ACCESSORY KIT INSTALLATION INSTRUCTIONS Masonry Chimney Draft Hood Kit GENERAL INFORMATION DESCRIPTION Tile Lined Chimney Kit Model Numbers CK060 and CK0604 permits the venting of an 80% induced draft furnace to be vented into a properly sized masonry lined chimney, without the installing a metal liner. The kit can be used on model numbers P4HU, PDU, G8T, L8T, G8D, L8D, G8V, - BGU-Upflow Category I Furnaces, P4DN, PDD, G8T, L8T, FL8, G8D -Counterflow Category I and G8C-MU, G8C-MD, and FG8 Multi-Position furnaces (see Table for complete listing). Thiskitisonlytobeusedonupflowandcounterflow(downflow) installations only. The kit is not intended to be used with horizontally installed furnaces, or on furnaces where the lateral vent length exceeds the length specified in Table. The Tiled Chimney Kit is certified for use with Natural or LP gas. Installation Checklist! Select Correct Kit Model (page ) For your safety, read and understand the instructions before installing the kit. Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service, or maintenance can cause injury or property damage. Refer to this manual for assistance or additional information. Consult a qualified installer, service agency or the gas supplier.! Verify Chimney Condition (page 4)! Properly Size Flue Pipe (Table or )! Attach Chimney Kit (Figure 4)! Connect Limit Switch Wiring (Figure ) This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and national codes including but not limited to building, electrical and mechanical codes.! Check Kit for Spillage (Page 8)! Place Furnace into Operation (Page 8) Unitary Products Group
SAFETY STATEMENT The installer should pay particular attention to the words: NOTE, CAUTION and WARNING. NOTES are intended to clarify or make the installation easier. CAUTIONS are given to prevent equipment damage. WARNINGS are given to alert the installer that personal injury and/or equipment or property damage may occur if installation procedures are not handled properly. This furnace should be installed in accordance with all national and local building and safety codes and requirements, or in the absence of local codes, with the National Fuel Gas Code, ANSI Z.- (latest edition) or in Canada, The National Canadian Installation Code CAN/CGA B49. or B49. - (latest edition), and other applicable codes. This furnace shall not be connected to a chimney flue serving a separate appliance designed to burn solid fuel. This kit is permitted to be used in any building in which the space surrounding the furnace is not depressurized by more than 0.0 in.w.c. ( Pa) below outdoor pressure by equipment such as exhaust fans or clothes dryers. any model other than the models listed in Table. The room temperature surrounding the furnaces and vent connectors shall be 60 F (4 C) or warmer. CHIMNEY INSPECTION For venting guidelines, refer to the venting tables in this manual. For additional requirements, refer to the National Fuel Gas Code NFPA 4/ANSI Z. and Standard for Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances ANSI/NFPA, or The National Canadian Installation Code CAN/CGA-B49. or 49. in Canada. Also refer to Figure, Chimney Inspection Chart. FURNACE SIZING Size the furnace not to exceed 0% incremental of the design heating load. Oversizing beyond 0% incremental of the design load increases the likelihood of condensate problems. Minimum clearances to combustibles for the furnace that the kit is applied shall be maintained. This kit shall not be used on UnitaryProductsGroup
TABLE : LIST OF APPROVED MODELS APPROVED FURNACE TILE LINED CHIMNEY KIT MODEL NUMBER FURNACE FLUE OUTLET SIZE MODEL NUMBERS P4HUA(N,L)0 (G,L)8T040UHA FL8A040UHA P4HUA(N,L)0480 (G,L)8T060UHA FL8A060UHA P4HUA(N,L)0640 (G,L)8T080UHA FL8A080UHA P4HUB6(N,L)0640 (G,L)8T0806UHB FL8B0806UHA P4HUC(N,L)0640 G8T080UHC P4HUB(N,L)0800 G8T0UHB CK0604 4" P4HUB6(N,L)0800 (G,L)8T06UHB FL8B06UHA P4HUC(N,L)0800 (G,L)8T0UHC FL8C0UHA P4HUC6N09 G8T6UHC FL8CUHA P4HUC(N,L)09 (G,L)8TUHC P4HUD(N,L)40 G8T0UHD PDUA(N,L)0480 (G,L)8D060UHA PDUA(N,L)0640 (G,L)8D080UHA PDUB6(N,L)0640 (G,L)8D0806UHB CK0604 4" PDUB(N,L)0800 G8D0UHB PDUC(N,L)0800 (G,L)8D0UHC PDUC6(N,L)0960 G8D6UHC PDUC(N,L)0960 (G,L)8DUHC PDUAV0640 G8V080UHA PDUB6V0800 G8V06UHB CK0604 4" PDUCV0800 G8V0UHC PDUCV0960 G8VUHC P4DNA(N,L)0 (G,L)8T040DNA P4DNA(N,L)0480 (G,L)8T060DNA P4DNA(N,L)0640 (G,L)8T080DNA P4DNB6(N,L)0640 (G,L)8T0806DNB CK0604 4" P4DNB(N,L)0800 (G,L)8T0DNB P4DNC(N,L)0800 (G,L)8T0DNC P4DNC6(N,L)09 G8T6DNC P4DNC(N,L)09 (G,L)8TDNC P4DND(N,L)40 (G,L)8T0DND PDDAN0480 G8D060DNA PDDAN0640 G8D080DNA CK0604 4" PDDB6N0640 G8D0806DNB PDDBN0800 G8D0DNB PDDCN0960 G8DDNC BGU00A FG8B00MU BGU07A FG8B07MU BGU076A FG8C076MU CK060 " BGU06A FG8C06MU BGU0A FG8D0MU BGUA FG8DMU BGU0A FG8D0UH CK0604 4" G8C00MUB G8C00MDB G8C07MUB G8C07MDB G8C076MUB G8C076MDB CK060 " G8C06MUC G8C06MDC G8C0MUD G8C0MDD G8CMUD G8CMDD G8C0UHD CK0604 4" UnitaryProductsGroup
