CONTROL AND INDICATOR MODULE. Potok-BKI INSTRUCTION MANUAL

Similar documents
Orion ISS. Intrusion and Fire Alarm Panel. Signal-10. User s Manual

S2000-ASPT. Fire Alarm and Extinguishing Control Panel. Engineer s and User s Manual

S INTRUSION&FIRE ALARM AND ACCESS CONTROL PANEL

UO-4S Revision 02 GSM Four-Input Alarm Panel

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

PERMACONN PM1030 Includes DI300. Installation Manual

CSP-204 CSP-208 CSP-104 CSP-108

FIRE AND ALARM CONSOLE S2000M

Installation, Operating and Maintenance Manual

Fire Control Panel FS5100

Version 1.03 January-2002 USER S MANUAL

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

E DATA SHEET

Fire Control Panel FS4000

M2500 Engine Controller Installation Manual

Control/Communicator Installation Manual

All-In-One Wireless Security System V3.2 Programming Guide. Model # MG6130 / MG6160

Security System. User Guide for the LED Command Center

External Wireless Sounder

Operator's Handbook. Release 3. Fire Alarm Control Panel, BS-310 / 320 / Operator Panel BS-330. System Program Version 3.8.0

User manual. KNXgal. version

2000 Series. Program Entry Guide. Control Panels

Operator's Handbook. Interactive Fire Alarm System Release 3. Information Panel, BV-320. Protecting life, environment and property...

Protégé EliteSuite Eclipse LED Keypad Installation Manual ELT-KLES

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

The EN54 Part 2 & 4 Fire System

2000 SERIES DIAGNOSTIC ALARM CONTROL SYSTEM

CONVENTIONAL FIRE ALARM CONTROL PANEL Model: ARTON-08F

BENTEL SECURITY reserves the right to modify the technical features of this product without prior notice.

The EN54 Part 2, 4 and 13 Fire System

Installation and user manual for the FX range of fire panels. 1, 2, 4 and 8 zone panels

Contents. Glossary

Fire Command Keypad. XR5 User s Guide

VAP304 PRO INSTALLATION & OPERATION MANUAL

Summary of Keypad Main User Commands

Series. NX-4-EUR Control Panel. Installation manual

Section 9 System Operation

OPERATING GUIDE FOR YOUR RP1054D KEYPAD

Conventional Releasing Control Panel

Installation and user manual for the CF5000, MF5000 and FXP5000 range of fire panels

Operation Manual For model CM706E

Security System With Scheduling. User Guide. N5943-8V4 7/04 Rev A

Alarm Control Panel WIC-16Z4P WIC-5Z2P. User Instructions

User s Guide. SUB-MA7240O-0001.OG.Solution doc. Created: 6/05/03. Last Updated: 23/09/03. MA7240AO-0001 Version 1.0

Destiny Destiny Owners Manual

BENTEL SECURITY srl reserves the right to modify the technical specifications of this product without prior notice.

NX-148 LCD CODE PAD TABLE OF CONTENTS

EXTINGUISHING AGENT RELEASE MODULE

Control/Communicator

NetworX Series. NX-8 Commercial Fire Panel Installation and Startup

Conventional Fire Alarm System 2014 V1.2

Table of Contents. Appendix A Special Characters 31

Premier Hazard STC Instructions

Zerio Plus EDA-D6000 Radio Combined Heat Detector and Sounder Installation Instructions

SECURITY SYSTEM 4110DL. Programming Form Programming Form Programming Form 4110DL-PRV3 10/96

The most user friendly Security Alarm System L S Section 1 Overview of System Section 2 Planning your Installation

Honeywell Control Panels FOR RESIDENTIAL AND COMMERCIAL INSTALLATIONS. Feature Charts

Ethernet General Purpose

Revision November 2013 JVA Technologies. Ethernet General Purpose IO Technical Manual

ABORT Light flashes during an abort delay time; is on during or after an alarm report to the central station. EMERGENCY ACTIVATION KEYS

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

Smoke Detector and Siren. Manual

NetworX NX-8V2. LED Keypad User Manual

OVEN INDUSTRIES, INC.

