in Lead/Lag Sequence Touchscreen operator that allows the user to independently Enable/Disable each of the Steam boilers in the loop. A Disabled boiler will not be used in the Lead/Lag sequence and cannot be controlled by the ModSync. Auto/Man Select Touchscreen operator that allows the user to select the Operation mode of each Steam boiler. In Auto mode, the ModSync will control operation of the boiler. In Manual mode, the user can Start/Stop the Steam boiler and manually enter a firing rate. Steam Manual Start/Stop Touchscreen operator that allows the user to start and stop the Steam boiler while in Manual mode. 0% 0% to 100% Manual Firing Rate % Touchscreen operator that allows the user to manually enter the firing rate of the Steam boiler when in Manual mode. - 17 -

Process Configuration Screen Process Configuration Screen The Process Configuration Screen is used to define the Steam loop pressure based on the header pressure and configuration of associated parameters. The Process Configuration screen is used to set the header pressure setpoint. Separate setpoint variables are available and used based on the Setback Schedule. To adjust the Setpoint: Touch the operator corresponding to the pressure that you wish to adjust. A cursor will appear in the block. Using the keypad, enter the new pressure and press the Enter key on the keypad. - 18 -

Process Configuration Screen Process Configuration Screen Fulton Setting Parameter Range Description 150 psi 0 to 150 psi Normal Mode Setpoint Setpoint used when the ModSync is in Normal Mode operation as selected by the Setback Schedule. 120 psi Setback Mode Setpoint 0 to 150 psi Setpoint used when the ModSync is in Setback Mode operation as selected by the Setback Schedule. ModSync ModSync Remote BMS Setpoint Mode Control Determines what setpoint the ModSync uses to sequence the boilers. ModSync mode uses the setpoint provided from the Process Config screen. Remote uses a 4-20mA signal supplied from the customer. BMS uses a modbus supplied setpoint. Loop Sensor Range (High) 200 psi 30 psi Header Sensor range high value. The pressure sensor supplied has a range determined by 100 psi 200 psi the type of steam system (0-30, 0-100, and 0-200). The Loop Sensor Range High value needs to be set at the high-end value of the sensor. - 19 -

Lead/Lag Configuration Screens Lead/Lag Configuration Screens The Lead/Lag Configuration Screens are used to define the parameters associated with the lead/lag operation of the ModSync, such as rotation schedule, control variable adjustment and response time. It is very important to tune these parameters with each Steam loop so that precise and consistent pressure control is maintained. Lead/Lag Configuration This screen configures the rotation schedule for the Lead Boiler in the loop. Cycles to Auto Rotate: Touch the Cycles to Auto Rotate operator and enter the number of cycles the lead boiler will have before a rotation is performed. Hours to Auto Rotate: Touch the Hours to Auto Rotate operator and enter the number of hours the lead boiler will operate before a rotation is performed. Note: The ModSync monitors both cycles and hours of the lead boiler. Rotation will be based on which ever of these values occurs first. During a call for heat the lead boiler will only change if hours are met. Status Indicators are used to show the lead/lag position of each boiler, along with the current number of cycles/hours that the lead boiler has. Lead/Lag Configuration (cont.) To adjust the Lag Boiler(s) operation: This screen configures the Lead and Lag boiler(s) start/stop values and their associated delays. - 20 -

