Compact Genset Controller, CGC 400 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

Similar documents
Generator Control Unit, GCU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

Engine Control Unit, ECU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL

Protection and Power Management, PPM-3 Display and push-button functions Alarm handling Log list Failure mode and effect analysis

DEIF A/S. Operator s Manual. Basic Gen-set Controller. Display readings. Push-button functions. Alarm handling. Log list C (UK)

DEIF A/S. Operator s Manual. Multi-line 2/version 2-GS E (UK) SW version 2.4X.X. Display readings. Push-button functions.

CAN bus-based I/O module, CIO relays Mounting Terminals and wiring Commissioning, using the utility software

DEIF A/S. Description of options. Option A4, Loss of mains protection package Automatic Gen-set Controller. Description of option

Engine Control Unit, ECU 100 Functional description Additional functions Parameter list

DEIF A/S. Description of options. Option M17, Configurable inputs and RPM supervision Engine Controller EC-1/EC-1M. Description of option

Option M16.x Configurable I/O extension cards, four multi-inputs (4-20 ma/0-5 V/Pt100) Description of option Functional description

Generator Paralleling Controller, GPC-3 Hydro Start and stop sequences, water level control

DELOMATIC 400, DM-400 HYDRO

INSTALLATION INSTRUCTIONS. Anti Knocking System, AKR 3. Document no.: A SW version:

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

Tri-Stack Smart System

PowerWizard. Level 1.0 & Level 2.0 Control Systems Training

User Manual. Dryer Controller M720

Operation Manual Fighter ProVision Software. Version: 0.0 Revision: 1

Halton SAFE / 7.14 user guide and installation instructions

MPT Electric Fire Pump Controller

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

Dryer Controller M720

TE809-Ats Instructions Manual

QuadraTouch Pro Software Manual Dryer Control System

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

DEIF A/S. Technical Manual. Type EC-2 Engine Control Unit D. Technical Manual

M2000 Engine Controller

Manual# User s Manual. DCU 410/408 Engine Control Unit RP 410 Remote Panel FW 2.3

CONTROL PANEL INTERFACE ACTIVATE THE GENERATOR DISPLAY INTERFACE MENUS. Control Panel USING THE AUTO/OFF/MANUAL SWITCH

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

THX-DL Data Logger USER & INSTALLATION MANUAL V

Emergency power automatics MS-2. High resistance to shock, vibrations and transients. All output are 2A relay contacts

Master User Guide Premier Elite Series

Intelligent Security & Fire Ltd

EXPERT TRI-STAR. Temperature controller. User s Manual

ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Procidia iware AlarmWorX32. AlarmWorX32 Viewer January 2010

U ser's Guide PC6010

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

M2000 Engine Controller

MPT Electric Fire Pump Controller

HIGH EFFICIENCY FIRETUBE CONDENSING GAS BOILER

Spa Touch Control Panel with BP2100, BP6013 spa controllers. (Spa Owner s Manual insert)

M3092 Programmer. User s Manual. M3096B-33 E Copyright 2017 SELCO

SmarTemp Control fx 2.0

Tasman Sea Control System

DS7446KP. User Guide. Keypad

TPOne-B. Electronic Programmable Room Thermostat. Installation Guide. Danfoss Heating

Temperature Controller CC24-7 UNIBOX USER S MANUAL Legion Dr. Mason, MI USA October 2010 Ph. (517) Fax (517)

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

Sensor Control Panel

CSP-204 CSP-208 CSP-104 CSP-108

Dryer Master DM510 Commissioning Guide

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Table of Contents. Part I SAFETY MESSAGE TO INSTALLERS OF EMERGENCY WARNING EQUIPMENT 2 Part II Vehicle Operation 4. Part III Safety Messages 13

PRODUCT BULLETIN. Rev. A Monitoring Station offering PN Rev. B as a direct replacement. OVERVIEW / DESCRIPTION