OPERATOR S MANUAL MR-2100/2200. Fire Alarm Control Unit. Revision 0 Document #: LT-2002

BURGLAR ALARM PANEL BS-468

Zerio Plus EDA-R6000 Radio Combined Optical Smoke Detector and Sounder Installation Instructions

IRIS Touch Firmware Enhancements and Additions from Version to Version

Interactive Fire Control Panel IFS7002 four signal loops Instruction Manual

VANDAL RESISTANT BACK-LIT WEATHERPROOF RFID ACCESS CONTROL KEYPAD

KFP-AF Series Fire Alarm Control Panel Installation Manual

AXI LED USER MANUAL (REV. 1.0)

Program version Alarm Control Panel USER MANUAL GDAŃSK. versa_u_en 03/09

ECO N DATE DESCRIPTION OF CHANGE CHG

Section 8 System Operation

Installation Manual Premier 412/816/832. Issue 10

Program version Alarm Control Panels PROGRAMMING GDAŃSK. versa_p_en 03/09

TABLE OF CONTENTS TABLE OF CONTENTS 1

ELT-KLED EliteSuite LED Keypad Installation Manual

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

RANGER 8600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

CC880/LP880, SC8016. Operators Guide Solution-16, Solution-16 Safecom

Laptop / PC Programming Manual

English. Italiano. Português. Françias. Español

Sigma. K1000 Series 1, 2, 4 & 6 Zone Fire Control Panels. Operation and Maintenance Manual. Man-1048 Issue 05 October 2009

RANGER 7600 DOWNLOADABLE CONTROL COMMUNICATOR INSTALLATION MANUAL

Ref.1067/032 Ref.1067/042

IDS S E C U R I T Y IDS816. User Manual MANUAL NO B ISSUED DEC 2004 VERSION 2.00

LS800S Intruder Alarm System. Engineering Manual

ADE Gen4. Speech Dialler Engineering Information. Description. Features

REPEATER FS5200R INSTRUCTION MANUAL

FW-SIREN2EXT -8/9F FW-SIREN2CP -8/9F

EasyLoader AV-2005 & AV-2008

Michigan State University Construction Standards FIRE DETECTION AND ALARM PAGE

Fire Control Panel FS4000

SC-F3G User Manual 1.0

QUICK USER GUIDE. Alarm Control Panel

SYSTEM MANUAL FT1-SB. Single Zone Fire Alarm System

Transcription:

CONTROL AND INDICATOR MODULE Potok-BKI INSTRUCTION MANUAL 1. TECHNICAL DATA 1.1 General 1.1.1 The control and indicator module Potok-BKI of version 1.00 (hereinafter referred to as the module) is designed to operate as part of a water or foam fire-fighting system in an Orion ISS in cooperation with a Potok-3N panel of version 1.04 or higher under control of the network controller (S2000M console of version 2.03 or higher or Orion Pro Software 1.12). 1.1.2 The module provides light and sound indication of states of partitions of a pump station and remote control for a Potok-3N panel (switching automatic mode on and off, start of discharge / cancel of extinguishing). 1.1.3 The view of the module is shown in Figure 1. 1.1.4 The module is to be mounted inside the protected premises and is destined for round the clock operation. 1.1.5 The module must not be used in aggressive medium or dust condition, or in explosionhazardous premises. 1.2 Specifications Light Indication Logic groups of indicators: «Unit 1» to «Unit 4»: «Pump Station»: Indicators of extra partitions «1» to «12»: 24 LEDs grouped as four columns to indicate states of four fire-fighter units; 14 LEDs to indicate states of a Potok-3N panel and the Potok-BKI module; 12 LEDs indicating states of the Potok-3N zones not related to the indicators of the groups said above and states of the fire partitions Partitions - 17 Power Voltage - 10.2 V dc to 28.4 V dc. Bolid manufactured RIP-12 or RIP-24 power supplies are recommended to be used Consumed Power - 3 W max Consumed Current alarm mode quiescent mode (all LEDs are off) - 200 ma max at 12 V dc - 100 ma max at 24 V dc - 50 ma max at 12 V dc - 50 ma max at 24 V dc Tamper Switch - Yes Built-in Sounder - Yes RS-485 Communication Port (to work as part of an Orion ISS) - Yes Pre-Operation Time - 2 s max Programming - By means of UProg (ver. 4.1.0.38 and higher) Reader Input - 1 for a reader with Touch Memory output interface Weight - 0.6 kg max Overall Dimensions - 170 mm 340 mm 25.5 mm 1.3 Parts List 1) Potok-BKI Control and Indicator Module 1 2) This Instruction Manual 1 3) Woodscrew 4 4) Wall Plug 4 5) Package 1 1

