TCB-DP22CUL. Drain Pump Kit. Model name : AIR CONDITIONER (SPLIT TYPE) Installation Manual. Installation Manual 2 Air Conditioner (Split type) English

Similar documents
Installation Manual PMV Kit RBM-PMV0363E RBM-PMV0903E

Installation Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SP180CT-UL RAV-SP240CT-UL RAV-SP300CT-UL RAV-SP360CT-UL RAV-SP420CT-UL.

Installation manual. Branch kit 1:3 RBC-TRP100E AIR CONDITIONER (SPLIT TYPE) Model name: Installation manual. Air conditioner (Split type) 1 English

AIR CONDITIONER (MULTI TYPE) Installation Manual. Indoor Unit. Model name:

SUPER MODULAR MULTI SYSTEM AIR CONDITIONER

Installation Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SM404SDT-E RAV-SM454SDT-E RAV-SM564SDT-E. Model name: Slim Duct Type.

Installation Manual MMU-AP0154SH-E MMU-AP0184SH-E MMU-AP0244SH-E AIR CONDITIONER (MULTI TYPE) Indoor Unit. Model name: 1-Way Cassette Type.

AIR CONDITIONER (SPLIT TYPE) Installation Manual. Indoor Unit. Installation Manual 1 English. Kurulum kılavuzu 26 Türkçe.

MMC-AP0181H2UL MMC-AP0241H2UL MMC-AP0361H2UL MMC-AP0421H2UL

Installation Manual AIR CONDITIONER (SPLIT TYPE) Indoor Unit RAV-SM1403DT-A RAV-SM1603DT-A. Model name: Concealed Duct High Static Pressure Type

RAV-SP181BT-UL RAV-SP241BT-UL RAV-SP301BT-UL RAV-SP361BT-UL RAV-SP421BT-UL

RAV-SM567CTP-E RAV-SM807CTP-E RAV-SM1107CTP-E RAV-SM1407CTP-E RAV-SM1607CTP-E

INSTALLATION MANUAL SPLIT TYPE ROOM AIR CONDITIONER (PART NO )

[FLARE CONNECTION TYPE] ATTENTION

RAV-SM406BT-E RAV-SM456BT-E RAV-SM566BT-E RAV-SM806BT-E RAV-SM1106BT-E RAV-SM1406BT-E RAV-SM1606BT-E

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

Air Conditioner. user installation & manual manual. imagine the possibilities

38VYX110/38VYX130 I S O INSTALLATION MANUAL

INSTALLATION MANUAL Duct Type Series MH FECA

1. BEFORE INSTALLATION

INSTALLATION MANUAL MODELS DAIKIN ROOM AIR CONDITIONER. R410A Split Series. Installation manual Manuel d installation Manual de instalación

CONTENTS INSTALLATION MANUAL HFC FOR INSTALLER R410A. utilized 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY... 2

RAV-SM2244DTP-E RAV-SM2804DTP-E

MODELS DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL FTXN50KV1B FTXN60KV1B. R410A Split Series

Split-type Air-Conditioner

INVERTER SPLIT - TYPE

FLOOR TYPE AIR CONDITIONERS

Split-type Air-Conditioner INSTALLATION MANUAL CONTENTS FOR INSTALLER MXZ-3B54VA MXZ-4B71VA. English

MULTI HEAT PUMP PANEL CONSOLE TYPE DUCTLESS INVERTER INDOOR UNIT INSTALLATION MANUAL. Models: CH09MCU230VI CH12MCU230VI CH18MCU230VI

INSTALLATION MANUAL. R-410A Split Series. Models. Installation manual R-410A Split series. Installationsanleitung Split-Baureihe R-410A

RAV-SM2246AT8-E RAV-SM2246AT8J-E RAV-SM2806AT8-E RAV-SM2806AT8J-E

Installation manual for room air conditioner

AIR CONDITIONER (SPLIT TYPE) Installation manual. Outdoor Unit. English. Model name: For commercial use