FIGURE - Chimney Inspection Chart Is the crown missing mortar or brick? Rebuild crown. Is the crown missing mortar or brick? Is liner and top seal in good condition? Repair liner or top seal or reline Reline chimney as necessary. Repair Is there mortar, tile, fuel oil residue or other debris in the cleanout? Is the clay tile misaligned, have missing sections, or gapped? Is the chimney exposed to the outdoors below the roofline? Is the chimney serving one or more draft hooded appliance(s)? Is the chimney properly sized per these instructions? The Chimney is acceptable to use with this kit Line chimney with the properly sized, listed flexable metal liner or Type-B vent per NFGC or National Canadian Code vent sizing tables, and liner or vent manufacturer's intallation instructions. 4 UnitaryProductsGroup
Single Appliance for Interior Chimney Only TABLE : VENT TABLE - INTERIOR CHIMNEYS ONLY Interior Chimneys Only Capacity of Masonry Chimney Flue with Type B Double-Wall Vent Connectors Serving a Single Furnace Equipped with the Tile Lined Chimney Kit. Type B Double Wall Connector Diameter - D (inches) To be used with chimney areas within the size limits at the bottom of table CHIMINEY HEIGHTS H (FT.) 6 8 0 0 LATERAL L (FT.) 8 0 Minimum area of Chimney-A (sq. inches) Maximum area of Chimney-A((sq. inches) " 4" " 6" 7" 8" Appliance Input Rate in Thousands of BTU per Hour 8 4 9 6 4 8 4 8 8 6 49 48 6 7 0 67 6 48 74 68 60 4 8 76 67 86 80 9 88 8 96 87 4 7 97 89 4 6 7 97 8 7 8 7 9 0 7 4 4 7 6 48 9 79 64 4 84 7 9 48 6 98 84 7 9 9 6 8 7 0 99 8 80 6 98 8 7 4 9 0 6 74 4 7 6 0 8 6 4 7 88 04 8 64 47 0 66 47 9 98 77 6 6 96 8 7 0 4 9 4 9 7 88 477 44 44 400 76 9 8 8 0 6 49 88 7 98 69 tes ) Seal any unused openings in the venting system. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z. or CAN/CGA B49 Canadian Installation Codes, and these instructions. Determine that there is not blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. ) The vent tables are designed for two 90 elbows or equivalent. If additional elbows are used, five feet should be subtracted for each elbow from the above values. ) High altitude installation input rates shall be derated starting at 00 ft. altitude. Sea level input rates shall be used for chimney sizing and venting guidelines. 4) Vent connector length is limited to ½ ft. for each inch of vent connector diameter. ) Vent connectors shall not be upsized more than two sizes greater than the listed appliance vent outlet diameter. 6) For multiple appliance installations, the flow area of the chimney shall not exceed 7 times the smallest draft hood outlet area. FIGURE - Table shall be used when a Type B, double walled vent connector is attached to a tile lined masonry chimney serving a single furnace. L TYPE B DOUBLE L GAS VENT USED AS CONNECTOR D H TILE-LINED MASOY CHIMNEY A UnitaryProductsGroup
MULTIPLE APPLIANCE-INTERIOR OR EXTERIOR CHIMNEY TABLE : VENT TABLE - INTERIOR OR EXTERIOR CHIMNEY INTERIOR OR EXTERIOR CHIMNEYS Capacity of Masonry Chimney Flue with Type B Double-Wall Vent Connectors Serving a Furnace Equipped with the Tile Lined Chimney Kit, and One or More Draft Hooded Appliances. Type B Double Wall Connector Diameter - D (inches) To be used with chimney areas within the size limits at the bottom of table CHIMNEY HEIGHT H (ft.) 6 0 0 CONNECTOR RISE R (ft.) Largest " 4" " 6" 7" 8" Appliance Rating Limits in Thousands of BTU per Hour 8 4 9 6 6 40 6 4 4 6 44 64 46 6 6 48 8 66 6 69 66 8 97 7 87 0 74 89 77 9 4 8 9 7 89 4 4 8 9 48 4 4 9 8 7 7 4 6 4 60 80 4 7 84 8 64 9 7 99 86 9 60 0 70 6 47 8 9 60 9 9 70 0 87 7 94 6 7 tes ) Seal any unused openings in the venting system. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z. or CAN/CGA B49 Canadian Installation Codes, and these instructions. Determine that there is not blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition. ) The vent tables are designed for two 90 elbows or equivalent. If additional elbows are used, five feet should be subtracted for each elbow from the above values. ) High altitude installation input rates shall be derated starting at 00 ft. altitude. Sea level input rates shall be used for chimney sizing and venting guidelines. 