Front View: Rear View: Two holes to pass the cables Two holes to attach the module on the wall Figure 1. View and Overall and Mounting Dimensions of the Potok-BKI Module 2

2. MOUNTING AND WIRING 2.1 Mounting the Module 2.1.1 Mount the module in accordance with your applicable local standards, codes, regulations, and ordinances. Mount the module at that height above the floor which is suitable to operate and maintain it. 2.1.2 The module is to be mounted on walls or other constructions of premises at places protected against atmospheric fallouts and mechanical damage. 2.1.3 Prior to attaching the module, please ensure that the wall the module is to be mounted to is solid, flat, clean, and dry. 2.1.4 Mark four mounting points on the wall in accordance with Figure 1. 2.1.5 Drill the mounting holes. Then insert wall plugs into the holes and screw two woodscrews provided in the two upper holes so that the distance between a woodscrew head and the wall is about 7 mm. Figure 2. 2.1.6 Remove the front cover of the module by bending it relative to point How to Open the «0» in accordance with Figure 2. Place your thumbs over the clips as close to Front Cover the point «0» as you can. 2.1.7 Hang the module on two woodscrews. Screw the remaining woodscrews into the lower mounting holes and fix the module on the wall. 2.2 Wiring the Module 2.2.1 Connect wires to the module s terminals as shown in Figure 3. 2.2.2 Please observe polarity while connecting the module to the power supply. 2.2.3 Use wires with the cross section of no more than 1.5 sq. mm. 2.2.4 If the module, or the console, or other Orion system devices connected to the RS-485 interface bus are supplied with power by different power supplies, couple their 0V circuits. 2.2.5 Unless the module is the last or the first device in the RS-485 interface bus, remove the EOL jumper from the module s PCB (see Figure 3). 2.2.6 Connect the module to an ibutton reader as shown in Figure 3. 2.2.7 Close the front cover of the module in the order which is opposite to that one in which the cover was open (see Figure 2). Figure 3. Module s Connection Diagram 3. INSPECTING THE MODULE 3.1 To make sure your Potok-BKI module keeps proper operability, it must be inspected by a competent specialist at least on receipt and annually. 3

3.2 Inspect the module at following ambient conditions: The relative humidity 45% through 80%; The ambient temperature 15 C through 35 C; The atmospheric pressure 630 mm Hg through 800 mm Hg. 3.3 While inspecting the module, always shut off the module s power before connecting and disconnecting its external circuits. 3.4 Full inspection of the module implies inspecting the module s operability and testing module s indication in self-diagnostic mode. 3.2.1 Preparing for inspection: а) Check the packing and unpack the module; б) Inspect the parts list in accordance with Clause 1.3; в) Ensure the module case is undamaged; г) Shake the module to ensure there are no debris inside the module s case; д) Ensure the terminals are tightened properly. 3.5 Inspecting Operability of the Module 3.5.1 To inspect the module, use an S2000M console. Connect the module s RS-485 circuits and power circuits to the relevant terminals of the console (see the S2000M manual for detailed instructions). 3.5.2 Connect a milliammeter in series with the power circuit of the module. 3.5.3 Apply power to the module and the console. 3.5.4 READY LED of the Potok-BKI shall show green solid light within 2 s. 3.5.5 Measure the current consumed by the module. Its value shall not exceed 200 ma. 3.5.6 Within a minute since powering on the console it shall display a message about detecting a device with the network address assigned to the Potok-BKI (factory value of the module address is 127). Figure 4 shows the display of the S2000M console with the relevant message. 3.5.7 If several messages accumulated by the module have been received by the console, you can browse them by the arrow buttons and on the S2000M. 3.6 Testing the Module in the Self-Diagnostic Mode 3.6.1 Switch the module to the self-diagnostic mode by pressing the button TEST. If the module operates properly, the indicators turn on as follows: a) All LEDs except for the indicators of the right column switch on simultaneously in green, then in amber, then in red, and finally all the said indicators switch off; b) The LEDs of the right column switch on one at a time (from up to down). READY LED switches on with green, ACCESS LED switches firstly with green, then in red, and other LED switch on with amber. 3.6.2 The self-diagnostic mode terminates automatically in 15 s. 4. PROGRAMMING THE MODULE Figure 4 4.1 To be adjusted for a specific application, the module supports changing its configuration parameters which are stored in its non-volatile memory with the help of UProg Configuration Tool (of version 4.1.0.38 or higher). To do this, please use a computer and an interface converter such as PI-GR, S2000-PI, S2000-USB, USB-RS485, or S2000M (of version 2.03 or higher). The last version of UProg Configuration Tool along with additional information related to using the module is available at the address http://bolid.ru. Table 1 shows configuration parameters of the module. Table 1. Configuration Parameters of the Module Parameter Description Value Range Default Value The Partition Number is to be assigned 1. Partition Number 0 9999 0 with an indicator 4