Ref. 1067/024 Ref. 1067/032A Ref. 1067/052A

User Guide IM/SM3000 EN Rev. L. SM3000 Multipoint Videographic Recorder

OPERATING INSTRUCTIONS. G214 Software - Version 4

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

TV2 Room Pressure Monitor Quick Start Guide

Memcom Emergency Telephone

ZERIO PLUS EDA-Z5008, Z5020 & Z5100

Ontech GSM 9040/50. Reference Manual English -1 -

User s Manual DCU 305 R3 DCU 305 R3 LT. Diesel Engine Control Unit. Auto-Maskin

Spa Touch Control Panel with 2000, 2100 controllers. (Spa Owner s Manual insert)

INSTRUCTION FOR THE USER THC V E OIL BLU

Manual# User s Manual

Diplomat Inverter/Diplomat Duo Inverter

INSTALLATION MANUAL AND OPERATING INSTRUCTIONS

MANUAL FOR MODEL MP600 HIGH VOLTAGE ELECTRIC MOTOR DRIVEN FIRE PUMP CONTROLLERS

Lift Station Level Controller

Flopurge TS. Operation Manual

Lyric T6 & T6R Smart Thermostat

Operator's Handbook. Release 3. Fire Alarm Control Panel, BS-310 / 320 / Operator Panel BS-330. System Program Version 3.8.0

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

Laptop / PC Programming Manual

Conviron CMP5090 User Guide

CRX Single Zone Wireless Controller. Installation and User Guide. 1. Getting to know your CRX2 wireless controller

A WORLD OF COMFORT. Quick start guide. following control units and mounting parts: Control units EasyStart Remote, 12 /24 V

Rooftop Thermostat Controller Specification and Installation Instructions. Model TRT2422

DYGIZONE GJD910 Lighting Controller & Enunciator

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

Entero Voice Alarm system.

Patriot Systems Limited

Fire Command Keypad. XR5 User s Guide

SILENCING AN ALARM When the alarm bell or siren is sounding, enter your user code or present your SecuraProx fob to your keypad.

User & Installer Manual SMT-400 "Enterprise" Wi-Fi Thermostat

User Guide

FIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -

Smart thermostat with Humidification/De-humidification control

User Operation Manual

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

Heller Industries A688951: Rev-D Jan-2007 Oven System Setup Wizard: Software version

Fridge-tag 2 OPERATION MANUAL ENGLISH PAGE 1-35 GEBRAUCHSANWEISUNG DEUTSCH SEITE with external sensor

Control of the system, MLP RO pump station

EasyTronic III MANUAL SERVICE

Diagnostics and Monitoring System WEB Tool 2. User Manual

Transcription:

OPERATOR'S MANUAL Compact Genset Controller, CGC 400 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list DEIF A/S Frisenborgvej 33 DK-7800 Skive Tel.: +45 9614 9614 Fax: +45 9614 9615 info@deif.com www.deif.com Document no.: 4189340787A SW version: 1.00

1. General information 1.1. Warnings, legal information and safety...3 1.1.1. Warnings and notes...3 1.1.2. Legal information and disclaimer...3 1.1.3. Safety issues...3 1.1.4. Electrostatic discharge awareness...3 1.1.5. Factory settings...4 1.2. About the operator's manual...4 1.2.1. General purpose...4 1.2.2. Intended users...4 1.2.3. Contents and overall structure...4 2. Push-buttons and LEDs 2.1. Push-button functions...5 2.2. LED functions...6 3. Display and menu structure 3.1. Menu...7 3.1.1. Menu system...7 3.1.2. View menu...7 3.1.3. Menu structure example...8 3.2. Display functions...9 3.2.1. Functional examples...9 4. Status line text 4.1. Status line text...11 4.1.1. Standard texts...11 5. Running modes 5.1. Running mode overview...13 6. Alarm handling and log list 6.1. Alarm handling...14 6.2. Log list...14 DEIF A/S Page 2 of 14

General information 1. General information 1.1 Warnings, legal information and safety 1.1.1 Warnings and notes Throughout this document, a number of warnings and notes with helpful user information will be presented. To ensure that these are noticed, they will be highlighted as follows in order to separate them from the general text. Warnings Notes Warnings indicate a potentially dangerous situation, which could result in death, personal injury or damaged equipment, if certain guidelines are not followed. Notes provide general information, which will be helpful for the reader to bear in mind. 1.1.2 Legal information and disclaimer DEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate the engine/generator controlled by the unit, the company responsible for the installation or the operation of the set must be contacted. The unit is not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost. Disclaimer DEIF A/S reserves the right to change any of the contents of this document without prior notice. 1.1.3 Safety issues Installing and operating the unit may imply work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment. Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death. DEIF do not recommend to use the USB as the primary power supply for the unit. 1.1.4 Electrostatic discharge awareness Sufficient care must be taken to protect the terminal against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary. DEIF A/S Page 3 of 14