Split-type Air-Conditioner

INSTALLATION MANUAL R410A Split Series

R32 INSTALLATION MANUAL ENGLISH AIR CONDITIONER (SPLIT TYPE) Indoor unit RAS-10PKVPG-E RAS-13PKVPG-E RAS-16PKVPG-E

AIR CONDITIONER CASSETTE

AIR CONDITIONER SPLIT WALL MOUNTED

Installation Manual. Indoor Unit MMK-AP0073H2UL MMK-AP0093H2UL MMK-AP0123H2UL MMK-AP0153H2UL MMK-AP0183H2UL MMK-AP0243H2UL

INSTALLATION MANUAL. R410A Split Series. Models ATX20J2V1B ATX25J2V1B ATX35J2V1B. Installation manual R410A Split series

Split-type Air-Conditioner

SPLIT WALL-MOUNTED AIR CONDITIONER

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO

R32. Installation Manual Split Type Wall Mounted Air Conditioner. This appliance shall be installed in accordance with: REFRIGERANT

MXZ-4B80VA MXZ-5B100VA INSTALLATION MANUAL

MULTI TYPE ROOM AIR CONDITIONERS INSTALLATION INSTRUCTIONS

MODELS DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL FTXS20K2V1B FTXS25K2V1B CTXS15K2V1B CTXS35K2V1B. R410A Split Series

DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump

AIR TO WATER HEAT PUMP. Installation Manual. Outdoor Unit. Model name: HWS-P804HR-E HWS-P1104HR-E. English

MODELS DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL FTXL20G2V1B FTXL25G2V1B FTXL35G2V1B

INSTALLATION INSTRUCTIONS

42PHW / 42PHQ 42PHQ...K

INSTALLATION MANUAL. R410A Split Series. Model RXS24LVJU. Installation manual R410A Split series. Manual de instalación Serie Split R410A.

INSTALLATION MANUAL. R22 Split Series. Models FTY25GXV1 FTY35GXV1. Installation manual R22 Split series

RAV-SM566KRT-E RAV-SM806KRT-E

Installation manual AIR CONDITIONER (SPLIT TYPE) Outdoor Unit RAV-SP300AT2-UL RAV-SP360AT2-UL RAV-SP420AT2-UL. For OUTDOOR USE only.

HFC 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY 2. SELECTING THE INSTALLATION LOCATION R410A INSTALLATION MANUAL

MMY-MAP0804T8P-E MMY-MAP1004T8P-E MMY-MAP1204T8P-E MMY-MAP1404T8P-E MMY-MAP1604T8P-E

INSTALLATION MANUAL AIR CONDITIONER

1. ACCESSORIES SUPPLIED WITH THE AIR CONDITIONER 2. LOCATION OF INDOOR AND OUTDOOR UNIT 3. INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 4.

AIR CONDITIONER (SPLIT TYPE) Installation manual. Outdoor Unit

DAIKIN AIR CONDITIONER

ROOM AIR CONDITIONER INSTALLATION MANUAL

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

Ductless Split Air Conditioner

INSTALLATION MANUAL. R410A Split Series. Models RXS15LVJU RXS18LVJU. Installation manual R410A Split series. Manuel dinstallation Série split R410A

Installation Manual. Indoor Unit

AIR CONDITIONER CASSETTE

INSTALLATION INSTRUCTION

DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL

Air Conditioner Accessory DRAIN WATER LIFT-UP KIT Installation Manual

1. BEFORE INSTALLATION

OWNER S AND INSTALLATION MANUAL RAV-480FS2B/RAV-480AS2B RAV-600FS8B/RAV-600AS8B

1. BEFORE INSTALLATION

INSTALLATION MANUAL. R410A Split Series

AIR CONDITIONER CONSOLE

MODELS DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL. R410A Split Series

INSTALLATION MANUAL. R410A Split Series. Models. Installation manual R410A Split series. Installationsanleitung Split-Baureihe R410A

INSTALLATION MANUAL. Decoration Panel Provided with Filter Auto Cleaning Function Self Cleaning decoration panel BYCQ140D7GW1 BYCQ140D7GFW1

SPLIT TYPE ROOM AIR CONDITIONER INSTALLATION MANUAL (PART NO )