Lead/Lag Configuration Screens Lead / Lag Configuration Screens Default Setting Parameter Range Description 20 1 to 9999 1 1 to 9999 Cycles to Auto Rotate: Touchscreen operator that defines the number of cycles the lead boiler will have before it is rotated. Hours to Auto Rotate: Touchscreen operator that defines the number of hours the lead boiler will have before it is rotated. Default Setting 00:30 00:30 Parameter Range 00:00 to 99:99 (M:S) 00:00 to 99:99 (M:S) Description Lag Boiler Start Delay (M:S): Touchscreen operator that allows the user to enter a delay before each lag boiler stage starts. This helps to prevent short cycling of the lag stages. Lag Boiler Stop Delay (M:S): Touchscreen operator that allows the user to enter a delay before each lag boiler stage stops. This helps to prevent short cycling of the lag stages. 5 psi -99psi to 99psi 0 psi -99psi to 99psi 20% 0% to 100% 10% 0% to 100% 30% 0% to 100% 40% 0% to 100% 50% 0% to 100% Lead Boiler Start Deviation: Touchscreen operator that allows the user to enter a deviation from setpoint before the lead boiler starts. If the setpoint is 120psi and the start deviation is 5psi, the lead boiler will not start until the steam loop pressure drops to 115psi. Lead Boiler Stop Deviation: Touchscreen operator that allows the user to enter a deviation from setpoint before the lead boiler stops. If the setpoint is 120psi and the stop deviation is 5psi, the lead boiler will not stop until the steam loop pressure reaches 125psi. Lead High Flame Stage Start CV: Touchscreen operator that defines the Control Variable value that will bring the lead boiler on high flame. The CV value will be determined by the PID parameters selected on the second Lead/Lag Config screen. Lag 1 Low Flame Stage Start CV: Touchscreen operator that defines the Control Variable value that will bring the first lag boiler on low flame. The CV value will be determined by the PID parameters selected on the second Lead/Lag Config screen. Lag 1 High Flame Stage Start CV: Touchscreen operator that defines the Control Variable value that will bring the first lag boiler on high flame. The CV value will be determined by the PID parameters selected on the second Lead/Lag Config screen. Lag 2 Low Flame Stage Start CV: Touchscreen operator that defines the Control Variable value that will bring the second lag boiler on low flame. The CV value will be determined by the PID parameters selected on the second Lead/Lag Config screen. Lag 2 High Flame Stage Start CV: Touchscreen operator that defines the Control Variable value that will bring the second lag boiler on high flame. The CV value will be determined by the PID parameters selected on the second Lead/Lag Config screen. - 21 -

Lead/Lag Configuration Screens Lead/Lag Configuration Screens continued: The next Lead/Lag Screen is used to configure the PID parameters that determine the Control Variable (CV). The CV is used to stage the Steam boilers on and off based on the steam loop heat requirements. Proportional, Integral, Derivative: Variables that determine reaction of the Control Variable based on the steam loop heat load changes. Manual Reset: Allows a shift in the control band to utilize low fire operation. PID Status: Provide status information regarding the PID loop for troubleshooting purposes. - 22 -

Lead/Lag Configuration Screens Lead / Lag Configuration Screens Default Setting Parameter Range Description Proportional Band (% of 200): 20 0% to 100% Touchscreen operator that defines the proportional band setting for the steam loop. 0 0 to 240 seconds Integral Time (Units of 1 sec): Touchscreen operator that defines the Integral time base for the steam loop. 0 0 to 240 seconds Derivative Time (Units of 1 sec): Touchscreen operator that defines the Derivative time base for the steam loop. 5 psi -100psi to100psi Manual Reset Value (psi): Touchscreen operator that shifts the PID controlling setpoint. Manual Reset will adjust the PID loop to control off of the actual setpoint minus the Manual Reset value. This will keep the lead boiler at low fire after the Manual Reset setpoint until the Lead Boiler Stop Deviation pressure value is reached. - 23 -

Setback Schedule Screen Setback Schedule Configuration Screen The Setback Schedule screen is used to define the operating mode of the steam loop based on the Day of the Week and Time of Day. There are two modes that the steam loop can operate in: Normal and Setback. The Setback Schedule determines the mode of operation based on how the Normal mode time for each day has been configured. The steam loop will be in Setback mode when the actual time is outside the defined Normal mode timeframe. Normal Mode: Defines the start and stop times for each day that the steam loop will be in Normal mode. To change the time, simply touch the operator and a cursor will appear. Use the keypad to enter a new time (24Hr format) and press the Enter key. Mode Change: Allows the user to select auto or manual control over the steam loop mode. Mode Select: Allows the user to select the steam loop mode when the Mode Change is in Manual. - Building is in Normal Mode. - Building is in Setback Mode. - 24 -