General information 1.1.5 Factory settings The unit is delivered from factory with certain factory settings. These are based on average values and are not necessarily the correct settings for matching the engine/generator set in question. Precautions must be taken to check the settings before running the engine/generator set. 1.2 About the operator's manual 1.2.1 General purpose This Operator's Manual mainly includes general product information, display readings, push-button and LED functions, alarm handling descriptions and presentation of the log list. The general purpose of this document is to give the operator important information to be used in the daily operation of the unit. Please make sure to read this document before starting to work with the unit and the generator set to be controlled. Failure to do this could result in human injury or damage to the equipment. 1.2.2 Intended users This Operator's Manual is mainly intended for the daily user. On the basis of this document, the operator will be able to carry out simple procedures such as start/stop and control of the generator set. 1.2.3 Contents and overall structure This document is divided into chapters, and in order to make the structure simple and easy to use, each chapter will begin from the top of a new page. DEIF A/S Page 4 of 14

Push-buttons and LEDs 2. Push-buttons and LEDs 2.1 Push-button functions The push-buttons on the unit have the following functions: 1 2 3 4 5 6 15 14 13 12 11 10 9 8 7 No. Function No. Secondary functionality 1: Scroll the display up once 1: Programming: Increase setpoint value 2: Scroll the display down once 2: Programming: Decrease setpoint value 3: Enter menus/enter value/acknowledges alarm 4: Back button 4: Remove pop-up messages 5: Manual/Block running mode selector 5: Press MAN twice to activate Block mode 6: Lamp test 7: AUTO running mode selector 8: Test running mode selector 9: Close mains breaker 10: Open mains breaker 11: Close generator breaker 12: Open generator breaker 13: Start engine (manual running mode) 14: Stop engine (manual running mode) 15: Reset horn relay 15: Press and hold for 2 seconds to see alarm list DEIF A/S Page 5 of 14

Push-buttons and LEDs 2.2 LED functions The display unit holds 10 LED functions. Dependent on the situation, the colour of the LEDs is green, red or a combination. The table below describes the functionality of the LEDs on the CGC 400: 3 2 1 10 9 8 7 6 5 4 LED no. LED name LED function 1: Alarm LED steady light indicates that all alarms are acknowledged, but some are still present. 2 : Power LED indicates that the auxiliary supply is switched on. If it is green, the controller is operational. If it is red, the self-check has failed. LED flashing indicates that unacknowledged alarms are present. 3: 4 x LED 4 x LEDs with selectable indication function. Selection is made in M-Logic. 4: MAN LED steady light indicates that Manual mode is active. LED flashing green indicates that Block mode is active. 5: AUT LED indicates that Auto mode is active. 6: Mains OK LED is green if the mains is present and OK. LED is red at a mains failure. LED is flashing green when the mains returns during the "mains OK delay" time. 7: MB on LED Indicates that the mains breaker is closed. 8: GB on LED Indicates that the generator breaker is closed. 9: Hz/V ok LED Indicates that voltage and frequency is present and OK. 10: Run LED indicates that running feedback is present. DEIF A/S Page 6 of 14

Display and menu structure 3. Display and menu structure 3.1 Menu 3.1.1 Menu system The display includes the menu systems listed below which can be used/viewed without password entry: View menu system: This is the commonly used menu system, which contains displaying of the measured values. Log menu: This menu contains event, alarm and battery logs. Setup menu (not commonly used by the operator): This menu is used for setting up the unit, and if the operator needs detailed information that is not available in the view menu system. Changing of parameter settings is password-protected. Alarm list: This list shows active acknowledged and unacknowledged alarms. Alarms can also be acknowledged by pressing the OK button Service menu: This menu contains input-, output-, M-Logic status and data about the unit. 3.1.2 View menu The view menus are the daily use menus for the operator. There are 20 configurable display views, with up to three configurable display lines in each view. View configuration is done through the PC utility software (USW). In the view menus, various measured values are on the display. AMF G P G Q G S Run absolute MAN 0 kw 0 kvar 0 kva 0 hrs First display line: Genset mode and running mode Second display line: Measurements relating to operational status Third display line: Measurements relating to operational status Fourth display line: Measurements relating to operational status Fifth display line: Running hours DEIF A/S Page 7 of 14