HFC 1. THE FOLLOWING SHOULD ALWAYS BE OBSERVED FOR SAFETY 2. SELECTING THE INSTALLATION LOCATION

Split Air Conditioner

AIR CONDITIONER (SPLIT TYPE) Installation manual. Outdoor Unit RAV-SM1603AT-E1 RAV-SM1603ATJ-E1. Model name: English. For commercial use

KFTC Series 18,000 to 48,000 Btu/h Cooling Only & Heat Pump INSTALLATION MANUAL

1. BEFORE INSTALLATION

Installation Instructions

INSTALLATION MANUAL. R410A Split Series

Safety Precautions (1)

DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL

RAV-SM1104AT8P-E RAV-SM1104AT8JP-E RAV-SM1404AT8P-E RAV-SM1404AT8JP-E

52 CEILING FAN READ AND SAVE THESE INSTRUCTIONS FAN RATING AC 120V.

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL. Decoration Panel BYCP125K-W1 MODELS

INSTALLATION MANUAL. Decoration panel BYFQ60C3W1W BYFQ60C3W1S MODELS

CENTRAL AIR CONDITIONER SPLIT SYSTEM

GUF-100RDH3. Model name The picture is shown GUF-50RDH3. Notice: The term of validity is for a year from the issued date.

G-10s. Instruction Manual. G-Series Cooler UPRIGHT COOLER. Part No.11IPA

AIR CONDITIONER FLOOR CEILING

Transcription:

AIR CONDITIONER (SPLIT TYPE) Model name : TCB-DP22CUL 2 Air Conditioner (Split type) English Manuel D installation Climatiseur (Type split) 12 Français

Please read this carefully before installing the Air Conditioner. This Manual describes the installation method of the DRAIN PUMP KIT. For installation of the outdoor unit, follow the attached to the outdoor unit. WARNING For this, please use the Elbow Piping Kit (MODEL: TCB-KP12CUL, TCB-KP22CUL) sold separately. If using a piping kit procured locally, it may cause a water leak or so on. ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer. CONTENTS Accessory parts and Parts to be procured locally...3 1 PRECAUTIONS FOR SAFETY...4 2 PREPARATION FOR INSTALLATION OF DRAIN PUMP KIT...5 3 INSTALLATION PROCEDURE OF DRAIN PUMP KIT...6 4 DRAIN PIPING WORK...10 5 THERMAL INSULATOR FOR CEILING PLATE...10 6 CABLE CONNECTION...11 7 TEST RUN...11 English-1 2

Accessory parts and Parts to be procured locally r Accessory parts Part name Q ty Shape Usage 1 fixture 1 For mounting Drain hose 1 For connecting vinyl chloride pipe of Dain Pump kit Thermal insulating pipe 1 For thermal insulation of drain hose 1 This manual Be sure to hand to users. Drain hose fixing band 2 For fixing drain hose Thermal insulator for drain connecting section 2 For thermal insulation of drain hose connecting section Thermal insulator of ceiling panel 1 For sealing upper piping hole of indoor unit Screw 4 For fixing For fixing fixture of Banding band 2 For fixing wires r Specification model name TCB-DP22CUL Height of drain up 23.6 (600mm) or lower from top face of the set En 3 English-2

1 PRECAUTIONS FOR SAFETY Ensure that all Local, National and International regulations are satisfied. Read this PRECAUTIONS FOR SAFETY carefully before Installation. The precautions described below include the important items regarding safety. Observe them without fail. After the installation work, perform a trial operation to check for any problem. Follow the Owner s Manual to explain how to use and maintain the unit to the customer. Turn off the main power supply switch (or breaker) before the unit maintenance. Ask the customer to keep the together with the Owner s Manual. WARNINGS Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner. Inappropriate installation may result in water leakage, electric shock or fire. Turn off the main power supply switch or breaker before attempting any electrical work. Make sure all power switches are off. Failure to do so may cause electric shock. Connect the connecting cable correctly. If the connecting cable is connected in a wrong way, electric parts may be damaged. When moving the air conditioner for the installation into another place, be very careful not to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle. If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnormally high and it resultingly causes pipe burst and injuries on persons. Do not modify this unit by removing any of the safety guards or by by-passing any of the safety interlock switches. Exposure of unit to water or other moisture before installation may cause a short-circuit of electrical parts. Do not store it in a wet basement or expose to rain or water. After unpacking the unit, examine it carefully if there are possible damage. To avoid personal injury (with sharp edges), be careful when handling parts. Perform installation work properly according to the. Inappropriate installation may result in water leakage, electric shock or fire. Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. An insufficient power supply capacity or inappropriate installation may cause fire. English-3 4