Parameter Description Value Range Default Value 2. Network Address The address of the module within the RS-485 interface bus 1 127 127 3. Response Pause A time before module s answering for a request from the network controller (3 500) ms 3 ms 4. Both Power Inputs Monitoring On / Off Off 5. OPERATING MODES OF THE MODULE 5.1 Indication Modes 5.1.1 Table 2 shows behavior of indicator groups «Unit 1» «Unit 4». Table 2. Behavior of Indicator Groups «Unit 1» «Unit 4» Indicator Unit Condition Indicator Behavior READY The partition (unit) is not configured - Off The unit operates properly Green Lit steady The unit is out of service Amber 1 s on / 1 s off ON The unit is on Green Lit steady The unit is off - Off TROUBLE The unit is out of service Amber 1 s on / 1 s off The unit operates properly - Off POWER FAILURE Power has failed Amber 1 s on / 1 s off The unit operates properly - Off CONTROL Group Indicators MANUAL The unit is controlled in manual mode Amber Lit steady The unit is not controlled or controlled - Off automatically DISABLED The unit is not controlled at all Amber Lit steady The unit is controlled manually or - Off automatically 5.1.2 Table 3 shows the indicator group «Pump Station» which is designed to indicate condition of a Potok-3N panel: fire conditions, extinguishing process, automatic control conditions, and troubles if any. Table 3. Behavior of the Pump Station Indicator Group Indicator Conditions of the Pump Station Indicator Behavior FIRE Quiescent Mode - Off Fire Red Lit steady SUPPRESSION Extinguishing/Emergency Start Red Lit steady Others - Off TEST Indication of the Potok-BKI is being tested Amber Lit steady Others - Off SILENCED Sounder is disabled Amber Lit steady Others - Off READY Power has been applied to the module Green Lit steady ACCESS (external Access Request for access Green 0.25 s On / 0.25 s Off indicator) Access has granted Green Lit steady Access has rejected - Off Indicators of the AUTOMATIC CONTROL Group OFF Automatic control for the pump station has been off Amber Lit steady NOT AVAILABLE* The pump station is controlled automatically - Off The pump station is controlled automatically - Off The pump station cannot be controlled automatically Amber Lit steady 5

Indicator Conditions of the Pump Station Indicator Behavior TROUBLE Indicator Group** POWER, INPUT, Amber 1 s On / 1 s A trouble OUTPUT, Off OFFLINE, - Off FIRMWARE No troubles ERROR * This situation means that this attempt to switch the automatic control mode on for the pump station has failed. For example, if automatic control is switched off for at least for a single unit. ** Operating of these indicators depends only on conditions of the partitions of the Potok-3N panel (Unit 1 Unit 4, Pump Station) and doesn t depend on states of the zones which were included to the extra partitions «1» «12». 5.1.3 Table 4 demonstrates operating modes of the indicators «1» to «12». The group of indicators of extra partitions is designed to indicate states of the zones of a Potok-3N panel not related with indicators of previous logic groups, in order to get more information. These states can be states of fire partitions, inputs of starting extinguishing, sensors of process stabilization, control sensors of jockey pumps, emergency level switches, end switches of dampers, etc. Table 4. Operation of Indicators of Extra Partitions «1» «12» Status of the Indicated Zone* Indicator Behavior Fire Prealarm Red 0.5 s On / 0.5 s Off Emergency Discharge / Fire Alarm / Discharge / Extinguishing Red Lit steady AC Power Failed Amber 1 s On /1 s Off Fire Equipment Failed Open / Short circuit failure of an input / output Too Low / High Level Tamper Alarm Power Failure Battery Failed / Discharged Pressure Indicator Failed Auxiliary Zone Alarm Green 1 s On /1 s Off Low Level High Level Green Lit steady Pump On Automatic Mode Off Amber Lit steady Others - Off * States of the zones included in the extra partitions don't affect operation of the Pump Station indicators and are not indicated by them. 6 5.2 Sound Signaling 5.2.1 Table 5 shows operating of the module s sounder. Table 5. Souder Behavior Status of Partition / Device Module Sounder Operating A button has been pressed (can be controlled) Beep A command has been executed Access is not granted A long sound A button has been pressed (cannot be controlled) A command has not been executed Access granted Two beeps Control timeout has been reached Two beeps Extinguishing Long dual-tone solid signal (1) Discharge failed Long dual-tone solid signal (2) Fire Alarm / Discharge Delay / Discharge Short dual-tone solid signal