Setback Schedule Screen Fulton Setting Parameter Range Description Normal Mode Start/Stop (24Hr Time of Day): Start: 06:00 00:00 to 23:59 Touchscreen operator that defines the Normal mode start time and stop time for each day of Stop: 20:00 the week. Mode Change: Auto Auto Touchscreen operator that determines if the steam loop mode will be automatically controlled Manual by the programmed time schedule or will be manually controlled by the user. Mode Select: Normal Normal Touchscreen operator that defines the steam loop mode if the Mode Change is set to Setback manual. - 25 -

Boiler Status Screen Boiler Status Screen The Boiler Status screen can be accessed by pressing the operator on the System Status screen. This screen will provide current operating status, cycles, mode, firing rate (if applicable) and Lead/lag stage information. - 26 -

System Configuration Screens System Configuration Screens The System Configuration Screen Menu allows access to multiple values used to configure the ModSync. This screen can be accessed by pressing the unlabeled soft key while on the Main Screen. - 27 -

System Configuration Screens System Configuration Number of Boilers: Select the number of boilers that the ModSync will interface with. Default Factory Settings: Pressing this operator sets all of the ModSync variables back to their factory default settings. Scaling Configuration Remote SP Scaling: Defines the analog input (4 20 ma) range when a remote setpoint signal is used. BMS Interface Configuration: Used to configure the communication parameters between the ModSync and a Building/Energy Management System. Web Server Configuration: Defines the server login and page refresh rate. The login for the web server will be mod and the four-digit login number (ex. mod0000). - 28 -

System Configuration Screens System & Scaling Configuration Screen Default Setting Low 0 High 250 Parameter Range 0 250 psi Description Remote SP Scaling Remote Setpoint analog input (4-20 ma) scaling. BMS & Web Server Screen Default Setting Parameter Range Description RS-485 RS-485 RS-232 2 1-20 19200 9600 19200 5555 0-9999 2 0 100 seconds Comm Standard Defines the communication standard that will be used by the ModSync to interface with the BMS Node Address Defines the unique address for the ModSync on the Modbus network Baud Rate Defines the transmission speed of the ModSync com port Modbus Reset Resets the Modbus network. This should be done whenever a device is added or modified Login Password used to access the ModSync configuration screens when a web server is used. Refresh Rate Configures how often the pages are updated when a web server is used. - 29 -

System Configuration Screens Password Configuration: Allows a 4-digit password to be entered that prevents unauthorized access to the setup screens. The Password Bypass Timer allows access to the setup screens (once the password has been entered) for the configured time. When the password bypass timer expires, the password will need to be entered to access the setup screens. Maintenance Configuration: The Preventive Maintenance Boiler Hours is used to define the number of run hours for the boilers before a PM is required. The Cycle Status displays the number of cycles for each boiler in the loop. Steam Sensor Input: The Steam Sensor configuration allows for selection of where the ModSync will receive the actual header pressure signal. Alarm Configuration: The Alarm Delay prevents the ModSync from disabling a boiler until the boiler s alarm input has been activated for the user defined time delay. The Boiler Enable after Alarm Clear, if in Auto, will allow the boiler to be automatically re-enabled if the boiler alarm is cleared. The Alarm History can also be cleared. - 30 -