4) Vent connector length is limited to ½ ft. for each inch of vent connector diameter. ) Vent connectors shall not be upsized more than two sizes greater than the listed appliance vent outlet diameter. 6) For multiple appliance installations, the flow area of the chimney shall not exceed 7 times the smallest draft hood outlet area. TYPE B DOUBLE WALL GAS VENT USED AS CONNECTOR H D A SINGLE WALL OR TYPE-B VENT FIGURE : Table shall be sed with a Type B, double-walled vent connector is attached to a tile lined masonry chimney serving a sinle furnace. D TILE-LINED MASOY CHIMNEY R CONNECTOR RISE "R" R Inside Diameter Inside Diameter minal Liner of Liner or Equivalent Equivalent Area Size (inches) (inches) Diameter (inches) (square inches) 4 x 8 / x 6 / 4. 9.6 6 8. 7 8. 8 x 8 6 /4 x 6 /4 7.4 4.7 8 0. 8 x 6 / x / 9 6.6 78. x 9 /4 x 9 /4.4 8. 9 x 6 9 / x /.8 7. 4.9 6 x 6 /4 x /4 4. 6.9 76.7 6 x x 7 6. 6. 8 4.4 x 6 /4 x 6 /4 8. 60. 4. Table 4: Masonry Chimney Liner Dimensions with Circular Equivalents 6 UnitaryProductsGroup
INSTALLATION OF CHIMNEY KIT ASSEMBLY The Tile Lined Chimney Kit is for use on P4HU, PDU, P4DN, PDD, G8T, L8T, G8D, L8D, FL8, G8V, BGU, G8C- MU, and G8C-MD and FG8 models.. Disconnect power and shut off the gas supply to the furnace.. Turn off gas supply to the furnace at the manual valve.. Remove burner access door. 4. Remove screw from the front of the chimney kit. Set the screw aside.. Attach the chimney kit onto the flue outlet of the furnace. 6. Secure the chimney kit to the furnace with the screw that was set aside. 7. Install the black bushing that is provided in the parts bag of the kit into one of the 7/8 diameter holes located on the side of the furnace. 9. Removetheredinsulatedwirefromtheprimarylimit switch and connect it to the chimney kit wire harness lead.. Connect the second lead from the chimney kit wire harness to the primary limit terminal. (See Figure below) The wire harness to the kit shall not be routed into the junction box. 8. Route the wire harness from the chimney kit into the burner compartment of the furnace through the bushing. For counterflow furnaces, route the wire through the D-grommet and then into the burner compartment. FIGURE. Secure the wire harness from the chimney kit to the cabinet with the wire clips provided.. All excess wire should be fastened inside the furnace with the cable tie wrap provided in the parts bag. The wire harness should be routed above the burner box to avoid the possibility of any damage to the wire. (See Figure 4 below). The wire should be secured away from the burner compartment, or from any live metal or rotating part. Attach the proper size of vent pipe and fasten the pipe to the chimney kit securely. (See Tables and for proper size) FIGURE 4 7 UnitaryProductsGroup
INSTRUCTIONS TO PLACE THE FURNACE INTO OPERATION ) Verify that all the electrical connections that were made while installing the chimney kit are secure. ) Inspect the vent system for any leakage, corrosion, or restrictions. ) As practical, close all doors and windows including doors that are in the same room as the furnace. Turn on all exhaust fans (range hoods, bathroom fans) not including summer exhaust fans. Fireplace dampers should be closed. 4) Turn on the power to the furnace and open manual gas valve. ) Adjust the thermostat to allow the furnace to operate for at least minutes. 6) Once the furnace has operated, check for vent gas spillage at the draft openings with the open flame of a match or candle. 7) If the furnace is installed where it is common vented to another draft hooded appliance(s) (i.e.water heater), follow operating instructions and adjust for continuous operation. 8) Check for spillage at the draft hood of the other appliance(s) and again at the chimney kit. 9) If there is any flue gas spillage from any of the draft hoods, the vent system and the connections must be corrected. ) Once proper installation and operation are verified, turn off all the appliances, return fans and vent dampers to their original position. ) The installation instruction for the chimney kit should be located near or around the furnace for future reference. PARTS LIST Item Part. Qty. Chimney Kit CK060, CK0604 Limit Switch 0-779-00 Bushing 0-68-000 Wire Clip n/a Cable Strap 0-69-000 Wire Harness 0-96-000 Instruction Manual 0-74-000 Subject to change without notice. Printed in U.S.A. Copyright by Unitary Products Group 00. All rights reserved. Supersedes: thing Unitary 00 rman Product York OK Group Drive 7069