2 PREPARATION FOR INSTALLATION OF DRAIN PUMP KIT n Cautions on installation In the installation work of the, the pipe cannot be drawn out from other side than the upper side. Apply thermal insulation for all the drain pipes. Open two opening holes (Ø3.9 (100mm), 2 positions) on the ceiling surface to be installed in order to pass refrigerant pipe and drain pipe. Set a 17.7 (450mm-square) check port on the ceiling surface to be installed. Hole for remote controller wires (Ø1.6 (40) knockout) 8.5 (216) 1.5 (39) 2 (52) 4.3 (110) 3 (76) 2.1 (53) Conduit hole (Hole for power supply cable, knockout) 2 (50) 5.1 (130) Knockout hole for upper piping of indoor unit 2.8 (70) 12.6 (320) 6.7 (170) Opening hole on ceiling (Ø3.9 (100), 2 positions) 5.2 (130) 4.7 (120) 3.9 (100) 6.3 (160) 12.6 (320) 6.7 (170) 17.7 (450) Check port 17.7 (450) 1.1 (27.5) 1.1 (27.5) 7.9 (200) Knockout positions at the upper part of indoor unit (Unit: in (mm)) Opening hole positions on ceiling (Unit: in (mm)) Flexible hose of drain pipe (Attached to ) Drain pipe 4.3 (109) 1.1 (27.5) 12.7 (323) Refrigerant pipe (Elbow piping kit) 6.3 (160) 3.5 (90) 6.1 (155) Refrigerant pipe at liquid side (Elbow piping kit) Refrigerant pipe at gas side (Elbow piping kit) 2.2 (55) 3.8 (97) Refrigerant pipe and drain pipe positions (Unit: in (mm)) 5 English-4

3 INSTALLATION PROCEDURE OF DRAIN PUMP KIT n Before installation 1. Removal of suction grille Slide the suction grille fixing knobs (2 positions) toward the arrow direction, and then open the suction grille. Under the condition of suction grille opened, push the hook section of hinges (2 positions) at the rear side, and then pull out the suction grille. NOTE After installation of the, be sure to mount the wire guard as original. Do maintenance work after removing the screws which are fixing the wire guard and hanging up the wire guard with the clamps. Hinge Pull out suction grille while pushing hook. 3. Removal of side panel After removing the side panel fixing screws (1 each at right and left), slide the side panel forward and then remove it. Removing the side panel fixing screws Slide Suction grille fixing knob Suction grille 2. Wire guard open Remove the screws (2 pcs.) which are fixing the wire guard. Using clamps mounted to the wire guard, hang up the wire guard. Do not remove the fixing screws of clamps of the indoor unit. Side forward Clamps Screws English-5 6

n Knockout hole Open the draw-out port (Knockout hole) at upper side. u Tightening connection CAUTION Do not apply excessive torque. Otherwise, the nut may crack depending on the conditions. Draw-out port at upper side (Knockout hole) Outer diam. of copper pipe 1/4 ( 6.4 mm) (diam.) 3/8 ( 9.5 mm) (diam.) 1/2 (12.7 mm) (diam.) 5/8 (15.9 mm) (diam.) Unit : ft lbs (N m) Tightening torque 10.3 to 13.3 (14 to 18) 24.3 to 31.0 (33 to 42) 36.9 to 45.7 (50 to 62) 50.2 to 60.5 (68 to 82) n Connection of ELBOW PIPING KIT Connect ELBOW PIPING KIT sold separately to the indoor unit. Elbow type pipe at gas side Elbow type pipe at liquid side Draw-out port at upper side Tightening torque of flare pipe connections Pressure of R410A is higher than that of R22. (Approx. 1.6 times) Therefore, using a torque wrench, tighten the flare pipe connecting sections which connect the indoor and outdoor units of the specified tightening torque. Incorrect connections may cause not only a gas leak, but also a trouble of the refrigeration cycle. Flare at indoor unit side Flare at outdoor unit side Align the centers of the connecting pipes and tighten the flare nut as far as possible with your fingers. Then tighten the nut with a spanner and torque wrench as shown in the figure. Externally threaded side Half union Use a wrench to secure. Flare nut Internally threaded side Use a torque wrench to tighten. 7 English-6