System Configuration Screens Password & Screen Saver Configuration Screen Default Setting Parameter Range Description 0 0-9999 New Password 4-digit password required to access setup screens. Setting to 0 removes the password requirement. 5:00 Enabled 5:00 10:00 0 to 99:99 (MM:SS) Enabled Disabled 0 to 99:99 (MM:SS) 0 to 99:99 (MM:SS) Password Bypass Timer Setup screens can be accessed for this time period after the password has been entered. Status Enables/Disables the ModSync screensaver option. Time Defines the timeframe the ModSync will wait before entering screensaver mode. Dim Time Defines the timeframe the ModSync will wait before dimming the ModSync screen. Maintenance Configuration Screen Default Setting Parameter Range Description 2000 0-8760 0 0-999,999 Preventative Maintenance Boiler Hours Configures the number of run hours before a boiler preventative maintenance is required. Cycle Status Displays the current cycle count for each boiler. The cycle count can be modified by selecting the rectangle next to the boiler description and entering the new value. Sensor & Alarm Configuration Screen Default Parameter Range Description Setting ModSync 00:00 Auto ModSync BMS 0 to 99:99 (MM:SS) Auto Manual Header Sensor Determines where the header pressure input is being received from. If ModSync is selected, a header pressure sensor is sending the signal directly to the ModSync. If BMS is selected, a Modbus value is being provided to the ModSync. Header BMS Value Visual indicator of the setpoint being received from the external device if ModBus is being used. Alarm Delay Determines the delay time between when an alarm from the boiler is received to when the ModSync disables the boiler. Boiler Enable after Alarm Clear Defines if the boiler will automatically be re-enabled at the ModSync after the local alarm is cleared. In Manual, the boiler will need to be re-enabled at the ModSync even if the local alarm has been reset. Alarm History Clears the ModSync alarm history. - 31 -

Alarm Status Screen Alarm Status Screen The Alarm Status screen will provide a text display of any existing alarm conditions that the ModSync monitors. Alarm History Screen Alarm History Screen The Alarm History Screen will display the last eight alarm conditions that the ModSync has recorded. This will assist Service personnel in troubleshooting any steam loop errors. - 32 -

Alarm Screen Schedule Troubleshooting Alarm messages are shown on the Alarm Status screen. The alarm messages will provide a detailed description of the alarm condition. Alarm Messages: Message System Active Explanation / Recommended Action The ModSync is active and no alarms are sensed. Steam Sensor Error The Steam Sensor is providing a value outside of the allowable scale. Verify the pressure sensor wiring. Replace the sensor if required. Steam Boiler X Alarm The Burner control on the Steam boiler has indicated that an alarm condition has occurred at the boiler or a Call for Heat signal was provide by the ModSync and the boiler did not start within 2 minutes. Check flame programmer and safety limit string for locked out devices. - 33 -

- 34 -

- 35 -

- 36 -

Modbus Network Network Parameter Configuration and Address Listings. The ModSync Sequencing System provides a Modbus interface to communicate the status of each steam boiler in the loop to a SCADA System. This network can also be used to receive start/stop and remote setpoint commands from the SCADA System. The following tables detail the communication parameters and the ModSync addresses available for an FMS-2 through FMS-8 Steam System. Communication The following communication parameters should be used when configuring a ModSync Communication Network: Parameter Protocol Modbus (RS-485), RTU. Setting Baud Rate 9600, 19200 Start Bits 8 Parity None Timeout 5 Seconds. Nodes Up to 20. - 37 -

Modbus Network ModSync Addresses Modbus Registers Address Description Range Units 2001 (R/W) Steam Loop Pressure 0 to 150 psi 2002 (R/W) Modbus Setpoint Input (if applicable) 0 to 150 psi 2003 (R/W) ModSync Setpoint Mode 0 - ModSync 1 Remote SP 2 - BMS 2004 (R) ModSync Setpoint psi 2005 (R) ModSync Alarm Code 0 No Alarm 1- Steam Sensor 2 N/A 3 Steam 1 Alarm 4 Steam 2 Alarm 5 Steam 3 Alarm 6 Steam 4 Alarm 7 Steam 5 Alarm 8 Steam 6 Alarm 9 Steam 7 Alarm 10 Steam 8 Alarm 11 Modbus Alarm 2006 (R) Steam 1 Firing Rate 0 to 100 % 2008 (R) Steam 2 Firing Rate 0 to 100 % 2010 (R) Steam 3 Firing Rate 0 to 100 % 2012 (R) Steam 4 Firing Rate 0 to 100 % 2014 (R) Steam 5 Firing Rate 0 to 100 % 2016 (R) Steam 6 Firing Rate 0 to 100 % 2018 (R) Steam 7 Firing Rate 0 to 100 % 2020 (R) Steam 8 Firing Rate 0 to 100 % - 38 -