Status of Partition / Device Fire Prealarm Trouble Module Sounder Operating Dual-tone pulse signal Single-tone pulse signal * Operating modes are listed in order of priority, i.e. Beep is of the most priority while Single-tone pulse signal is of the lowest priority. 5.2.2 Sounds are to be silenced by pressing the SILENCE button. But sound signaling will be activated again in case of receiving a new event which requires to be indicated by a sound. To cancel silencing, press the button repeatedly. 5.3 Two access levels are implemented for the module. The first access level (without limitations) enables silencing (by the SILENCE button) and starting the indication test (by the TEST button). The second access level enables remote controlling the Potok-3N panel. 5.4 Remote Control for the Potok-3N Panel 5.4.1 To enable control by buttons AUTOMATIC CONTROL, SUPPRESSION, and RESET, a relevant ibutton must be presented to an ibutton reader (the built-in or external one). The ibutton must be pre-programmed with the list of partitions which the user can control and the user s control rights. These partitions, in turns, must be associated with the indicators of the Potok-BKI module. The control mode is active within 20 s since presenting the ibutton. Each press on a control button increases control time by 10 s. Using the buttons, you can do the following: Switch the automatic mode on Switch the automatic mode off Send a discharge command Cancel discharge Pressing AUTOMATIC CONTROL when the automatic mode is off Pressing AUTOMATIC CONTROL when the automatic mode is on Pressing SUPPRESSION Pressing RESET 5.4.2 If access is granted, the module issues a double beep, otherwise if access is rejected the module issues a long sound. The result and the process of granting access are indicated by ACCESS LED. 5.4.3 If access is granted, pressing a control button is acknowledged by a beep, otherwise, if access is not granted the module issues a long sound when you press a control button. 5.4.4 Executing a command (receiving an acknowledgement from the Potok-3N panel) also is accompanied by a beep. If the command is not executed, the module issues a long solid sound. 5.4.5 Each press on a control button increases control time by 10 s. 5.4.6 When the control time has reached, the indicator ACCESS is off and three beeps are issued. 5.5 Messages Transmitted to the Network Controller 5.5.1 The module transfers the network controller the following messages over the RS-485 interface: TAMPER ALARM The module s case has been open TAMPER RESTORED The module s case has been closed POWER FAILED The power voltage has been below the normal value POWER RESTORED The power voltage is in norm 5.6 Operating Offline 5.6.1 In case communications over the RS-485 interface have lost for more than 60 s, all events are transmitted with the time registered in accordance with the internal module clock. The module is synchronized with the S2000M console at the beginning of every hour. 6. OPERATION DIRECTIVES 6.1 Main Operating Factors 6.1.1 The module design provides IP20 ingress protection rating. 6.1.2 The module is designed to operate under ambient temperatures from minus 30 C to +50 C. 6.2 Safety Precautions 6.2.1 The module has no circuits under a hazardous voltage. 7

7. MAINTENANCE 7.1 To make sure your Potok-BKI module keeps proper operability, it must be inspected by a competent specialist at least on receipt and annually. The inspection algorithm shall include: Visual checking the Potok-BKI against contaminations and mechanical damage; Verifying the Potok-BKI for secure mounting and wire connection conditions; Inspection of the Potok-BKI operability in accordance with Section 3 of this Manual. 8 ZAO NVP Bolid, 4 Pionerskaya Str., Korolev 141070, Moscow Region, Russia Phone/fax: +7 495 775-7155 Email: info@bolid.ru Technical Support: support@bolid.ru http://bolid.ru