Display and menu structure 3.1.3 Menu structure example The figure below is an example of how the menu structure is arranged, and it also shows the meaning of the entry symbols.... (up to 20 views) ISLAND MODE G U-L1L2 G U-L2L3 G U-L3L1 Run absolute 400 V 400 V 400 V ISLAND MODE G U-L1N G U-L2N G U-L3N Run absolute 230 V 230 V 230 V ISLAND MODE G U-L1L2 G U-L2L3 G U-L3L1 Run absolute Use arrows to toggle betweeen menus LOG MENU Event log Alarm log Battery test log SETUP MENU 1000 Protections 2000 Breaker 2500 Regulation 3000 Digital input Alarm list: Start failure Ch 4570 UNACK 2/2 alarm(s) Service menu Status binary input Status relay output Status analog input M-logic Line Status Event log: 2012-10-01 08:15:00 GB ON 1/50 Log(s) SETUP MENU 1000 G-P> 1 1010 G-P> 2 1020 G 1> 1 1030 G 1> 2 Alarm list: GB Ext. tripped Ch 1981 UNACK 1/2 alarm(s) Service menu Auto start/stop 1 Digital in 11 0 Digital in 12 0 Digital in 13 0 1000 -P> 1 Set point: -5.0% Timer: 0.5 sec Output A: Not used Output B: Not used Use the arrows to change the setpoint DEIF A/S Page 8 of 14

Display and menu structure 3.2 Display functions 3.2.1 Functional examples The display indicates both readings and alarms. The examples below are with icons and English language. View examples Service menu Appl. Ver.: 9.90.0 Appl. Rev.: 0 Boot Ver.: 9.99.1 Boot Rev.: 0 The software version can be found in the Service menu AMF G P G Q G S Run absolute MAN 0 kw 0 kvar 0 kva 0 hrs Status, Generator P, Q and S. Run hours. AMF MAN Serv1 1 d 0 h Serv2 1 d 0 h Service timer 1 and 2. Run hours. Run absolute 0 hrs Alarm acknowledge ISLAND MODE G U-L1L2 G U-L2L3 G U-L3L1 G f-l1 Alarm list: BB U> 1 Ch 1270 UNACK Press the OK button to enter the list of active alarms. The alarm list shows the active alarms. Press the OK button to ackowledge alarms 1/1 alarm(s) Parameter settings ISLAND MODE G U-L1L2 G U-L2L3 G U-L3L1 G f-l1 SETUP MENU 1000 Protections 2000 Synchronization 2500 Regulation 3000 Digital input Press the OK button to enter the parameter setting. Select menu group with the OK button to edit. DEIF A/S Page 9 of 14

Display and menu structure 1000 -P> 1 Set point: -5.0% Timer: 0.5 sec Output A: Not used Output B: Not used Edit value with up and down arrows and save the value by pressing the OK button. For detailed information about changing parameters and setup, please see the Designer's Reference Handbook. DEIF A/S Page 10 of 14