n Thermal insulating process Apply thermal insulation to pipes at liquid and gas sides separately. Be sure to use thermal insulator with heat resisting temperature 248 F (120 C) or more for pipes at gas side. Using thermal insulators attached to the indoor unit and Elbow Piping Kit, apply thermal insulating process surely to pipe connecting section without clearance. When fixing insulator to the elbow type pipe temporarily with the banding band attached to the Elbow Piping Kit, wrap the insulator using vinyl tape so that there is no clearance. n How to install 1. Mount the fixture to the rear side inside of the indoor unit. (1 screw) Screwing of fixture fixture CAUTION Apply thermal insulating process surely so that no exposure cannot be found up to the end of the pipe connecting section of the indoor unit. (If a part of the pipe is exposed, leakage may be caused.) 2. Hang the temporary hanging hook of the Drain Pump Kit to the side slit of the indoor unit from inner side. Screw the to the indoor unit. (3 screws: Ceiling surface, side face, and fixture) Fix with vinyl tape. Set the notch upward. Temporary hanging hook of to the side slit of indoor unit Screwing (To side face) Elbow Piping Kit side Banding band Attached thermal insulating pipe For the connection of refrigerant pipe and thermal insulating process after hanging down the indoor unit, refer to the attached to the indoor unit. Screwing (To fixture) Screwing (To ceiling surface) English-7 8

n Connection of drain hose at indoor unit side 1. Insert the drain hose attached to the indoor unit into the drain pipe connecting port of the indoor unit s and into the drain pipe connecting port of the s drain pan. In this time, insert the drain hose until it strikes on the connecting port of the drain pipe. 2. Align the hose band attached to the indoor unit with the end of pipe connecting port, and then tighten it firmly. 3. Cut off to 6.3 7.9 (160mm 200mm) the thermal insulator 7.9 7.9 (200mm 200mm) for drain hose attached to the indoor unit. Using it, lap the connecting section of drain pan and drain hose without clearance, and then tighten it with two banding bands attached to the indoor unit so that thermal insulator does not open. n Connection of drain hose at side 1. Insert the drain hose attached to the Drain Pump Kit into the connecting port of drain pipes at the upper side of the. 2. Align the hose band attached to the Drain Pump Kit with the end of pipe connecting port, and then tighten it firmly. 3. Fit the drain connecting thermal insulator attached to the to sheet metal at the upper side of the, and then lap it covering the drain hose without clearance. Drain hose (Attached to ) Thermal insulator for drain connecting section (Attached to ) Drain pipe connecting port Attached drain hose Fit the drain connecting thermal insulator to sheet metal at the upper side of the, and then lap it without clearance. Indoor unit drain pan Check the soft hose is pushed in to the end of drain pan. drain pan Align the attached hose bands with the end of hose and then tighten it while turning the knob to the side. Lap insulator over the connecting section of drain pan and drain hose. Drain hose 23.6 (600mm) or less from the top face of indoor unit Hard vinyl chloride pipe VP-25 (Procured locally) 12.7 (323mm) Thermal insulating pipe (Attached to ) Thermal insulator for drain connecting section (Attached to ) Hose band (Attached to ) Drain hose (Attached to ) Fit the thermal insulating pipe to sheet metal at the upper side of the, and then lap it without clearance. Banding band Hose band Thermal insulator attached to indoor unit (Cut to 6.3 7.9 (160mm 200mm)) Lap the one side of the attached thermal insulator on the other side at the upper side. When using the drain hose within 5.9 (150mm) or less from the top face of the indoor unit, do not use an elbow but connect the attached drain hose directly, which was bent (with larger round as possible as you can). 9 English-8