Modbus Network Modbus Coils Address Description Value = 1 2500 (R) Steam Loop Mode (Normal/Setback) Normal 2501 (R) Remote Enable/Disable (if applicable) Enabled 2502 2503 (R) Lead Boiler Select (Auto/Manual) Auto 2504 (R) Steam Boiler 1 Local/Remote Switch Remote 2505 (R) Steam Boiler 1 ModSync Enable/Disable Enabled 2506 (R) Steam Boiler 1 Run Status On 2507 (R) Steam Boiler 1 Alarm Status On 2508 (R) Steam Boiler 2 Local/Remote Switch Remote 2509 (R) Steam Boiler 2 ModSync Enable/Disable Enabled 2510 (R) Steam Boiler 2 Run Status On 2511 (R) Steam Boiler 2 Alarm Status On 2512 (R) Steam Boiler 3 Local/Remote Switch Remote 2513 (R) Steam Boiler 3 ModSync Enable/Disable Enabled 2514 (R) Steam Boiler 3 Run Status On 2515 (R) Steam Boiler 3 Alarm Status On 2516 (R) Steam Boiler 4 Local/Remote Switch Remote 2517 (R) Steam Boiler 4 ModSync Enable/Disable Enabled 2518 (R) Steam Boiler 4 Run Status On 2519 (R) Steam Boiler 4 Alarm Status On 2520 (R) Steam Boiler 5 Local/Remote Switch Remote 2521 (R) Steam Boiler 5 ModSync Enable/Disable Enabled 2522 (R) Steam Boiler 5 Run Status On 2523 (R) Steam Boiler 5 Alarm Status On 2524 (R) Steam Boiler 6 Local/Remote Switch Remote 2525 (R) Steam Boiler 6 ModSync Enable/Disable Enabled 2526 (R) Steam Boiler 6 Run Status On 2527 (R) Steam Boiler 6 Alarm Status On 2528 (R) Steam Boiler 7 Local/Remote Switch Remote 2529 (R) Steam Boiler 7 ModSync Enable/Disable Enabled 2530 (R) Steam Boiler 7 Run Status On 2531 (R) Steam Boiler 7 Alarm Status On 2532 (R) Steam Boiler 8 Local/Remote Switch Remote 2533 (R) Steam Boiler 8 ModSync Enable/Disable Enabled 2534 (R) Steam Boiler 8 Run Status On 2535 (R) Steam Boiler 8 Alarm Status On - 39 -

- 40 -

- 41 -

ModSync Limited Warranty Fulton warrants that it will replace or repair any ModSync components or part thereof which is found defective in workmanship or material, within one year from the date of installation or 18 months from the factory shipment date, whichever comes first. The foregoing is in lieu of all other warranties, expressed or implied, and Fulton specifically disclaims any and all merchantability or fitness for a particular purpose. Under no circumstances shall Fulton, its authorized Representatives, affiliated or subsidiary companies be liable for special, consequential or incidental damages. Liability by Fulton shall be limited to replacement or repair of the ModSync or associated ModSync components only. - 42 -

Specifications ModSync Sequencing System Model: FMS Mechanical: Size: Weight: Environmental: Operating Temp: Storage Temp: Front Panel: Electrical: Input Power: Height: 420mm; Width: 370mm; Depth: 211mm 10 Kgs 32ºF to 125ºF (0ºC to 52ºC) -20ºF to 150ºF (-28ºC to 65ºC) NEMA 4, IP65 120/230 VAC (+/- 10%), less than 2 Amps. Agency Listings: UL 508A Industrial Control Panels. Parts Information Part Number Description 2-45-001034 ModSync Operator Interface Terminal 2-45-001039 I/O Expansion Module 2-45-001035 Expansion Adapter 2-45-001038 RS-485 Communication Port 2-45-001040 24VDC Power Supply - 43 -