Status line text 4. Status line text 4.1 Status line text 4.1.1 Standard texts BLOCK Condition SIMPLE TEST FULL TEST SIMPLE TEST ###.#min FULL TEST ###.#min ISLAND MAN READY ISLAND AUTO ISLAND ACTIVE AMF MAN READY AMF AUTO AMF ACTIVE LOAD TAKEOVER MAN READY LTO AUTO LTO ACTIVE DG BLOCKED FOR START GB ON BLOCKED SHUTDOWN OVERRIDE ACCESS LOCK Block mode is activated Test mode is activated Comment Test mode activated and test timer counting down Genset stopped or running and no other action taking place Genset stopped in Auto Genset running in Auto Genset stopped or running and no other action taking place Genset stopped in Auto Genset running in Auto Genset stopped or running and no other action taking place Genset stopped in Auto Genset running in Auto Generator stopped and active alarm(s) on the generator Generator running, GB open and an active "Trip GB" alarm The configurable input is active The configurable input is activated, and the operator tries to activate one of the blocked keys GB TRIP EXTERNALLY Some external equipment has tripped the breaker An external trip is logged in the event log MB TRIP EXTERNALLY Some external equipment has tripped the breaker An external trip is logged in the event log IDLE RUN IDLE RUN ###.#min Aux. test ##.#V ####s START PREPARE START RELAY ON The "Idle run" function is active. The genset will not stop until a timer has expired The timer in the "Idle run" function is active Battery test activated The start prepare relay is activated The start relay is activated DEIF A/S Page 11 of 14

Status line text Condition START RELAY OFF MAINS FAILURE MAINS FAILURE IN ###s Comment The start relay is deactivated during the start sequence Mains failure and mains failure timer expired Frequency or voltage measurement is outside the limits The timer shown is the Mains failure delay.text in mains units MAINS U OK DEL ####s Mains voltage is OK after a mains failure The timer shown is the Mains OK delay MAINS f OK DEL ####s Mains frequency is OK after a mains failure The timer shown is the Mains OK delay Hz/V OK IN ###s The voltage and frequency on the genset is OK When the timer runs out it is allowed to operate the generator breaker COOLING DOWN ###s Cooling-down period is activated COOLING DOWN Cooling-down period is activated and infinite Cooling down timer is set to 0.0 s GENSET STOPPING EXT. STOP TIME ###s This info is shown when cooling down has finished EXT. START ORDER A planned AMF sequence is activated There is no failure on the mains during this sequence DEIF A/S Page 12 of 14

Running modes 5. Running modes 5.1 Running mode overview The unit has four different running modes and one block mode. The different running modes are selected via the display or the PC utility software. For detailed information please see Designer's Reference Handbook. Auto In auto mode, the unit will operate automatically, and the operator cannot initiate any sequences manually. Test The test sequence will start when the test mode is selected. The type of test is selected in parameter 7040. Manual Manual means that the unit will not initiate any sequences automatically, as is the case with the auto mode. It will only initiate sequences, if external signals are given. Block When the block mode is selected, the unit is not able to initiate any sequences, e.g. the start sequence. Block mode must be selected when maintenance work is carried out on the genset. The genset will shut down if block mode is selected while the genset is running. DEIF A/S Page 13 of 14

Alarm handling and log list 6. Alarm handling and log list 6.1 Alarm handling When an alarm occurs, the unit will automatically go to the alarm list for display of the alarm. If reading of the alarms is not desired, use the BACK push-button to exit the alarm list. If you decide to enter the alarm list later, press the HORN push-button for 2 seconds to jump directly to the alarm list reading. The alarm list contains both acknowledged and unacknowledged alarms provided that they are still active (i.e. the alarm condition is still present). Once an alarm is acknowledged and the condition has disappeared, the alarm will no longer be displayed in the alarm list. This means that if there are no alarms, the alarm list will be empty. This display example below indicates an unacknowledged alarm. The display can show only one alarm at a time. Therefore, all other alarms are hidden. Alarm list: BB U> 1 Ch 1270 UNACK 1/1 alarm(s) To see the other alarms, use the up and down push-buttons to scroll in the display. To acknowledge an alarm press OK button. 6.2 Log list The log is divided into three different lists: 1. Event log 2. Alarm log 3. Battery test log The log list contains up to 50 events, the alarm list contains up to 30 historical alarms, and the battery test list contains up to 52 historical battery tests. An event is e.g. closing of breaker and starting of engine. An alarm is e.g. overcurrent or high cooling water temperature. A battery test is e.g. test OK or test failed. To enter the log list: 1. Enter the LOG TYPE SELECT from the setup menu 2. Select the list which is needed with the up and down arrows and choose with the OK push-button. 3. To scroll up and down in the list, use the up and down push-buttons. DEIF A/S Page 14 of 14