4 DRAIN PIPING WORK CAUTION Following the, perform the drain piping work so that water is properly drained, and apply a heat insulation so as not to cause a dew. Inappropriate piping work may result in water leakage in the room and wet of furniture. REQUIREMENT n Piping/Heat insulating material Require the following materials for piping and heat insulating at site. Piping Heat insulator Hard vinyl chloride pipe VP25 (Outer dia. : Ø1.3 (Ø32mm)) Foam polyethylene : Thickness 0.4 (10mm) or more Be sure to perform heat insulation of the drain pipes of the indoor unit. Never forget to perform heat insulation of the connecting part with the indoor unit. An incomplete heat insulation causes dewing. Set the drain pipe with downward slope (1/100 or more), and do not make swelling or trap on the piping. It may cause an abnormal sound. For length of the traversing drain pipe, restrict to 65 7 (20m) or less. In case of a long pipe, provide support brackets with interval of 4 11 to 6 7 (1.5m 2m) in As long as possible 3.9 (100mm) order to prevent waving. VP25 VP25 Heat insulator VP25 4 11 to 6 7 (1.5m 2m) Support bracket 1/100 or more downward Arched shape Trap NO GOOD VP30 or more Set the collective piping as shown in the right figure. Be sure not to apply force to the connecting part of the drain pipe. Downward slope 1/100 or more Extended ventilating pipe The hard vinyl-chloride pipe cannot be directly connected to the drain pipe connecting port of the indoor unit. For connection with the drain pipe connecting port, be sure to use/fix the attached flexible hose with the hose band, otherwise a damage or water leak is caused on the drain pipe connecting port. Adhesive inhibited : Use the attached flexible hose and hose band for connecting the drain hose to the drain piping connecting part. If applying the adhesive, socket will be damaged and cause water leakage. 5 THERMAL INSULATOR FOR CEILING PLATE Adhere the ceiling thermal insulator attached to the to positions of the refrigerant pipe and the drain pipe. n Connection of drain pipe Connect hard vinyl chloride pipe (procured locally) to the attached drain hose which has been installed. Drain pipe thermal insulator pipe Refrigerant pipe Ceiling thermal insulator (Attached to ) English-9 10

6 CABLE CONNECTION 1. Loosen the mounting screws (2 positions) of the cover of the electric parts box, and then remove the cover. 2. In the, connect the connector (Blue 3P) for drain pump to P.C. board CN68 (Blue 3P) of the indoor unit, and the connector (Red 3P) for float switch to P.C. board CN34 (Red 3P) of the indoor unit respectively. In this time, remove 3P connector (Red 3P) for short-circuit of CN34 (Red 3P). 3. Using one of two banding bands attached to the electric parts box, fix the wires. Use the other banding band to bind the wires so that they are not caught in the cover of electric parts box. Pass connecting cable through the slot at this side of the electric parts box. (Fix the wires with banding band.) Electric parts box 2 screws CN68 (Blue 3P) P.C. board CN34 (Red 3P) (Connect white removing 3P connector for short-circuit.) 7 TEST RUN n Check the draining In the test run, check that water drain is properly performed and water does not leak from the connecting part of the pipes. Be sure to check draining also when installed in heating period. Using a pitcher or hose, pour water 0.3 galoon (1200cc) into the discharge port before installation of the ceiling panel. Pour water gradually so that water does not spread on the motor of the drain pump. After the electric work has finished, pour water during COOL mode operation. Single phase 208/230V If the electric work has not yet finished, pull out the float switch connector (CN34: Red) from the electric parts box, and check draining by plugging the single phase 208/ 230V power to the terminal blocks and. If doing so, the drain pump motor operates. Test water drain while checking the operation sound of the drain pump motor. (If the operation sound changes from continuous sound to intermittent sound, water is normally drained.) After the check, the drain pump motor runs, connecting the float switch connector. (In case of check by pulling out the float switch connector, be sure to return the connector to the original position.) CN34 (RED) Black Black 1 2 Red White Pull out connector CN34 (Red) from P.C. board. Pump for oil-heater Bucket 11 English-10

EH99866301